AC Power For Business-Critical Continuity™ Liebert® NXL™ Battery System Installation Manual BATTERY CABINET PRECAUTIONS The following warning applies to all battery cabinets supplied with UPS systems. Additional warnings and cautions applicable to battery cabinets may be found in Important Safety Instructions beginning on page 1. ! WARNING Internal battery strapping must be verified prior to moving a battery cabinet (after initial installation). • Battery cabinets contain non-spillable batteries. • Keep units upright. • Do not stack. • Do not tilt. Failure to heed this warning could result in smoke, fire or electric hazard. Call 1-800-LIEBERT prior to moving battery cabinets (after initial installation). CONTACTING EMERSON NETWORK POWER® FOR SUPPORT To contact the Emerson Network Power Liebert® Services for information or repair service in the United States, call 1-800-LIEBERT (1-800-543-2378). Liebert Services offers a complete range of startup services, repair services, preventive maintenance plans and service contracts. For repair or maintenance service outside the 48 contiguous United States, contact Liebert Services, if available in your area. For Liebert Services to assist you promptly, have the following information available: Part Numbers: Serial Numbers: Rating: Date Purchased: Date Installed: Location: Battery Voltage: Battery Reserve Time: Product Warranty Registration To register for warranty protection, visit the Service and Support section of our Web site at: www.liebert.com Click on Product Registration and fill out the form. TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1.0 MECHANICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.2 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.3 Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.3.1 1.3.2 1.4 Battery Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.4.1 1.4.2 1.4.3 Moving the Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Raised Floor Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.5 System Composition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.0 BATTERY INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 2.1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.2 Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.3 Cable Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.4 Power Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.4.1 2.4.2 2.4.3 2.4.4 Connected System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Stand-Alone System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Attached/Detached System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 8 9 9 2.5 Control Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 2.6 Alber Monitoring System—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.7 External Battery Room Temperature Sensor—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 3.0 INSTALLATION DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 4.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45 FIGURES Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Shipping bolts—Top-Terminal Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Battery cabinets connected, attached to UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Battery cabinets connected, detached from UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Stand-alone battery cabinets, detached from UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Wiring external interface board in UPS to battery interface board in battery cabinet . . . . . . . . 10 Control cable layout—Liebert NXL UPS to Liebert NXL Battery Cabinet . . . . . . . . . . . . . . . . . . 11 Battery temperature sensor control connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Outline drawing, Liebert Top-Terminal Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Main components, Liebert Top-Terminal Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Terminal details, Liebert Top-Terminal Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Front Terminal Battery Cabinet shipping split . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Front Terminal Battery Cabinet outline drawing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Front Terminal Battery Cabinet main components, layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Front terminal detail drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Liebert NXL Stand-Alone Junction Cabinet terminal wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 i Figure 16 Figure 17 Figure 18 Figure 19 Figure 20 Figure 21 Figure 22 Figure 23 Figure 24 Figure 25 Figure 26 Figure 27 Figure 28 Figure 29 Figure 30 Figure 31 Figure 32 Figure 33 Figure 34 Figure 35 Figure 36 Figure 37 Figure 38 Figure 39 Figure 40 Liebert NXL Attached Junction Cabinet—terminal detail and outline drawing . . . . . . . . . . . . . Liebert NXL Battery Cabinet control wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Attached battery cabinet connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ground strap location for connected cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Top-Terminal Battery Cabinet interconnection wiring to 250-400kVA UPS . . . . . . . . . . . . . . . . Liebert NXL Top-Terminal Battery Cabinet interconnect wiring to Liebert NXL Stand-Alone Junction Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details Liebert NXL UPS 250kVA - 400kVA to front terminal battery point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details Liebert NXL 250-400kVA front terminal battery and Stand-Alone Junction Cabinet point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Attached Junction Cabinet, point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Stand-Alone Junction Cabinet, point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details Liebert NXL 500kVA to Top-Terminal battery point-to-point wiring . . . . . . . . Terminal details Liebert NXL UPS 500kVA to front terminal battery point-to-point wiring . . . Liebert NXL terminal details UPS 625/750kVA to front terminal battery and Attached Junction Cabinet point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Liebert NXL terminal details UPS 625/750kVA to front terminal battery and Stand-Alone Junction Cabinet point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and Attached Junction Cabinet, point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and Stand-Alone Junction Cabinet, point-to-point wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details Liebert NXL UPS 625/750kVA to battery point-to-point wiring . . . . . . . . . . . Terminal details UPS 625/750kVA to front terminal battery and Attached Junction Cabinet point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details 625/750kVA to front terminal battery and Stand-Alone Junction Cabinet point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Typical Alber battery monitoring connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alber battery monitoring wiring to multiple battery cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alber battery monitoring assembly diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Top-Terminal battery configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Front-Terminal battery configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Busbar connection between Battery Cabinet and Attached Junction Cabinet . . . . . . . . . . . . . . . ii 21 22 23 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 TABLES Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Table 9 Table 10 Table 11 Table 12 Table 13 Table 14 Table 15 Table 16 Table 17 Table 18 Table 19 Table 20 Table 21 Table 22 Table 23 Table 24 Table 25 Table 26 Top-Terminal Battery Cabinet interconnection wiring to 250-400kVA UPS . . . . . . . . . . . . . . . . Liebert NXL Top-Terminal Battery Cabinet interconnect wiring to Liebert NXL Junction Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details Liebert NXL UPS 250kVA - 400kVA to front terminal battery point-to-point interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details Liebert NXL 250-400kVA front terminal battery and Stand-Alone Junction Cabinet point-to-point interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Attached Junction Cabinet, point-to-point interconnect wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Stand-Alone Junction Cabinet, point-to-point interconnect wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details Liebert NXL 500kVA to top-terminal battery point-to-point interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details Liebert NXL UPS 500kVA to front terminal battery point-to-point interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Liebert NXL terminal details UPS 625/750kVA to front terminal battery and Attached Junction Cabinet point-to-point Interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LIebert NXL terminal details UPS 625/750kVA to front terminal battery and Stand-Alone Junction Cabinet point-to-point interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and Attached Junction Cabinet, point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and Stand-Alone Junction Cabinet, point-to-point interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . Terminal details Liebert NXL UPS 625/750kVA to battery point-to-point interconnect wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details UPS 625/750kVA to front terminal battery and Attached Junction Cabinet point-to-point interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal details 625/750kVA to front terminal battery and Stand-Alone Junction Cabinet point-to-point interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alber battery monitoring assembly connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Liebert NXL Battery Cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Liebert NXL Junction Cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alber® battery monitoring option specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DC currents for Liebert NXL modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Liebert NXL Battery Cabinet internal breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Liebert NXL Battery Cabinet approximate weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Recommended external conduit and cable sizes from Liebert NXL UPS to DC source . . . . . . . . Recommended lug sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Torque specifications, unless otherwise labeled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery torque values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii 24 25 26 28 28 29 30 31 32 33 34 35 36 37 38 41 45 46 46 46 47 47 48 48 49 49 iv Important Safety Instructions IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation of your Liebert NXL Battery Cabinet and accessories. Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the battery system. Retain this manual for use by installing personnel. ! WARNING Risk of electrical shock. Can cause personal injury and death. Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system. Only properly trained and qualified personnel wearing appropriate personal protective equipment should be involved in installing the Liebert NXL Battery system or preparing the system for installation. Special care must be taken when working with the batteries associated with this equipment. When connected together, the battery terminal voltage will exceed 400VDC and is potentially lethal. Be constantly aware that the battery system contains high DC as well as AC voltages. Check for voltage with AC and DC voltmeters before making contact. Observe all DC safety precautions before working on or near the DC system. Follow all battery safety precautions when installing, charging or servicing batteries. In addition to the hazard of electric shock, gas produced by batteries can be explosive and sulfuric acid can cause severe burns. The following precautions must be observed when working on batteries: • • • • • • Remove watches, rings and other metal objects. Use tools with insulated handles. Wear rubber gloves and boots. Do not lay tools or metal parts on top of batteries. Disconnect charging source prior to connecting or disconnecting battery terminals. Determine whether the battery is grounded. If it is grounded, remove source of ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance. If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations. If electrolyte comes into contact with the skin, the affected area should be washed immediately with water. ! WARNING Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment damage, personal injury and death. Lead-acid batteries contain hazardous materials. Batteries must be handled, transported and recycled or discarded in accordance with federal, state and local regulations. Because lead is a toxic substance, lead-acid batteries must be recycled rather than discarded. Do not dispose of a battery in a fire. The battery may explode. Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It is toxic. ! WARNING Risk of electric shock. Can cause personal injury and death. In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires. 1 Liebert® NXL™ Battery System Important Safety Instructions ! WARNING Risk of heavy unit falling over. Can cause equipment damage, injury and death. Exercise extreme care when handling battery cabinets to avoid equipment damage or injury to personnel. The battery system cabinets weigh from 3760 to 8990 lb. (1706 to 4078kg). Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times. Slots at the base of the cabinets are intended for forklift use. Base slots will support the unit only if the forks are completely beneath the unit. ! WARNING Risk of electric shock. Can cause equipment damage, personal injury and death. The area around the battery system must be kept free of puddles of water, excess moisture and debris. Observe all precautions in the Operation and Maintenance Manual, SL 25425, before as well as during all installation and maintenance procedures. Observe all battery safety precautions before working on or near the battery. This equipment contains several circuits that are energized with high voltage. Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high potential electric charges may exist at the capacitor banks and at the batteries. All power and control wiring must be installed by a properly trained and qualified electrician. All power and control wiring must comply with the NEC and applicable local codes. When performing maintenance with any part of the equipment under power, service personnel and test equipment must be standing on rubber mats. The service personnel must wear insulating shoes for isolation from direct contact with the floor (earth ground). One person should never work alone, even if all power is disconnected from the equipment. A second person should be standing by to assist and to summon help in case of an accident. NOTE Materials sold hereunder cannot be used in the patient vicinity (e.g., use where UL, cUL or IEC 60601-1 is required). Medical applications such as invasive procedures and electrical life support equipment are subject to additional terms and conditions. NOTICE This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense. Liebert® NXL™ Battery System 2 Mechanical Installation 1.0 MECHANICAL INSTALLATION 1.1 Introduction This following section describes the requirements that must be taken into account when planning the positioning and cabling of the Liebert NXL battery equipment. This chapter is a guide to general procedures and practices that should be observed by the installing engineer. The particular conditions of each site will determine the applicability of such procedures. NOTICE Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer. 1.2 Preliminary Checks Before installing the battery equipment, please carry out the following preliminary checks: • Visually examine the equipment for transit damage, both internally and externally. Report any damage to the shipper immediately. • Verify that the correct equipment is being installed. The equipment supplied has an identification tag inside the main door. • Verify that the battery room satisfies the environmental conditions stipulated in the equipment specification, paying particular attention to the ambient temperature and air exchange system. 1.3 Environmental Considerations 1.3.1 Battery Room Batteries should be mounted in an environment where the temperature is consistent and even over the whole battery. Temperature is a major factor in determining the battery life and capacity. Typical battery manufacturer performance data are quoted for an operating temperature between 68 and 77°F (20 and 25°C). Operating above this range will reduce the battery life while operation below this range will reduce the battery capacity. Battery Temperature In a normal installation, the battery temperature should be kept between 59 and 77°F (15°C and 25°C). NOTE Keep batteries away from main heat sources, main air inlets, etc. 1.3.2 Storage Should the equipment not be installed immediately, it must be stored in a room for protection against excessive humidity and heat sources (see Table 17). NOTICE Risk of deep discharge can cause permanent damage to batteries. An unused battery must be recharged periodically as recommended by the battery manufacturer. 3 Liebert® NXL™ Battery System Mechanical Installation 1.4 Positioning The cabinet is structurally designed to handle lifting from the base. Power terminals, auxiliary terminals blocks and power switches are accessed from the front and top. Removable panels on the top are secured to the chassis by screws. The door can be opened to give access to the power connections bars, auxiliary terminal blocks and power isolators. The front door can be opened 180° for easier service and more flexibility in installation. 1.4.1 Moving the Cabinets The route to be travelled between the point of arrival and the unit’s installation location must be planned to make sure that all passages are wide enough for the unit and that floors are capable of supporting its weight (for instance, check that doorways, lifts, ramps, etc., are adequate and that there are no impassable corners or changes in the level of corridors). Ensure that the cabinet weight is within the designated surface weight loading (kg/cm2) of any handling equipment. See Table 17 for weight details. Ensure that any lifting equipment used to move the battery equipment has sufficient lifting capacity. Battery system equipment can be handled by a forklift or similar equipment. Because the weight distribution in the cabinet is not symmetrical, use extreme care during handling and transporting. When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a 15° tilt with the forklift. Bottom structure will support the unit only if the forks are completely beneath the unit. Handling the unit with straps is not authorized. ! WARNING Risk of heavy unit falling over. Can cause equipment damage, injury and death. Exercise extreme care when handling battery cabinets. The battery system cabinets weigh from 3760 to 8990 lb. (1706 to 4078kg). Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times. Slots at the base of the cabinets are intended for forklift use. Base slots will support the unit only if the forks are completely beneath the unit. The cabinet with top terminal batteries ships with extra bolts installed on the interior doors. Once the cabinet is in the final position, these bolts can be removed. See Figure 1 Figure 1 Shipping bolts—Top-Terminal Battery Cabinet Shipping Bolts Shipping Bolts Shipping Bolts * Outer doors removed for clarity Shipping Bolts Shipping Bolts Shipping Bolts Shipping Shipping Bolts Bolts Liebert® NXL™ Battery System 4 Mechanical Installation 1.4.2 Clearances Liebert NXL has no ventilation grilles at either side or at the rear of the battery system equipment. Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened. It is important to leave a distance of 24" (610mm) between the top of the cabinet and the ceiling of the room in which it is installed to permit adequate circulation of air coming out of the unit and for service access. 1.4.3 Raised Floor Mounting If the equipment is to be placed on a raised floor, it should be mounted on a pedestal suitably designed to accept the equipment point loading. Refer to the base view to design this pedestal. 1.5 System Composition A battery system can consist of a number of equipment cabinets, depending on the individual system design requirements, e.g., Battery Cabinet, Junction Cabinet. Refer to 3.0 - Installation Drawings for the positioning of the cabinets described below. 5 Liebert® NXL™ Battery System Battery Installation 2.0 BATTERY INSTALLATION 2.1 Safety Special care should be taken when working with the batteries associated with the Liebert NXL Battery System equipment. When all the cells are connected together, the battery terminal voltage will exceed 400V and is potentially lethal. A primary safety consideration is to install the battery equipment in an isolated area, accessible only to properly trained and qualified maintenance personnel. ! WARNING Risk of electric shock. Can cause equipment damage, personal injury and death. Hazardous battery voltage present behind covers. No user-serviceable parts are located behind covers that require a tool for removal. Only properly trained and qualified service personnel are authorized to remove such covers or perform installation or maintenance. The following general battery safety precautions and warnings must be observed at all times: • A battery can present risk of electric shock or burn from high short circuit currents. • When connected in a string, the voltage will exceed 400VDC. This voltage is potentially lethal. Always observe high-voltage precautions. • Eye protection must be worn to prevent injury from accidental electrical arcs. • Remove rings, watches, necklaces, bracelets and all other metal objects. • Use only tools with insulated handles. • Wear appropriate personal protective equipment when handling batteries. • If a battery leaks electrolyte or is otherwise physically damaged, it should be placed in a container resistant to wire and disposed of in accordance with local regulations. • If electrolyte comes into contact with the skin, the affected area should be washed immediately with plenty of clean water. • Batteries must always be disposed of according to local environmental laws. • When replacing batteries, use the same number and type that were originally fitted. • Disconnect charging source prior to connecting or disconnecting battery terminals. • Determine if the battery is grounded. If it is grounded, remove source of ground. Contact with any part of a grounded battery can result in electrical shock. • Battery support tray must be used whenever a battery tray is being pulled out. 2.2 Layout Depending on the site layout, the battery cabinets can be installed in any of several ways: • • • • Connected—Multiple battery cabinets bolted together Stand-Alone—Cabinet not bolted to Liebert NXL equipment Attached—Battery cabinets are bolted to a Liebert NXL UPS Detached—Battery cabinets are not bolted to a Liebert NXL UPS See Figures 2 through 4. Liebert® NXL™ Battery System 6 Battery Installation Figure 2 Battery cabinets connected, attached to UPS Liebert NXL Battery Cabinet Liebert NXL UPS Additional Liebert NXL Battery Cabinet If the Liebert NXL UPS is 500kVA to 750kVA, battery cabinets must be attached to the left side of the UPS. Additional Liebert NXL Battery Cabinet Figure 3 Liebert NXL Battery Cabinet Liebert NXL UPS Battery cabinets connected, detached from UPS Liebert NXL UPS Attached Junction Cabinet Liebert NXL Battery Cabinet Additional Liebert NXL Battery Cabinet The junction cabinet allows for sufficient conduit landing space. It is required for systems of 500kVA or above. Additional Liebert NXL Battery Cabinet Liebert NXL Battery Cabinet 7 Attached Junction Cabinet Liebert NXL UPS Liebert® NXL™ Battery System Battery Installation Figure 4 Stand-alone battery cabinets, detached from UPS StandAlone Junction Cabinet Liebert NXL UPS Liebert NXL Battery Cabinet Additional Liebert NXL Battery Cabinet Maximum of eight battery cabinets. The junction cabinet provides sufficient conduit landing space and is required for all systems in this configuration. Additional Liebert NXL Battery Cabinet 2.3 Liebert NXL Battery Cabinet StandAlone Junction Cabinet Liebert NXL UPS Cable Entry Cables may enter the battery cabinet from the top or bottom. Cable entry is made possible by installing conduit to the removable plate fitted at the top or bottom. See 3.0 - Installation Drawings. 2.4 Power Connection Depending on the site layout, the battery cabinets can be cabled several ways. See Figures 2 through 4. ! CAUTION Cables between batteries and the UPS should be run in matched pairs, positive-with- negative, within each conduit or cable run. Grouping like-polarity cables together (i.e., positive-with-positive and negative-with-negative) can cause stress or damage to the cables, conduit or buswork 2.4.1 Connected System For cabinets ordered as connected (battery cabinets will bolt to each other), the positive and negative busbars are connected between battery cabinets with the supplied busbar connector extensions. See Figure 18 2.4.2 Stand-Alone System For cabinets that are ordered as stand-alone, customer must supply all the interconnecting cables and hardware. See Table 23 for current ratings and recommended cable sizes. Liebert® NXL™ Battery System 8 Battery Installation 2.4.3 Attached/Detached System For battery cabinets that are connecting to a Liebert NXL UPS, (see Figure 2), cables will run from the positive and negative busbars of the adjacent battery cabinet to the positive and negative DC connections of UPS. For battery cabinets that are connecting to a Liebert NXL Junction Cabinet (see Figure 3), busbars will be connected from the positive and negative busbars of the adjacent battery cabinet to the positive and negative DC connections of Junction Cabinet. For attached systems (the cabinets bolt to each other), the cables can run internal to the cabinets and will be supplied. For detached systems (the cabinets do not bolt to each other), the cables must be run outside the cabinets. The customer must supply all the interconnecting cables and hardware. See Table 23 for current ratings and recommended cable sizes. 2.4.4 Grounding For cabinets that have been ordered as connected or attached, the ground cables and hardware will be supplied. See Figure 19 for location of cabinet-to-cabinet grounding. For cabinets ordered as detached or stand-alone, customer must supply the cables and hardware. See Table 23 for current ratings and recommended cable sizes. See terminal detail drawings for location of ground busbar. 2.5 Control Connection Each Liebert NXL Battery Cabinet contains a Battery Interface Board (BIB). See 3.0 - Installation Drawings. All cabinets in a system must have their Battery Interface boards connected in series. See Figure 10 for battery cabinet details NOTE Care must be taken to route the control cables away from high voltage cables or busbars. 9 Liebert® NXL™ Battery System Battery Installation Figure 5 Wiring external interface board in UPS to battery interface board in battery cabinet Detail A TB1154A EXT BATT CAN External Interface Board (in UPS) Detail A TB1154A +24V GND CANH CANL 1 2 3 4 Battery Interface Board (in Battery Cabinet) Detail B TB1154 Liebert® NXL™ Battery System 1 Detail B +24V 2 GND 3 CANH CANL 4 TB1154 10 Battery Installation Figure 6 Control cable layout—Liebert NXL UPS to Liebert NXL Battery Cabinet Liebert NXL UPS Liebert NXL Battery Cabinet Ext. Interface Board (EIB) TB1154A Bat. Interface Board (BIB) TB1154 CAN Cable Additional Liebert NXL Battery Cabinet Bat. Interface Board (BIB) TB1154 CAN Cable The CAN cables must be two, twisted pair, shielded 18AWG (Belden 9156 or equivalent). All interconnecting cables and hardware for connected and attached cabinets will be provided. NOTICE Risk of improper installation. Can cause equipment damage. During system commissioning, Emerson® Network Power Liebert Services will set the jumpers on the EIB and the BIB. If another battery cabinet is added to the system after commissioning, it is imperative that Liebert Services reset the jumpers on the EIB board and the BIB board. 11 Liebert® NXL™ Battery System Battery Installation 2.6 Alber Monitoring System—Optional The Liebert matching battery cabinet allows installing an optional Alber battery monitoring system in the cabinet. The Alber battery monitoring continuously checks all critical battery parameters, such as cell voltage, overall string voltage, current and temperature. Automatic periodic tests of internal resistance of each battery will verify the battery’s operating integrity. Additional capabilities include automatic internal DC resistance tests and trend analysis providing the ability to analyze performance and aid in troubleshooting. The Alber monitoring system is installed inside the battery cabinet (see Figure 37). The monitoring system requires approximately 0.5A, single-phase power. This power can come from the output of the UPS the battery cabinet is suppling (see Figure 37). The Alber monitoring system consists of a Controller Module and Data Collector Module (see Figure 35). One Controller Module can monitor up to six battery cabinets with a Data Collector Module installed. The battery cabinet with the Controller Module (Battery Cabinet #1) must be installed in the position closest to the UPS. For details about operating the Alber system, see the Alber Monitoring System manual, available at the Liebert Web Site, www.liebert.com 2.7 External Battery Room Temperature Sensor—Optional For systems that do not use Liebert NXL Battery Cabinets, an optional temperature sensor can be installed to monitor the ambient room temperature. This sensor is connected to the BIB board (see Figure 7). This sensor will allow the Liebert NXL UPS to perform temperature compensation charging. Figure 7 Battery temperature sensor control connection Battery Interface Board P1153 TB1154 Liebert® NXL™ Battery System 12 Installation Drawings 3.0 INSTALLATION DRAWINGS Figure 8 Outline drawing, Liebert Top-Terminal Battery Cabinet 56.3 (1430) 16.6 (422) 27.7 (705) 76.8 (1950) CG CG 42.8 (1088) 3.7 (95) Front 1.6 (40) Typ 3.7 (95) 33.5 (850) 28.7 ( 730) 3 (76) Right Side View 64.1 (1629) 8.8 8.3 11.2 (223) 11.2 6.4 (210) (285) (285) (161) TOP VIEW (Doors Open) Bottom View NOTE: 1. All dimensions are in in. (mm) 2. 24" minimum clearance above unit required for air exhaust. 3. Keep cabinet within 15 degrees of vertical. 4. Top and bottom cable entry available through removable access plates. 5. Widths are with side panels. The width is 55.1" (1400mm) without side panels. 6.The depth dimension includes the front door and rear panel. 13 Liebert® NXL™ Battery System Installation Drawings Figure 9 Main components, Liebert Top-Terminal Battery Cabinet Negative Battery Bus Positive Battery Bus High Voltage Control Cable Trough Low Voltage Control Cable Trough Location for Optional Alber Monitoring Equipment Battery Service Tray Battery Breaker Battery Service Tray Supports Battery Interface Board (BIB) Ground Bus Batteries (Typical View Shown) Front View NOTCHED END OF SUPPORT SLIPS INTO SLOT AT BATTERY RAIL ABOVE SERVICE TRAY SUPPORTS ANGLED OUT TO PROVIDE BATTERY CLEARANCE SLOT IN SUPPORT IS SECURED BY SCREW-IN CONNECTOR AT CORNER OF BATTERY SERVICE TRAY BATTERY TRAY EXTENDED ONTO SERVICE TRAY SERVICE TRAY INSTALLED Liebert® NXL™ Battery System 14 Installation Drawings Figure 10 Terminal details, Liebert Top-Terminal Battery Cabinet See Bus Termination Detail Negative Term. Bus (-) Positive Term. Bus (+) Top View + - Ground Bus (See Detail) 1.75 (45) ø.56 (14) 1.75 (45) Ground Bus Detail 1.75 (45) 1.75 (45) ø.53 (14) Front View Right Side View * Doors And Covers Removed for Clarity Bus Termination Detail CB1-3 CB1-3 Notes 1. All dimensions are in inches (mm) 2.Top and bottom cable entry available through removable access plates. 3. Control wiring and power wiring must be run in separate conduit. 4. Unless otherwise noted, use copper or aluminum DO NOT conductors suitable for at least 75°C. 5. All wiring must be in accordance with national DOUBLE-STACK and local electrical codes. 6. For cabinets ordered as stand-alone, the negative and positive terminal bus does not extend to full width of battery cabinet. 7. 24" minimum clearance above unit is required for air exhaust and service access. 15 1.75 (45) LUGS Liebert® NXL™ Battery System Liebert® NXL™ Battery System 16 Detail B Detail A A Jar 16 B Install M10 washer, lockwasher and bolt to secure units together front and rear Note: Jar 28 must be moved forward or removed to install rear hardware. Rear cutouts are provided if rear access is provided. Install M10 washer, lockwasher and bolt to secure units together front and rear Note: Jar 16 must be Negative (-) moved forward or removed to install rear hardware. Rear Positive (+) cutouts are provided if rear access is provided. Isometric View Install snap bushing in corner post before routing these wires Jar 28 Install snap bushing in corner post before routing these wires Top View Reuse M12 hardware Torque to 480 in-lb (54Nm) Front Use M10 hardware supplied on bus Torque to 240 in-lb (27Nm) Tywrap here to secure wires in place Tywrap here to secure wires in place Busbars shown connected between Cabinet A & Cabinet B (busbar quantity varies) Remove these busbars and keep the hardware to secure busbars between Cabinet A & Cabinet B Route two supplied wires (W17) from Jar 15 (+) to Jar 16 (-) Note: Install bushing first. Install snap bushing in corner post before routing these wires Remove M6 hardware used to secure lugs in place and discard Connect lugs to bus directly above insulator and secure with M8 hardware supplied on bus. Typ 8 places. Torque to 180 in-lb (20Nm) Route two supplied wires (W16) from Jar 1 (-) to BCB breaker in (-) Note: Install bushings first. Tywrap here to secure wires in place Cabinet B Figure 11 Use M8 hardware supplied on bus Torque to 180 in-lb (20Nm) Cabinet A Installation Drawings Front Terminal Battery Cabinet shipping split 17 14" (356mm) 37.8" (960mm) Bottom Cable Entry See Detail B 76.8" (1950mm) Front 18" (457mm) Center of Gravity Both Sections 33.5" (850mm) Notes: Front View Right Side 1. All dimensions are in in [mm]. 2. 24" minimum clearance above unit required for air exhaust. 3. Keep cabinet within 15 degrees of vertical. 4. Top cable entry available through removable access plates. 5. Control wiring and power wiring must be run in separate conduit. 6. Width dimension is with side panels. Subtract 1.4" (35mm) for dimensions with both side panels removed. 7. Depth dimension includes the front door and rear panel. 8. Refer to battery technical information drawing. 12.2" (311mm) 38" (965mm) Center of Gravity 25.2" (640) 63" (1600mm) Top View Cable Entry See Detail A Bottom Cable Entry High Voltage Cable Entry 0.9" (22.7mm) 4.3" [110.0] 3.7" (95mm) to Panel 3.6" (91mm) to Panel 10" (254mm) Low Voltage Cable Entry 1.8" (45mm) to Panel 10.1" (257mm) to Panel 21.2" (538mm) Detail B Front 9.4" (257mm) Front Detail A 11.3" (287mm) Installation Drawings Figure 12 Front Terminal Battery Cabinet outline drawing Liebert® NXL™ Battery System Installation Drawings Figure 13 Front Terminal Battery Cabinet main components, layout High Voltage Control Cable Trough Positive Battery Bus Low Voltage Control Cable Trough Negative Battery Bus Location for Optional Alber Monitoring Equipment Front Battery Breaker Battery Typ. Battery Typ. Battery Interface Board (BIB) Ground Bus Right Side View With Panels Removed Front View Liebert® NXL™ Battery System 18 Installation Drawings Figure 14 Front terminal detail drawing See Bus Termination Detail Negative Term. Bus (-) Positive Term. Bus (+) (+) (-) * Doors and covers removed for clarity Ø.56 [14] TYP. FRONT 1.75 [44] TOP VIEW (SECTION "B") 1.75 [44] GROUND BUS DETAIL 1.75 [45] TYP. Ground Bus (See Detail) 1.75 [44] Ø.56 X .75" SLOT [Ø14 X 19] TYP. BUS TERMINATION DETAIL FOR POS. AND NEG. BUSBAR RIGHT SIDE VIEW FRONT VIEW (SECTION "B") NOTES: 1. All dimensions are in in [mm]. 2. Top and bottom cable entry available through removable access plates. 3. Control wiring and power wiring must be run in separate conduit. 4. Unless otherwise noted, use copper or aluminum conductors suitable for at least 75°C. 5. All wiring is to be in accordance with national and local electrical codes. 6. For cabinets ordered as stand-alone, the negative and positive terminal bus does not extend to full width of battery cabinet. 7. 24" minimum clearance above unit is required for air exhaust and service. 19 Liebert® NXL™ Battery System Installation Drawings Figure 15 Liebert NXL Stand-Alone Junction Cabinet terminal wiring .56 (14) Typ 2.2 (55) 16 Places .56 (14) Typ .56 (14) Typ 1.7 (44) X 0.7 (18) Slot 16 Places 1.8 (45) Typ. Each Busbar 16 Places 2.2 (55) 18 Places 2.2 (55) 16 Places 2.2 (55) 18 Places Ground Bus 2.2 (55) 18 Places Negative Bus Positive Bus 30.9 (785) 33.5 (805) CB1-3 CB1-3 Positive Bus Do not double stack lugs (two lugs on same side of busbar). This is to prevent the cables from coming into contact with other busbars. Ground Bus Lugs 76.9 (1952) Negative Bus 41.3 (1050) Bolt Busbar DUAL LUG CONNECTION DETAIL 13.7 (348) 8.7 7.4 9.0 (189) (221) (228) Right Side View Front View 13.6 (346) Notes: 1. All dimensions are in inches (mm). 2. Control wiring and power wiring must be run in separate conduit. 3. Unless otherwise noted, use copper or aluminum conductors suitable for at least 75°C. 4. Widths are without side panels. The width is 32.1" (815mm) with side panels. 5.The depth dimension includes the front door and rear panel. Liebert® NXL™ Battery System 20 Installation Drawings Figure 16 Liebert NXL Attached Junction Cabinet—terminal detail and outline drawing 1.75 (44) Typ Terminal Details O .56 (14) Typ 11.4 (290) 7 (178) Positive Bus Bottom 2 (51) Typ 4.4 (112) 1.75 (44) Typ Positive Bus O .56 (14) Typ 2 (51) Typ Negative Bus Bottom O .56 (14) Typ Negative Bus Ground Bus 1.75 (44) Typ CB1-3 Do not double stack lugs (two lugs on same side of busbar). This is to prevent the cables from coming into contact with other busbars. .56 (14) TYP 1.25 x 0.5 (32 x 13) 49.1 (1248) 1.75 (44) TYP 37.3 (948) CB1-3 Bus Detail Ground Bus Slot 8 Places Typical Lugs 26.0 (661) Bolt Front View Positive Bus Top Right Side Mounting Slots 8 Places Typical Negative Bus Top Busbar DUAL LUG CONNECTION DETAIL Outline Drawing 76.8 (1950) WARNING!!! Unit Removal and Unit Mobility Instructions Brackets MUST remain attached to the frame until such time that the unit is being located in its final installed position. (The final installation will always require the unit to be bolted to another Liebert NXL product.) Failure to comply with these instructions could result in equipment damage and/or injury to personnel 38.3 (973) 38.3 (973) 7.9 (201) 15.5 ( 393) Front View 21 33.5 ( 850) 15.1 ( 382) Right Side Liebert® NXL™ Battery System Installation Drawings Figure 17 Liebert NXL Battery Cabinet control wiring CAN cable to be run in trough closest to the front of the unit TROUGH UVR TRIP - Optional UVR TRIP- Optional AUX. CONTACT 1 AUX. CONTACT 1 (RED) AUX. CONTACT 1 3-BRKR-POS Optional Battery Voltage Sense Cable (BLK) Thermistor (Optional) 1- BRKR- NEG 1 1 2 3 1 2 3 4 5 TB1150 1 7 6 5 4 3 2 1 P1152 NOTES USE WIRE TIE AS NECCESSARY FOR ROUTING AND SECURING WIRE HARNESSES. This end field-connected to other cabinets P1153 Liebert NXL Battery Cabinet Control Wiring Routing TB1151 TB1158 ( BATTERY MONITORING SYSTEM ) BATTERY INTERFACE BOARD (BIB) 24V (RED) GND (BLK) CANH (WHT) Liebert® NXL™ Battery System TB1156 1 +24V (RED) 2 GND (BLK) 3 CANH (WHT) CAN Cable (Belden 9156 or Equivalent) TB1154 4 CANL (BLK) CANL (BLK) 2 1 Control Wiring Diagram 22 Installation Drawings Figure 18 Attached battery cabinet connections Jumper Busbars (supplied with battery cabinet) Note: Torque to 240in-lb (27 N-M) Jumper Busbars (supplied with battery cabinet) Note: Connections cannot be made if cabinets ordered as stand-alone. Figure 19 Ground strap location for connected cabinets BATTERY CABINET BATTERY CABINET REFERENCE OF CORNER POST OF CONNECTED CABINETS A FRONT SIDE OF UNITS TYPICA L GROUND STRA P INSTALLATION FOR BATTERY CABINE T TO BATTERY CABINE T CONNECTIONS CABINE T-TO-CABINE T BOLTING INSTRUCTIONS B 2 BATTERY CABINET 1 DETAIL A 1 2 DETAIL B TYPICA L GROUND STRA P INSTALLATION FOR BATTERY CABINE T TO UPS OR ANCILLA RY CABINE T CONNECTIONS FRONT SIDE OF UNITS 23 NOTES: 1. Apply ground strap hardware to specified locations. 2. Torque Values: M6: ( 5 Nm ) 40 IN-LB M10: ( 14 Nm ) 120 IN-LB Liebert® NXL™ Battery System Installation Drawings Figure 20 Top-Terminal Battery Cabinet interconnection wiring to 250-400kVA UPS A2 B2 B2 B1 For left -mounted installations, the DC cables will be routed along the interior rear of the UPS. The cables can be supported using lances in the UPS sheet metal. A1 A2 D A1 D B1 C C UPS Table 1 Run BATTERY CABINET Top-Terminal Battery Cabinet interconnection wiring to 250-400kVA UPS From To Conductors Battery Cabinet - DC+ Busbar Positive Power - RH Mount/Stand Alone A1 UPS - DC+ Busbar B1 UPS - DC- Busbar Battery Cabinet - DC- Busbar Negative Power - RH Mount/Stand Alone A2 UPS - DC+ Busbar Battery Cabinet - DC+ Busbar Positive Power - Left Mount B2 UPS - DC- Busbar Battery Cabinet - DC- Busbar Negative Power - Left Mount C* UPS - Ground Battery Cabinet - Ground Ground UPS - External Interface Board (EIB) Battery Cabinet - Battery Interface Board (BIB) CAN Control Cables D * This is used only for detached cabinets. If the cabinets are attached, use the grounding shown in Figure 19. Liebert® NXL™ Battery System 24 Installation Drawings Figure 21 Liebert NXL Top-Terminal Battery Cabinet interconnect wiring to Liebert NXL Stand-Alone Junction Cabinet A B B C A C Battery Cabinet Table 2 Junction Cabinet Liebert NXL Top-Terminal Battery Cabinet interconnect wiring to Liebert NXL Junction Cabinet Run From To A Battery Cabinet Negative Bus Junction Negative Bus Negative DC Power B Battery Cabinet Positive Bus Junction Positive Bus Positive DC Power C Battery Cabinet Ground Junction Ground Ground 25 Conductors Liebert® NXL™ Battery System Installation Drawings Figure 22 Terminal details Liebert NXL UPS 250kVA - 400kVA to front terminal battery point-to-point wiring A2 B2 All power and control wiring is supplied if units are ordered as attached. B1 UPS - REAR VIEW DC BUS CONNECTIONS B2 For left-mounted installations, the DC A1 cables will be routed along the interior rear of the UPS. The cables can be supported using lances in the UPS sheet metal. A2 D TOP VIEW A1 B1 D C C BATTERY CABINET UPS Table 3 Terminal details Liebert NXL UPS 250kVA - 400kVA to front terminal battery point-topoint interconnect wiring Run From To Conductors A1 UPS DC Positive Busbar Battery Cabinet Positive Bus Positive DC Power RH Mount / Stand Alone B1 UPS DC Negative Busbar Battery Cabinet Negative Bus Negative DC Power RH Mount / Stand-Alone A2 UPS DC Positive Busbar Battery Cabinet Positive Bus Positive DC Power Left Mount B2 UPS DC Negative Busbar Battery Cabinet Negative Bus Negative DC Power Left Mount C* UPS Ground Battery Cabinet Ground Ground UPS External Interface Board (EIB) Battery Cabinet Battery Interface Board (BIB) CAN Control Cables D * For detached units only Liebert® NXL™ Battery System 26 Installation Drawings A E C TOP VIEW Battery Cabinet G B A B D Stand-Alone Junction Cabinet C F All power and control wiring is supplied by others. UPS G F E D Figure 23 Terminal details Liebert NXL 250-400kVA front terminal battery and Stand-Alone Junction Cabinet point-to-point wiring 27 Liebert® NXL™ Battery System Installation Drawings Table 4 Terminal details Liebert NXL 250-400kVA front terminal battery and Stand-Alone Junction Cabinet point-to-point interconnect wiring Run From To Conductors A Battery Cabinet Negative Bus Junction Negative Bus Negative DC Power B Battery Cabinet Positive Bus Junction Positive Bus Positive DC Power C Battery Cabinet Ground Junction Ground Ground D Junction Positive Bus UPS Cabinet Positive Bus Positive DC Power E Junction Negative Bus UPS Cabinet Negative Bus Negative DC Power F Junction Ground UPS Cabinet Ground Ground G Battery Cabinet Battery Interface Board (BIB) UPS External Interface Board (EIB) CAN Control Cables Figure 24 Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Attached Junction Cabinet, point-to-point wiring A2 and B2 - RH Mount A1 and B1 - LH Mount A1 A2 B1 B2 B A TOP VIEW D E DC (-) Input E DC (+) Input D G C F ABC F G Ground Bus DC Input C Attached Junction Cabinet Right Side UPS Left Front (Part A) UPS Left Side Rectifier (Part A) Table 5 Battery Cabinet Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Attached Junction Cabinet, point-to-point interconnect wiring Run From A1 Battery Cabinet Negative Bus Junction Negative Bus Negative DC Power (LH Mount) B1 Battery Cabinet Positive Bus Junction Positive Bus Positive DC Power (LH Mount) A2 Battery Cabinet Negative Bus Junction Negative Bus Negative DC Power (RH Mount) B2 Battery Cabinet Positive Bus Junction Positive Bus Positive DC Power (RH Mount) D Junction Positive Bus UPS Cabinet Positive Bus Positive DC Power E Junction Negative Bus UPS Cabinet Negative Bus Negative DC Power F Junction Ground UPS Cabinet Ground Ground G Battery Cabinet Battery Interface Board (BIB) UPS External Interface Board (EIB) CAN Control Cables Liebert® NXL™ Battery System To 28 Conductors Installation Drawings Figure 25 Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Stand-Alone Junction Cabinet, point-to-point wiring B A C F A E B D Top View E DC (-) Input DC (+) Input D G C ABC G Ground Bus DC Input F UPS Left Side Rectifier (Part A) Stand-Alone Junction Cabinet Battery Cabinet UPS Left Front (Part A) Table 6 Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Stand-Alone Junction Cabinet, point-to-point interconnect wiring Run From To Conductors A Battery Cabinet Negative Bus Junction Negative Bus Negative DC Power B Battery Cabinet Positive Bus Junction Positive Bus Positive DC Power C Battery Cabinet Ground Junction Ground Ground D Junction Positive Bus UPS Cabinet Positive Bus Positive DC Power E Junction Negative Bus UPS Cabinet Negative Bus Negative DC Power F Junction Ground UPS Cabinet Ground Ground G Battery Cabinet Battery Interface Board (BIB) UPS External Interface Board (EIB) CAN Control Cables 29 Liebert® NXL™ Battery System Installation Drawings Figure 26 Terminal details Liebert NXL 500kVA to Top-Terminal battery point-to-point wiring B DC (-) INPUT DC (+) INPUT D A A UPS LEFT SIDE RECTIFIER (PART A) B C UPS LEFT FRONT (PART A) B D A TOP VIEW NOTE: 1. All power and control wiring is supplied. 2. The units must be attached. 3. UPS cabinet not to scale to battery cabinet. BATTERY CABINET Table 7 Terminal details Liebert NXL 500kVA to top-terminal battery point-to-point interconnect wiring Run From To Conductors A UPS Positive Bus Battery Cabinet Positive Bus Positive DC Power B UPS Negative Bus Battery Cabinet Negative Bus Negative DC Power D UPS External Interface Board (Eib) Battery Cabinet Battery Interface Board (BIB) CAN Control Cables Liebert® NXL™ Battery System 30 Installation Drawings Figure 27 Terminal details Liebert NXL UPS 500kVA to front terminal battery point-to-point wiring B DC (-) Input DC (+) Input D A A UPS LEFT SIDE RECTIFIER (PART A) B C UPS LEFT FRONT (PART A) A B D TOP VIEW NOTE: 1. All power and control wiring is supplied. 2. The units must be attached. 3. UPS cabinet not to scale to battery cabinet. BATTERY CABINET Table 8 Terminal details Liebert NXL UPS 500kVA to front terminal battery point-to-point interconnect wiring Run From A UPS Positive Bus B D To Conductor Battery Cabinet Positive Bus Positive DC Power UPS Negative Bus Battery Cabinet Negative Bus Negative DC Power UPS External Interface Board (EIB) Battery Cabinet Battery Interface Board (BIB) CAN Control Cables 31 Liebert® NXL™ Battery System Installation Drawings Figure 28 Liebert NXL terminal details UPS 625/750kVA to front terminal battery and Attached Junction Cabinet point-to-point wiring E DC (-) INPUT DC (+) INPUT D A B C G A2 & B2 - RH MOUNT A1 & B1 - LH MOUNT A1 A2 B1 B2 GROUND BUS DC INPUT F UPS Left Side Rectifier (Part A) B Top View UPS Left Front (Part A) A D E G F Battery Cabinet Table 9 1. All power and control wiring between battery cabinet and junction cabinet is supplied. 2. All power wiring between junction cabinet and UPS is supplied by others. 3. All control wiring between battery cabinet and UPS is supplied by others Attached Junction Cabinet Right Side Liebert NXL terminal details UPS 625/750kVA to front terminal battery and Attached Junction Cabinet point-to-point Interconnect wiring Run From A1 Battery Cabinet Negative Bus To Conductors Junction Negative Bus Negative DC Power (LH Mount) B1 Battery Cabinet Positive Bus Junction Positive Bus Positive DC Power (LH Mount) A2 Battery Cabinet Negative Bus Junction Negative Bus Negative DC Power (RH Mount) B2 Battery Cabinet Positive Bus Junction Positive Bus Positive DC Power (RH Mount) D Junction Positive Bus UPS Cabinet Positive Bus Positive DC Power E Junction Negative Bus UPS Cabinet Negative Bus Negative DC Power F Junction Ground UPS Cabinet Ground Ground G Battery Cabinet Battery Interface Board (BIB) UPS External Interface Board (EIB) CAN Control Cables Liebert® NXL™ Battery System 32 Installation Drawings TOP VIEW Battery Cabinet C G B D B A C F Stand-Alone Junction Cabinet A E UPS Left Side Rectifier (Part A) F GROUND BUS DC INPUT G D E DC (-) INPUT DC (+) INPUT A All power and control wiring is supplied by others. B C UPS Left Front (Part A) Figure 29 Liebert NXL terminal details UPS 625/750kVA to front terminal battery and Stand-Alone Junction Cabinet point-to-point wiring Table 10 LIebert NXL terminal details UPS 625/750kVA to front terminal battery and Stand-Alone Junction Cabinet point-to-point interconnect wiring Run From To Conductors A Battery Cabinet Negative Bus Junction Negative Bus Negative DC Power B Battery Cabinet Positive Bus Junction Positive Bus Positive DC Power C Battery Cabinet Ground Junction Ground Ground D Junction Positive Bus UPS Cabinet Positive Bus Positive DC Power E Junction Negative Bus UPS Cabinet Negative Bus Negative DC Power F Junction Ground Ps Cabinet Ground Ground G Battery Cabinet Battery Interface Board (BIB) UPS External Interface Board (EIB) CAN Control Cables 33 Liebert® NXL™ Battery System Installation Drawings Figure 30 Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and Attached Junction Cabinet, point-to-point wiring A2 and B2 - RH Mount A1 and B1 - LH Mount A1 A2 B1 B2 B Top View DC (-) E INPUT A D DC (+) Input D G G E A B F C Ground Bus DC Input F UPS Left Side Rectifier (Part A) Table 11 Run UPSLeft Front (Part A) Attached Junction Cabinet Right Side Battery Cabinet Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and Attached Junction Cabinet, point-to-point wiring From To Conductor A1 Battery Cabinet Negative Bus Junction Negative Bus Negative DC Power (LH Mount) B1 Battery Cabinet Positive Bus Junction Positive Bus Positive DC Power (LH Mount) A2 Battery Cabinet Negative Bus Junction Negative Bus Negative DC Power (RH Mount) B2 Battery Cabinet Positive Bus Junction Positive Bus Positive DC Power (RH Mount) D Junction Positive Bus UPS Cabinet Positive Bus Positive DC Power E Junction Negative Bus UPS Cabinet Negative Bus Negative DC Power F Junction Ground UPS Cabinet Ground Ground G Battery Cabinet, Battery Interface Board (BIB) UPS External Interface Board (EIB) CAN Control Cables Liebert® NXL™ Battery System 34 Installation Drawings Figure 31 Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and Stand-Alone Junction Cabinet, point-to-point wiring A B C F Top View DC (-) E Input DC (+) Input D B D A E G G A B C C GROUND BUS DC INPUT F UPS Left Side Rectifier (Part A) Table 12 Battery Cabinet Stand-Alone Junction Cabinet Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and Stand-Alone Junction Cabinet, point-to-point interconnect wiring Run A UPS Left Front (Part A) From To Conductors Battery Cabinet Negative Bus Junction Negative Bus Negative DC Power B Battery Cabinet Positive Bus Junction Positive Bus Positive DC Power C Battery Cabinet Ground Junction Ground Ground D Junction Positive Bus UPS Cabinet Positive Bus Positive DC Power E Junction Negative Bus UPS Cabinet Negative Bus Negative DC Power F Junction Ground UPS Cabinet Ground Ground G Battery Cabinet Battery Interface Board (BIB) UPS External Interface Board (EIB) CAN Control Cables 35 Liebert® NXL™ Battery System Installation Drawings D UPS LEFT SIDE RECTIFIER (PART A) DC (+) INPUT A BATTERY CABINET B A NOTE: 1. All power and control wiring is supplied. 2. The units must be attached. 3. UPScabinet not to scale to battery cabinet. B DC (-) INPUT A B C UPS LEFT FRONT (PART A) D Figure 32 Terminal details Liebert NXL UPS 625/750kVA to battery point-to-point wiring Table 13 Terminal details Liebert NXL UPS 625/750kVA to battery point-to-point interconnect wiring Run From A UPS Positive Bus B D To Conductor Battery Cabinet Positive Bus Positive DC Power UPS Negative Bus Battery Cabinet Negative Bus Negative DC Power UPS External Interface Board (EIB) Battery Cabinet Battery Interface Board (BIB) CAN Control Cables Liebert® NXL™ Battery System 36 Installation Drawings UPS Left Side Rectifier (Part A) Attached Junction Cabinet Right Side E A Battery Cabinet F G D Top View B2 B A2 B1 A2 & B2 - RH MOUNT A1 A1 & B1 - LH MOUNT Table 14 Run F GROUND BUS DC INPUT A D DC (+) INPUT DC (-) E INPUT NOTES 1. All power and control wiring between battery cabinet and junction cabinet is supplied. 2. All power wiring between junction cabinet and UPS is supplied by others. 3. All control wiring between battery cabinet and UPS is supplied by others. B C UPS Left Front (Part A) G Figure 33 Terminal details UPS 625/750kVA to front terminal battery and Attached Junction Cabinet point-to-point wiring Terminal details UPS 625/750kVA to front terminal battery and Attached Junction Cabinet point-to-point interconnect wiring From To Conductor A1 Battery Cabinet Negative Bus Junction Negative Bus Negative DC Power (LH Mount) B1 Battery Cabinet Positive Bus Junction Positive Bus Positive DC Power (LH Mount) A2 Battery Cabinet Negative Bus Junction Negative Bus Negative DC Power (RH Mount) B2 Battery Cabinet Positive Bus Junction Positive Bus Positive DC Power (RH Mount) D Junction Positive Bus UPS Cabinet Positive Bus Positive DC Power E Junction Negative Bus UPS Cabinet Negative Bus Negative DC Power F Junction Ground UPS Cabinet Ground Ground G Battery Cabinet Battery Interface Board (BIB) UPS External Interface Board (EIB) CAN Control Cables 37 Liebert® NXL™ Battery System Installation Drawings GROUND BUS DC INPUT F UPS Left Side Rectifier (Part A) DC (+) INPUT D A E Stand-Alone Junction Cabinet C F TOP VIEW Battery Cabinet C G B D B A All power and control wiring is supplied by others. DC (-) E INPUT A B C UPS Left Front (Part A) G Figure 34 Terminal details 625/750kVA to front terminal battery and Stand-Alone Junction Cabinet point-to-point wiring Table 15 Terminal details 625/750kVA to front terminal battery and Stand-Alone Junction Cabinet point-to-point interconnect wiring Run From To Conductor A Battery Cabinet Negative Bus Junction Negative Bus Negative DC Power B Battery Cabinet Positive Bus Junction Positive Bus Positive DC Power C Battery Cabinet Ground Junction Ground Ground D Junction Positive Bus UPS Cabinet Positive Bus Positive DC Power E Junction Negative Bus UPS Cabinet Negative Bus Negative DC Power F Junction Ground UPS Cabinet Ground Ground G Battery Cabinet Battery Interface Board (BIB) UPS External Interface Board (EIB) CAN Control Cables Liebert® NXL™ Battery System 38 Installation Drawings Figure 35 Typical Alber battery monitoring connections Input Fuse for Alber Power Alber Data Collector Module Alber Controller Module TR AY #1 TR AY #1 0 TR AY #2 TR AY #9 TR AY #3 TR AY #8 TR AY #7 TR AY #4 TR AY #5 Alber Power Transformer TR AY #6 39 Liebert® NXL™ Battery System Installation Drawings --- --- --RX TX --- --TX RX 24VAC Input 24VAC #3 24VAC #4 24VAC #5 24VAC #6 TELCO 24VAC #2 --- --- RX TX 24VAC #1 LAN/LOCAL 24VAC Input 230VAC 60Hz 230VAC 60Hz --- BDS-40 Data Collection Module #1 Liebert® NXL™ Battery System UPS Cabinet 40 480VAC 60Hz Battery Interface Board TB1158 RESET RESET MAJOR NO MAJOR NC MAJOR CM MINOR NO MINOR NC MINOR CM RX TX --- BDS-40 Data Controller +24VAC INPUT ETHERNET BATTERY CABINET #1 24VAC Input RX BDS-40 Data Collection Module #2 TX BATTERY CABINET #3 BDS-40 Data Collection Module #3 --- BATTERY CABINET #4 BDS-40 Data Collection Module #4 BATTERY CABINET #2 Figure 36 Alber battery monitoring wiring to multiple battery cabinets Installation Drawings Figure 37 Alber battery monitoring assembly diagram UPS Output - Phase A Use Pilot Hole on Busbar Locate fuse label as close to fuses as possible UPS Output - Phase C Use Pilot Hole on Busbar Mount fuses to corner post in input/output compartment of UPS module. Choose best location based on bottom or top power cabling. Connect cables from UPS output busbars to fuse block. UPS Output Section Fuse Block Installation This harness is intended for use only when battery cabinet is connected directly to UPS. For all other instances, customer must supply wire. Secure supplied wire harness to busbar with supplied hardware. ALBER BATTERY MONITORING XFMR Harness factory-installed. Verify transformer connection Prior to startup. See diagram below. Wire Harness V_OUT_A F4 F75 F5 F76 V_OUT_C NXL BATTERY CABINET UPS MODULE OUTPUT TOP TERMINALS FROM F5 FUSE IN BAT CAB BOTTOM TERMINALS FROM F4 FUSE IN BAT CAB 300 V 240 V 270 V 208 V 200 V 0V 300 V 240 V 270 V 208 V 200 V 0V XFMR CONNECTION DIAGRAM X1 Table 16 230 V X2 Alber battery monitoring assembly connections Input Voltage Alber Transformer-2 (Wht) Jumper Alber Transformer-1 (Blk) F4-F5 Fuse Rating 600 0 (Top) 300 (Top) to 0 (Bottom) 300 (Bottom) 2.25 A, 600VAC 480 0 (Top) 240 (Top) to 0 (Bottom) 240 (Bottom) 1.25 A, 600VAC 380 0 (Top) 300 (Top) to 208 (Bottom) 300 (Bottom) 1 A, 600VAC 208 0 (Top) 0 (Top) to 0 (Bottom) and 208 (Top) to 208 (Bottom) 208 (Top) 0.75A, 600VAC 41 Liebert® NXL™ Battery System Installation Drawings Figure 38 Top-Terminal battery configuration REAR OF TRAY JAR 2 + JAR 3 + + + + - + FRONT OF TRAY REAR OF TRAY 10 TR AY # JAR 5 + JAR 6 + JAR 7 + 2 + - TRAY #9 AY # TRAY #2 TR + 9 + FRONT OF TRAY 3 TR AY # 8 JAR 9 + + + + AY # TRAY #4 TR AY # 6 FRONT OF TRAY REAR OF TRAY + JAR 13 JAR 14 + JAR 15 + + JAR 20 JAR 19 + JAR 18 + JAR 16 JAR 17 FRONT OF TRAY JAR 26 FRONT OF TRAY REAR OF TRAY + - + JAR 27 JAR 25 REAR OF TRAY + + + - FRONT OF TRAY + 5 JAR 30 JAR 28 JAR 29 TRAY #5 TR JAR 31 + - REAR OF TRAY + JAR 32 JAR 12 7 4 JAR 11 AY # AY # JAR 10 + TR TR REAR OF TRAY + - TRAY #8 TRAY #3 AY # JAR 33 REAR OF TRAY TR JAR 34 + - + JAR 35 FRONT OF TRAY AY # JAR 36 JAR 8 TR JAR 37 REAR OF TRAY 1 JAR 38 FRONT OF TRAY AY # JAR 39 JAR 4 TR JAR 40 TRAY #7 + TRAY #10 JAR 1 TRAY #1 REAR OF TRAY + - FRONT OF TRAY TRAY #6 + JAR 24 + JAR 23 + JAR 22 + JAR 21 FRONT OF TRAY JAR (BATTERY) CONFIGURATION Liebert® NXL™ Battery System 42 Installation Drawings Figure 39 Front-Terminal battery configuration JAR #30 JAR #28 JAR #3 JAR #1 CABINET A CABINET B Top of Cabinet - + - + - + - 30 29 28 JAR #27 JAR #25 JAR #6 3 + - + - + - JAR #9 JAR #7 + - 6 JAR #19 JAR #12 JAR #10 + - + - + 1 + - + - + - 5 + 4 + - + - 9 24 23 22 - + - JAR #21 2 - + - 27 26 25 JAR #22 + - JAR #4 - JAR #24 + - 8 + - + 7 + - + 21 20 19 12 11 10 - + - + - + - + - + - + 18 17 16 15 14 13 Bottom of Cabinet JAR #18 JAR #17 JAR #16 JAR #15 JAR #14 JAR #13 CABLE INTERCONNECT DIAGRAM FRONT 43 Liebert® NXL™ Battery System Installation Drawings Figure 40 Busbar connection between Battery Cabinet and Attached Junction Cabinet Left-Side Busbar Connections Note: This connection is the same for top-terminal (12V) battery cabinets and front-terminal (16V) battery cabinets. Right-Side Busbar Connections Liebert® NXL™ Battery System 44 Specifications 4.0 SPECIFICATIONS Table 17 Liebert NXL Battery Cabinet specifications Values Top-Terminal Cabinet Battery Cabinet Parameters Battery Type Front-Terminal Cabinet VRLA (Valve Regulated Lead Acid) Nominal Battery Bus, VDC 480V Battery Float Voltage, VDC 540V 384V (for VRLA / Flooded Lead Acid) Minimum EOD Voltage, VDC Battery Discharging Maximum Current (EOD), A See Table 20 Physical Parameters and Standards Width, in. (mm) 1 Depth, in. (mm) 56.5 (1435) 2 Height, in. (mm) Weight, lb (kg) approx. 63.0 (1600) 33.5 (850) 33.5 (850) 76.8 (1950) 76.8 (1950) Table 22 Standard Color Black (ZP-7021) More than 180° Front Door Opening (for serviceability) IP 20 (with and without front door open) Degree of Protection for UPS Enclosure Minimum Clearance, Top 24" (610mm) Minimum Clearance, Back 0" Minimum Clearance, Sides 0" Cable Entrance Top or Bottom UL 1778; CSA 22.2 107.3 FCC Part 15, Class A; ISTA Procedure 1H; WEEE; IBC 2012/CBC 2010 Standards & Conformities Environmental Storage Temperature Range, °F (°C) -13°F to 158°F (-25°C to 70°C) 74°F to 80°F (23-27°C) for optimal battery life Operating Temperature Range, °F (°C) 32°F to 104°F (0 to 40°C) 74°F to 80°F (23-27°C) for optimal battery life up to 95% Non-Condensing (Operating and Non-Operating) Relative Humidity Maximum Altitude Above MSL, ft (m) 4920 (1500) (as per IEC 62040/3) 1% Maximum kW derate / 100m rise between 1500-3000m 1. Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels. 2. Depth dimensions include the front door and rear panel. 45 Liebert® NXL™ Battery System Specifications Table 18 Liebert NXL Junction Cabinet specifications Value Top-Terminal Attached Battery Specifications Stand-Alone Attached 480V Nominal Battery Bus, VDC Battery Float Voltage, VDC 540V 384V (for VRLA / Flooded Lead Acid) Minimum EOD Voltage, VDC Battery Discharging Max current (EOD), A Table 20 Physical Parameters Width, * in (mm) 15.5 (393) 30.9 (785) 17.5 (445) Depth, in (mm) ** 33.5 (850) 33.5 (850) 33.5 (850) 76.8 (1950) 76.8 (1950) 76.8 (1950) 255 (115) 400 (180) 255 (115) Height, in (mm) Weight, lb (kg) approx. Color Black (ZP-7021) Degree of Protection for UPS Enclosure IP 20 Minimum clearance, Top 24" (610mm) Minimum clearance, Back 0" Minimum clearance, Sides 0" Location of cable entrance Top or Bottom UL 1778; CSA 22.2 107.3; FCC Part 15, Class A ISTA Procedure 1H; WEEE; IBC 2012/CBC 2010 Standards and Conformities Environmental Storage Temperature Range, °F (°C) -13°F to 158°F (-25°C to 70°C) Operating Temperature Range, °F (°C) 32°F to 104°F (0 to 40°C) Maximum 95% Non-Condensing (Operating and Non-Operating) Relative Humidity Maximum Altitude above MSL, ft (m) 4920 (1500) (as per IEC 62040/3) 1% maximum kW derate / 328ft rise between 4900-9800ft (100m rise between 1500-3000m) * Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels. ** Depth dimensions include the front door and rear panel. Alber® battery monitoring option specifications Table 19 Electrical Data Value Input Voltage 220-600VAC Input Current < 0.5A Frequency 60Hz Table 20 DC currents for Liebert NXL modules UPS Rating kVA kW Max Battery Current at EOD 250 225 615 300 270 730 400 360 980 500 450 1241 625 625 1645 750 675 1850 800 800 2061 1100 1100 2860 Liebert® NXL™ Battery System 46 Specifications Table 21 Liebert NXL Battery Cabinet internal breaker Model # Code Battery Type Required Breaker Thermal Trip Amps PR UPS12-300MR 400 RR UPS12-350MR 450 UR UPS12-400MR 500 WS UPS12-490MRLP 600 XR UPS12-540MR 600 PX HX300-FR 400 RX HX330-FR 450 UX HX400-FR 500 WX HX500-FR 600 XX HX540-FR 600 2K 16HX800F-FR 250kVA - 700A 300kVA - 800A 400kVA & above - 900A 4K 16HX925F-FR 600 RA 27HR3500 400 UA 31HR4000 500 WA 31HR5000 600 PG XE60 700 PH XE60 w/Jacket 700 VG XE95 700 VH XE95 w/Jacket 700 Table 22 Battery Code Liebert NXL Battery Cabinet approximate weights Manufacturer PR RR UR C&D Batteries Battery Model Total Weight lb (kg) UPS12-300MR 3910 (1774) UPS12-350MR 4265 (1935) UPS12-400MR 4600 (2087) UPS12-490MRLP 5545 (2515) XR UPS12-540MR 5545 (2515) PX HX300-FR 3760 (1706) RX HX330-FR 4200 (1905) UX HX400-FR 4760 (2159) WX HX500-FR 5750 (2608) XX HX540-FR 5850 (2653) WS 2K Enersys 16HX800F-FR 8510 (3860) 4K 16HX925F-FR 8990 (4078) PG XE60 3586 (1626) PH XE60 w/Jacket 3586 (1626) VG XE95 4706 (2135) VH XE95 w/Jacke 4706 (2135) QA 27HR3500 4000 (1814) 31HR4000 4320 (1960) 31HR5000 5280 (2395) SA WA East Penn 47 Liebert® NXL™ Battery System Specifications Table 23 Recommended external conduit and cable sizes from Liebert NXL UPS to DC source UPS Rating kVA (# of conduits); size of conduits; # -size of phase cables per conduit; size of cable for ground per conduit 250 (2) 2C 2-600kcmil, #1/0AWG (2) 2.5C 2-750kcmil, #3/0AWG 300 (2) 2.5C 2-750kcmil, #1/0AWG (3) 2.0C 2-500kcmil, #3/0AWG 400 (3) 2C, 2-500kcmil, #2/0AWG (3) 2.0C 2-600kcmil, #4/0AWG 500 (3) 2.5C, 2-750kcmil, #4/0AWG (4) 2.5C 2-700kcmil, 350kcmil 625 (5) 2.5C 2-600kcmil, 250kcmil (6) 2.5C 2-600kcmil, 400kcmil 750 (5) 2.5C, 2-600kcmil, 250kcmil (6) 2.5C 2-600kcmil, 400kcmil 800 (6) 2.5C 2-600kcmil, 350kcmil (7) 2.5C 2-700kcmil, 600kcmil 1100 (7) 2.5C 2-750kcmil, 400kcmil (8) 2.5C 2-700kcmil, 600kcmil 1. Recommended cable sizes are 167°F (75°C) (THW) wire at 86°F (30°C) ambient. Unless otherwise noted, use copper or aluminum conductors suitable for at least 167°F (75°C). 2. For continuous operations not at 86°F (30°C), Emerson recommends that the site planner choose the appropriate cable type based on the particular installation requirements. 3. Conduit size is based on FMC type conduit Table 24 Recommended lug sizes Cable Size T&B Copper One Hole T&B Copper Two Hole T&B Aluminum One Hole T&B Aluminum Two Hole #8AWG 54930BE 54850BE 60104-TB — #6AWG 54905BE 256-30695-868 60109-TB — #4AWG 54906BE 256-30695-733 60114-TB — #2-3AWG 54942BE 54811BE 60120 — #1AWG 54947BE 54857BE 60126 — #1/0AWG 54950BE 256-30695-593 60132 — #2/0AWG 54951BE 54862BE 60138 60238 #3/0AWG 54965BE 54864BE 60144 60244 #4/0AWG 54970BE 54866BE 60150 60250 250kcmil 54913BE 54868BE 60156 60256 300kcmil 54914BE 54870BE 60162 60262 350kcmil 54915BE 54872BE 60165 60267 400kcmil 54916BE 54874BE 60168 60269 500kcmil 54918BE 54876BE 60171 60273 600kcmil 54920BE 54878BE 60176 60275 750kcmil 54922BE 54880BE 60178 60277 Liebert® NXL™ Battery System 48 Specifications Table 25 Battery torque values Battery Code Battery Model Torque Value in-lb (Nm) PR UPS12-300MR 110 (12.4) RR UPS12-350MR 110 (12.4) UR Manufacturer C&D Batteries UPS12-400MR 110 (12.4) WS UPS12-490MRLP 110 (12.4) XR UPS12-540MR 110 (12.4) PX HX300-FR 65 (7.3) RX HX330-FR 65 (7.3) UX HX400-FR 65 (7.3) WX HX500-FR 65 (7.3) XX HX540-FR 65 (7.3) 16HX800F 100 (11.3) Enersys 2K 4K 16HX925F 100 (11.3) PG XE60 60 (6.8) PH XE60 w/Jacket 60 (6.8) VG XE95 60 (6.8) VH XE95 w/Jacket 60 (6.8) QA 27HR3500 65 (7.3) 31HR4000 65 (7.3) 31HR5000 65 (7.3) SA East Penn WA Table 26 Torque specifications, unless otherwise labeled Nut and Bolt Combinations Bolt Shaft Size Grade 2 Standard lb-in (Nm) Electrical Connections with Belleville Washers lb-in (Nm) 1/4 (M6) 53 (6.0) 46 (5.2) 5/16 (M8) 107 (12) 60 (6.8) 3/8 (M10) 192 (22) 95 (11) 1/2 (M12) 428 (48) 256 (29) Circuit Breakers with Compression Lugs (For Power Wiring) Current Rating lb-in (Nm) — 400 - 1200 Amps 300 (34) — Circuit Breakers with Compression Lugs (For Control Wiring) AWG Wire Size or Range lb-in (Nm) — #22 - #14 3.5 to 5.3 (0.4 to 0.6) — 49 Liebert® NXL™ Battery System Ensuring The High Availability Of Mission-Critical Data And Applications. Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™ from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. Liebert AC power, precision cooling and monitoring products and services from Emerson Network Power deliver Efficiency Without Compromise™ by helping customers optimize their data center infrastructure to reduce costs and deliver high availability. Technical Support / Service Web Site www.liebert.com Monitoring liebert.monitoring@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Single-Phase UPS & Server Cabinets liebert.upstech@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Three-Phase UPS & Power Systems 800-543-2378 Outside North America: 614-841-6598 Environmental Systems 800-543-2778 Outside the United States: 614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 Fax: +63 2 730 9572 While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2010 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. SL-25430_REV8_09-13 Emerson Network Power. The global leader in enabling Business-Critical Continuity™ AC Power Connectivity Embedded Computing Embedded Power DC Power Infrastructure Management & Monitoring Outside Plant Power Switching & Controls Precision Cooling EmersonNetworkPower.com Racks & Integrated Cabinets Services Surge Protection Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2010 Emerson Electric Co.