BUS SHELTER OFCI, 6"
CONCRET PAD INCLUDED
IN ALTERNATE #1
REVISIONS:
GENERAL NOTES
GENERAL: THESE DRAWINGS REMAIN THE SOLE PROPERTY OF SOL CHAVEZ AND ASSOCIATES AND MAY BE USED ONLY FOR THE PROJECT AS
INDICATED BY NAME AND LOCATION. ANY OTHER USE REQUIRES PRIOR, WRITTEN PERMISSION.
THE CONTRACTOR WILL PROVIDE ALL MATERIALS, LABOR, EQUIPMENT, TOOLS, TRANSPORTATION, LICENSES, FEES, PERMITS, ETC. TO
COMPLETE THE ELECTRICAL WORK DESCRIBED ON THE DRAWINGS. THE CONTRACTOR WILL WARRANT EQUIPMENT, MATERIAL AND
WORKMANSHIP FOR A MINIMUM PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE. WARRANTY SHALL INCLUDE REPLACEMENTS OR
REPAIRS WITHOUT COST TO THE OWNER DURING THE WARRANTY PERIOD.
ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC) 2011 AND ALL OTHER APPLICABLE
LOCAL CODES AND ORDINANCES. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS.
119 West Cucharras St
Colorado Springs
Colorado 80903
WIRING METHODS: ALL WIRING FOR LIGHTING AND POWER SYSTEMS WILL BE IN CONDUIT OR CABLE ASSEMBLIES APPROVED BY THE GOVERNING
AUTHORITIES. CONDUCTOR SIZES SHOWN ARE BASED ON AMPACITIES FOR COPPER CONDUCTORS, UNLESS OTHERWISE NOTED. WHEN
APPROVED BY ENGINEER, FEEDERS MAY BE ALUMINUM CONDUCTORS OF EQUIVALENT AMPACITIES. GROUNDING CONDUCTORS SHALL BE
PROVIDED FOR ALL CIRCUITS SHOWN ON THE DRAWINGS. PROVIDE BLOCKING AND OTHER NECESSARY SUPPORTS IN WALLS AND CEILINGS FOR
MATERIAL AND EQUIPMENT TO BE PROVIDED. BRANCH CIRCUIT NUMBERS SHOWN ON THE DRAWINGS MAY BE REARRANGED WITHIN A GIVEN
PANELBOARD TO SUIT THE NEEDS OF THE INSTALLATION. ELECTRICAL BRANCH CIRCUITS SHALL BE BALANCED BETWEEN LINES AND PHASES.
MULTIWIRE BRANCH CIRCUITS SHALL HAVE A MEANS TO SIMULTANEOUSLY DISCONNECT ALL UNDERGROUNDED CONDUCTORS AT THE POINT
WHERE BRANCH CIRCUITS ORIGINATE (HANDLE TIES ARE AN APPROVED MEANS). THE GROUNDED AND UNDERGROUNDED CONDUCTOR OF EACH
MULTIWIRE BRANCH CIRCUIT SHALL BE GROUPED BY WIRE TIES AT ONE LOCATION IN PANELBOARD.
ALL PATIENT CARE AREAS SHALL COMPLY WITH NEC 517.13(A)(B) TO INCLUDE LUMINAIRES.
UTILITY COORDINATION: PROVIDE ALL COORDINATION WITH THE UTILITY INCLUDING LOAD DATA FORMS AND APPLICATION FOR SERVICE AS
APPLICABLE. INSTALLATION OF SERVICE, PRIMARY OR SECONDARY FEEDERS AND METERING SHALL BE PERFORMED IN ACCORDANCE WITH THE
UTILITIY REQUIREMENTS.
BOLT COVER
UNIVERSITY OF COLORADO, COLORADO SPRINGS
GREEN PARKING LOT
GROUT POLE BASE.
1" CHAMFER
PARKING LOT FINISH SURFACE
OR TOP OF GRADE.
CADWELD CONN. TO
GROUND ROD.
LIGHTING FIXTURES: SEE LIGHT FIXTURE SCHEDULE. PROVIDE ALL FIXTURES WITH LAMPS AS INDICATED. WHERE REQUIRED, FIXTURES SHALL
BE WET OR DAMP LOCATION LABELED. VERIFY MOUNTING HEIGHTS PRIOR TO ELECTRICAL ROUGH-IN. PROVIDE ALL REQUIRED MOUNTING
ACCESSORIES REQUIRED FOR PROPER MOUNTING TO SURFACES SUCH ACCESSORIES TO INCLUDE BUT NOT LIMITED TO SLOPE ADAPTORS.
CANOPIES, AND VAULTED CEILING CANOPIES, ETC.
PROVIDE DISCONNECTING MEANS FOR LUMINAIRES THAT UTILIZE DOUBLE-ENDED LAMPS AND BALLASTS(S) IN ACCORDANCE WITH NEC 410.130(G)(1).
ALTERNATES NOT ACCEPTABLE UNLESS NOTED AS "OR EQUAL" ON LIGHT FIXTURE SCHEDULE.
4'-6"
3"
1'-0"
ANCHOR BOLTS (4).
2'-6" MINIMUM
PVC CONDUITS
WIRING DEVICES: PROVIDE SPECIFICATION GRADE 15 AND 20- AMPERE SWITCH AND RECEPTACLE DEVICES, AS APPLICABLE. OTHER DEVICES
SHALL BE PROVIDED AS INDICATED AND SHALL MATCH PLUG-CONNECTED EQUIPMENT FURNISHED FOR THE PROJECT. DEVICE WALL PLATES
SHALL BE SMOOTH, NYLON TYPE AND SHALL BE OFFICE WHITE IN COLOR OR AS OTHERWISE SPECIFIED. DEVICE COLOR SHALL MATCH WALL
PLATES.
DISCONNECT SWITCHES: HEAVY DUTY QUICK-MAKE, QUICK-BREAK TYPE, NON-FUSED UNLESS OTHERWISE NOTED. PROVIDE MEANS TO LOCK
SWITCH IN OFF POSITION WITH PAD-LOCK. ENCLOSURES SHALL BE NEMA TYPE 1 OR NEMA TYPE 3R FOR OUTDOOR INSTALLATION. PROVIDE
PERMANENT LABELS FOR DISCONNECTS TO INDICATE EQUIMENT SERVED.
LEVELING NUT.
UNDERGROUND ELEC. CONDUIT WITH EQUIPMENT GROUND CONDUCTOR
PER NEC 410.30(B)(5), #12 CU. GROUND CONDUCTOR,
SIZED PER NEC 250.122
#6 AWG
VOICE/DATA: RACEWAY SYSTEM BY CONTRACTOR. ALL RACEWAYS SHALL BE PROVIDED WITH PULLSTRINGS OF MINIMUM OF 400-LB. TEST
STRENGTH. ALL EQUIPMENT, RECEPTACLES AND CABLING BY OTHERS. PROVIDE BLANK COVERS OVER ALL UNUSED OUTLETS. CABLES,
DEVICES AND CABLE TERMINATION IS BY OTHERS.
24" DIAMETER
(4) #4 RE-BARS W/#4
TIES 6" O.C.
COPPERWELD GROUND
ROD, 5/8" x 10'-0"
FIRE ALARM: BY OTHERS, IF REQUIRED.
POLE SHORT BASE DETAIL
CONTRACTOR SHALL PROVIDE ENGINEERING FOR
LIGHT POLE BASE- DETAIL DEPTICTED AS
PREFERED CONDITION.
N.T.S.
LIGHT POLE,
1421 AUSTIN BLUFFS PARKWAY
COLORADO SPRINGS, COLORADO 80918
GROUNDING: PROVIDE A COMPLETE GROUNDING SYSTEM AS REQUIRED BY THE NEC AND LOCAL AUTHORITIES HAVING JURISDICTION. ALL
BRANCH CIRCUITS SHALL INCLUDE A GROUND CONDUCTOR. USE OF RACEWAY FOR GROUNDING IS NOT PERMITTED. GALVANIZED GROUND
RODS ARE NOT PERMITTED.
PANELBOARDS: PROVIDE MINIMUM INTEGRATED EQUIPMENT SHORT CIRCUIT RATING AS INDICATED ON PANEL SCHEDULES. PROVIDE BOLT-ON
BREAKERS UNLESS OTHERWISE NOTED. PROVIDE CIRCUIT BREAKERS SHOWN ON THE PANELBOARD SCHEDULES. ALL TERMINATIONS AND
LUGS SHALL BE RATED FOR 75-DEGREE CONDUCTORS.
PROVIDE TYPEWRITTEN CIRCUIT SCHEDULES TO IDENTIFY PANELBOARD AND EACH BRANCH BREAKER.
ACCEPTABLE MANUFACTURERS ARE SQUARE D, SIEMENS AND EATON.
Fax:(719)636-2547
USE OF DRAWINGS: DO NOT SCALE FROM THE ELECTRICAL DRAWINGS. FOR EXACT LOCATIONS USE ARCHITECT'S DIMENSIONED DRAWINGS,
SHOP DRAWINGS AND FIELD MEASUREMENTS. VERIFY ALL LOCATIONS WITH THE ARCHITECT PRIOR TO ELECTRICAL ROUGH-IN.
Tele:(719)636-0021
Consulting
Engineers
LIGHT POLE.
W/ 3" HOOK
24" DIA. FORMED CONC
BASE W/ 45 DEGREE
CHAMFERED EDGE
45889
FINISH DRIVE SURFACE
2'-0"
3'-0"
1'-0"
ISSUE HISTORY:
A
8'-0" MIN.
2'-0" MIN.
-- -EMON
DMON
M
2
#6 BARE GROUND WIRE CONNECTED TO
3/4" DIAMETER X 10" COPPER GROUND ROD.
BOND TO POLE AND REINF. BARS.
100AS
100AF
UNDERGROUND ELEC. CONDUIT WITH EQUIPMENT GROUND CONDUCTOR PER NEC 410.30(B)(5)
#12 CU. GROUND CONDUCTOR, SIZED PER NEC 250.122
EXISTING
GROUND TO
REMAIN
6 - #4 VERT. REINF.
BARS W/ #4 TIES @
12" O.C
EXISTING
METER
TAG 132
TO UTILITY TRANSFORMER
1
3 #3 CU. IN 1" CONDUIT
2
3 #3 CU., #8G. IN 1" CONDUIT
POLE HIGH BASE DETAIL
N.T.S.
JOB NO.
DRAWN BY
CHECKED BY
DATE
JJA
JJA
4/11/14
1
NOTE:
1.
ALL ELECTRICAL EQUIPMENT, PANELBOARDS AND FEEDERS ARE EXISTING TO REMAIN.
2. PROVIDE E-MON D-MON TO MONITOR PARKING LOT LIGHTING USAGE.
CONTRACTOR SHALL PROVIDE ENGINEERING FOR
LIGHT POLE BASE- DETAIL DEPTICTED AS
PREFERED CONDITION.
--
DRAWING TITLE
ELECTRICAL
SCHEDULES, NOTES
AND DETAILS
EXISTING ONE-LINE DIAGRAM
SCALE: NONE
DRAWING NO.
E101
REVISIONS:
Consulting
Engineers
Tele:(719)636-0021
MOUNT CONDUIT TO COLUMN SUPPORTS
UNIVERSITY OF COLORADO, COLORADO SPRINGS
GREEN PARKING LOT
UGE 2" CONDUIT TO LIGHT POLES, CONTRACTOR
SHALL FIELD VERIFY EXACT ROUTE.
APPROXIMATE DISTANCE 370 FEET.
PROVIDE GFCI RECEPTACLE WITH
WEATHERPROOF COVER FOR IRRIGATION
CONTROLLER. MOUNT RECEPTACLE TO PEDESTAL
BY CONTRACTOR. FIELD VERIFY EXACT LOCATION
OF CONTROLLER WITH OWNER.
A-17
BB2
A-13,15
#8W
13,15
BB2
13,15
BB2
13,15
BB2
BB2
13,15
BB1
MOUNT RF PHONE TO LIGHT POLE,
PROVIDE 120V CONNECTION FOR RF
PHONE, A-13. RF PHONE SHALL BE
OWNER FURNISHED, CONTRACTOR
INSTALLED. FIELD VERIFY MOUNTING
HEIGHT WITH OWNER PRIOR TO
INSTALLATION.
13,15
13,15
BB2
13,15
BB2
1421 AUSTIN BLUFFS PARKWAY
COLORADO SPRINGS, COLORADO 80918
119 West Cucharras St
Colorado Springs
Colorado 80903
APPROXIMATE LOCATION OF TRENCH OUT. FIELD VERIFY
EXACT LOCATION.
Fax:(719)636-2547
PROVIDE LIGHTING CONTRACTOR AND
ASTRONOMICAL TIMECLOCK FOR PARKING
LOT LIGHTS CONTROL.
45889
13,15
ISSUE HISTORY:
-- --
--
JOB NO.
DRAWN BY
CHECKED BY
DATE
JJA
JJA
4/11/14
N
DRAWING TITLE
ELECTRICAL SITE PLAN
ELECTRICAL SITE PLAN
DRAWING NO.
E102