Security Level: INTERNAL UPS5000-E-(40 kVA–320 kVA) Training Network Energy Product Line Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. www.huawei.com Contents Chapter 1 Working Principles Chapter 2 Introduction to the UPS Chapter 3 Installation and Commissioning Chapter 4 Acceptance Chapter 5Troubleshooting Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 1 1.1 Definition UPS: uninterruptable power system Power supply backup: batteries The UPS supplies continuous power to loads when the mains is abnormal. Transportation Government Finance Retail Communication ISP Energy Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Manufacturing Page 2 1.2 Why Is UPS Used? Peak Highfrequency interruption Too high Total harmonic distortion (THD) Too low Normal power grid Voltage dip Abnormal power grid The mains is not perfect, and mains outrage may occur. If the mains is abnormal, devices cannot run properly and even be damaged. The UPS removes the abnormal factors brought by the mains and supplies pure power to loads. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 3 1.2 Why Is UPS Used? Four Functions Uninterruptible power supply Pure power Power grid pollution removed A UPS increases the input power factor (PF) to decrease harmonic pollution. The UPS supplies pure power to loads. Mains outages resolved When the mains fails, batteries in a UPS supply power to loads. Functions Power management Stable AC outputs A UPS supports online management. Mains voltage stabilized A UPS supports a wide input voltage range, which ensures stable alternating current (AC) outputs to loads. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 4 1.3 UPS5000-E Conceptual Diagram UPS5000-E is an online double converter modular UPS. The conceptual diagram is as follows. Maintenance bypass Bypass input Bypass module Mains input Output Rectifier Battery string DC/DC Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Inverter Power module Page 5 1.4 UPS5000-E Working Mode_Normal Mode Maintenance bypass Bypass input Bypass module Mains input Output Rectifier Battery string DC/DC Inverter Power module When the UPS5000-E runs properly, the rectifier converts the mains input into DC power, and then the inverter converts DC power into AC power. During this process, the charger charges batteries. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 6 1.4 UPS5000E Working Modes_Battery Mode Maintenance bypass Bypass input Bypass module Mains input Output Rectifier Battery string DC/DC Inverter Power module When the mains is abnormal, the UPS5000-E enters battery mode. The rectifier boosts the voltage and provides DC power. The inverter converts the DC power into AC power. It takes 0 ms to transfer between normal mode and battery mode. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 7 1.4 UPS5000-E Working Modes_Bypass Mode Maintenance bypass Bypass input Bypass module Mains input Output Rectifier Battery string DC/DC Inverter Power module When the UPS works in bypass mode, currents flow through the bypass module to the loads, while the charger in the power module charges batteries. Note: In this mode, the power supplied to the loads may be interrupted. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 8 1.4 UPS5000-E Working Modes_Maintenance Bypass Maintenance bypass Bypass input Bypass module Mains input Output Rectifier Battery string DC/DC Inverter Power module During maintenance, the UPS5000-E works in maintenance bypass mode. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 9 1.4 UPS5000-E Working Mode_ECO Mode Maintenance bypass Bypass input Bypass module Mains input Output Rectifier Battery string DC/DC Inverter Power module ECO mode is very similar to bypass mode. In ECO mode, the UPS5000-E reaches an efficiency of up to 99.4%. If the bypass input is abnormal, the system transfers to normal mode in 10 ms, ensuring stable power supply to the loads. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 10 Contents Chapter 1 Working Principles Chapter 2 Introduction to the UPS Chapter 3 Installation and Commissioning Chapter 4 Acceptance Chapter 6 Troubleshooting Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 11 2.1 Overview No. Meaning Description 1 2 3 Product category UPS Product series 5000 UPS subcategory 4 Output capacity 5 Rack type E series 40K: The output capacity is 40 kVA. 80K: The output capacity is 80 kVA. 120K: The output capacity is 120 kVA. 160K: The output capacity is 160 kVA. 200K: The output capacity is 200 kVA. 240K: The output capacity is 240 kVA. 280K: The output capacity is 280 kVA. 320K: The output capacity is 320 kVA. F120: 120 kVA rack F200: 200 kVA rack F320: 320 kVA rack Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 12 2.1 Overview The UPS5000-E (40 kVA–200 kVA), together with the mains, AC transfer switch (ATS), and batteries, constitutes a power supply solution for a large equipment room, as shown in the following figure. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 13 2.1 Overview Single UPS Single UPS + Input and output PDCs Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 14 2.1 Overview Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. 1 Top tray cover 2 Control cable tray cover 3 Monitor display unit (MDU) 4 Castors Page 15 2.3 Components 1 Filler panels 2 Power modules 3 Bypass module 4 Energy control module (ECM) 5 Maintenance bypass switch 6 Power distribution module The UPS5000-E power components include the power module (a maximum of eight), bypass module, ECM, and power distribution module. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 16 2.3 Components - Power Module Power module Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 17 1 Phase lock 2 Run indicator 3 Alarm indicator 4 Fault indicator 5 In-position switch 6 Output port 7 Input port 2.3 Components - Bypass Module When the power module is faulty or when you manually transfer the UPS to bypass module, the bypass module provides the bypass voltage. In addition, the bypass module provides the system output voltage, output current, and output power. Therefore, if the bypass module is removed, the LCD may not correctly display the output voltage, current, and load ratio, and the UPS may generate a false alarm about power module current imbalance. The bypass module dimensions (H x W x D) are 420 mm x 130 mm x 500 mm. The weight is 19 kg. The maximum capacity is 200 kVA. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 18 2.3 Components - Bypass Module 9 Front panel Rear panel Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. 1 Phase lock 2 Cold startup button 3 Run indicator 4 Alarm indicator 5 Fault indicator 6 In-position switch 7 Signal port 8 Input and output ports 9 Crowbar Page 19 2.3 Components – Monitoring System (1) Ground terminal (2) Parallel port 1 (3) Indicator (4) Parallel port 2 (5) Indicator (6) Dry contact card (7) Dry contact port (8) MDU port (9) RS485 port (10) FE port (11) COM2 port (12) COM1 port (13) Battery temperature sensor port (14) Optional card slot (15) BSC port 2 (16) BSC port 1 Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 20 2.3 Components - ECM 1 BSC port 2 Parallel port 3 Run indicator 4 Alarm indicator 5 Fault indicator The energy control unit (ECU) processes intra-cabinet and inter-cabinet signals and status information, and transfers the information to the monitoring module. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 21 2.3 Components - Monitoring Interface Card Port DO_1 DO_2 DO_3 DO_4 Silk Screen Description DO_1_NO DO_1_COM DO_2_NO DO_2_ COM DO_3_NO DO_3_ COM DO_4_NO DO_4_ COM Each of the ports indicates battery mode, bypass mode, low battery voltage, critical alarm, or minor alarm. DB26 MDU Battery temperature B_TEMP Southbound communications port 2 Southbound communications port 1 Network port Northbound communications port Provides fast Ethernet (FE), RS485, Inter-Integrated Circuit (I2C), and control area network (CAN) signals. Connects to an indoor battery temperature sensor, such as a negative temperature coefficient (NTC) resistor. COM2 Connects to a southbound device, such as the BMU. COM1 Connects to an ambient temperature and humidity sensor. Two-wire. FE Network port RS485 Connects to a northbound network management device. Two-wire. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 22 2.3 Components - MDU Status On Off 1. Fault indicator 2. LCD screen Color Meaning Red A critical alarm is generated. Yellow A minor alarm is generated. Green The UPS is running properly. None The MDU powers off. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 23 2.3 Components - Dry Contact Card Dry contact card Port J1 J2 J3 Silk Screen BAT_GROUND_FAULT GND GEN_CONNECT GND BCB_ONLINE Description Detects battery grounding failures. If it is closed, a fault occurs. Secondary side ground Detects D.G. mode. If it is closed, the system works in D.G. mode. Secondary side ground Detects battery circuit breaker (BCB) connection. If it is closed, the BCB is connected. BCB_STATUS Monitors the battery circuit breaker. If it is closed, the battery circuit breaker is ON. BCB_DRIVER GND EPO_NO 12V_2 EPO_NC 12V_2 GND Controls battery circuit breaker trip. If the voltage is +12 V, the circuit breaker trips. Secondary side ground EPO port. It is normally open (NO). If it is closed, EPO is triggered. +12 V EPO port. It is normally closed (NC). When it is open, EPO is triggered. +12 V Monitors the UPS output circuit breaker on the output power distribution cabinet (PDC). If it is closed, the circuit breaker is ON. Secondary side ground Q_MAINTAIN_STATUS Monitors the maintenance circuit breaker on the output PDC. If it is closed, the switch is ON. GND GND Secondary side ground Monitors the bypass input circuit breaker on the input PDC. If it is closed, the circuit breaker is ON. Secondary side ground SPD_IN_STA Monitors the input AC surge protection device (SPD). If it is closed, the SPD is normal. GND Secondary side ground Q_OUT_STA J4 Q_BP_STA J5 Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 24 Contents Chapter 1 Working Principles Chapter 2 Introduction to the UPS Chapter 3 Installation and Commissioning Chapter 4 Acceptance Chapter 5 Routine Maintenance Chapter 6 Troubleshooting Chapter 7 Key Delivery Points Chapter 8 Test Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 25 3 Installation and Commissioning Site Survey Before Installation 1 Installation Preparations 2 Installation 3 Check After Installation 4 Check Before Powering On the UPS 5 Commissioning 6 Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 26 3.1 Site Survey Before Installation Environment Ambient temperature, humidity, altitude, verticality, pollution level, and ventilation condition Power supply Site survey Installation position Bearing capacity Neutral-ground voltage Sufficient mains capacity Circuit breaker or power distribution cabinet Position for installing the UPS and batteries Clearance between adjacent devices No blockage Bearing capacity and dimensions of the elevator UPS type and battery weight Bearing capacity of the floor For details, see the Engineer Guide. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 27 3.2 Installation Preparations Place the common tools in a tool kit. Tools Connects cables and tightens screws. Transports the UPS. Rapidly tightens bolts. Cut cables. Peels cables. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Tightens bolts. Tightens the screws on circuit breakers. Checks electrical connections and measures electrical properties. Page 28 Protect hands. Environment Requirements UPS location Typically, a USP is installed indoors. It is installed in a cool, dry, clean, and flat environment with good ventilation. Battery location Typically, batteries are installed in a stable temperature which ranges from 15°C to 25°C and away from heat source or the main air vent. Batteries are installed on a dedicated battery rack which is close to the UPS. The battery switch is installed near batteries. Ensure the shortest cabling distance. Operation space Proper clearance is reserved behind and above the UPS for air ventilation and heat dissipation, in the front of the UPS for operation, and on the left and right for routine maintenance. If there are multiple cabinets, connect them in one row. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 29 3.3 Installation Start Preparation Check that the UPS is intact and the UPS model is correct. Check that environment requirements are met. For details, see Chapter 3 in the Engineer Guide. Installation UPS and battery installation Separate installation of UPSs in a parallel system Ensure that you follow the installation procedure. Installation preparation Battery rack installation Cable connection Cable Connections Connections of power cables and signal cables Choose the correct cable configurations. Ensure that cables are connected in order and securely. UPS installation Optional component installation Check after installation Check After Installation Checking after the installation is mandatory. Follow the check items in the Engineer Guide. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. End Installation Process Page 30 3.3 Installation - Unpacking Step 1: Remove the binding tape. Step 2: Removing the box. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 31 3.3 Installation - Unpacking Step 3: Remove the L-shape angle. Step 4: Raise the feet. After the preceding four steps, move the cabinet over its castors to the installation position. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 32 3.3 Installation - Installing the UPS Cabinet 1. Raise the four leveling feet at the bottom of the cabinet by using a wrench until all the four castors at the bottom hang in the air and the leveling feet bear all of the cabinet weight. 2. Check the cabinet levelness by using a level. If the cabinet is not leveled, adjust the leveling feet. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 33 3.3 Installation - Installing the UPS Cabinet Secure Installation 1. On the planned installation position, draw the mounting holes based on the drawings. 2. Use a hammer drill to drill holes in the position for installing expansion bolts. 3. Install expansion bolts in the holes. Cabinet holes (standard configuration) Unit: (mm) Rear of the cabinet Cabinet hole (antiseismic kit configured) Unit: (mm) ≥ 800 Front of the cabinet Rear of the cabinet ≥ 800 Front of the cabinet ≥ 800 ≥ 800 Wall Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Wall Page 34 3.3 Installation - Installing the UPS Cabinet 1. Move the cabinet over its castors to the installation position. 2. Remove the four rubber plugs at the bottom of the cabinet. Removing rubber plugs Tightening expansion bolts The UPS in standard configuration is installed. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 35 3.3 Installation - Installing the Top Outlet Kit (Optional) Remove the rear panel and the rear cover at the top. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Install a baffle plate on the real panel. Page 36 3.3 Installation - Routing Cables (from the Top) Remove the cable tray cover, and route cables in the middle of the cover. If you need to drill holes based on the site requirements such as the number of cables and cable size, drill holes on the large cover in the middle of the cabinet top. After routing cables, use fireproof mud to fill in the gap between the cables and the cabinet. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Routing signal cables at the top of the cabinet Page 37 3.3 Installation - Routing Power Cables (from the Top) 1. Mains input power cable 2. Mains input L1 3. Mains input L2 4. Mains input L3 5. Mains input N 9. Bypass input L3 6. Bypass input power cable N 10. Bypass input N 7. Bypass input L1 11. Output power cable 8. Bypass input L2 12. Output U 13. Output V 14. Output W 15. Output N 16. Battery input positive terminal 17. Battery input N 18. Battery input negative terminal Only UPS5000-E-200 kVA cables can be routed from the top. UPS5000-E-320 kVA cables can be routed only from the bottom; if you need to route cables from the top, install a top entry cabinet. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 38 3.3 Installation - Routing Cables (from the Bottom) Remove the power distribution cover. Remove the cable tray cover from the bottom of the cabinet. After routing cables, use fireproof mud to fill in the gap between the cables and the cabinet. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 39 3.3 Installation - Routing Power Cables (from the Bottom) Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 40 1 Mains input power cable 2 Mains input L1 (U) 3 Mains input L2 (V) 4 Mains input L3 (W) 5 Mains input N 6 Mains input power cable 7 Bypass input L1 (U) 8 Bypass input L2 (V) 9 Bypass input L3 (W) 10 Bypass input N 11 Output power cable 12 Output U 13 Output V 14 Output W 15 Output N 16 Battery input positive terminal 17 Battery input N 18 Battery input negative terminal 3.3 Installation - Routing Signal Cables (from the Bottom) Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 41 3.3 Single UPS Installation - Connecting Power Cables (AC Input Power Cables) One mains input: You need only to connect four mains input power cables. The bypass module connects to the mains over a copper bar. 1. Input terminal L1 2. Input L2 Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. 3. Input L3 4. Input N Page 42 3.3 Single UPS Installation - Connecting Power Cables (AC Input Power Cables) Two mains inputs: Remove the copper bar between the bypass module and the mains, and connect the mains and bypass input power cables. 1. Bypass input L3 2. Bypass input L2 3. Bypass input L1 4. Bypass input N 5. Mains input L1 6. Mains input L2 7. Mains input L3 8. Mains input N Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 43 3.3 Single UPS Installation - Connecting Power Cables (AC Output Power Cables and Battery Cable) Connecting the output power cables 1. Output N 2. Output U 3. Output V 4. Output W Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Connecting the battery cable 1. Battery input+ Page 44 Battery 2. Battery input N 3. input – 3.3 Single UPS Installation - Connecting Power Cables Ground the cabinet. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 45 3.3 Single UPS Installation - Connecting Control Cables - BCB Box (Optional) Open the BCB box cover, and connect J2 on the dry contact card to the dry contact on the BCB box. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 46 3.4 Check After Installation Purpose Ensure that the UPS runs properly. Prerequisite The UPSs have been installed, and the input and output cables, communications cables, dry contact signal cables, and parallel cables are connected. No. 01 Item Consistency between the system configuration and the delivery configuration Expected Result The system configuration, including model and number of modules, complies with the contract. 02 UPS and battery installation The cabinet and batteries are installed steadily and firmly. 03 Cable layout Cables are routed properly and meet engineering requirements. 04 Cable connections For the cables secured by screws, the spring washers are flattened. All cable connectors are secure. 05 Dry contact connections Correct cables are used and secured to the UPS and PC by using screws. 06 Voltage between the neutral wire and the ground cable The neutral-ground voltage is less than 5 V AC. 07 Cable labels Both ends of a cable are labeled. Labels are clean and correct, and provide concise and understandable cable description. 08 Ground cable connection The ground cable connects to the ground bar in the equipment room. 09 Distances between cable ties Distances between cable ties are the same, and no burr exists. 10 Battery cable connections Battery cables are connected correctly based on the + and – signs. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 47 3.5 Check Before Powering On the UPS Purpose Ensure that the UPS is ready for power-on. Prerequisite The UPS has been installed and power cables are connected, and the installation has been verified. No. Item 01 The UPS input switch, bypass switch, output switch, maintenance bypass switch, and battery circuit breaker are all OFF. 02 The load switches are OFF, and the loads have shut down. 03 The UPS input live wire and neutral wire are connected correctly. Live wires are connected in a correct sequence. No short circuit occurs between the live wire and the ground cable. The UPS output has no short circuit. Check cable connections. If cables are not correctly connected, the UPS may be damaged upon power-on. 04 Use a multimeter to measure the front-end AC voltage of the mains and bypass input switches. The AC input voltage must be 304–478 V AC. Otherwise, you need to start the UPS5000 in non-mains mode. 05 Use a multimeter to measure the front-end DC voltage of the battery switch. The battery string voltage must meet specifications, preventing reverse connections. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 48 3.6 Commissioning_LCD Main Menus The LCD screen is divided into four parts: status bar, alarm bar, menu bar, and information display area. 1. Status bar 2. Alarm bar Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. 3. Information area Page 49 4. Menu bar 3.6 Commissioning _ Initial Start Settings 1. Select a language. 2. Set the date and time. After you select a language, click Next to set the date and time. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 50 3.6 Commissioning _ Initial Start Settings 3. Set network parameters. 4. Set the system parameters. The initial start-up settings are complete. To set other parameters, enter the main menu Settings. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 51 3.6 Commissioning _ Other System Settings After initial start-up settings, check some important system parameters so that the system runs properly. Enter the Settings menu. Touch the Settings button to enter the Settings menu. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 52 3.6 Commissioning _ Common Settings Touch the Common button to enter the Common menu. On the Common screen, set the language, date, time, and user password. Most of the parameters have been set during initial start-up setting. You need only to set the user password. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 53 3.6 Commissioning _ Communication Settings Touch the Communication button to enter the Communication menu. Set IP address allocation to Manual or Automatic. You can change RS485 baud rate and RS485 address. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 54 3.6Commissioning _ Basic Parameter Settings Touch the Dry Contacts button to enter the Dry Contacts menu. Select Single or Parallel. When you select Parallel, more menus will be displayed. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 55 3.6 Commissioning _ Advanced Parameter Settings Most of the parameters affect normal UPS running. Therefore, set them correctly. For details, see the Engineer Guide. After you install a top outlet fan, set Top air outlet option to Enabled. Otherwise, top outlet kit cannot work properly. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 56 3.6 Commissioning _ Input Parameter Settings You can set input parameters, mainly including current limiting and D.G. settings. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 57 3.6 Commissioning _ Output Parameter Settings On the Output Param. screen, set output parameters and output mode. You can adjust the output voltage within the range of ±5%. The self-load mode is set here. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 58 3.6 Commissioning _ Bypass Parameter Settings Set the bypass voltage and frequency range. Set the ECO voltage range (ECO mode is set on the Advanced Param. screen.) Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 59 3.6 Commissioning _ Battery Parameter Settings Set Battery string sharing as required. For Battery capacity, see the battery configurations or ask for help. Most parameters involve the battery lifespan. Set the parameters carefully. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 60 3.6 Commissioning _ Dry Contact Settings Before you set dry contact parameters, set MUE05 connection to Enabled. If a backfeed protection card is configured, set MUE06 connection to Enabled. If no optional component is configured, set the parameters to Disabled to prevent misoperations. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 61 3.6 Commissioning _ Fast Settings Fast settings refer to first start-up settings. For detail, see 3.6 "Commissioning _ First Start-Up Settings." Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 62 3.6 Commissioning _ Basic Operations Touch the Common Functions button to enter the menu. Yan perform startup and shutdown and mute the buzzer. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 63 3.6 Commissioning _ Basic Operations Touch the System Status button to view the system status. View the information such as UPS running status and current flow. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 64 3.6 Commissioning _ Basic Operations Touch the Alarms button to view the system alarms. View the UPS alarm information. Analyze active alarms and historical alarms to identify faults. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 65 3.6 Commissioning _ Single UPS Startup Continuous, pure, and stable power After system settings, start and commission the UPS. Step 5 Start loads. Step 4 Turn on the battery switch. Turn on the battery switch. The Battery Disconnected alarm will be cleared after 1 minute, and the running status is Battery charging. Step 3 Start the inverter. Perform operations on the LCD to run the UPS in normal mode. Check that the UPS runs properly. Step 2 Set parameters and check the system status. Set system parameters and view the LCD. Normally, there is only Battery Disconnected alarm. Step 1 Turn on the mains and bypass input switches. The indicator of each module starts. The LCD powers on. Huawei logo is displayed. One minute later, the operation screen is displayed. The Battery Disconnected alarm is displayed. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 66 3.6 Commissioning _ Single UPS Shutdown Check that the loads have shut down. After you shut down the bypass module, the UPS will supply no power. To continue supplying power, use maintenance bypass mode. Step 4 The loads power off completely. The MDU and indicators turn off. Step 3 a. Turn off the input switch SWIN. b. Turn off the bypass switch SWBY. Step 3 Turn off the battery string switch. Step 2 Turn off the output or load switch. Step 1 Shut down loads. Keep the UPS running without loads to dissipate its heat. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 67 Contents Chapter 1 Working Principles Chapter 2 Introduction to the UPS Chapter 3 Installation and Commissioning Chapter 4 Acceptance Chapter 6 Troubleshooting Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 68 4.3 Critical Check Items and Check Methods The UPS is firmly attached to the ground without visible Mechanical installation and cable connection gap. The spring washers are flattened. Connect a multimeter to two terminals to check whether they are short-circuited. Input and output power cables If the cables are connected in wrong phase sequence, AC input phase sequence Battery positive and negative terminals Phase locking of a parallel system the LCD displays an error message. To rectify the fault, switch two phases. Use a multimeter to measure the DC voltage on the UPS battery input terminals (BAT+/BAT-). In normal mode or battery mode, two UPSs in a parallel system provide output voltages with a gap of less than 5 V in each phase. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 69 4.3 Critical Check Items and Check Methods Cable layout Cables are routed straightly and bound neatly, and sufficient space is reserved for installing new cables. The communications cables are correctly connected Communications cable Neutral-ground voltage and the UPS data can be read on the upper-layer equipment. Use a multimeter to check whether the neutral- ground voltage is less than 5 V AC. Cable label Cable labels provide simple and clear instructions. Functions Commission the UPS based on the Engineer Guide. Check whether the UPS functions properly. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 70 Contents Chapter 1 Working Principles Chapter 2 Introduction to the UPS Chapter 3 Installation and Commissioning Chapter 4 Acceptance Chapter 6 Troubleshooting Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 71 6.1Troubleshooting Process Report faults. Fault Record UPS status (panel information) Record faults. bypass voltage amplitude fast check Record environmental data. UPS input and output and battery parameters check Identify fault types. Status of all switches and circuit breakers Internal faults External cause Component damaged and cable disconnected Identify and rectify faults. Environment Condition Record Identify faulty boards. Ventilation Replace faulty boards. Ambient temperature Installation clearance N Normal? Y Startup Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Surrounding environment Battery cable distribution Load name, type, and rated power Page 72 6.2 Fault Information Collection and Diagnosis Collect fault information onsite by following the troubleshooting flowchart (see the Engineer Guide). Power system status (panel information): Actual input, output, and battery parameters of the power system Status of all switches and circuit breakers Record: 1. Ventilation 2. Ambient temperature 3. Installation clearance Type UPS Status Silent The UPS is working properly. Warnings 4. Dust and humidity 5. Input and output power cables; cable diameters; insulation layer; wiring terminals 6. Load name, type, and rated power (available from the customer) Identify the fault by referring the engineer guide. Record the alarm ID and locate the fault information in the engineer guide. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 73 Intermittent buzzing Minor alarms Long buzzing Critical alarms 6.2 Fault Information Collection and Diagnosis Choose USB Local Collection Wizard. After you choose UPS Wizard, the following menus are displayed. Typically, you need to export logs, fault data, E-labels, and alarm information. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 74 6.2 Fault Information Collection and Diagnosis - Local Collection Export E-labels. Click E-label. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 75 6.2 Fault Information Collection and Diagnosis - Local Collection Export alarm information. Click Export Alarms. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 76 6.2 Fault Information Collection and Diagnosis - Local Collection Download fault data. Click Download Fault Data. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 77 6.2 Fault Information Collection and Diagnosis - Local Collection Download Logs Click Download Logs. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 78 6.3 Replacing Modules - Power Module Normal mode Bypass mode Redundancy (N+X) or dualbus? Yes Hot-swap No To replace a power module in bypass mode: 1. Shut down the inverter on the LCD to transfer the UPS to bypass mode. 2. Rotate the in-position switch to unlocked state. 3. Loosen the screws that fasten the power module. Wait 2 minutes and remove the power module. During this process, press down the phase lock. 4. After power module maintenance, ensure that the in-position switch is in unlocked state. Insert the power module, and tighten the screws. 5. Rotate the in-position switch to locked state. As required by the Upgrade Guide, check the power module program version. If the version is incompatible, upgrade the version. After operations are complete, manually start the inverter to recover normal mode. View the bypass status: LCD or multimeter Bypass voltage is normal? No Power-off and replacement No Transfer to maintenance bypass module and maintenance Yes View the load status on the LCD Yes N-1 modules support loads? To replace a power module in normal mode: 1. Remove the power module, as shown in the following figure. Insert a new module, and turn on the in-position switch. 2. The new module starts working. (If the version is incompatible, upgrade it.) Yes Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 79 6.3 Replacing Modules - Power Module Removing a power module Step 1 Step 2 Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 80 6.3 Replacing Modules - Power Module Removing a power module Step 1 Step 2 Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 81 6.3 Replacing Modules - Bypass Module To replace a bypass module in normal mode: 1. Remove the power module, as shown in the following figure. Insert a new module, and turn on the inposition switch. 2. The new module starts working. (If the version is incompatible, upgrade it.) Replace a bypass module. Running in bypass mode? Yes Transfer to maintenance bypass and maintenance No Hot swap To replace a bypass module in maintenance bypass mode: 1. Shut down the inverter on the LCD to transfer the UPS to bypass mode. 2. Turn on the maintenance bypass switch to transfer the UPS to maintenance bypass mode. 3. Rotate the in-position switch of the bypass module to unlocked state. 4. Loosen the screws that fasten the bypass module, and quickly remove the bypass module. 5. After bypass module maintenance or replacement, check that the in-position switch is in unlocked state and insert the bypass module. 6. Tighten the screws that fasten the bypass module, and rotate the in-position switch to locked state. Check the bypass module program version following the Upgrade Guide. If the version is incompatible, upgrade the module. 7. Turn off the maintenance bypass switch. The UPS transfers to bypass mode. Start the inverter. The UPS transfers to normal mode. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 82 6.3 Replacing Modules - ECU (ECU01A) 1. View alarms on the LCD to identify the ECM No. to be replaced. During replacement, check that the FAULT or ALM indicator on the ECU is on. If the ECU to be replaced is still running, perform operations on the LCD to transfer the ECM to standby state (the green indicator blinks). 2. Loosen captive screws, and push the micro switch on the ejector lever. Pull the ejector lever outwards to remove the ECM from the subrack. 3. Remove the ECM. In a parallel system, you need to remove the parallel cable. After replacement, connect the parallel cable to the new module. 4. Check on the LCD that all alarms are cleared. The replacement is complete. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 83 6.3 Replacing Modules - Dry Contract Card (MUE05A) Captive screws Ejector lever 1. Disable the dry contact card functions on the LCD. 2. Remove the dry contact card, and remove the terminals connected on the dry contact board. 3. Connect the external cables to the terminals on the new dry contact board, and insert the new dry contact board. Note: Ensure that the EPO switch status is the same as before. The LCD will report a dry contact board fault. After replacement, the alarm will be cleared automatically. 4. On the LCD, enable the dry contact card functions. The replacement is complete. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 84 Replace the backfeed protection card (MUE06A) and monitoring expansion card (MUE07A) in the same way as you replace the dry contact card. 6.3 Replacing Modules - Parallel Cable/BSC Cable Replace the parallel cable and BSC cable by removing it directly. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 85 6.4 Upgrading Software Module software upgrade is a common method during maintenance. Typically, there are two types of software upgrade: 1. Centralized upgrade of all modules 2. Separate upgrade of a new module During software upgrade, you may encounter upgrade failure or software and hardware incompatibility. In this case, resolve problems flexibly. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 86 6.4 Upgrading Software Upgrading a New Module During System Running Note: This upgrade method does not require you to turn on the maintenance bypass switch and the EPO switch. You can perform upgrade during system running. If the new module's software version is different from the software version running on the MDU, a message is displayed, asking you whether to upgrade software (module 1 is used as an example). Note: This message is displayed when the following two conditions are met: 1. The module software version is different from the running software version. 2. The module hardware version matches the source software version. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 87 6.4 Upgrading Software If software and hardware packages are incompatible, when you activate the upgrade package, the message "Software cannot be activated if hardware does not match" is displayed. Before the upgrade, ensure that the packages are compatible. It is recommended that you check the software package version. If the software package running on the MDU does not support the hardware version of the new module, the "Incompatible hardware version" message is displayed. The software version of the new module will not be upgraded. If you require this module to work, upgrade the software package. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 88 6.5 Fault Information Alarm ID Alarm Name Cause ID Alarm Generation Conditions 0001 Mains voltage abnormal 1 Alarm Clear Conditions Measures 80 V < Input voltage Vi ≤ 276 V Possible cause: The mains is abnormal. Proposal: Check the mains. 80 V < Input voltage Vi = 276 V Possible cause: The mains is abnormal. Proposal: Check the mains. Mains frequency f < 40 Hz or f > 40 Hz < Mains frequency f < 70 70 Hz Hz Possible cause: The mains is abnormal. Proposal: Check the mains. Input voltage Vi > 276 V 0001 Mains voltage abnormal 2 0001 Mains voltage abnormal 3 Input voltage 0004 Mains ph. 1 Reversed 0005 Mains neutral absent 1 Vi ≤ 80 V D-axis component filter D-axis component filter < ¼ of D-axis component amplitude (normalized) > ¼ of D-axis component amplitude (normalized) The three-phase mains average value is greater than the specified value. The three-phase mains average value is not greater than the specified value. For more information, see chapter 8 in the Engineer Guide. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 89 Possible cause: Power distribution is incorrect. Proposal: Check cable distribution. Possible cause: Power distribution is incorrect. Proposal: Check cable distribution. 6.6 Typical Case Analysis Symptom: The buzzer buzzes. The Fault indicator is on. The alarm ID 0040-01 is displayed. Cause: According to the alarm list, the fault results from failure in mains soft startup. Case 1: The rectifier is abnormal. Possible causes: (1) The rectifier SCR or SCR drive board is faulty. (2) The rectifier monitoring board is faulty. (3) The rectifier PFC IGBT short-circuits. Solution: Replace the faulty module. Symptom: The buzzer buzzes. The Fault indicator is on. The alarm ID 0060-01 is displayed. Cause: According to the alarm list, the fault results from the abnormal inverter output voltage. Case 2: The inverter is abnormal. Possible causes: (1) The inverter IGBT or IGBT drive board is faulty. (2) The inverter monitoring board is faulty. (3) The inverter voltage monitoring cable is faulty. Solution: Replace the faulty module. Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 90 Acronyms and Abbreviations C CE Conformite Europeenne E EPO Emergency Power Off L LCD Liquid Crystal Display P PFC Power Factor Correction PE Protective Earthing R RS232 Recommend Standard 232 S SNMP Simple Network Management Protocol U UPS Uninterruptible Power System Copyright © 2013 Huawei Technologies Co., Ltd. All rights reserved. Page 91 Page91 Thank you www.huawei.com