Liebert NXL Battery System Installation Manual

AC Power
For Business-Critical Continuity™
Liebert® NXL™ Battery System
Installation Manual
BATTERY CABINET PRECAUTIONS
The following warning applies to all battery cabinets supplied with UPS systems. Additional
warnings and cautions applicable to battery cabinets may be found in Important Safety
Instructions beginning on page 1.
! WARNING
Internal battery strapping must be verified prior to moving a battery cabinet (after initial
installation).
• Battery cabinets contain non-spillable batteries.
• Keep units upright.
• Do not stack.
• Do not tilt.
Failure to heed this warning could result in smoke, fire or electric hazard.
Call 1-800-LIEBERT prior to moving battery cabinets (after initial installation).
CONTACTING EMERSON NETWORK POWER® FOR SUPPORT
To contact the Emerson Network Power Liebert® Services for information or repair service in the
United States, call 1-800-LIEBERT (1-800-543-2378). Liebert Services offers a complete range of
startup services, repair services, preventive maintenance plans and service contracts.
For repair or maintenance service outside the 48 contiguous United States, contact Liebert Services,
if available in your area.
For Liebert Services to assist you promptly, have the following information available:
Part Numbers:
Serial Numbers:
Rating:
Date Purchased:
Date Installed:
Location:
Battery Voltage:
Battery Reserve Time:
Product Warranty Registration
To register for warranty protection, visit the Service and Support section of our Web site at:
www.liebert.com
Click on Product Registration and fill out the form.
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.0
MECHANICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2
Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3
Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3.1
1.3.2
1.4
Battery Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4.1
1.4.2
1.4.3
Moving the Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Raised Floor Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.5
System Composition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.0
BATTERY INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.1
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2
Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3
Cable Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4
Power Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4.1
2.4.2
2.4.3
2.4.4
Connected System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stand-Alone System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Attached/Detached System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
8
9
9
2.5
Control Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.6
Alber Monitoring System—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.7
External Battery Room Temperature Sensor—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.0
INSTALLATION DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
4.0
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
FIGURES
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
Figure 6
Figure 7
Figure 8
Figure 9
Figure 10
Figure 11
Figure 12
Figure 13
Figure 14
Figure 15
Shipping bolts—Top-Terminal Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Battery cabinets connected, attached to UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Battery cabinets connected, detached from UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Stand-alone battery cabinets, detached from UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring external interface board in UPS to battery interface board in battery cabinet . . . . . . . . 10
Control cable layout—Liebert NXL UPS to Liebert NXL Battery Cabinet . . . . . . . . . . . . . . . . . . 11
Battery temperature sensor control connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Outline drawing, Liebert Top-Terminal Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Main components, Liebert Top-Terminal Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Terminal details, Liebert Top-Terminal Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Front Terminal Battery Cabinet shipping split . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Front Terminal Battery Cabinet outline drawing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Front Terminal Battery Cabinet main components, layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Front terminal detail drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Liebert NXL Stand-Alone Junction Cabinet terminal wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
i
Figure 16
Figure 17
Figure 18
Figure 19
Figure 20
Figure 21
Figure 22
Figure 23
Figure 24
Figure 25
Figure 26
Figure 27
Figure 28
Figure 29
Figure 30
Figure 31
Figure 32
Figure 33
Figure 34
Figure 35
Figure 36
Figure 37
Figure 38
Figure 39
Figure 40
Liebert NXL Attached Junction Cabinet—terminal detail and outline drawing . . . . . . . . . . . . .
Liebert NXL Battery Cabinet control wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Attached battery cabinet connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ground strap location for connected cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Top-Terminal Battery Cabinet interconnection wiring to 250-400kVA UPS . . . . . . . . . . . . . . . .
Liebert NXL Top-Terminal Battery Cabinet interconnect wiring to Liebert NXL
Stand-Alone Junction Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details Liebert NXL UPS 250kVA - 400kVA to front terminal battery
point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details Liebert NXL 250-400kVA front terminal battery and Stand-Alone
Junction Cabinet point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Attached
Junction Cabinet, point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Stand-Alone
Junction Cabinet, point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details Liebert NXL 500kVA to Top-Terminal battery point-to-point wiring . . . . . . . .
Terminal details Liebert NXL UPS 500kVA to front terminal battery point-to-point wiring . . .
Liebert NXL terminal details UPS 625/750kVA to front terminal battery and Attached
Junction Cabinet point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liebert NXL terminal details UPS 625/750kVA to front terminal battery and Stand-Alone
Junction Cabinet point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and Attached
Junction Cabinet, point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and
Stand-Alone Junction Cabinet, point-to-point wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details Liebert NXL UPS 625/750kVA to battery point-to-point wiring . . . . . . . . . . .
Terminal details UPS 625/750kVA to front terminal battery and Attached Junction
Cabinet point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details 625/750kVA to front terminal battery and Stand-Alone Junction Cabinet
point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical Alber battery monitoring connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alber battery monitoring wiring to multiple battery cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alber battery monitoring assembly diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Top-Terminal battery configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Front-Terminal battery configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Busbar connection between Battery Cabinet and Attached Junction Cabinet . . . . . . . . . . . . . . .
ii
21
22
23
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
TABLES
Table 1
Table 2
Table 3
Table 4
Table 5
Table 6
Table 7
Table 8
Table 9
Table 10
Table 11
Table 12
Table 13
Table 14
Table 15
Table 16
Table 17
Table 18
Table 19
Table 20
Table 21
Table 22
Table 23
Table 24
Table 25
Table 26
Top-Terminal Battery Cabinet interconnection wiring to 250-400kVA UPS . . . . . . . . . . . . . . . .
Liebert NXL Top-Terminal Battery Cabinet interconnect wiring to Liebert NXL
Junction Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details Liebert NXL UPS 250kVA - 400kVA to front terminal battery
point-to-point interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details Liebert NXL 250-400kVA front terminal battery and Stand-Alone
Junction Cabinet point-to-point interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Attached
Junction Cabinet, point-to-point interconnect wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Stand-Alone
Junction Cabinet, point-to-point interconnect wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details Liebert NXL 500kVA to top-terminal battery point-to-point
interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details Liebert NXL UPS 500kVA to front terminal battery point-to-point
interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liebert NXL terminal details UPS 625/750kVA to front terminal battery and Attached
Junction Cabinet point-to-point Interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LIebert NXL terminal details UPS 625/750kVA to front terminal battery and
Stand-Alone Junction Cabinet point-to-point interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and
Attached Junction Cabinet, point-to-point wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and
Stand-Alone Junction Cabinet, point-to-point interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details Liebert NXL UPS 625/750kVA to battery point-to-point interconnect
wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details UPS 625/750kVA to front terminal battery and Attached Junction
Cabinet point-to-point interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal details 625/750kVA to front terminal battery and Stand-Alone Junction
Cabinet point-to-point interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alber battery monitoring assembly connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liebert NXL Battery Cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liebert NXL Junction Cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alber® battery monitoring option specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DC currents for Liebert NXL modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liebert NXL Battery Cabinet internal breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liebert NXL Battery Cabinet approximate weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Recommended external conduit and cable sizes from Liebert NXL UPS to DC source . . . . . . . .
Recommended lug sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Torque specifications, unless otherwise labeled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery torque values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iii
24
25
26
28
28
29
30
31
32
33
34
35
36
37
38
41
45
46
46
46
47
47
48
48
49
49
iv
Important Safety Instructions
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation of your
Liebert NXL Battery Cabinet and accessories. Read this manual thoroughly, paying special attention
to the sections that apply to your installation, before working with the battery system. Retain this
manual for use by installing personnel.
! WARNING
Risk of electrical shock. Can cause personal injury and death.
Special safety precautions are required for procedures involving handling, installation and
maintenance of the UPS system. Only properly trained and qualified personnel wearing
appropriate personal protective equipment should be involved in installing the Liebert NXL
Battery system or preparing the system for installation.
Special care must be taken when working with the batteries associated with this equipment.
When connected together, the battery terminal voltage will exceed 400VDC and is potentially
lethal. Be constantly aware that the battery system contains high DC as well as AC voltages.
Check for voltage with AC and DC voltmeters before making contact.
Observe all DC safety precautions before working on or near the DC system.
Follow all battery safety precautions when installing, charging or servicing batteries. In
addition to the hazard of electric shock, gas produced by batteries can be explosive and
sulfuric acid can cause severe burns.
The following precautions must be observed when working on batteries:
•
•
•
•
•
•
Remove watches, rings and other metal objects.
Use tools with insulated handles.
Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect charging source prior to connecting or disconnecting battery terminals.
Determine whether the battery is grounded. If it is grounded, remove source of ground.
Contact with any part of a grounded battery can result in electrical shock. The likelihood of
such shock will be reduced if such grounds are removed during installation and maintenance.
If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored
in a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with the skin, the affected area should be washed
immediately with water.
! WARNING
Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment
damage, personal injury and death.
Lead-acid batteries contain hazardous materials. Batteries must be handled, transported and
recycled or discarded in accordance with federal, state and local regulations. Because lead is a
toxic substance, lead-acid batteries must be recycled rather than discarded.
Do not dispose of a battery in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin
and eyes. It is toxic.
! WARNING
Risk of electric shock. Can cause personal injury and death.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or
those approved for use in fighting electrical fires.
1
Liebert® NXL™ Battery System
Important Safety Instructions
! WARNING
Risk of heavy unit falling over. Can cause equipment damage, injury and death.
Exercise extreme care when handling battery cabinets to avoid equipment damage or injury
to personnel. The battery system cabinets weigh from 3760 to 8990 lb. (1706 to 4078kg).
Locate center of gravity symbols
and determine unit weight before handling each
cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from
vertical at all times.
Slots at the base of the cabinets are intended for forklift use. Base slots will support the unit
only if the forks are completely beneath the unit.
! WARNING
Risk of electric shock. Can cause equipment damage, personal injury and death.
The area around the battery system must be kept free of puddles of water, excess moisture
and debris.
Observe all precautions in the Operation and Maintenance Manual, SL 25425, before as well
as during all installation and maintenance procedures. Observe all battery safety precautions
before working on or near the battery.
This equipment contains several circuits that are energized with high voltage. Only test
equipment designed for troubleshooting should be used. This is particularly true for
oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making
contact or using tools. Even when the power is turned Off, dangerously high potential electric
charges may exist at the capacitor banks and at the batteries.
All power and control wiring must be installed by a properly trained and qualified electrician.
All power and control wiring must comply with the NEC and applicable local codes.
When performing maintenance with any part of the equipment under power, service
personnel and test equipment must be standing on rubber mats. The service personnel must
wear insulating shoes for isolation from direct contact with the floor (earth ground).
One person should never work alone, even if all power is disconnected from the equipment. A
second person should be standing by to assist and to summon help in case of an accident.
NOTE
Materials sold hereunder cannot be used in the patient vicinity (e.g., use where UL, cUL or IEC
60601-1 is required). Medical applications such as invasive procedures and electrical life
support equipment are subject to additional terms and conditions.
NOTICE
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J
of the FCC rules. These limits provide reasonable protection against harmful interference in a
commercial environment. This unit generates, uses and radiates radio frequency energy and,
if not installed and used in accordance with this instruction manual, may cause harmful
interference to radio communications. Operation of this unit in a residential area may cause
harmful interference that the user must correct at his own expense.
Liebert® NXL™ Battery System
2
Mechanical Installation
1.0
MECHANICAL INSTALLATION
1.1
Introduction
This following section describes the requirements that must be taken into account when planning the
positioning and cabling of the Liebert NXL battery equipment.
This chapter is a guide to general procedures and practices that should be observed by the installing
engineer. The particular conditions of each site will determine the applicability of such procedures.
NOTICE
Do not apply electrical power to the UPS equipment before the arrival of the commissioning
engineer.
1.2
Preliminary Checks
Before installing the battery equipment, please carry out the following preliminary checks:
• Visually examine the equipment for transit damage, both internally and externally. Report any
damage to the shipper immediately.
• Verify that the correct equipment is being installed. The equipment supplied has an identification
tag inside the main door.
• Verify that the battery room satisfies the environmental conditions stipulated in the equipment
specification, paying particular attention to the ambient temperature and air exchange system.
1.3
Environmental Considerations
1.3.1
Battery Room
Batteries should be mounted in an environment where the temperature is consistent and even over
the whole battery. Temperature is a major factor in determining the battery life and capacity. Typical
battery manufacturer performance data are quoted for an operating temperature between 68 and
77°F (20 and 25°C). Operating above this range will reduce the battery life while operation below this
range will reduce the battery capacity.
Battery Temperature
In a normal installation, the battery temperature should be kept between 59 and 77°F (15°C and
25°C).
NOTE
Keep batteries away from main heat sources, main air inlets, etc.
1.3.2
Storage
Should the equipment not be installed immediately, it must be stored in a room for protection against
excessive humidity and heat sources (see Table 17).
NOTICE
Risk of deep discharge can cause permanent damage to batteries.
An unused battery must be recharged periodically as recommended by the battery
manufacturer.
3
Liebert® NXL™ Battery System
Mechanical Installation
1.4
Positioning
The cabinet is structurally designed to handle lifting from the base.
Power terminals, auxiliary terminals blocks and power switches are accessed from the front and top.
Removable panels on the top are secured to the chassis by screws. The door can be opened to give
access to the power connections bars, auxiliary terminal blocks and power isolators. The front door
can be opened 180° for easier service and more flexibility in installation.
1.4.1
Moving the Cabinets
The route to be travelled between the point of arrival and the unit’s installation location must be
planned to make sure that all passages are wide enough for the unit and that floors are capable of
supporting its weight (for instance, check that doorways, lifts, ramps, etc., are adequate and that
there are no impassable corners or changes in the level of corridors).
Ensure that the cabinet weight is within the designated surface weight loading (kg/cm2) of any
handling equipment. See Table 17 for weight details.
Ensure that any lifting equipment used to move the battery equipment has sufficient lifting capacity.
Battery system equipment can be handled by a forklift or similar equipment.
Because the weight distribution in the cabinet is not symmetrical, use extreme care during handling
and transporting.
When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a 15° tilt
with the forklift. Bottom structure will support the unit only if the forks are completely beneath the
unit.
Handling the unit with straps is not authorized.
! WARNING
Risk of heavy unit falling over. Can cause equipment damage, injury and death.
Exercise extreme care when handling battery cabinets. The battery system cabinets weigh
from 3760 to 8990 lb. (1706 to 4078kg).
Locate center of gravity symbols
and determine unit weight before handling each
cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from
vertical at all times.
Slots at the base of the cabinets are intended for forklift use. Base slots will support the unit
only if the forks are completely beneath the unit.
The cabinet with top terminal batteries ships with extra bolts installed on the interior doors. Once the
cabinet is in the final position, these bolts can be removed. See Figure 1
Figure 1
Shipping bolts—Top-Terminal Battery Cabinet
Shipping
Bolts
Shipping
Bolts
Shipping
Bolts
* Outer doors removed
for clarity
Shipping
Bolts
Shipping
Bolts
Shipping
Bolts
Shipping
Shipping Bolts Bolts
Liebert® NXL™ Battery System
4
Mechanical Installation
1.4.2
Clearances
Liebert NXL has no ventilation grilles at either side or at the rear of the battery system equipment.
Clearance around the front of the equipment should be sufficient to enable free passage of personnel
with the doors fully opened. It is important to leave a distance of 24" (610mm) between the top of the
cabinet and the ceiling of the room in which it is installed to permit adequate circulation of air coming
out of the unit and for service access.
1.4.3
Raised Floor Mounting
If the equipment is to be placed on a raised floor, it should be mounted on a pedestal suitably designed
to accept the equipment point loading. Refer to the base view to design this pedestal.
1.5
System Composition
A battery system can consist of a number of equipment cabinets, depending on the individual system
design requirements, e.g., Battery Cabinet, Junction Cabinet. Refer to 3.0 - Installation Drawings
for the positioning of the cabinets described below.
5
Liebert® NXL™ Battery System
Battery Installation
2.0
BATTERY INSTALLATION
2.1
Safety
Special care should be taken when working with the batteries associated with the Liebert NXL
Battery System equipment. When all the cells are connected together, the battery terminal voltage
will exceed 400V and is potentially lethal. A primary safety consideration is to install the battery
equipment in an isolated area, accessible only to properly trained and qualified maintenance
personnel.
! WARNING
Risk of electric shock. Can cause equipment damage, personal injury and death.
Hazardous battery voltage present behind covers. No user-serviceable parts are located
behind covers that require a tool for removal. Only properly trained and qualified service
personnel are authorized to remove such covers or perform installation or maintenance.
The following general battery safety precautions and warnings must be observed at all times:
• A battery can present risk of electric shock or burn from high short circuit currents.
• When connected in a string, the voltage will exceed 400VDC. This voltage is potentially
lethal. Always observe high-voltage precautions.
• Eye protection must be worn to prevent injury from accidental electrical arcs.
• Remove rings, watches, necklaces, bracelets and all other metal objects.
• Use only tools with insulated handles.
• Wear appropriate personal protective equipment when handling batteries.
• If a battery leaks electrolyte or is otherwise physically damaged, it should be placed in a
container resistant to wire and disposed of in accordance with local regulations.
• If electrolyte comes into contact with the skin, the affected area should be washed immediately with plenty of clean water.
• Batteries must always be disposed of according to local environmental laws.
• When replacing batteries, use the same number and type that were originally fitted.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine if the battery is grounded. If it is grounded, remove source of ground. Contact
with any part of a grounded battery can result in electrical shock.
• Battery support tray must be used whenever a battery tray is being pulled out.
2.2
Layout
Depending on the site layout, the battery cabinets can be installed in any of several ways:
•
•
•
•
Connected—Multiple battery cabinets bolted together
Stand-Alone—Cabinet not bolted to Liebert NXL equipment
Attached—Battery cabinets are bolted to a Liebert NXL UPS
Detached—Battery cabinets are not bolted to a Liebert NXL UPS
See Figures 2 through 4.
Liebert® NXL™ Battery System
6
Battery Installation
Figure 2
Battery cabinets connected, attached to UPS
Liebert
NXL
Battery
Cabinet
Liebert
NXL
UPS
Additional
Liebert
NXL
Battery
Cabinet
If the Liebert NXL UPS is
500kVA to 750kVA, battery
cabinets must be attached to
the left side of the UPS.
Additional
Liebert
NXL
Battery
Cabinet
Figure 3
Liebert
NXL
Battery
Cabinet
Liebert
NXL
UPS
Battery cabinets connected, detached from UPS
Liebert
NXL
UPS
Attached
Junction
Cabinet
Liebert
NXL
Battery
Cabinet
Additional
Liebert
NXL
Battery
Cabinet
The junction cabinet allows for
sufficient conduit landing space.
It is required for systems of
500kVA or above.
Additional
Liebert
NXL
Battery
Cabinet
Liebert
NXL
Battery
Cabinet
7
Attached
Junction
Cabinet
Liebert
NXL
UPS
Liebert® NXL™ Battery System
Battery Installation
Figure 4
Stand-alone battery cabinets, detached from UPS
StandAlone
Junction
Cabinet
Liebert
NXL
UPS
Liebert
NXL
Battery
Cabinet
Additional
Liebert
NXL
Battery
Cabinet
Maximum of eight battery
cabinets.
The junction cabinet provides
sufficient conduit landing
space and is required for all
systems in this configuration.
Additional
Liebert
NXL
Battery
Cabinet
2.3
Liebert
NXL
Battery
Cabinet
StandAlone
Junction
Cabinet
Liebert
NXL
UPS
Cable Entry
Cables may enter the battery cabinet from the top or bottom. Cable entry is made possible by
installing conduit to the removable plate fitted at the top or bottom. See 3.0 - Installation
Drawings.
2.4
Power Connection
Depending on the site layout, the battery cabinets can be cabled several ways. See Figures 2
through 4.
! CAUTION
Cables between batteries and the UPS should be run in matched pairs, positive-with-
negative, within each conduit or cable run.
Grouping like-polarity cables together (i.e., positive-with-positive and negative-with-negative)
can cause stress or damage to the cables, conduit or buswork
2.4.1
Connected System
For cabinets ordered as connected (battery cabinets will bolt to each other), the positive and negative
busbars are connected between battery cabinets with the supplied busbar connector extensions. See
Figure 18
2.4.2
Stand-Alone System
For cabinets that are ordered as stand-alone, customer must supply all the interconnecting cables and
hardware. See Table 23 for current ratings and recommended cable sizes.
Liebert® NXL™ Battery System
8
Battery Installation
2.4.3
Attached/Detached System
For battery cabinets that are connecting to a Liebert NXL UPS, (see Figure 2), cables will run from
the positive and negative busbars of the adjacent battery cabinet to the positive and negative DC
connections of UPS. For battery cabinets that are connecting to a Liebert NXL Junction Cabinet (see
Figure 3), busbars will be connected from the positive and negative busbars of the adjacent battery
cabinet to the positive and negative DC connections of Junction Cabinet.
For attached systems (the cabinets bolt to each other), the cables can run internal to the cabinets
and will be supplied.
For detached systems (the cabinets do not bolt to each other), the cables must be run outside the
cabinets. The customer must supply all the interconnecting cables and hardware. See Table 23 for
current ratings and recommended cable sizes.
2.4.4
Grounding
For cabinets that have been ordered as connected or attached, the ground cables and hardware will be
supplied. See Figure 19 for location of cabinet-to-cabinet grounding.
For cabinets ordered as detached or stand-alone, customer must supply the cables and hardware. See
Table 23 for current ratings and recommended cable sizes. See terminal detail drawings for location
of ground busbar.
2.5
Control Connection
Each Liebert NXL Battery Cabinet contains a Battery Interface Board (BIB). See 3.0 - Installation
Drawings. All cabinets in a system must have their Battery Interface boards connected in series. See
Figure 10 for battery cabinet details
NOTE
Care must be taken to route the control cables away from high voltage cables or busbars.
9
Liebert® NXL™ Battery System
Battery Installation
Figure 5
Wiring external interface board in UPS to battery interface board in battery cabinet
Detail A
TB1154A
EXT BATT
CAN
External Interface Board (in UPS)
Detail A
TB1154A
+24V
GND
CANH
CANL
1
2
3
4
Battery Interface Board
(in Battery Cabinet)
Detail B
TB1154
Liebert® NXL™ Battery System
1
Detail B
+24V
2
GND
3
CANH
CANL
4
TB1154
10
Battery Installation
Figure 6
Control cable layout—Liebert NXL UPS to Liebert NXL Battery Cabinet
Liebert
NXL
UPS
Liebert
NXL
Battery
Cabinet
Ext. Interface
Board (EIB)
TB1154A
Bat. Interface
Board (BIB)
TB1154
CAN Cable
Additional
Liebert
NXL
Battery
Cabinet
Bat. Interface
Board (BIB)
TB1154
CAN Cable
The CAN cables must be two, twisted pair, shielded 18AWG (Belden 9156 or equivalent). All
interconnecting cables and hardware for connected and attached cabinets will be provided.
NOTICE
Risk of improper installation. Can cause equipment damage.
During system commissioning, Emerson® Network Power Liebert Services will set the
jumpers on the EIB and the BIB. If another battery cabinet is added to the system after
commissioning, it is imperative that Liebert Services reset the jumpers on the EIB board and
the BIB board.
11
Liebert® NXL™ Battery System
Battery Installation
2.6
Alber Monitoring System—Optional
The Liebert matching battery cabinet allows installing an optional Alber battery monitoring system
in the cabinet. The Alber battery monitoring continuously checks all critical battery parameters, such
as cell voltage, overall string voltage, current and temperature. Automatic periodic tests of internal
resistance of each battery will verify the battery’s operating integrity. Additional capabilities include
automatic internal DC resistance tests and trend analysis providing the ability to analyze
performance and aid in troubleshooting.
The Alber monitoring system is installed inside the battery cabinet (see Figure 37). The monitoring
system requires approximately 0.5A, single-phase power.
This power can come from the output of the UPS the battery cabinet is suppling (see Figure 37).
The Alber monitoring system consists of a Controller Module and Data Collector Module (see
Figure 35). One Controller Module can monitor up to six battery cabinets with a Data Collector
Module installed. The battery cabinet with the Controller Module (Battery Cabinet #1) must be
installed in the position closest to the UPS.
For details about operating the Alber system, see the Alber Monitoring System manual, available at
the Liebert Web Site, www.liebert.com
2.7
External Battery Room Temperature Sensor—Optional
For systems that do not use Liebert NXL Battery Cabinets, an optional temperature sensor can be
installed to monitor the ambient room temperature. This sensor is connected to the BIB board (see
Figure 7). This sensor will allow the Liebert NXL UPS to perform temperature compensation
charging.
Figure 7
Battery temperature sensor control connection
Battery Interface Board
P1153
TB1154
Liebert® NXL™ Battery System
12
Installation Drawings
3.0
INSTALLATION DRAWINGS
Figure 8
Outline drawing, Liebert Top-Terminal Battery Cabinet
56.3
(1430)
16.6
(422)
27.7
(705)
76.8
(1950)
CG
CG
42.8
(1088)
3.7
(95)
Front
1.6
(40)
Typ
3.7
(95)
33.5
(850)
28.7
( 730)
3
(76)
Right
Side
View
64.1
(1629)
8.8
8.3
11.2 (223) 11.2
6.4 (210)
(285)
(285) (161)
TOP VIEW
(Doors Open)
Bottom View
NOTE:
1. All dimensions are in in. (mm)
2. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
5. Widths are with side panels. The width is 55.1" (1400mm) without side panels.
6.The depth dimension includes the front door and rear panel.
13
Liebert® NXL™ Battery System
Installation Drawings
Figure 9
Main components, Liebert Top-Terminal Battery Cabinet
Negative
Battery Bus
Positive
Battery Bus
High Voltage
Control
Cable Trough
Low Voltage
Control
Cable Trough
Location for Optional
Alber Monitoring
Equipment
Battery
Service
Tray
Battery
Breaker
Battery
Service
Tray
Supports
Battery
Interface Board
(BIB)
Ground
Bus
Batteries
(Typical View
Shown)
Front View
NOTCHED END OF SUPPORT
SLIPS INTO SLOT AT
BATTERY RAIL ABOVE
SERVICE TRAY SUPPORTS
ANGLED OUT TO PROVIDE
BATTERY CLEARANCE
SLOT IN SUPPORT IS SECURED
BY SCREW-IN CONNECTOR
AT CORNER OF BATTERY
SERVICE TRAY
BATTERY TRAY EXTENDED ONTO SERVICE TRAY
SERVICE TRAY INSTALLED
Liebert® NXL™ Battery System
14
Installation Drawings
Figure 10 Terminal details, Liebert Top-Terminal Battery Cabinet
See Bus
Termination Detail
Negative Term. Bus (-)
Positive Term. Bus (+)
Top View
+
-
Ground Bus
(See Detail)
1.75
(45)
ø.56
(14)
1.75 (45)
Ground Bus Detail
1.75 (45)
1.75
(45)
ø.53
(14)
Front View
Right Side View
* Doors And Covers Removed for Clarity
Bus Termination Detail
CB1-3
CB1-3
Notes
1. All dimensions are in inches (mm)
2.Top and bottom cable entry available through
removable access plates.
3. Control wiring and power wiring must be run
in separate conduit.
4. Unless otherwise noted, use copper or aluminum
DO NOT
conductors suitable for at least 75°C.
5. All wiring must be in accordance with national
DOUBLE-STACK
and local electrical codes.
6. For cabinets ordered as stand-alone, the negative
and positive terminal bus does not extend to full width of battery cabinet.
7. 24" minimum clearance above unit is required for air exhaust and service access.
15
1.75
(45)
LUGS
Liebert® NXL™ Battery System
Liebert® NXL™ Battery System
16
Detail B
Detail A
A
Jar 16
B
Install M10 washer, lockwasher
and bolt to secure units together
front and rear
Note: Jar 28 must be
moved forward or removed
to install rear hardware. Rear
cutouts are provided if rear
access is provided.
Install M10 washer, lockwasher
and bolt to secure units together
front and rear
Note: Jar 16 must be
Negative (-)
moved forward or removed
to install rear hardware. Rear
Positive (+)
cutouts are provided if rear
access is provided.
Isometric View
Install snap bushing
in corner post before
routing these wires
Jar 28
Install snap bushing
in corner post before
routing these wires
Top View
Reuse M12 hardware
Torque to 480 in-lb (54Nm)
Front
Use M10 hardware
supplied on bus
Torque to 240 in-lb
(27Nm)
Tywrap here to
secure wires in place
Tywrap here to
secure wires in place
Busbars shown
connected between
Cabinet A & Cabinet B
(busbar quantity varies)
Remove these busbars and keep
the hardware to secure busbars
between Cabinet A & Cabinet B
Route two supplied wires (W17)
from Jar 15 (+) to Jar 16 (-)
Note: Install bushing first.
Install snap
bushing
in corner
post before
routing these
wires
Remove M6 hardware
used to secure lugs
in place and discard
Connect lugs to bus
directly above insulator
and secure with M8 hardware
supplied on bus. Typ 8 places.
Torque to 180 in-lb (20Nm)
Route two supplied wires (W16)
from Jar 1 (-) to BCB breaker in (-)
Note: Install bushings first.
Tywrap here to
secure wires in place
Cabinet B
Figure 11
Use M8 hardware supplied on bus
Torque to 180 in-lb (20Nm)
Cabinet A
Installation Drawings
Front Terminal Battery Cabinet shipping split
17
14"
(356mm)
37.8" (960mm)
Bottom
Cable Entry
See Detail B
76.8"
(1950mm)
Front
18"
(457mm)
Center of
Gravity
Both Sections
33.5" (850mm)
Notes:
Front View
Right Side
1. All dimensions are in in [mm].
2. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top cable entry available through removable access plates.
5. Control wiring and power wiring must be run in separate conduit.
6. Width dimension is with side panels. Subtract 1.4" (35mm) for dimensions
with both side panels removed.
7. Depth dimension includes the front door and rear panel.
8. Refer to battery technical information drawing.
12.2"
(311mm)
38"
(965mm)
Center of
Gravity
25.2" (640)
63" (1600mm)
Top View
Cable Entry
See Detail A
Bottom
Cable Entry
High Voltage
Cable Entry
0.9"
(22.7mm)
4.3"
[110.0]
3.7"
(95mm)
to Panel
3.6"
(91mm)
to Panel
10"
(254mm)
Low Voltage
Cable Entry
1.8" (45mm)
to Panel
10.1"
(257mm) to Panel
21.2"
(538mm)
Detail B
Front
9.4"
(257mm)
Front
Detail A
11.3"
(287mm)
Installation Drawings
Figure 12 Front Terminal Battery Cabinet outline drawing
Liebert® NXL™ Battery System
Installation Drawings
Figure 13 Front Terminal Battery Cabinet main components, layout
High Voltage
Control Cable
Trough
Positive
Battery Bus
Low Voltage
Control Cable
Trough
Negative
Battery Bus
Location for Optional
Alber Monitoring Equipment
Front
Battery
Breaker
Battery
Typ.
Battery
Typ.
Battery
Interface
Board (BIB)
Ground Bus
Right Side View
With Panels Removed
Front View
Liebert® NXL™ Battery System
18
Installation Drawings
Figure 14 Front terminal detail drawing
See Bus Termination
Detail
Negative Term. Bus (-)
Positive Term. Bus (+)
(+)
(-) * Doors and covers removed for clarity
Ø.56
[14]
TYP.
FRONT
1.75
[44]
TOP VIEW
(SECTION "B")
1.75
[44]
GROUND BUS DETAIL
1.75
[45]
TYP.
Ground Bus
(See Detail)
1.75
[44]
Ø.56 X .75" SLOT
[Ø14 X 19]
TYP.
BUS TERMINATION DETAIL
FOR POS. AND NEG. BUSBAR
RIGHT SIDE VIEW
FRONT VIEW
(SECTION "B")
NOTES:
1. All dimensions are in in [mm].
2. Top and bottom cable entry available through removable access plates.
3. Control wiring and power wiring must be run in separate conduit.
4. Unless otherwise noted, use copper or aluminum conductors suitable
for at least 75°C.
5. All wiring is to be in accordance with national and local electrical codes.
6. For cabinets ordered as stand-alone, the negative and positive terminal
bus does not extend to full width of battery cabinet.
7. 24" minimum clearance above unit is required for air exhaust and service.
19
Liebert® NXL™ Battery System
Installation Drawings
Figure 15 Liebert NXL Stand-Alone Junction Cabinet terminal wiring
.56 (14)
Typ
2.2 (55)
16 Places
.56
(14) Typ
.56
(14) Typ 1.7 (44) X 0.7 (18)
Slot 16 Places
1.8 (45)
Typ. Each Busbar
16 Places
2.2 (55)
18 Places
2.2 (55)
16 Places
2.2 (55)
18 Places
Ground Bus
2.2 (55)
18 Places
Negative Bus
Positive Bus
30.9 (785)
33.5 (805)
CB1-3
CB1-3
Positive
Bus
Do not double stack lugs
(two lugs on same side of
busbar). This is to prevent
the cables from coming into
contact with other busbars.
Ground
Bus
Lugs
76.9
(1952)
Negative
Bus
41.3
(1050)
Bolt
Busbar
DUAL LUG
CONNECTION DETAIL
13.7
(348)
8.7
7.4
9.0
(189) (221) (228)
Right Side
View
Front View
13.6
(346)
Notes:
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduit.
3. Unless otherwise noted, use copper or aluminum conductors
suitable for at least 75°C.
4. Widths are without side panels. The width is 32.1" (815mm) with side panels.
5.The depth dimension includes the front door and rear panel.
Liebert® NXL™ Battery System
20
Installation Drawings
Figure 16 Liebert NXL Attached Junction Cabinet—terminal detail and outline drawing
1.75 (44) Typ
Terminal Details
O .56 (14) Typ
11.4
(290)
7
(178)
Positive Bus Bottom
2 (51) Typ
4.4
(112)
1.75 (44) Typ
Positive
Bus
O .56 (14) Typ
2 (51) Typ Negative Bus Bottom
O .56 (14) Typ
Negative
Bus
Ground Bus
1.75 (44) Typ
CB1-3
Do not double stack lugs
(two lugs on same side of
busbar). This is to prevent
the cables from coming into
contact with other busbars.
.56
(14)
TYP
1.25 x 0.5 (32 x 13)
49.1
(1248)
1.75
(44)
TYP
37.3
(948)
CB1-3
Bus Detail
Ground
Bus
Slot 8 Places
Typical
Lugs
26.0
(661)
Bolt
Front View
Positive
Bus Top
Right Side
Mounting Slots
8 Places
Typical
Negative
Bus Top
Busbar
DUAL LUG
CONNECTION DETAIL
Outline Drawing
76.8
(1950)
WARNING!!!
Unit Removal and Unit Mobility Instructions
Brackets MUST remain attached to the frame until
such time that the unit is being located in its final
installed position. (The final installation will always
require the unit to be bolted to another Liebert NXL
product.)
Failure to comply with these instructions could
result in equipment damage and/or injury to
personnel
38.3
(973)
38.3
(973)
7.9
(201)
15.5
( 393)
Front View
21
33.5
( 850)
15.1
( 382)
Right Side
Liebert® NXL™ Battery System
Installation Drawings
Figure 17 Liebert NXL Battery Cabinet control wiring
CAN cable to be run
in trough closest to
the front of the unit
TROUGH
UVR TRIP - Optional
UVR TRIP- Optional
AUX. CONTACT 1
AUX. CONTACT 1
(RED)
AUX. CONTACT 1
3-BRKR-POS
Optional
Battery
Voltage
Sense
Cable
(BLK)
Thermistor
(Optional)
1- BRKR- NEG
1
1
2
3
1 2
3 4 5
TB1150
1
7 6
5 4 3 2 1
P1152
NOTES
USE WIRE TIE AS NECCESSARY FOR ROUTING AND
SECURING WIRE HARNESSES.
This end field-connected
to other cabinets
P1153
Liebert NXL Battery Cabinet
Control Wiring Routing
TB1151
TB1158
( BATTERY
MONITORING
SYSTEM )
BATTERY
INTERFACE
BOARD (BIB)
24V (RED)
GND (BLK)
CANH (WHT)
Liebert® NXL™ Battery System
TB1156
1
+24V (RED)
2
GND (BLK)
3
CANH (WHT)
CAN Cable
(Belden 9156
or Equivalent)
TB1154
4
CANL (BLK)
CANL (BLK)
2
1
Control Wiring Diagram
22
Installation Drawings
Figure 18 Attached battery cabinet connections
Jumper Busbars
(supplied with battery cabinet)
Note: Torque to 240in-lb (27 N-M)
Jumper Busbars
(supplied with battery cabinet)
Note: Connections cannot be made
if cabinets ordered as stand-alone.
Figure 19 Ground strap location for connected cabinets
BATTERY
CABINET
BATTERY
CABINET
REFERENCE OF
CORNER POST OF
CONNECTED CABINETS
A
FRONT SIDE OF
UNITS
TYPICA L GROUND STRA P INSTALLATION
FOR BATTERY CABINE T TO BATTERY CABINE T
CONNECTIONS
CABINE T-TO-CABINE T
BOLTING INSTRUCTIONS
B
2
BATTERY
CABINET
1
DETAIL A
1
2
DETAIL B
TYPICA L GROUND STRA P INSTALLATION
FOR BATTERY CABINE T TO
UPS OR ANCILLA RY CABINE T CONNECTIONS
FRONT SIDE OF
UNITS
23
NOTES:
1. Apply ground strap hardware to specified locations.
2. Torque Values: M6: ( 5 Nm ) 40 IN-LB
M10: ( 14 Nm ) 120 IN-LB
Liebert® NXL™ Battery System
Installation Drawings
Figure 20 Top-Terminal Battery Cabinet interconnection wiring to 250-400kVA UPS
A2
B2
B2
B1
For left -mounted
installations, the DC
cables will be routed
along the interior rear
of the UPS. The cables
can be supported using
lances in the UPS
sheet metal.
A1
A2
D
A1
D
B1
C
C
UPS
Table 1
Run
BATTERY CABINET
Top-Terminal Battery Cabinet interconnection wiring to 250-400kVA UPS
From
To
Conductors
Battery Cabinet - DC+ Busbar
Positive Power - RH Mount/Stand Alone
A1
UPS - DC+ Busbar
B1
UPS - DC- Busbar
Battery Cabinet - DC- Busbar
Negative Power - RH Mount/Stand Alone
A2
UPS - DC+ Busbar
Battery Cabinet - DC+ Busbar
Positive Power - Left Mount
B2
UPS - DC- Busbar
Battery Cabinet - DC- Busbar
Negative Power - Left Mount
C*
UPS - Ground
Battery Cabinet - Ground
Ground
UPS - External Interface
Board (EIB)
Battery Cabinet - Battery
Interface Board (BIB)
CAN Control Cables
D
* This is used only for detached cabinets. If the cabinets are attached, use the grounding shown in Figure 19.
Liebert® NXL™ Battery System
24
Installation Drawings
Figure 21 Liebert NXL Top-Terminal Battery Cabinet interconnect wiring to Liebert NXL Stand-Alone
Junction Cabinet
A
B
B
C
A
C
Battery Cabinet
Table 2
Junction Cabinet
Liebert NXL Top-Terminal Battery Cabinet interconnect wiring to Liebert NXL Junction
Cabinet
Run
From
To
A
Battery Cabinet Negative Bus
Junction Negative Bus
Negative DC Power
B
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power
C
Battery Cabinet Ground
Junction Ground
Ground
25
Conductors
Liebert® NXL™ Battery System
Installation Drawings
Figure 22 Terminal details Liebert NXL UPS 250kVA - 400kVA to front terminal battery point-to-point
wiring
A2
B2
All power and control wiring is supplied
if units are ordered as attached.
B1
UPS - REAR VIEW
DC BUS CONNECTIONS
B2
For left-mounted
installations, the DC A1
cables will be routed
along the interior rear
of the UPS. The cables
can be supported using
lances in the UPS
sheet metal.
A2
D
TOP VIEW
A1
B1
D
C
C
BATTERY CABINET
UPS
Table 3
Terminal details Liebert NXL UPS 250kVA - 400kVA to front terminal battery point-topoint interconnect wiring
Run
From
To
Conductors
A1
UPS DC Positive Busbar
Battery Cabinet Positive Bus
Positive DC Power RH Mount /
Stand Alone
B1
UPS DC Negative Busbar
Battery Cabinet Negative Bus
Negative DC Power
RH Mount / Stand-Alone
A2
UPS DC Positive Busbar
Battery Cabinet Positive Bus
Positive DC Power Left Mount
B2
UPS DC Negative Busbar
Battery Cabinet Negative Bus
Negative DC Power Left Mount
C*
UPS Ground
Battery Cabinet Ground
Ground
UPS External Interface Board (EIB)
Battery Cabinet
Battery Interface Board (BIB)
CAN Control Cables
D
* For detached units only
Liebert® NXL™ Battery System
26
Installation Drawings
A E
C
TOP VIEW
Battery Cabinet
G
B
A
B D
Stand-Alone
Junction Cabinet
C F
All power and control wiring is supplied by others.
UPS
G
F
E
D
Figure 23 Terminal details Liebert NXL 250-400kVA front terminal battery and Stand-Alone Junction
Cabinet point-to-point wiring
27
Liebert® NXL™ Battery System
Installation Drawings
Table 4
Terminal details Liebert NXL 250-400kVA front terminal battery and Stand-Alone
Junction Cabinet point-to-point interconnect wiring
Run
From
To
Conductors
A
Battery Cabinet Negative Bus
Junction Negative Bus
Negative DC Power
B
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power
C
Battery Cabinet Ground
Junction Ground
Ground
D
Junction Positive Bus
UPS Cabinet Positive Bus
Positive DC Power
E
Junction Negative Bus
UPS Cabinet Negative Bus
Negative DC Power
F
Junction Ground
UPS Cabinet Ground
Ground
G
Battery Cabinet Battery Interface Board (BIB)
UPS External Interface Board (EIB)
CAN Control Cables
Figure 24 Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Attached Junction
Cabinet, point-to-point wiring
A2 and B2 - RH Mount
A1 and B1 - LH Mount
A1
A2
B1
B2
B
A
TOP VIEW
D
E
DC (-)
Input
E
DC (+)
Input
D
G
C F
ABC
F
G
Ground
Bus
DC Input
C
Attached Junction
Cabinet Right Side
UPS Left Front (Part A)
UPS Left Side
Rectifier (Part A)
Table 5
Battery Cabinet
Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Attached
Junction Cabinet, point-to-point interconnect wiring
Run
From
A1
Battery Cabinet Negative Bus
Junction Negative Bus
Negative DC Power (LH Mount)
B1
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power (LH Mount)
A2
Battery Cabinet Negative Bus
Junction Negative Bus
Negative DC Power (RH Mount)
B2
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power (RH Mount)
D
Junction Positive Bus
UPS Cabinet Positive Bus
Positive DC Power
E
Junction Negative Bus
UPS Cabinet Negative Bus
Negative DC Power
F
Junction Ground
UPS Cabinet Ground
Ground
G
Battery Cabinet
Battery Interface Board (BIB)
UPS External Interface Board (EIB)
CAN Control Cables
Liebert® NXL™ Battery System
To
28
Conductors
Installation Drawings
Figure 25 Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Stand-Alone Junction
Cabinet, point-to-point wiring
B
A
C F
A E
B D
Top View
E
DC (-)
Input
DC (+)
Input
D
G
C
ABC
G
Ground
Bus DC
Input
F
UPS Left Side
Rectifier (Part A)
Stand-Alone
Junction Cabinet
Battery Cabinet
UPS Left Front (Part A)
Table 6
Terminal details, Liebert NXL 500kVA UPS to Top-Terminal battery and Stand-Alone
Junction Cabinet, point-to-point interconnect wiring
Run
From
To
Conductors
A
Battery Cabinet Negative Bus
Junction Negative Bus
Negative DC Power
B
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power
C
Battery Cabinet Ground
Junction Ground
Ground
D
Junction Positive Bus
UPS Cabinet Positive Bus
Positive DC Power
E
Junction Negative Bus
UPS Cabinet Negative Bus
Negative DC Power
F
Junction Ground
UPS Cabinet Ground
Ground
G
Battery Cabinet Battery Interface Board (BIB)
UPS External Interface Board (EIB)
CAN Control Cables
29
Liebert® NXL™ Battery System
Installation Drawings
Figure 26 Terminal details Liebert NXL 500kVA to Top-Terminal battery point-to-point wiring
B
DC (-)
INPUT
DC (+)
INPUT
D
A
A
UPS LEFT SIDE RECTIFIER (PART A)
B
C
UPS LEFT FRONT (PART A)
B
D
A
TOP VIEW
NOTE:
1. All power and control wiring is supplied.
2. The units must be attached.
3. UPS cabinet not to scale to battery cabinet.
BATTERY CABINET
Table 7
Terminal details Liebert NXL 500kVA to top-terminal battery point-to-point interconnect
wiring
Run
From
To
Conductors
A
UPS Positive Bus
Battery Cabinet Positive Bus
Positive DC Power
B
UPS Negative Bus
Battery Cabinet Negative Bus
Negative DC Power
D
UPS External Interface Board (Eib)
Battery Cabinet Battery Interface Board (BIB)
CAN Control Cables
Liebert® NXL™ Battery System
30
Installation Drawings
Figure 27 Terminal details Liebert NXL UPS 500kVA to front terminal battery point-to-point wiring
B
DC (-)
Input
DC (+)
Input
D
A
A
UPS LEFT SIDE RECTIFIER (PART A)
B
C
UPS LEFT FRONT (PART A)
A
B
D
TOP VIEW
NOTE:
1. All power and control wiring is supplied.
2. The units must be attached.
3. UPS cabinet not to scale to battery cabinet.
BATTERY CABINET
Table 8
Terminal details Liebert NXL UPS 500kVA to front terminal battery point-to-point
interconnect wiring
Run
From
A
UPS Positive Bus
B
D
To
Conductor
Battery Cabinet Positive Bus
Positive DC Power
UPS Negative Bus
Battery Cabinet Negative Bus
Negative DC Power
UPS External Interface Board (EIB)
Battery Cabinet
Battery Interface Board (BIB)
CAN Control Cables
31
Liebert® NXL™ Battery System
Installation Drawings
Figure 28 Liebert NXL terminal details UPS 625/750kVA to front terminal battery and Attached Junction
Cabinet point-to-point wiring
E
DC (-)
INPUT
DC (+)
INPUT
D
A
B
C
G
A2 & B2 - RH MOUNT
A1 & B1 - LH MOUNT
A1
A2
B1
B2
GROUND BUS
DC INPUT
F
UPS Left Side
Rectifier (Part A)
B
Top View
UPS Left Front (Part A)
A
D
E
G
F
Battery Cabinet
Table 9
1. All power and control wiring between battery
cabinet and junction cabinet is supplied.
2. All power wiring between junction cabinet and
UPS is supplied by others.
3. All control wiring between battery cabinet and
UPS is supplied by others
Attached Junction
Cabinet Right Side
Liebert NXL terminal details UPS 625/750kVA to front terminal battery and Attached
Junction Cabinet point-to-point Interconnect wiring
Run
From
A1
Battery Cabinet Negative Bus
To
Conductors
Junction Negative Bus
Negative DC Power (LH Mount)
B1
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power (LH Mount)
A2
Battery Cabinet Negative Bus
Junction Negative Bus
Negative DC Power (RH Mount)
B2
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power (RH Mount)
D
Junction Positive Bus
UPS Cabinet Positive Bus
Positive DC Power
E
Junction Negative Bus
UPS Cabinet Negative Bus
Negative DC Power
F
Junction Ground
UPS Cabinet Ground
Ground
G
Battery Cabinet Battery
Interface Board (BIB)
UPS External Interface Board (EIB)
CAN Control Cables
Liebert® NXL™ Battery System
32
Installation Drawings
TOP VIEW
Battery Cabinet
C
G
B D
B
A
C F
Stand-Alone
Junction Cabinet
A E
UPS Left Side
Rectifier (Part A)
F
GROUND BUS
DC INPUT
G
D
E
DC (-)
INPUT
DC (+)
INPUT
A
All power and control wiring is supplied by others.
B
C
UPS Left Front
(Part A)
Figure 29 Liebert NXL terminal details UPS 625/750kVA to front terminal battery and Stand-Alone
Junction Cabinet point-to-point wiring
Table 10
LIebert NXL terminal details UPS 625/750kVA to front terminal battery and Stand-Alone
Junction Cabinet point-to-point interconnect wiring
Run
From
To
Conductors
A
Battery Cabinet Negative Bus
Junction Negative Bus
Negative DC Power
B
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power
C
Battery Cabinet Ground
Junction Ground
Ground
D
Junction Positive Bus
UPS Cabinet Positive Bus
Positive DC Power
E
Junction Negative Bus
UPS Cabinet Negative Bus
Negative DC Power
F
Junction Ground
Ps Cabinet Ground
Ground
G
Battery Cabinet Battery Interface Board (BIB)
UPS External Interface Board (EIB)
CAN Control Cables
33
Liebert® NXL™ Battery System
Installation Drawings
Figure 30 Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and Attached Junction
Cabinet, point-to-point wiring
A2 and B2 - RH Mount
A1 and B1 - LH Mount
A1
A2
B1
B2
B
Top View
DC (-)
E INPUT
A
D
DC (+)
Input
D
G
G
E
A
B
F
C
Ground
Bus
DC Input
F
UPS Left Side
Rectifier (Part A)
Table 11
Run
UPSLeft
Front (Part A)
Attached Junction
Cabinet Right Side
Battery Cabinet
Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and Attached
Junction Cabinet, point-to-point wiring
From
To
Conductor
A1
Battery Cabinet Negative Bus
Junction Negative Bus
Negative DC Power (LH Mount)
B1
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power (LH Mount)
A2
Battery Cabinet Negative Bus
Junction Negative Bus
Negative DC Power (RH Mount)
B2
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power (RH Mount)
D
Junction Positive Bus
UPS Cabinet Positive Bus
Positive DC Power
E
Junction Negative Bus
UPS Cabinet Negative Bus
Negative DC Power
F
Junction Ground
UPS Cabinet Ground
Ground
G
Battery Cabinet, Battery
Interface Board (BIB)
UPS External Interface Board (EIB)
CAN Control Cables
Liebert® NXL™ Battery System
34
Installation Drawings
Figure 31 Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and Stand-Alone
Junction Cabinet, point-to-point wiring
A
B
C F
Top View
DC (-)
E Input
DC (+)
Input
D
B D
A E
G
G
A
B
C
C
GROUND
BUS
DC INPUT
F
UPS Left Side
Rectifier (Part A)
Table 12
Battery Cabinet
Stand-Alone
Junction Cabinet
Terminal details, Liebert NXL 625/750kVA UPS to Top-Terminal battery and Stand-Alone
Junction Cabinet, point-to-point interconnect wiring
Run
A
UPS Left
Front (Part A)
From
To
Conductors
Battery Cabinet Negative Bus
Junction Negative Bus
Negative DC Power
B
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power
C
Battery Cabinet Ground
Junction Ground
Ground
D
Junction Positive Bus
UPS Cabinet Positive Bus
Positive DC Power
E
Junction Negative Bus
UPS Cabinet Negative Bus
Negative DC Power
F
Junction Ground
UPS Cabinet Ground
Ground
G
Battery Cabinet Battery Interface Board (BIB)
UPS External Interface Board (EIB)
CAN Control Cables
35
Liebert® NXL™ Battery System
Installation Drawings
D
UPS LEFT SIDE RECTIFIER (PART A)
DC (+)
INPUT
A
BATTERY CABINET
B
A
NOTE:
1. All power and control wiring is supplied.
2. The units must be attached.
3. UPScabinet not to scale to battery cabinet.
B DC (-)
INPUT
A
B
C
UPS LEFT FRONT (PART A)
D
Figure 32 Terminal details Liebert NXL UPS 625/750kVA to battery point-to-point wiring
Table 13
Terminal details Liebert NXL UPS 625/750kVA to battery point-to-point interconnect
wiring
Run
From
A
UPS Positive Bus
B
D
To
Conductor
Battery Cabinet Positive Bus
Positive DC Power
UPS Negative Bus
Battery Cabinet Negative Bus
Negative DC Power
UPS External Interface Board (EIB)
Battery Cabinet
Battery Interface Board (BIB)
CAN Control Cables
Liebert® NXL™ Battery System
36
Installation Drawings
UPS Left Side
Rectifier (Part A)
Attached Junction
Cabinet Right Side
E
A
Battery Cabinet
F
G
D
Top View
B2
B
A2
B1
A2 & B2 - RH MOUNT
A1
A1 & B1 - LH MOUNT
Table 14
Run
F
GROUND BUS
DC INPUT
A
D
DC (+)
INPUT
DC (-)
E INPUT
NOTES
1. All power and control wiring between battery
cabinet and junction cabinet is supplied.
2. All power wiring between junction cabinet and UPS
is supplied by others.
3. All control wiring between battery cabinet and UPS
is supplied by others.
B
C
UPS Left Front
(Part A)
G
Figure 33 Terminal details UPS 625/750kVA to front terminal battery and Attached Junction Cabinet
point-to-point wiring
Terminal details UPS 625/750kVA to front terminal battery and Attached Junction
Cabinet point-to-point interconnect wiring
From
To
Conductor
A1
Battery Cabinet Negative Bus
Junction Negative Bus
Negative DC Power (LH Mount)
B1
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power (LH Mount)
A2
Battery Cabinet Negative Bus
Junction Negative Bus
Negative DC Power (RH Mount)
B2
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power (RH Mount)
D
Junction Positive Bus
UPS Cabinet Positive Bus
Positive DC Power
E
Junction Negative Bus
UPS Cabinet Negative Bus
Negative DC Power
F
Junction Ground
UPS Cabinet Ground
Ground
G
Battery Cabinet
Battery Interface Board (BIB)
UPS External
Interface Board (EIB)
CAN Control Cables
37
Liebert® NXL™ Battery System
Installation Drawings
GROUND
BUS
DC INPUT
F
UPS Left Side
Rectifier (Part A)
DC (+)
INPUT
D
A E
Stand-Alone
Junction Cabinet
C F
TOP VIEW
Battery Cabinet
C
G
B D
B
A
All power and control wiring is supplied by others.
DC (-)
E INPUT
A
B
C
UPS Left Front
(Part A)
G
Figure 34 Terminal details 625/750kVA to front terminal battery and Stand-Alone Junction Cabinet
point-to-point wiring
Table 15
Terminal details 625/750kVA to front terminal battery and Stand-Alone Junction Cabinet
point-to-point interconnect wiring
Run
From
To
Conductor
A
Battery Cabinet Negative Bus
Junction Negative Bus
Negative DC Power
B
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power
C
Battery Cabinet Ground
Junction Ground
Ground
D
Junction Positive Bus
UPS Cabinet Positive Bus
Positive DC Power
E
Junction Negative Bus
UPS Cabinet Negative Bus
Negative DC Power
F
Junction Ground
UPS Cabinet Ground
Ground
G
Battery Cabinet Battery Interface Board (BIB)
UPS External Interface Board (EIB)
CAN Control Cables
Liebert® NXL™ Battery System
38
Installation Drawings
Figure 35 Typical Alber battery monitoring connections
Input Fuse
for Alber Power
Alber Data
Collector
Module
Alber
Controller
Module
TR
AY
#1
TR
AY
#1
0
TR
AY
#2
TR
AY
#9
TR
AY
#3
TR
AY
#8
TR
AY
#7
TR
AY
#4
TR
AY
#5
Alber
Power
Transformer
TR
AY
#6
39
Liebert® NXL™ Battery System
Installation Drawings
---
---
--RX
TX
---
--TX
RX
24VAC
Input
24VAC
#3
24VAC
#4
24VAC
#5
24VAC
#6
TELCO
24VAC
#2
---
---
RX
TX
24VAC #1
LAN/LOCAL
24VAC
Input
230VAC
60Hz
230VAC
60Hz
---
BDS-40 Data Collection
Module #1
Liebert® NXL™ Battery System
UPS Cabinet
40
480VAC
60Hz
Battery
Interface
Board
TB1158
RESET
RESET
MAJOR NO
MAJOR NC
MAJOR CM
MINOR NO
MINOR NC
MINOR CM
RX
TX
---
BDS-40 Data Controller
+24VAC
INPUT
ETHERNET
BATTERY CABINET #1
24VAC
Input
RX
BDS-40 Data
Collection
Module #2
TX
BATTERY
CABINET #3
BDS-40 Data
Collection
Module #3
---
BATTERY
CABINET #4
BDS-40 Data
Collection
Module #4
BATTERY
CABINET #2
Figure 36 Alber battery monitoring wiring to multiple battery cabinets
Installation Drawings
Figure 37 Alber battery monitoring assembly diagram
UPS Output - Phase A
Use Pilot Hole on Busbar
Locate fuse label as
close to fuses as possible
UPS Output - Phase C
Use Pilot Hole on Busbar
Mount fuses to corner post
in input/output compartment
of UPS module. Choose best
location based on bottom or top
power cabling.
Connect cables from UPS output
busbars to fuse block.
UPS Output Section
Fuse Block Installation
This harness is intended for use only when
battery cabinet is connected directly to UPS.
For all other instances, customer must supply wire.
Secure supplied wire
harness to busbar with
supplied hardware.
ALBER BATTERY
MONITORING XFMR
Harness factory-installed.
Verify transformer connection
Prior to startup.
See diagram below.
Wire Harness
V_OUT_A
F4
F75
F5
F76
V_OUT_C
NXL BATTERY CABINET
UPS MODULE OUTPUT
TOP TERMINALS
FROM F5 FUSE IN BAT CAB
BOTTOM TERMINALS
FROM F4 FUSE IN BAT CAB
300 V
240 V
270 V
208 V
200 V
0V
300 V
240 V
270 V
208 V
200 V
0V
XFMR CONNECTION DIAGRAM
X1
Table 16
230 V
X2
Alber battery monitoring assembly connections
Input
Voltage
Alber Transformer-2
(Wht)
Jumper
Alber Transformer-1
(Blk)
F4-F5
Fuse Rating
600
0 (Top)
300 (Top) to 0 (Bottom)
300 (Bottom)
2.25 A, 600VAC
480
0 (Top)
240 (Top) to 0 (Bottom)
240 (Bottom)
1.25 A, 600VAC
380
0 (Top)
300 (Top) to 208 (Bottom)
300 (Bottom)
1 A, 600VAC
208
0 (Top)
0 (Top) to 0 (Bottom) and
208 (Top) to 208 (Bottom)
208 (Top)
0.75A, 600VAC
41
Liebert® NXL™ Battery System
Installation Drawings
Figure 38 Top-Terminal battery configuration
REAR OF TRAY
JAR 2
+
JAR 3
+
+
+
+
-
+
FRONT OF TRAY
REAR OF TRAY
10
TR
AY
#
JAR 5
+
JAR 6
+
JAR 7
+
2
+
-
TRAY #9
AY
#
TRAY #2
TR
+
9
+
FRONT OF TRAY
3
TR
AY
#
8
JAR 9
+
+
+
+
AY
#
TRAY #4
TR
AY
#
6
FRONT OF TRAY
REAR OF TRAY
+
JAR 13
JAR 14
+
JAR 15
+
+
JAR 20
JAR 19
+
JAR 18
+
JAR 16
JAR 17
FRONT OF TRAY
JAR 26
FRONT OF TRAY
REAR OF TRAY
+
-
+
JAR 27
JAR 25
REAR OF TRAY
+
+
+
-
FRONT OF TRAY
+
5
JAR 30
JAR 28
JAR 29
TRAY #5
TR
JAR 31
+
-
REAR OF TRAY
+
JAR 32
JAR 12
7
4
JAR 11
AY
#
AY
#
JAR 10
+
TR
TR
REAR OF TRAY
+
-
TRAY #8
TRAY #3
AY
#
JAR 33
REAR OF TRAY
TR
JAR 34
+
-
+
JAR 35
FRONT OF TRAY
AY
#
JAR 36
JAR 8
TR
JAR 37
REAR OF TRAY
1
JAR 38
FRONT OF TRAY
AY
#
JAR 39
JAR 4
TR
JAR 40
TRAY #7
+
TRAY #10
JAR 1
TRAY #1
REAR OF TRAY
+
-
FRONT OF TRAY
TRAY #6
+
JAR 24
+
JAR 23
+
JAR 22
+
JAR 21
FRONT OF TRAY
JAR (BATTERY) CONFIGURATION
Liebert® NXL™ Battery System
42
Installation Drawings
Figure 39 Front-Terminal battery configuration
JAR #30
JAR #28
JAR #3
JAR #1
CABINET A CABINET B
Top of Cabinet
- + -
+ -
+
-
30 29 28
JAR #27
JAR #25
JAR #6
3
+ -
+ -
+
-
JAR #9
JAR #7
+ -
6
JAR #19
JAR #12
JAR #10
+ -
+
-
+
1
+ -
+
-
+ -
5
+
4
+ - + -
9
24 23 22
- + -
JAR #21
2
- + -
27 26 25
JAR #22
+ -
JAR #4
-
JAR #24
+ -
8
+ -
+
7
+ -
+
21 20 19
12 11 10
-
+ - + - +
- + - + - +
18 17 16
15 14 13
Bottom of Cabinet
JAR #18 JAR #17 JAR #16
JAR #15 JAR #14 JAR #13
CABLE
INTERCONNECT
DIAGRAM
FRONT
43
Liebert® NXL™ Battery System
Installation Drawings
Figure 40 Busbar connection between Battery Cabinet and Attached Junction Cabinet
Left-Side Busbar Connections
Note: This connection is
the same for top-terminal
(12V) battery cabinets and
front-terminal (16V)
battery cabinets.
Right-Side Busbar Connections
Liebert® NXL™ Battery System
44
Specifications
4.0
SPECIFICATIONS
Table 17
Liebert NXL Battery Cabinet specifications
Values
Top-Terminal Cabinet
Battery Cabinet Parameters
Battery Type
Front-Terminal Cabinet
VRLA (Valve Regulated Lead Acid)
Nominal Battery Bus, VDC
480V
Battery Float Voltage, VDC
540V
384V (for VRLA / Flooded Lead Acid)
Minimum EOD Voltage, VDC
Battery Discharging Maximum Current (EOD), A
See Table 20
Physical Parameters and Standards
Width, in. (mm) 1
Depth, in. (mm)
56.5 (1435)
2
Height, in. (mm)
Weight, lb (kg) approx.
63.0 (1600)
33.5 (850)
33.5 (850)
76.8 (1950)
76.8 (1950)
Table 22
Standard Color
Black (ZP-7021)
More than 180°
Front Door Opening (for serviceability)
IP 20 (with and without front door open)
Degree of Protection for UPS Enclosure
Minimum Clearance, Top
24" (610mm)
Minimum Clearance, Back
0"
Minimum Clearance, Sides
0"
Cable Entrance
Top or Bottom
UL 1778; CSA 22.2 107.3
FCC Part 15, Class A; ISTA Procedure 1H; WEEE;
IBC 2012/CBC 2010
Standards & Conformities
Environmental
Storage Temperature Range, °F (°C)
-13°F to 158°F (-25°C to 70°C)
74°F to 80°F (23-27°C) for optimal battery life
Operating Temperature Range, °F (°C)
32°F to 104°F (0 to 40°C)
74°F to 80°F (23-27°C) for optimal battery life
up to 95% Non-Condensing
(Operating and Non-Operating)
Relative Humidity
Maximum Altitude Above MSL, ft (m)
4920 (1500) (as per IEC 62040/3) 1% Maximum kW derate / 100m rise between 1500-3000m
1. Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels.
2. Depth dimensions include the front door and rear panel.
45
Liebert® NXL™ Battery System
Specifications
Table 18
Liebert NXL Junction Cabinet specifications
Value
Top-Terminal
Attached
Battery Specifications
Stand-Alone
Attached
480V
Nominal Battery Bus, VDC
Battery Float Voltage, VDC
540V
384V (for VRLA / Flooded Lead Acid)
Minimum EOD Voltage, VDC
Battery Discharging Max current (EOD), A
Table 20
Physical Parameters
Width, * in (mm)
15.5 (393)
30.9 (785)
17.5 (445)
Depth, in (mm) **
33.5 (850)
33.5 (850)
33.5 (850)
76.8 (1950)
76.8 (1950)
76.8 (1950)
255 (115)
400 (180)
255 (115)
Height, in (mm)
Weight, lb (kg) approx.
Color
Black (ZP-7021)
Degree of Protection for UPS Enclosure
IP 20
Minimum clearance, Top
24" (610mm)
Minimum clearance, Back
0"
Minimum clearance, Sides
0"
Location of cable entrance
Top or Bottom
UL 1778; CSA 22.2 107.3; FCC Part 15, Class A
ISTA Procedure 1H; WEEE; IBC 2012/CBC 2010
Standards and Conformities
Environmental
Storage Temperature Range, °F (°C)
-13°F to 158°F (-25°C to 70°C)
Operating Temperature Range, °F (°C)
32°F to 104°F (0 to 40°C)
Maximum 95% Non-Condensing
(Operating and Non-Operating)
Relative Humidity
Maximum Altitude above MSL, ft (m)
4920 (1500) (as per IEC 62040/3) 1% maximum kW derate / 328ft rise between 4900-9800ft
(100m rise between 1500-3000m)
* Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels.
** Depth dimensions include the front door and rear panel.
Alber® battery monitoring option specifications
Table 19
Electrical Data
Value
Input Voltage
220-600VAC
Input Current
< 0.5A
Frequency
60Hz
Table 20
DC currents for Liebert NXL modules
UPS Rating
kVA
kW
Max Battery
Current at EOD
250
225
615
300
270
730
400
360
980
500
450
1241
625
625
1645
750
675
1850
800
800
2061
1100
1100
2860
Liebert® NXL™ Battery System
46
Specifications
Table 21
Liebert NXL Battery Cabinet internal breaker
Model #
Code
Battery Type
Required Breaker
Thermal Trip Amps
PR
UPS12-300MR
400
RR
UPS12-350MR
450
UR
UPS12-400MR
500
WS
UPS12-490MRLP
600
XR
UPS12-540MR
600
PX
HX300-FR
400
RX
HX330-FR
450
UX
HX400-FR
500
WX
HX500-FR
600
XX
HX540-FR
600
2K
16HX800F-FR
250kVA - 700A
300kVA - 800A
400kVA & above - 900A
4K
16HX925F-FR
600
RA
27HR3500
400
UA
31HR4000
500
WA
31HR5000
600
PG
XE60
700
PH
XE60 w/Jacket
700
VG
XE95
700
VH
XE95 w/Jacket
700
Table 22
Battery
Code
Liebert NXL Battery Cabinet approximate weights
Manufacturer
PR
RR
UR
C&D
Batteries
Battery Model
Total Weight
lb (kg)
UPS12-300MR
3910 (1774)
UPS12-350MR
4265 (1935)
UPS12-400MR
4600 (2087)
UPS12-490MRLP
5545 (2515)
XR
UPS12-540MR
5545 (2515)
PX
HX300-FR
3760 (1706)
RX
HX330-FR
4200 (1905)
UX
HX400-FR
4760 (2159)
WX
HX500-FR
5750 (2608)
XX
HX540-FR
5850 (2653)
WS
2K
Enersys
16HX800F-FR
8510 (3860)
4K
16HX925F-FR
8990 (4078)
PG
XE60
3586 (1626)
PH
XE60 w/Jacket
3586 (1626)
VG
XE95
4706 (2135)
VH
XE95 w/Jacke
4706 (2135)
QA
27HR3500
4000 (1814)
31HR4000
4320 (1960)
31HR5000
5280 (2395)
SA
WA
East Penn
47
Liebert® NXL™ Battery System
Specifications
Table 23
Recommended external conduit and cable sizes from Liebert NXL UPS to DC source
UPS Rating
kVA
(# of conduits); size of conduits;
# -size of phase cables per conduit; size of cable for ground per conduit
250
(2) 2C 2-600kcmil, #1/0AWG
(2) 2.5C 2-750kcmil, #3/0AWG
300
(2) 2.5C 2-750kcmil, #1/0AWG
(3) 2.0C 2-500kcmil, #3/0AWG
400
(3) 2C, 2-500kcmil, #2/0AWG
(3) 2.0C 2-600kcmil, #4/0AWG
500
(3) 2.5C, 2-750kcmil, #4/0AWG
(4) 2.5C 2-700kcmil, 350kcmil
625
(5) 2.5C 2-600kcmil, 250kcmil
(6) 2.5C 2-600kcmil, 400kcmil
750
(5) 2.5C, 2-600kcmil, 250kcmil
(6) 2.5C 2-600kcmil, 400kcmil
800
(6) 2.5C 2-600kcmil, 350kcmil
(7) 2.5C 2-700kcmil, 600kcmil
1100
(7) 2.5C 2-750kcmil, 400kcmil
(8) 2.5C 2-700kcmil, 600kcmil
1. Recommended cable sizes are 167°F (75°C) (THW) wire at 86°F (30°C) ambient. Unless otherwise noted, use copper or
aluminum conductors suitable for at least 167°F (75°C).
2. For continuous operations not at 86°F (30°C), Emerson recommends that the site planner choose the appropriate cable type
based on the particular installation requirements.
3. Conduit size is based on FMC type conduit
Table 24
Recommended lug sizes
Cable
Size
T&B Copper
One Hole
T&B Copper
Two Hole
T&B Aluminum
One Hole
T&B Aluminum
Two Hole
#8AWG
54930BE
54850BE
60104-TB
—
#6AWG
54905BE
256-30695-868
60109-TB
—
#4AWG
54906BE
256-30695-733
60114-TB
—
#2-3AWG
54942BE
54811BE
60120
—
#1AWG
54947BE
54857BE
60126
—
#1/0AWG
54950BE
256-30695-593
60132
—
#2/0AWG
54951BE
54862BE
60138
60238
#3/0AWG
54965BE
54864BE
60144
60244
#4/0AWG
54970BE
54866BE
60150
60250
250kcmil
54913BE
54868BE
60156
60256
300kcmil
54914BE
54870BE
60162
60262
350kcmil
54915BE
54872BE
60165
60267
400kcmil
54916BE
54874BE
60168
60269
500kcmil
54918BE
54876BE
60171
60273
600kcmil
54920BE
54878BE
60176
60275
750kcmil
54922BE
54880BE
60178
60277
Liebert® NXL™ Battery System
48
Specifications
Table 25
Battery torque values
Battery
Code
Battery Model
Torque Value
in-lb (Nm)
PR
UPS12-300MR
110 (12.4)
RR
UPS12-350MR
110 (12.4)
UR
Manufacturer
C&D Batteries
UPS12-400MR
110 (12.4)
WS
UPS12-490MRLP
110 (12.4)
XR
UPS12-540MR
110 (12.4)
PX
HX300-FR
65 (7.3)
RX
HX330-FR
65 (7.3)
UX
HX400-FR
65 (7.3)
WX
HX500-FR
65 (7.3)
XX
HX540-FR
65 (7.3)
16HX800F
100 (11.3)
Enersys
2K
4K
16HX925F
100 (11.3)
PG
XE60
60 (6.8)
PH
XE60 w/Jacket
60 (6.8)
VG
XE95
60 (6.8)
VH
XE95 w/Jacket
60 (6.8)
QA
27HR3500
65 (7.3)
31HR4000
65 (7.3)
31HR5000
65 (7.3)
SA
East Penn
WA
Table 26
Torque specifications, unless otherwise labeled
Nut and Bolt Combinations
Bolt Shaft Size
Grade 2 Standard
lb-in (Nm)
Electrical Connections
with Belleville Washers
lb-in (Nm)
1/4 (M6)
53 (6.0)
46 (5.2)
5/16 (M8)
107 (12)
60 (6.8)
3/8 (M10)
192 (22)
95 (11)
1/2 (M12)
428 (48)
256 (29)
Circuit Breakers with Compression Lugs (For Power Wiring)
Current Rating
lb-in (Nm)
—
400 - 1200 Amps
300 (34)
—
Circuit Breakers with Compression Lugs (For Control Wiring)
AWG Wire Size or Range
lb-in (Nm)
—
#22 - #14
3.5 to 5.3 (0.4 to 0.6)
—
49
Liebert® NXL™ Battery System
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Emerson Network Power, a business of Emerson (NYSE:EMR),
is the global leader in enabling Business-Critical Continuity™
from grid to chip for telecommunication networks, data centers,
health care and industrial facilities. Emerson Network Power
provides innovative solutions and expertise in areas including
AC and DC power and precision cooling systems, embedded
computing and power, integrated racks and enclosures,
power switching and controls, infrastructure management,
and connectivity. All solutions are supported globally by local
Emerson Network Power service technicians. Liebert AC power,
precision cooling and monitoring products and services
from Emerson Network Power deliver Efficiency Without
Compromise™ by helping customers optimize their data center
infrastructure to reduce costs and deliver high availability.
Technical Support / Service
Web Site
www.liebert.com
Monitoring
liebert.monitoring@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 2010 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks
or registered trademarks of their respective owners.
SL-25430_REV8_09-13
Emerson Network Power.
The global leader in enabling Business-Critical Continuity™
AC Power
Connectivity
Embedded Computing
Embedded Power
DC Power
Infrastructure Management & Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
EmersonNetworkPower.com
Racks & Integrated Cabinets
Services
Surge Protection