BUS SHELTER OFCI, 6" CONCRET PAD INCLUDED IN ALTERNATE #1 REVISIONS: GENERAL NOTES GENERAL: THESE DRAWINGS REMAIN THE SOLE PROPERTY OF SOL CHAVEZ AND ASSOCIATES AND MAY BE USED ONLY FOR THE PROJECT AS INDICATED BY NAME AND LOCATION. ANY OTHER USE REQUIRES PRIOR, WRITTEN PERMISSION. THE CONTRACTOR WILL PROVIDE ALL MATERIALS, LABOR, EQUIPMENT, TOOLS, TRANSPORTATION, LICENSES, FEES, PERMITS, ETC. TO COMPLETE THE ELECTRICAL WORK DESCRIBED ON THE DRAWINGS. THE CONTRACTOR WILL WARRANT EQUIPMENT, MATERIAL AND WORKMANSHIP FOR A MINIMUM PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE. WARRANTY SHALL INCLUDE REPLACEMENTS OR REPAIRS WITHOUT COST TO THE OWNER DURING THE WARRANTY PERIOD. ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC) 2011 AND ALL OTHER APPLICABLE LOCAL CODES AND ORDINANCES. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS. 119 West Cucharras St Colorado Springs Colorado 80903 WIRING METHODS: ALL WIRING FOR LIGHTING AND POWER SYSTEMS WILL BE IN CONDUIT OR CABLE ASSEMBLIES APPROVED BY THE GOVERNING AUTHORITIES. CONDUCTOR SIZES SHOWN ARE BASED ON AMPACITIES FOR COPPER CONDUCTORS, UNLESS OTHERWISE NOTED. WHEN APPROVED BY ENGINEER, FEEDERS MAY BE ALUMINUM CONDUCTORS OF EQUIVALENT AMPACITIES. GROUNDING CONDUCTORS SHALL BE PROVIDED FOR ALL CIRCUITS SHOWN ON THE DRAWINGS. PROVIDE BLOCKING AND OTHER NECESSARY SUPPORTS IN WALLS AND CEILINGS FOR MATERIAL AND EQUIPMENT TO BE PROVIDED. BRANCH CIRCUIT NUMBERS SHOWN ON THE DRAWINGS MAY BE REARRANGED WITHIN A GIVEN PANELBOARD TO SUIT THE NEEDS OF THE INSTALLATION. ELECTRICAL BRANCH CIRCUITS SHALL BE BALANCED BETWEEN LINES AND PHASES. MULTIWIRE BRANCH CIRCUITS SHALL HAVE A MEANS TO SIMULTANEOUSLY DISCONNECT ALL UNDERGROUNDED CONDUCTORS AT THE POINT WHERE BRANCH CIRCUITS ORIGINATE (HANDLE TIES ARE AN APPROVED MEANS). THE GROUNDED AND UNDERGROUNDED CONDUCTOR OF EACH MULTIWIRE BRANCH CIRCUIT SHALL BE GROUPED BY WIRE TIES AT ONE LOCATION IN PANELBOARD. ALL PATIENT CARE AREAS SHALL COMPLY WITH NEC 517.13(A)(B) TO INCLUDE LUMINAIRES. UTILITY COORDINATION: PROVIDE ALL COORDINATION WITH THE UTILITY INCLUDING LOAD DATA FORMS AND APPLICATION FOR SERVICE AS APPLICABLE. INSTALLATION OF SERVICE, PRIMARY OR SECONDARY FEEDERS AND METERING SHALL BE PERFORMED IN ACCORDANCE WITH THE UTILITIY REQUIREMENTS. BOLT COVER UNIVERSITY OF COLORADO, COLORADO SPRINGS GREEN PARKING LOT GROUT POLE BASE. 1" CHAMFER PARKING LOT FINISH SURFACE OR TOP OF GRADE. CADWELD CONN. TO GROUND ROD. LIGHTING FIXTURES: SEE LIGHT FIXTURE SCHEDULE. PROVIDE ALL FIXTURES WITH LAMPS AS INDICATED. WHERE REQUIRED, FIXTURES SHALL BE WET OR DAMP LOCATION LABELED. VERIFY MOUNTING HEIGHTS PRIOR TO ELECTRICAL ROUGH-IN. PROVIDE ALL REQUIRED MOUNTING ACCESSORIES REQUIRED FOR PROPER MOUNTING TO SURFACES SUCH ACCESSORIES TO INCLUDE BUT NOT LIMITED TO SLOPE ADAPTORS. CANOPIES, AND VAULTED CEILING CANOPIES, ETC. PROVIDE DISCONNECTING MEANS FOR LUMINAIRES THAT UTILIZE DOUBLE-ENDED LAMPS AND BALLASTS(S) IN ACCORDANCE WITH NEC 410.130(G)(1). ALTERNATES NOT ACCEPTABLE UNLESS NOTED AS "OR EQUAL" ON LIGHT FIXTURE SCHEDULE. 4'-6" 3" 1'-0" ANCHOR BOLTS (4). 2'-6" MINIMUM PVC CONDUITS WIRING DEVICES: PROVIDE SPECIFICATION GRADE 15 AND 20- AMPERE SWITCH AND RECEPTACLE DEVICES, AS APPLICABLE. OTHER DEVICES SHALL BE PROVIDED AS INDICATED AND SHALL MATCH PLUG-CONNECTED EQUIPMENT FURNISHED FOR THE PROJECT. DEVICE WALL PLATES SHALL BE SMOOTH, NYLON TYPE AND SHALL BE OFFICE WHITE IN COLOR OR AS OTHERWISE SPECIFIED. DEVICE COLOR SHALL MATCH WALL PLATES. DISCONNECT SWITCHES: HEAVY DUTY QUICK-MAKE, QUICK-BREAK TYPE, NON-FUSED UNLESS OTHERWISE NOTED. PROVIDE MEANS TO LOCK SWITCH IN OFF POSITION WITH PAD-LOCK. ENCLOSURES SHALL BE NEMA TYPE 1 OR NEMA TYPE 3R FOR OUTDOOR INSTALLATION. PROVIDE PERMANENT LABELS FOR DISCONNECTS TO INDICATE EQUIMENT SERVED. LEVELING NUT. UNDERGROUND ELEC. CONDUIT WITH EQUIPMENT GROUND CONDUCTOR PER NEC 410.30(B)(5), #12 CU. GROUND CONDUCTOR, SIZED PER NEC 250.122 #6 AWG VOICE/DATA: RACEWAY SYSTEM BY CONTRACTOR. ALL RACEWAYS SHALL BE PROVIDED WITH PULLSTRINGS OF MINIMUM OF 400-LB. TEST STRENGTH. ALL EQUIPMENT, RECEPTACLES AND CABLING BY OTHERS. PROVIDE BLANK COVERS OVER ALL UNUSED OUTLETS. CABLES, DEVICES AND CABLE TERMINATION IS BY OTHERS. 24" DIAMETER (4) #4 RE-BARS W/#4 TIES 6" O.C. COPPERWELD GROUND ROD, 5/8" x 10'-0" FIRE ALARM: BY OTHERS, IF REQUIRED. POLE SHORT BASE DETAIL CONTRACTOR SHALL PROVIDE ENGINEERING FOR LIGHT POLE BASE- DETAIL DEPTICTED AS PREFERED CONDITION. N.T.S. LIGHT POLE, 1421 AUSTIN BLUFFS PARKWAY COLORADO SPRINGS, COLORADO 80918 GROUNDING: PROVIDE A COMPLETE GROUNDING SYSTEM AS REQUIRED BY THE NEC AND LOCAL AUTHORITIES HAVING JURISDICTION. ALL BRANCH CIRCUITS SHALL INCLUDE A GROUND CONDUCTOR. USE OF RACEWAY FOR GROUNDING IS NOT PERMITTED. GALVANIZED GROUND RODS ARE NOT PERMITTED. PANELBOARDS: PROVIDE MINIMUM INTEGRATED EQUIPMENT SHORT CIRCUIT RATING AS INDICATED ON PANEL SCHEDULES. PROVIDE BOLT-ON BREAKERS UNLESS OTHERWISE NOTED. PROVIDE CIRCUIT BREAKERS SHOWN ON THE PANELBOARD SCHEDULES. ALL TERMINATIONS AND LUGS SHALL BE RATED FOR 75-DEGREE CONDUCTORS. PROVIDE TYPEWRITTEN CIRCUIT SCHEDULES TO IDENTIFY PANELBOARD AND EACH BRANCH BREAKER. ACCEPTABLE MANUFACTURERS ARE SQUARE D, SIEMENS AND EATON. Fax:(719)636-2547 USE OF DRAWINGS: DO NOT SCALE FROM THE ELECTRICAL DRAWINGS. FOR EXACT LOCATIONS USE ARCHITECT'S DIMENSIONED DRAWINGS, SHOP DRAWINGS AND FIELD MEASUREMENTS. VERIFY ALL LOCATIONS WITH THE ARCHITECT PRIOR TO ELECTRICAL ROUGH-IN. Tele:(719)636-0021 Consulting Engineers LIGHT POLE. W/ 3" HOOK 24" DIA. FORMED CONC BASE W/ 45 DEGREE CHAMFERED EDGE 45889 FINISH DRIVE SURFACE 2'-0" 3'-0" 1'-0" ISSUE HISTORY: A 8'-0" MIN. 2'-0" MIN. -- -EMON DMON M 2 #6 BARE GROUND WIRE CONNECTED TO 3/4" DIAMETER X 10" COPPER GROUND ROD. BOND TO POLE AND REINF. BARS. 100AS 100AF UNDERGROUND ELEC. CONDUIT WITH EQUIPMENT GROUND CONDUCTOR PER NEC 410.30(B)(5) #12 CU. GROUND CONDUCTOR, SIZED PER NEC 250.122 EXISTING GROUND TO REMAIN 6 - #4 VERT. REINF. BARS W/ #4 TIES @ 12" O.C EXISTING METER TAG 132 TO UTILITY TRANSFORMER 1 3 #3 CU. IN 1" CONDUIT 2 3 #3 CU., #8G. IN 1" CONDUIT POLE HIGH BASE DETAIL N.T.S. JOB NO. DRAWN BY CHECKED BY DATE JJA JJA 4/11/14 1 NOTE: 1. ALL ELECTRICAL EQUIPMENT, PANELBOARDS AND FEEDERS ARE EXISTING TO REMAIN. 2. PROVIDE E-MON D-MON TO MONITOR PARKING LOT LIGHTING USAGE. CONTRACTOR SHALL PROVIDE ENGINEERING FOR LIGHT POLE BASE- DETAIL DEPTICTED AS PREFERED CONDITION. -- DRAWING TITLE ELECTRICAL SCHEDULES, NOTES AND DETAILS EXISTING ONE-LINE DIAGRAM SCALE: NONE DRAWING NO. E101 REVISIONS: Consulting Engineers Tele:(719)636-0021 MOUNT CONDUIT TO COLUMN SUPPORTS UNIVERSITY OF COLORADO, COLORADO SPRINGS GREEN PARKING LOT UGE 2" CONDUIT TO LIGHT POLES, CONTRACTOR SHALL FIELD VERIFY EXACT ROUTE. APPROXIMATE DISTANCE 370 FEET. PROVIDE GFCI RECEPTACLE WITH WEATHERPROOF COVER FOR IRRIGATION CONTROLLER. MOUNT RECEPTACLE TO PEDESTAL BY CONTRACTOR. FIELD VERIFY EXACT LOCATION OF CONTROLLER WITH OWNER. A-17 BB2 A-13,15 #8W 13,15 BB2 13,15 BB2 13,15 BB2 BB2 13,15 BB1 MOUNT RF PHONE TO LIGHT POLE, PROVIDE 120V CONNECTION FOR RF PHONE, A-13. RF PHONE SHALL BE OWNER FURNISHED, CONTRACTOR INSTALLED. FIELD VERIFY MOUNTING HEIGHT WITH OWNER PRIOR TO INSTALLATION. 13,15 13,15 BB2 13,15 BB2 1421 AUSTIN BLUFFS PARKWAY COLORADO SPRINGS, COLORADO 80918 119 West Cucharras St Colorado Springs Colorado 80903 APPROXIMATE LOCATION OF TRENCH OUT. FIELD VERIFY EXACT LOCATION. Fax:(719)636-2547 PROVIDE LIGHTING CONTRACTOR AND ASTRONOMICAL TIMECLOCK FOR PARKING LOT LIGHTS CONTROL. 45889 13,15 ISSUE HISTORY: -- -- -- JOB NO. DRAWN BY CHECKED BY DATE JJA JJA 4/11/14 N DRAWING TITLE ELECTRICAL SITE PLAN ELECTRICAL SITE PLAN DRAWING NO. E102