SAMSUNG Electronics HVAC
HVAC Guide Specifications
Variable Refrigerant Flow
Mini VRF Heat Pump Models with Multiple Indoor Units
Size Range:
3 TO 5 TONS NOMINAL
SAMSUNG Electronics Mini DVM S Eco 208/230 VAC Model Numbers:
AM036FXMDCH/AA
AM048FXMDCH/AA
AM053FXMDCH/AA
Part 1 – General
1.1
SYSTEM DESCRIPTION
A. The variable capacity, heat pump air conditioning system shall be a SAMSUNG
Electronics MINI DVM S ECO (Variable Refrigerant Flow) System.
B. The heat pump system shall consist of an AM0**FXMDCH/AA outdoor unit,
multiple indoor units (AM****N*DCH/AA models), and SAMSUNG DVM S
NASA Control Network Solution (Control systems). The AM0**FXMDCH/AA
outdoor unit shall be a horizontal discharge, 208/230 volt, single phase unit.
The AM0**FXMDCH/AA outdoor system model numbers and the associated
number of connectable indoor units per AM0**FXMDCH/AA outdoor unit is
indicated in the following table. Each indoor unit or group of indoor units shall
be independently controlled.
Model Number
AM036FXMDCH/AA
AM048FXMDCH/AA
AM053FXMDCH/AA
1.2.
1-6
1-8
1-9
PIPING
A.
1.3
Connectable Number
of Indoor Units
Piping to multiple indoor units requires additional piping components.
SAMSUNG Y-joint fittings and/or SAMSUNG HP 4 or 8 port header fittings
must be used to branch the main refrigerant lines.
QUALITY ASSURANCE
A.
The units shall be listed by Electrical Laboratories (ETL) and bear the ETL
label.
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
1
SAMSUNG Electronics HVAC
B.
All wiring shall be in accordance with the National Electrical Code (N.E.C.).
C.
The units shall be manufactured in a facility registered to ISO 9001 and
ISO14001 which is a set of standards applying to environmental protection
set by the International Standard Organization (ISO).
D.
A full charge of R-410A for the condensing unit only shall be provided in the
condensing unit. Additional refrigerant is required based on diameters and
lengths of system liquid refrigerant lines.
Part 2 – Warranty
2.01
WARRANTY
Applicable Only for SAMSUNG “DVM-S” and “DVM-S ECO” Systems
Distributed From January 1, 2014
1. LIMITED WARRANTY – QUIETSIDE CORPORATION (“QUIETSIDE”) warrants to
the original end-user (“you”) of SAMSUNG “DVM-S” or “DVM-S ECO” Air-Conditioner
and Heat Pump System (“Product”) that, if purchased from and installed by a contractor
licensed for HVAC installation under applicable local and state laws within the
continental United States, Alaska, Hawaii and Canada, and if it proves defective by
reason of defects arising from improper workmanship and/or material:
(a) FIVE YEARS ON PARTS. The parts are warranted for a period of five (5) years to
the original end-user of this Product. If it should prove defective due to improper
workmanship and/or material for a period of five (5) years from the date of
installation, QUIETSIDE will replace any defective part without charge for the part.
Parts used for replacement may be of like kind and quality and may be new or
remanufactured. Defective parts must be made available to QUIETSIDE in
exchange for the replacement part and become the property of QUIETSIDE.
(b) SEVEN YEAR COMPRESSOR WARRANTY. The compressor is warranted for a
total period of seven (7) years to the original end-user of this Product. If it should
prove defective due to improper workmanship and/or material for a period of seven
(7) years from the date of installation, QUIETSIDE will replace any defective
compressor without charge for the compressor. Compressors used for replacement
may be of like kind and quality and may be new or remanufactured. Defective
compressors must be made available to QUIETSIDE in exchange for the
replacement compressor and become the property of QUIETSIDE.
(c) NO LABOR. THESE LIMITED WARRANTIES DO NOT INCLUDE LABOR or any
other costs incurred for service, maintenance, repair, removing, replacing, installing,
complying with local building and electric codes, shipping or handling, or
replacement of the Product, compressors or any other parts. For items that are
designed to be maintained or replaced by the owner, the owner is solely responsible
for all labor and other costs of maintaining, installing, replacing, disconnecting or
dismantling the Product and parts (such as filters or belts) in connection with ownerDRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
2
SAMSUNG Electronics HVAC
required maintenance. Air filter cleaning and/or replacement for each applicable
indoor unit are owner-required maintenance, and labor for this procedure is not
covered under warranty.
(d) The warranty on the replacement compressor and replacement parts will be limited
to the unexpired term of the original warranty for the Product.
2. CONDITIONS – The Limited Warranty applies only if the Product: (a) was initially
installed within the continental United States, Hawaii or Canada and remains at the site
of its original installation (except for mobile home installations); and (b) was installed
and operated and maintained in accordance with all written instructions, all applicable
local laws, regulations, permits and building codes, and good industry practices.
3. THIS LIMITED WARRANTY DOES NOT COVER damages caused by: (a) accident,
abuse, negligence or misuse; (b) operating the Product in a corrosive atmosphere
containing chlorine, fluorine, or any other damaging chemicals; (c) modification, alteration,
repair service by any person other than an authorized Product distributor, dealer or HVAC
contractor; (d) improper matching or application of the Product or components or loss of
refrigerant; (e) failure to provide proper maintenance or service to the Product according
to manufacturer’s instructions; (f) failure to apply, install, and operate the Product in
compliance with SAMSUNG’s (or QUIETSIDE’s) written instructions, training seminars
and recommendations; or (g) fluctuations in electrical power;(h) lightning, flood, fire or
other acts of God.
This Limited Warranty does not cover if the Product has not been paid for in full.
4.
TO OBTAIN WARRANTY SERVICE:
a) Contact the licensed contractor who installed the Product or the nearest licensed and
authorized contractor, dealer or distributor of any defect within the applicable warranty
time period.
b) Proof of the installation date by a licensed contractor is required when requesting
warranty service. Present the sales receipt, building permit or other document which
establishes proof and date of installation. Otherwise, this Limited Warranty shall be
deemed to begin one hundred twenty (120) days after the date of manufacture
stamped on the System. THE RETURN OF THE OWNER REGISTRATION CARD IS
NOT A CONDITION OF COVERAGE UNDER THIS LIMITED WARRANTY. However,
please return the Owner Registration Card so that QUIETSIDE can contact you if a
question of safety arises.
c) To obtain the name of the nearest authorized QUIETSIDE HVAC distributor, dealer or
contractor or additional information on warranty program, you may contact:
QUIETSIDE CORPORATION
8750 PIONEER BLVD, SANTA FE SPRINGS
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
3
SAMSUNG Electronics HVAC
CA 90670. Telephone: 1-562-699-6066
6. This Limited Warranty shall not be enlarged, extended or affected by, and no
obligation or liability shall arise or grow out of, QUIETSIDE providing, directly or
indirectly, any technical advice, information and/or service to you in connection with the
Product.
7. EXCEPT AS OTHERWISE PROVIDED IN THIS LIMITED WARRANTY, QUIETSIDE
MAKES NO OTHER WARRANTIES OF ANY KIND WHATSOEVER REGARDING THE
PRODUCT. QUIETSIDE DISCLAIMS AND EXCLUDES ALL WARRANTIES NOT
EXPRESSLY
PROVIDED HEREIN AND ALL REMEDIES WHICH, BUT FOR THIS PROVISION,
MIGHT ARISE BY IMPLICATION OR OPERATION OF LAW, INCLUDING, WITHOUT
LIMITATION, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND OF
FITNESS FOR ANY
PARTICULAR PURPOSE. NO ONE IS AUTHORIZED TO CHANGE THIS LIMITED
WARRANTY IN ANY RESPECT OR TO CREATE ANY OTHER OBLIGATION OR
LIABILITY FOR QUIETSIDE IN CONNECTION WITH THE PRODUCT. QUIETSIDE
DISCLAIMS ALL LIABILITY FOR THE ACTS, OMISSIONS AND CONDUCT OF ALL
THIRD PARTIES (including, without limitation, the installing contractor) IN
CONNECTION WITH OR RELATED TO THE PRODUCT.
8. UNDER NO CIRCUMSTANCES SHALL QUIETSIDE BE LIABLE FOR ANY
INCIDENTAL, SPECIAL OR CONSEQUENTIAL DAMAGES INCLUDING, WITHOUT
LIMITATION, LOST GOODWILL, LOST REVENUES OR PROFITS, WORK
STOPPAGE, SYSTEM FAILURE,
IMPAIRMENT OF OTHER GOODS, COSTS OF REMOVAL AND REINSTALLATION
OF THE PRODUCT, LOSS OF USE, INJURY TO PERSONS OR PROPERTY
ARISING OUT OR RELATED TO THE PRODUCT WHETHER BASED ON BREACH
OF WARRANTY, BREACH OF CONTRACT, TORT OR OTHERWISE, EVEN IF
QUIETSIDE HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. IN NO
EVENT SHALL QUIETSIDE’S LIABILITY EXCEED THE ACTUAL PURCHASE PRICE
OF THE PRODUCT WITH RESPECT TO WHICH ANY CLAIM IS MADE.
9. Some states do not allow limitations on warranties or exclusions or limitation of
damages, so the above limitations or exclusions may not apply.
10. This Limited Warranty gives the owner specific legal rights and the owner may also
have other rights that vary from state to state.
11. This Limited Warranty is valid only in the continental United States, Alaska, Hawaii
and Canada, and it is not transferable.
12. This warranty contains the sole express warranty made by QUIETSIDE in
connection with the Product. No QUIETSIDE distributor, dealer or contractor or other
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
4
SAMSUNG Electronics HVAC
person is authorized to make any other warranties or representations on behalf of
QUIETSIDE in connection with the Product.
Part 3 – Outdoor Unit Performance
3.01
The heat pump outdoor unit shall perform as indicated below (nominal capacity):
Outdoor Units
Nominal Cooling
Capacity
Rated Cooling
Capacity
(Btu/h)
Power Input
(kW)
AM036FXMDCH/AA
36,000
38,000
3.1
AM048FXMDCH/AA
48,000
48,000
4.2
AM053FXMDCH/AA
53,000
53,000
5.3
Outdoor Units
Nominal Heating
Capacity
Rated Heating
Capacity
(Btu/h)
Power Input
(kW)
AM036FXMDCH/AA
42,000
42,000
3.4
AM048FXMDCH/AA
54,000
54,000
4.4
AM053FXMDCH/AA
61,000
61,000
5.4
Part 4 – Products
HEAT PUMP OUTDOOR UNIT
4.01
A.
General:
1.
The heat pump outdoor unit shall be specifically used with
SAMSUNG DVM S Heat pump components. The SAMSUNG MINI
DVM S ECO HP outdoor unit shall consist of AM0**FXMDCH/AA
outdoor unit, indoor units (AM***FN*DCH/AA), and SAMSUNG DVM
S NASA Control Network Solution (Control systems).
AM0**FXMDCH/AA outdoor units shall be equipped with multiple
circuit boards that interface to the SAMSUNG DVM S NASA Control
Network Solution (Control systems) and shall perform all functions
necessary for operation. The outdoor unit shall have a powder
coated finish. The outdoor unit shall be completely factory
assembled, piped and wired. Each unit shall be run tested at the
factory.
2.
The sum of connected capacity of all indoor air handlers shall range
from 50% to 130% of outdoor rated capacity.
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
5
SAMSUNG Electronics HVAC
3.
The heat pump system compressors shall be SAMSUNG,
hermetically sealed, inverter driven, Twin BLDC Rotary type. No
fixed capacity compressors shall be present in the refrigerant system.
4.
The outdoor unit shall have a sound rating no higher than listed in
the table below.
Outdoor Unit Model
Maximum dB(A)
AM036FXMDCH/AA
50
AM048FXMDCH/AA
51
AM053FXMDCH/AA
53
5.
Both refrigerant lines from the outdoor unit shall be insulated.
6.
The heat pump outdoor unit shall have an accumulator
7.
The heat pump outdoor unit shall have a high pressure safety switch,
over-current protection, thermal fan protection, low pressure
protection, compressor overcurrent protection, fan motor voltage
protection, current transformer(s), crank case heaters, and intelligent
logic to ensure proper operation within unit design limitations and
operational parameters.
8.
The heat pump outdoor unit shall have the ability to operate with a
maximum height difference of 163 feet with the condensing unit
installed higher than the indoor units or 131 feet with the condensers
installed lower than the indoor units. The greatest length is not to
exceed 492 (574 equivalent) feet between outdoor unit and the
farthest indoor unit.
9.
The heat pump outdoor unit shall be capable of operating in cooling
mode between 23°F ~ 120°F outside ambient temperatures.
10.
The heat pump outdoor unit shall be capable of operating in heating
between -4F ~ 75F ambient temperatures.
11.
The heat pump system shall have installer enabled snow blowing
settings to prevent snow accumulation in front of idle outdoor units
during when below 35º F.
12.
The heat pump shall have the ability to adjust cooling and heating
temperature/pressure compensation values depending on project
conditions thus saving energy.
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
6
SAMSUNG Electronics HVAC
13.
The heat pump outdoor unit shall have a high efficiency oil separator
plus additional logic controls to ensure adequate oil volume in the
compressor is maintained.
14.
The heat pump outdoor unit shall have a flat plate type sub-cooler to
sub cool liquid refrigerant further to increase capacity and
performance with long pipe lengths and to decrease refrigerant
sounds at indoor equipment.
15.
The heat pump system shall have optional night quite modes to
reduce unit sound in evenings.
16.
The heat pump system shall have current control to limit current
adjustable at outdoor unit. Maximum current limitation shall 3 levels
of current limitation from design current.
17.
The heat pump outdoor unit shall have a removable EEPROM at the
main PCB to store all unit data. All data on the outdoor unit EEPROM
shall be viewable from the manufacturer provided service software.
The outdoor unit main EEPROM shall be removable allowing
replacement of outdoor unit PCB without losing digital, field
programmed data. The outdoor unit removable EEPROM shall store
the following unit data: unit model number, unit serial number, unit
main PCB firmware and MICOM version, sub-PCB firmware and
MICOM version, fan PCB firmware and MICOM version, inverter
PCB 1 and inverter PCB 2 firmware and MICOM version, auto-trial
commissioning startup data, the last 30 minutes of operation data,
and field programmed unit name/tag viewable on controls and
service software.
18.
The heat pump outdoor unit shall have outdoor unit pump-down
operation capability allowing storage of refrigerant while opening
sealed refrigerant pipe system outside of outdoor unit chassis while
performing service. The outdoor unit refrigerant storage shall be
greater than the supplied factory R-410A charge.
19.
The heat pump outdoor unit shall have individual outdoor module
pump-out operation capability allowing the majority of refrigerant in
an outdoor unit to be pumped out. The pump-out feature shall allow
service of sealed refrigerant system within an outdoor unit chassis.
20.
In the event of system error due to outdoor unit failure, the heat pump
outdoor unit shall display codes that specify a precise error and
which outdoor unit PCB is the cause.
21.
The heat pump outdoor unit shall have adjustable defrost operation
characteristics (4 total options) adjustable at the outdoor PCB.
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
7
SAMSUNG Electronics HVAC
B.
Unit Cabinet:
1.
C.
The chassis shall be fabricated of galvanized steel, bonderized and
finished with a powder coated baked enamel.
Fan:
1.
The heat pump outdoor unit shall be furnished with 2 axial fans with
BLDC motors.
2.
General:
a.
All fan motors shall have inherent protection, thermal protection, and
have permanently lubricated bearings, and be completely variable
speed.
b.
All fan motors shall be mounted for quiet operation.
c.
All fans shall be provided with a raised guard to prevent contact with
moving parts.
d.
The outdoor unit shall have horizontal discharge airflow.
D. Refrigerant:
E.
a.
R410A refrigerant shall be required for the heat pump system.
b.
Additional refrigerant is required. Amount is based on installed
refrigerant pipe diameters and lengths.
Coil:
a.
The outdoor coil shall be of nonferrous construction with lanced or
corrugated plate fins on copper tubing.
b.
The coil shall be protected with an integral metal guard.
c. Refrigerant flow from the outdoor unit shall be controlled by means of
capacity modulation capable Twin BLDC Rotary compressor.
F.
Compressor:
1. The 208/230 VAC heat pump systems shall have the compressor quantity
noted in the table below. All compressors shall be modulation capable, DC
inverter, Twin BLDC Rotary type.
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
8
SAMSUNG Electronics HVAC
208/230 VAC
Nominal System Capacity (btu/h)
Compressor Quantity
36,000
48,000
53,000
1
1
1
2. General:
a.
Crankcase heaters shall be factory mounted on the compressor.
b.
The outdoor unit compressor shall have a variable modulation
technology to modulate capacity.
c.
The compressor will be equipped with an internal thermal overload.
d.
The compressor shall be mounted to avoid the transmission of
vibration.
G. Electrical:
a.
The outdoor unit electrical power shall be 208/230 volts, 1 phase, 60
hertz.
b.
The 208/230 VAC unit shall be capable of satisfactory operation
within voltage limitations of 187-228 volts (208V/60Hz) or 207-253
volts (230V/60Hz).
c.
The outdoor unit shall be controlled by integral microprocessors.
d.
The control circuit between the indoor units and the outdoor unit shall
be 0.5VDC - 7VDC completed using stranded, annealed copper
conductor, 16 AWG, shielded, two-core cable to provide total
integration of the system.
4.02 ELECTRONIC EXPANSION VALVE KITS (MULTI ZONE) FOR HEAT PUMP
OUTDOOR UNITS (MXD)
A.
General:
1.
DRAFT: 07/29/2014
The MXD EEV Kit shall allow a liquid and suction pipe from the
condenser to connect and meter refrigerant to 2 or 3 wall
(AM0**FNTDCH/AA) or under-ceiling units (AM0**FNCDCH/AA).
The MXD units shall be equipped with a circuit board that interfaces
to the SAMSUNG DVM S NASA Control Network Solution (Control
www.SamsungDVM-S.com
Specifications are subject to change without notice.
9
SAMSUNG Electronics HVAC
systems) and shall perform all functions necessary for operation.
The unit shall have a galvanized steel finish. The MXD EEV kit shall
be completely factory assembled, piped and wired. Each unit shall
be run tested at the factory. This unit shall be mounted indoors. Only
compatible with DVM S heat pump systems (AM****XVA*H/AA and
AM0**FXMDCH/AA). The length of pipe between an MXD EEV kit
and a single indoor unit cannot exceed 65 actual feet. The MXD EEV
kit selection is based on the quantity of units and capacity of each
according to the table below.
B.
C.
MXD-E24K132A
2
MXD-E24K200A
2
2 X ≤ 12,000
MXD-E32K200A
2
2 X 18,000 – 24,000
MXD-E24K232A
3
MXD-E24K300A
3
MXD-E32K224A
3
MXD-E32K300A
3
Connectable Capacity
(Btu/h)
1 X ≤ 12,000,
1 x 18,000 – 24,000
2 X ≤ 12,000,
1 X 18,000 – 24,000
3 X ≤ 12,000
1 X ≤ 12,000,
2 X 18,000 – 24,000
3 X 18,000 – 24,000
1.
The chassis shall be fabricated of galvanized steel.
2.
Each cabinet shall house 2 or 3 (depending on model) electronic
expansion valves and a common suction connection.
Refrigerant:
R410A refrigerant shall be required for MXD EEV kits in conjunction
with R410A, heat pump unit systems.
Integral Drain Pan:
1.
E.
Number of
Connectable Indoor
Units
MXD EEV Kit Cabinet:
1.
D.
EEV Kit Model
Number
An integral condensate pan and drain shall be provided. Drain
termination is required upon installation with an appropriate
termination.
Electrical:
1.
DRAFT: 07/29/2014
The unit electrical power shall be 208/230 volts, 1 phase, 60 hertz.
www.SamsungDVM-S.com
Specifications are subject to change without notice.
10
SAMSUNG Electronics HVAC
2.
The unit shall be capable of satisfactory operation within voltage
limits of 187-228 volts (208V/60Hz) or 207-253V (230V/60Hz).
3.
The MXD EEV kit shall be controlled by integral microprocessors.
4.
The control circuit between the indoor units, EEV kit and the outdoor
unit shall be 0.5VDC - 7VDC completed using stranded, annealed
copper conductor, two conductor, 16 AWG, shielded cable to provide
total integration of the system. Operation is based on communication
on this main communication cable.
4.03 ELECTRONIC EXPANSION VALVE KIT (SINGLE ZONE) FOR HEAT PUMP AND
HEAT RECOVERY OUTDOOR UNITS
A.
General:
1.
B.
MEV-A24SA
≤ 12,000
MEV-A32SA
18,000 – 24,000
The chassis shall be fabricated of galvanized steel and HIPS certified
to UL94 V0.
For R410A systems only.
Electrical:
1.
4.04
Connectable Capacity
(Btu/h)
Refrigerant:
1.
D.
EEV Kit Model Number
Cabinet:
1.
C.
The MEV-A**SA device is a single zone electronic expansion valve
for Samsung DVM wall-mounted units (AM0***NTDCH/AA) and
under-ceiling units (AM0***NCDCH/AA). Compatible with DVM S
heat pump systems (AM****XVA*H/AA, AM0**FXMDCH/AA) and
DVM S Heat Recovery Systems. The MEV-A**SA EEV installs inline
on the liquid line for a single unit. It must be located nearby the unit,
within 7 feet (of pipe) between the MEV-A**SA and the connected
indoor unit. The appropriate expansion valve should be selected
based on the capacity of the connected unit per the table below.
The single zone EEV is powered and controlled directly from the
indoor unit that it is metering refrigerant to via included wire harness.
WALL-MOUNTED INDOOR UNIT (AM0**FNTDCH/AA)
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
11
SAMSUNG Electronics HVAC
A.
B.
General:
1.
The wall-mounted indoor unit section shall have a slim silhouette and
must be installed with an external modulating linear expansion valve
(MEV-A**SA) or two/three room EEV (Electronic Expansion Valve)
kits. The wall-mounted indoor unit shall be compatible with DVM S
HR (Heat Recovery) outdoor units and MCU (Mode Change Unit,
MCU-S*NEE1N) or DVM S HP (Heat Pump) outdoor unis. The wallmounted indoor unit shall support individual control using SAMSUNG
DVM S NASA Control Network Solution (Control systems). Indoor
model numbers shall be: AM007FNTDCH/AA, AM009FNTDCH/AA,
AM012FNTDCH/AA, AM018FNTDCH/AA, AM020FNTDCH /AA,
AM024FNTDCH/AA.
2.
Each system shall perform in accordance to the ratings shown in the
table below. Performance shall be based on nominal cooling
conditions of 80F DB, 67F WB for the indoor unit and 95F DB for
the outdoor unit and nominal heating conditions of 70F DB for the
indoor unit and 47F DB, 43F WB for the outdoor unit.
Btu/h
Cooling*
BTU/h
Heating*
AM007FNTDCH/AA
7,500
8,500
AM009FNTDCH/AA
9,500
10,500
AM012FNTDCH/AA
12,000
13,500
AM018FNTDCH/AA
18,000
20,000
AM020FNTDCH/AA
20,000
23,000
AM024FNTDCH/AA
*Nominal capacity
24,000
24,000
Indoor Unit:
1.
C.
System Model Number
The indoor unit shall be factory assembled, wired and run tested.
Contained within the unit shall be all factory wiring, piping, control
circuit board and fan motor. An optional electronic modulating linear
expansion valves is available for accessories. The unit shall have a
self-diagnostic function, 3-minute time delay mechanism, an auto
restart function. Indoor unit and refrigerant pipes shall be charged
with dehydrated air (Nitrogen gas) before shipment from the factory.
Unit Cabinet:
1.
DRAFT: 07/29/2014
The casing shall have a gloss white finish, HIPS chassis certified to
UL94 V0.
www.SamsungDVM-S.com
Specifications are subject to change without notice.
12
SAMSUNG Electronics HVAC
D.
E.
F.
2.
Multi directional drain and refrigerant piping offering four (4)
directions for refrigerant piping and four (4) directions for draining
shall be standard.
3.
There shall be a separate galvanized steel mounting plate which
secures the unit firmly to the wall.
Fan:
1.
The indoor fan assembly shall be a cross-flow fan direct driven by a
single motor.
2.
The indoor fan shall be statically and dynamically balanced to run on
a motor with permanently lubricated bearings.
3.
A manual adjustable guide vane shall be provided with the ability to
change the airflow from side to side (left to right).
4.
A motorized air sweep louver shall provide an automatic change in
airflow by directing the air up and down to provide uniform air
distribution.
5.
The indoor fan shall consist of various speeds, as indicated in below
table.
Model Number
Fan Speed Setting
AM007FNTDCH/AA
AM009FNTDCH/AA
AM012FNTDCH/AA
AM018FNTDCH/AA
AM020FNTDCH/AA
AM024FNTDCH/AA
(UL) – Low – Mid – High
Filter:
1.
Return air shall be filtered by means of an easily removable,
washable filter (2).
2.
Supplemental antibacterial and anti-odor filters shall be included.
Coil:
1.
The indoor coil shall be of nonferrous construction with slit fins on
copper tubing.
2.
The tubing shall have inner grooves for high efficiency heat
exchange.
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
13
SAMSUNG Electronics HVAC
G.
H.
4.05
3.
All tube joints shall be brazed with phos-copper or silver alloy.
4.
The coils shall be pressure tested at the factory.
5.
A condensate pan and drain shall be provided under the coil.
6.
The coil fins are coated with hydrophilic paints.
7.
Both refrigerant lines to the wall-mounted indoor unit shall be
insulated.
Electrical:
1.
The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz.
2.
The system shall be capable of satisfactory operation within voltage
limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz).
3.
The control circuit between the indoor units, MCU (Mode Change
Unit) and the outdoor unit shall be 0.5VDC - 7VDC completed using
stranded, annealed copper conductor, two-core, 16 AWG, shielded
cable to provide total integration of the system.
4.
The indoor unit shall have a thermal fuse under high-voltage terminal
block to disable unit in the event of overheating due to electrical
malfunction/poor connection.
Controls:
1.
This unit shall use controls provided by SAMSUNG Electronics to
perform functions necessary to operate the system. Please refer to
Part 5 of this guide specification for details on controllers and other
control options.
2.
The indoor unit shall have a removable EEPROM on its PCB to store
all unit data. All data on the indoor unit EEPROM shall be viewable
from the manufacturer provided service software. The indoor unit
main EEPROM shall be removable allowing replacement of indoor
unit PCB without losing digital, field programmed data. The indoor
unit removable EEPROM shall store the following unit data: unit
model number, unit serial number, unit PCB firmware and MICOM
version, and field programmed unit name/tag viewable on controls
and service software.
UNDER CEILING/WALL INDOOR UNIT (AM0**FNCDCH/AA)
A.
General:
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
14
SAMSUNG Electronics HVAC
B.
1.
The under-ceiling/wall indoor unit shall be installed under ceiling or
on wall (near floor). The under-ceiling/wall indoor unit shall be
compatible with DVM S HR (Heat Recovery) outdoor units and MCU
(Mode Change Unit) or DVM S HP (Heat Pump) outdoor units. The
under-ceiling/wall indoor unit shall support individual control using
SAMSUNG DVM S NASA Control Network Solution (Control
systems). Indoor model numbers shall be: AM018FNCDCH/AA and
AM024FNCDCH/AA.
2.
Each system shall perform in accordance to the ratings shown in the
table below. Performance shall be based on nominal cooling
conditions of 80F DB, 67F WB for the indoor unit and 95F DB for
the outdoor unit and nominal heating conditions of 70F DB for the
indoor unit and 47F DB, 43F WB for the outdoor unit.
D.
BTU/h
Cooling*
BTU/h
Heating*
AM018FNCDCH/AA
18,000
20,000
AM024FNCDCH/AA
*Nominal capacity
24,000
27,000
Indoor Unit:
1.
C.
System Model Number
The indoor unit shall be factory assembled, wired and run tested.
Contained within the unit shall be all factory wiring, piping, electronic
modulating linear expansion device, control circuit board and fan
motor. The unit shall have a self-diagnostic function, 3-minute time
delay mechanism, an auto restart function. The unit shall have a
single auto-swing louver. Indoor unit and refrigerant pipes shall be
charged with dehydrated air (Nitrogen gas) before shipment from the
factory. Gravity drain as standard.
Unit Cabinet:
1.
The cabinet shall be space-saving, under-ceiling type that can also
be installed on a wall (near floor).
2.
The casing shall be HIPS certified to UL94 V0.
3.
The casing shall have a white finish.
4.
There shall be separate galvanized steel mounting hangers that will
secure the unit firmly to wall (wall-mounted applications only).
Fan:
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
15
SAMSUNG Electronics HVAC
E.
1.
The indoor fan assembly shall be a Sirocco fan (2) direct driven by a
single motor.
2.
The indoor fan shall be statically and dynamically balanced to run on
a motor with permanently lubricated bearings.
3.
The indoor fan shall consist of three (3) speeds, Low, Mid, and High.
4.
The auto air swing louver shall be capable of automatically swinging
up and down for uniform air distribution.
Filter:
1.
F.
G.
Return air shall be filtered by means of a long-life washable
permanent filter (2).
Coil:
1.
The indoor coil shall be of nonferrous construction with slit fins on
copper tubing.
2.
The tubing shall have inner grooves for high efficiency heat
exchange.
3.
All tube joints shall be brazed with phos-copper or silver alloy.
4.
The coils shall be pressure tested at the factory.
5.
A condensate pan and drain outlet shall be provided under the coil
(gravity drain).
6.
The coil fins are coated with hydrophilic paints.
7.
Both refrigerant lines to the under-ceiling/wall indoor unit indoor units
shall be insulated.
Electrical:
1.
The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz.
2.
The system shall be capable of satisfactory operation within voltage
limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz).
3.
The control circuit between the indoor units, MCU (Mode Change
Unit) and the outdoor unit shall be 0.5VDC - 7VDC completed using
stranded, annealed copper conductor, two-core, 16 AWG, shielded
cable to provide total integration of the system
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
16
SAMSUNG Electronics HVAC
4.
H.
4.06
The indoor unit shall have a thermal fuse under high-voltage terminal
block to disable unit in the event of overheating due to electrical
malfunction/poor connection.
Controls:
1.
This unit shall use controls provided by SAMSUNG Electronics to
perform functions necessary to operate the system. Please refer to
Part 5 of this guide specification for details on controllers and other
control options.
2.
The indoor unit shall have a removable EEPROM on its PCB to store
all unit data. All data on the indoor unit EEPROM shall be viewable
from the manufacturer provided service software. The indoor unit
main EEPROM shall be removable allowing replacement of indoor
unit PCB without losing digital, field programmed data. The indoor
unit removable EEPROM shall store the following unit data: unit
model number, unit serial number, unit PCB firmware and MICOM
version, and field programmed unit name/tag viewable on controls
and service software.
4-WAY CEILING CASSETTE WITH GRILLE INDOOR UNIT (AM0**FN4DCH/AA)
A.
General:
1.
The 4-way cassette shall be style indoor unit shall recess into the
ceiling with a ceiling grille (ordered separately, part number:
PC4NUSKFN) and shall have a modulating linear expansion device.
The 4-way cassette shall be compatible with DVM S HR (Heat
Recovery) outdoor units and MCU (Mode Change Unit) or DVM S
HP (Heat Pump) outdoor units. The 4-way cassette shall support
individual control using SAMSUNG DVM S NASA Control Network
Solution (Control systems). Indoor model numbers shall be:
AM009FN4DCH/AA, AM012FN4DCH/AA, AM018FN4DCH/AA,
AM024FN4DCH/AA, AM030FN4DCH/AA, AM036FN4DCH/AA,
AM048FN4DCH/AA.
2.
Each system shall perform in accordance to the ratings shown in the
table below. Performance shall be based on nominal cooling
conditions of 80F DB, 67F WB for the indoor unit and 95F DB for
the outdoor unit and nominal heating conditions of 70F DB for the
indoor unit and 47F DB, 43F WB for the outdoor unit.
DRAFT: 07/29/2014
System Model Number
BTU/h
Cooling*
BTU/h
Heating*
AM009FN4DCH/AA
9,000
10,000
www.SamsungDVM-S.com
Specifications are subject to change without notice.
17
SAMSUNG Electronics HVAC
B.
D.
BTU/h
Cooling*
BTU/h
Heating*
AM012FN4DCH/AA
12,000
13,500
AM018FN4DCH/AA
18,000
20,000
AM024FN4DCH/AA
24,000
27,000
AM030FN4DCH/AA
30,000
34,000
AM036FN4DCH/AA
36,000
40,000
AM048FN4DCH/AA
*Nominal Capacity
48,000
54,000
Indoor Unit:
1.
C.
System Model Number
The indoor unit shall be factory assembled, wired and run tested.
Contained within the unit shall be all factory wiring, piping, electronic
modulating linear expansion device, control circuit board and fan
motor. The unit shall have a self-diagnostic function, 3-minute time
delay mechanism, an auto restart function. Indoor unit and
refrigerant pipes shall be charged with dehydrated air (Nitrogen gas)
before shipment from the factory.
Unit Cabinet:
1.
The cabinet shall be space-saving ceiling-recessed cassette.
2.
Construction shall be HIPS chassis and fascia panel certified to UL94
V0.
3.
Each corner portion of the panel cabinet is detachable, which gives
easy access to adjust the height.
4.
The cabinet shall have provisions for a field installed, filtered, outside
air intake. A booster fan is necessary. A 12V DC relay terminal is
available to control a booster fan (with separate PCB connector).
5.
Branch ducting shall be allowed from cabinet, available on 2 sides to
condition an adjacent space.
Fan:
1.
The indoor fan assembly shall be a turbo fan direct driven by a single
motor.
2.
The indoor fan shall be statically and dynamically balanced to run on
a motor with permanently lubricated bearings.
3.
The indoor fan shall consist of three (3) speeds, Low, Mid, and High.
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
18
SAMSUNG Electronics HVAC
E.
4.
The auto swing air outlet vanes (4) shall be capable of automatically
swinging up and down for uniform air distribution.
5.
The supply air vanes shall have independent control capability (32°
– 65° control range) adjustable with optional wireless or wired
controllers.
Filter:
1.
F.
G.
Return air shall be filtered by means of a long-life washable
permanent filter included with fascia panel.
Coil:
1.
The indoor coil shall be of nonferrous construction with slit fins on
copper tubing.
2.
The tubing shall have inner grooves for high efficiency heat
exchange.
3.
All tube joints shall be brazed with phos-copper or silver alloy.
4.
The coils shall be pressure tested at the factory.
5.
A condensate pan and drain shall be provided under the coil.
6.
The coil fins are coated with hydrophilic paints.
7.
The condensate lift mechanism shall be able to raise drain water 29
inches above the condensate pan with built in check valve and float
switch.
8.
Both refrigerant lines to the 4-way cassette indoor units shall be
insulated.
Electrical:
1.
The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz.
2.
The system shall be capable of satisfactory operation within voltage
limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz).
3.
The control circuit between the indoor units, MCU (Mode Change Uni)
and the outdoor unit shall be 0.5VDC - 7VDC completed using
stranded, annealed copper conductor, two-core, 16 AWG, shielded
cable to provide total integration of the system
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
19
SAMSUNG Electronics HVAC
4.
H.
4.07
The indoor unit shall have a thermal fuse under high-voltage terminal
block to disable unit in the event of overheating due to electrical
malfunction/poor connection.
Controls:
1.
This unit shall use controls provided by SAMSUNG Electronics to
perform functions necessary to operate the system. Please refer to
Part 5 of this guide specification for details on controllers and other
control options.
2.
The indoor unit shall have a removable EEPROM on its PCB to
store all unit data. All data on the indoor unit EEPROM shall be
viewable from the manufacturer provided service software. The
indoor unit main EEPROM shall be removable allowing replacement
of indoor unit PCB without losing digital, field programmed data.
The indoor unit removable EEPROM shall store the following unit
data: unit model number, unit serial number, unit PCB firmware and
MICOM version, and field programmed unit name/tag viewable on
controls and service software.
MINI 4-WAY CEILING
(AM0**FNNDCH/AA)
A.
CASSETTE
WITH
GRILLE
INDOOR
UNIT
General:
1.
The indoor unit shall be a mini four-way cassette style indoor unit that
recesses into the ceiling with a ceiling grille (part number:
PC4USUMAN, ordered separately) and shall have a modulating
linear expansion device. The mini four-way cassette shall be
compatible with DVM S HR (Heat Recovery) outdoor units and MCU
(Mode Change Unit) or DVM S HP (Heat Pump) outdoor units. The
mini four-way cassette shall support individual control using
SAMSUNG DVM S NASA Control Network Solution (Control
systems). Indoor model numbers shall be: AM009FNNDCH/AA,
AM012FNNDCH/AA, AM018FNNDCH/AA, AM020FNNDCH/AA.
2.
Each system shall perform in accordance to the ratings shown in the
table below. Performance shall be based on nominal cooling
conditions of 80F DB, 67F WB for the indoor unit and 95F DB for
the outdoor unit and nominal heating conditions of 70F DB for the
indoor unit and 47F DB, 43F WB for the outdoor unit.
DRAFT: 07/29/2014
System Model Number
BTU/h
Cooling*
BTU/h
Heating*
AM009FNNDCH/AA
9,500
10,500
www.SamsungDVM-S.com
Specifications are subject to change without notice.
20
SAMSUNG Electronics HVAC
System Model Number
BTU/h
Cooling*
BTU/h
Heating*
AM012FNNDCH/AA
12,000
13,500
AM018FNNDCH/AA
18,000
20,000
AM020FNNDCH/AA
20,000
23,000
*Nominal Capacity
B.
Indoor Unit:
1.
C.
D.
The indoor unit shall be factory assembled, wired and run tested.
Contained within the unit shall be all factory wiring, piping, electronic
modulating linear expansion device, control circuit board and fan
motor. The unit shall have a self-diagnostic function, 3-minute time
delay mechanism, an auto restart function. Indoor unit and
refrigerant pipes shall be charged with dehydrated air (Nitrogen gas)
before shipment from the factory.
Unit Cabinet:
1.
The cabinet shall be space-saving ceiling-recessed cassette.
2.
Construction shall be insulated HIPS chassis and fascia panel
certified to UL94 V0.
3.
The cabinet panel shall have provisions for a field installed, filtered,
outside air intake. A booster fan is necessary. A 12V DC relay
terminal is available to control the booster fan (with separate PCB
connector).
4.
The compact cabinet size can be installed in one standard ceiling tile
(24” x 24”).
Fan:
1.
The indoor fan assembly shall be a turbo fan direct driven by a single
motor.
2.
The indoor fan shall be statically and dynamically balanced to run on
a motor with permanently lubricated bearings.
3.
The indoor fan shall consist of three (3) speeds, Low, Mid, and High.
4.
The auto air swing vanes (4) shall be capable of automatically
swinging up and down for uniform air distribution.
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
21
SAMSUNG Electronics HVAC
E.
Filter:
1.
F.
G.
H.
Return air shall be filtered by means of a long-life washable
permanent filter included with fascia panel.
Coil:
1.
The indoor coil shall be of nonferrous construction with slit fins on
copper tubing.
2.
The tubing shall have inner grooves for high efficiency heat
exchange.
3.
All tube joints shall be brazed with phos-copper or silver alloy.
4.
The coils shall be pressure tested at the factory.
5.
A condensate pan and drain outlet shall be provided under the coil.
6.
The coil fins are coated with hydrophilic paints.
7.
The condensate lift mechanism shall be able to raise drain water 29
inches above the condensate pan with float switch.
8.
Both refrigerant lines to the mini four-way cassette indoor units shall
be insulated.
Electrical:
1.
The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz.
2.
The system shall be capable of satisfactory operation within voltage
limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz).
3.
The control circuit between the indoor units, MCU (Mode Change
Unit) and the outdoor unit shall be 0.5VDC - 7VDC completed using
stranded, annealed copper conductor, two-core, 16 AWG, shielded
cable to provide total integration of the system
4.
The indoor unit shall have a thermal fuse under high-voltage terminal
block to disable unit in the event of overheating due to electrical
malfunction/poor connection.
Controls:
1.
DRAFT: 07/29/2014
This unit shall use controls provided by SAMSUNG Electronics to
perform functions necessary to operate the system. Please refer to
Part 5 of this guide specification for details on controllers and other
control options.
www.SamsungDVM-S.com
Specifications are subject to change without notice.
22
SAMSUNG Electronics HVAC
2.
4.08
The indoor unit shall have a removable EEPROM on its PCB to store
all unit data. All data on the indoor unit EEPROM shall be viewable
from the manufacturer provided service software. The indoor unit
main EEPROM shall be removable allowing replacement of indoor
unit PCB without losing digital, field programmed data. The indoor
unit removable EEPROM shall store the following unit data: unit
model number, unit serial number, unit PCB firmware and MICOM
version, and field programmed unit name/tag viewable on controls
and service software.
SLIM 1-WAY, CEILING CASSETTE WITH GRILLE, INDOOR UNIT
A.
General:
1.
The indoor unit shall be a one-way cassette style indoor unit that
recesses into the ceiling with a ceiling grille (ordered separately, part
number: PC1NUSMAN or PC1NUPMAN) and shall have a
modulating linear expansion device. The one-way cassette shall be
compatible with DVM S HR (Heat Recovery) outdoor units and MCU
(Mode Change Unit) or DVM S HP (Heat Pump) outdoor units. The
one-way cassette shall support individual control using SAMSUNG
DVM S NASA Control Network Solution (Control systems). Indoor
model numbers shall be: AM007FN1DCH/AA, AM009FN1DCH/AA,
AM012FN1DCH/AA.
2.
Each system shall perform in accordance to the ratings shown in the
table below. Performance shall be based on nominal cooling
conditions of 80F DB, 67F WB for the indoor unit and 95F DB for
the outdoor unit and nominal heating conditions of 70F DB for the
indoor unit and 47F DB, 43F WB for the outdoor unit.
System Model Number
BTU/h
Cooling*
BTU/h
Heating *
AM007FN1DCH/AA
7,500
8,500
AM009FN1DCH/AA
9,500
10,500
AM012FN1DCH/AA
12,000
13,500
*Nominal capacity
B.
Indoor Unit.
1.
DRAFT: 07/29/2014
The indoor unit shall be factory assembled, wired and run tested.
Contained within the unit shall be all factory wiring, piping, electronic
modulating linear expansion device, control circuit board and fan
motor. The unit shall have a self-diagnostic function, 3-minute time
delay mechanism, an auto restart function. Indoor unit and
www.SamsungDVM-S.com
Specifications are subject to change without notice.
23
SAMSUNG Electronics HVAC
refrigerant pipes shall be charged with dehydrated air (Nitrogen gas)
before shipment from the factory.
C.
D.
E.
Unit Cabinet:
1.
The cabinet shall be space-saving ceiling recessed.
2.
Construction shall be HIPS chassis fascia panel certified to UL94.
3.
The one-way grille shall be fixed to bottom of cabinet allowing for
one-way airflow (PC1NUSMAN or PC1NUPMAN panel).
Fan:
1.
The indoor fan shall be an assembly with one line-flow fan direct
driven by a single motor.
2.
The indoor fan shall be statically and dynamically balanced to run on
a motor with permanently lubricated bearings.
3.
The indoor fan shall consist of three (3) speeds, Low, Mid, and High.
4.
Fascia panel PC1NUPMAN shall have a smooth (non-louvered)
return air inlet that opens on one side when unit is ON and closes
when unit is OFF.
5.
Return air shall be filtered by means of a long-life washable
permanent filter (2).
Coil:
1.
The indoor coil shall be of nonferrous construction with slit fins on
copper tubing.
2.
The tubing shall have inner grooves for high efficiency heat
exchange.
3.
All tube joints shall be brazed with phos-copper or silver alloy.
4.
The coils shall be pressure tested at the factory.
5.
A condensate pan and drain shall be provided under the coil.
6.
The condensate lift mechanism shall be able to raise drain water 29
inches above the condensate pan with built in check valve and float
switch.
7.
The coil fins are coated with hydrophilic paints.
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
24
SAMSUNG Electronics HVAC
8.
F.
G.
4.09
Both refrigerant lines to the one-way cassette indoor units shall be
insulated.
Electrical:
1.
The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz.
2.
The system shall be capable of satisfactory operation within voltage
limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz).
3.
The control circuit between the indoor units, MCU (Mode Change
Unit) and the outdoor unit shall be 0.5VDC - 7VDC completed using
stranded, annealed copper conductor, two-core, 16 AWG, shielded
cable to provide total integration of the system
4.
The indoor unit shall have a thermal fuse under high-voltage terminal
block to disable unit in the event of overheating due to electrical
malfunction/poor connection.
Controls:
1.
This unit shall use controls provided by SAMSUNG Electronics to
perform functions necessary to operate the system. Please refer to
Part 5 of this guide specification for details on controllers and other
control options.
2.
The indoor unit shall have a removable EEPROM on its PCB to store
all unit data. All data on the indoor unit EEPROM shall be viewable
from the manufacturer provided service software. The indoor unit
main EEPROM shall be removable allowing replacement of indoor
unit PCB without losing digital, field programmed data. The indoor
unit removable EEPROM shall store the following unit data: unit
model number, unit serial number, unit PCB firmware and MICOM
version, and field programmed unit name/tag viewable on controls
and service software.
CEILING-CONCEALED, SLIM, DUCTED, INDOOR UNIT (AM0**FNLDCH/AA)
A.
General:
1.
DRAFT: 07/29/2014
The indoor unit shall be a ceiling-concealed ducted indoor fan coil
design that mounts above the ceiling with a 2-position, field
adjustable return and a fixed horizontal discharge supply and shall
have a modulating linear expansion device. The ceiling-concealed
ducted unit shall be compatible with DVM S HR (Heat Recovery)
outdoor units and MCU (Mode Change Unit) or DVM S HP (Heat
Pump) outdoor units. The ceiling-concealed ducted unit shall support
individual control using SAMSUNG DVM S NASA Control Network
www.SamsungDVM-S.com
Specifications are subject to change without notice.
25
SAMSUNG Electronics HVAC
Solution (Control systems). Indoor model numbers shall be:
AM007FNLDCH/AA, AM009FNLDCH/AA, AM012FNLDCH/AA,
AM018FNLDCH/AA, AM024FNLDCH/AA, AM030FNLDCH/AA,
AM036FNLDCH/AA, AM048FNLDCH/AA.
2.
Each system shall perform in accordance to the ratings shown in the
table below. Performance shall be based on nominal cooling
conditions of 80F DB, 67F WB for the indoor unit and 95F DB for
the outdoor unit and nominal heating conditions of 70F DB for the
indoor unit and 47F DB, 43F WB for the outdoor unit.
System Model Number
Btu/h
Cooling*
Btu/h
Heating *
AM007FNLDCH/AA
7,500
8,500
AM009FNLDCH/AA
9,500
10,500
AM012FNLDCH/AA
12,000
13,500
AM018FNLDCH/AA
18,000
20,000
AM024FNLDCH/AA
24,000
27,000
AM030FNLDCH/AA
30,000
34,000
AM036FNLDCH/AA
36,000
40,000
AM048FNLDCH/AA
48,000
54,000
*Nominal capacity
B.
Indoor Unit:
1. The indoor unit shall be factory assembled, wired and run tested.
Contained within the unit shall be all factory wiring, piping, electronic
modulating linear expansion device, control circuit board and fan motor.
The unit shall have a self-diagnostic function, 3-minute time delay
mechanism, and an auto restart function. Indoor unit and refrigerant
pipes shall be charged with dehydrated air (Nitrogen gas) before
shipment from the factory.
2. The indoor unit shall have a discharge air temperature sensor.
3. The indoor unit discharge temperature sensor shall allow configuration
to control unit operation based on target cooling and heating discharge
air temperatures (cooling: 46~64º F, heating: 86~109º F).
4. The indoor unit discharge temperature sensor reading shall be visible
on central control options (MIM-D00AN, MIM-B16N, MIM-B17N) and
manufacturer provided service software.
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
26
SAMSUNG Electronics HVAC
C.
D.
E.
Unit Cabinet:
1.
The unit shall be space saving, ceiling-concealed, ducted.
2.
The cabinet shall be constructed of insulated galvanized steel.
Fan:
1.
The indoor unit fan assembly shall be two or three (dependent on
capacity) Sirocco fans direct driven by a single motor.
2.
The indoor fan shall be statically and dynamically balanced and run
on a motor with permanently lubricated bearings.
3.
The indoor fan shall consist of various speeds, as indicated in below
table.
Model Number
Fan Speed Setting
AM007FNLDCH/AA
AM009FNLDCH/AA
AM012FNLDCH/AA
AM018FNLDCH/AA
AM024FNLDCH/AA
AM030FNLDCH/AA
AM036FNLDCH/AA
AM048FNLDCH/AA
Low – Mid – High
4.
The indoor unit shall have a ducted air outlet and ducted return air
system (field provided).
5.
Standard external static pressure is 0.08” WC (min. 0”, max.
0.16”WC) for slim ducted indoor units up to 24,000 btu/h and 0.12”
WC (min. 0”, max. 0.24”) for units 30,000 btu/h and larger.
6.
The fan speed shall be adjustable by optional remote controller or
manufacturer provided service software according to external static
pressure.
Filter:
1.
Return air shall be filtered by means of a standard factory installed
return air filter on rear of unit.
2.
Optional return connection through rear or bottom of unit with
removal and replacement of return air conversion plate. Other
filtration is field provided (recommended).
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
27
SAMSUNG Electronics HVAC
F.
G.
Coil:
1.
The indoor coil shall be of nonferrous construction with slit fins on
copper tubing.
2.
The tubing shall have inner grooves for high efficiency heat
exchange.
3.
All tube joints shall be brazed with phos-copper or silver alloy.
4.
The coils shall be pressure tested at the factory.
5.
A condensate pan and drain shall be provided under the coil.
6.
The condensate shall be gravity drained from the fan coil.
7.
The coil fins are coated with hydrophilic paint.
8.
Both refrigerant lines to the ceiling-concealed ducted indoor units
shall be insulated.
9.
The condensate shall be gravity drained as standard (optional,
internally mounted, field installed, manufacturer provided
condensate pumps available).
Optional SAMSUNG Condensate Pumps
1. Condensate pump model: MDP-M075GU3D
H.
I.
Electrical:
1.
The unit electrical power shall be 208/230 volts, 1 phase, 60 hertz.
2.
The system shall be capable of satisfactory operation within voltage
limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz).
3.
The control circuit between the indoor units, MCU (Mode Change
Unit) and the outdoor unit shall be 0.5VDC - 7VDC completed using
stranded, annealed copper conductor, two-core, 16 AWG, shielded
cable to provide total integration of the system
4.
The indoor unit shall have a thermal fuse under high-voltage terminal
block to disable unit in the event of overheating due to electrical
malfunction/poor connection.
Controls:
1.
DRAFT: 07/29/2014
This unit shall use controls provided by SAMSUNG Electronics to
perform functions necessary to operate the system. Please refer to
www.SamsungDVM-S.com
Specifications are subject to change without notice.
28
SAMSUNG Electronics HVAC
Part 5 of this guide specification for details on controllers and other
control options.
2.
4.10
The indoor unit shall have a removable EEPROM on its PCB to store
all unit data. All data on the indoor unit EEPROM shall be viewable
from the manufacturer provided service software. The indoor unit
main EEPROM shall be removable allowing replacement of indoor
unit PCB without losing digital, field programmed data. The indoor
unit removable EEPROM shall store the following unit data: unit
model number, unit serial number, unit PCB firmware and MICOM
version, and field programmed unit name/tag viewable on controls
and service software.
MIDDLE STATIC PRESSURE, CEILING-CONCEALED, DUCTED, INDOOR UNIT
(AM0**FNMDCH/AA)
A.
General:
1.
The indoor unit shall be a high-performance ceiling-concealed
ducted indoor fan coil that mounts above the ceiling with a return and
a fixed horizontal discharge supply and shall have a modulating
linear expansion device. The ceiling-concealed ducted indoor unit
shall be compatible with DVM S HR (Heat Recovery) outdoor units
and MCU (Mode Change Unit) or DVM S HP (Heat Pump) outdoor
units. The ceiling-concealed ducted indoor unit shall support
individual control using SAMSUNG DVM S NASA Control Network
Solution (Control systems). Indoor model numbers shall be:
AM018FNMDCH/AA, AM024FNMDCH/AA, AM030FNMDCH/AA,
AM036FNMDCH/AA, and AM048FNMDCH/AA.
2.
Each system shall perform in accordance to the ratings shown in the
table below. Performance shall be based on nominal cooling
conditions of 80F DB, 67F WB for the indoor unit and 95F DB for
the outdoor unit and nominal heating conditions of 70F DB for the
indoor unit and 47F DB, 43F WB for the outdoor unit.
System Model Number
Btu/h
Cooling*
Btu/h
Heating*
AM018FNMDCH/AA
18,000
20,000
AM024FNMDCH/AA
24,000
27,000
AM030FNMDCH/AA
30,000
34,000
AM036FNMDCH/AA
36,000
40,000
AM048FNMDCH/AA
48,000
54,000
*Nominal capacity
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
29
SAMSUNG Electronics HVAC
B.
Indoor Unit:
1. The indoor unit shall be factory assembled, wired and run tested.
Contained within the unit shall be all factory wiring, piping, electronic
modulating linear expansion device, control circuit board and fan motor.
The unit shall have a self-diagnostic function, 3-minute time delay
mechanism, and an auto restart function. Indoor unit and refrigerant
pipes shall be charged with dehydrated air (Nitrogen gas) before
shipment from the factory.
2. The indoor unit shall have a discharge air temperature sensor.
3. The indoor unit discharge temperature sensor shall allow configuration
to control unit operation based on target cooling and heating discharge
air temperatures (cooling: 46~64º F, heating: 86~109º F).
4. The indoor unit discharge temperature sensor reading shall be visible
on central control options (MIM-D00AN, MIM-B16N, MIM-B17N) and
manufacturer provided service software.
C.
D.
Unit Cabinet:
1.
The cabinet shall be space saving, ceiling-concealed ducted.
2.
The cabinet shall be constructed of insulated galvanized steel.
Fan:
1.
The indoor unit fan shall be an assembly with two Sirocco fans direct
driven by 1 or 2 motors depending on capacity.
2.
Standard external static pressure for ceiling-concealed, medium
static pressure ducted indoor units 18,000 – 24,000 btu/h is 0.157”
WC. Acceptable range: 0” – 0.315” WC.
3.
Standard external static pressure for ceiling-concealed, medium
static pressure ducted indoor units 30,000 – 48,000 btu/h is 0.3” WC.
Acceptable range: 0.25” – 0.4” WC.
4.
The indoor fan shall be statically and dynamically balanced to run on
a motor with permanently lubricated bearings.
5.
The indoor fan shall consist of three (3) speeds, High, Mid, and Low.
6.
The indoor unit shall have a ducted air outlet system and ducted
return air system (field provided).
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
30
SAMSUNG Electronics HVAC
7.
E.
F.
The fan speed shall be adjustable by optional remote controller
according to external static pressure.
Filter:
1.
Return air shall be filtered by means of a standard factory installed
return air filter.
2.
Field provided filtration can be used within bounds of external
pressure drop (recommended).
Coil:
1.
The indoor coil shall be of nonferrous construction with slit fins on
copper tubing.
2.
The tubing shall have inner grooves for high efficiency heat
exchange.
3.
All tube joints shall be brazed with phos-copper or silver alloy.
4.
The coils shall be pressure tested at the factory.
5.
A condensate pan and drain shall be provided under the coil.
6.
The coil fins are coated with hydrophilic paint.
7.
Both refrigerant lines to the ceiling-concealed ducted indoor unit shall
be insulated.
8.
The condensate shall be gravity drained as standard (optional,
internally mounted, field installed, manufacturer provided
condensate pumps available).
G. Optional SAMSUNG Condensate Pumps
1.
Condensate
pump
model:
MDP-M075SGU3D
for
AM018FNMDCH/AA and AM024FNMDCH/AA indoor unit models.
2.
Condensate
pump
model:
MDP-M075SGU1D
for
AM
030FNMDCH/AA and AM036FNMDCH/AA indoor units models
3.
MDP-M075SGU2D for AM048FNMDCH/AA indoor unit model.
H. Electrical:
1.
DRAFT: 07/29/2014
The unit electrical power shall be 208/230 volts, 1 phase, 60 hertz.
www.SamsungDVM-S.com
Specifications are subject to change without notice.
31
SAMSUNG Electronics HVAC
I.
4.11
2.
The system shall be capable of satisfactory operation within voltage
limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz).
3.
The control circuit between the indoor units, MCU (Mode Change
Unit) and the outdoor unit shall be 0.5VDC - 7VDC completed using
stranded, annealed copper conductor, two-core, 16 AWG, shielded
cable to provide total integration of the system
4.
The indoor unit shall have a thermal fuse under high-voltage terminal
block to disable unit in the event of overheating due to electrical
malfunction/poor connection.
Controls:
1.
This unit shall use controls provided by SAMSUNG Electronics to
perform functions necessary to operate the system. Please refer to
Part 5 of this guide specification for details on controllers and other
control options.
2.
The indoor unit shall have a removable EEPROM on its PCB to store
all unit data. All data on the indoor unit EEPROM shall be viewable
from the manufacturer provided service software. The indoor unit
main EEPROM shall be removable allowing replacement of indoor
unit PCB without losing digital, field programmed data. The indoor
unit removable EEPROM shall store the following unit data: unit
model number, unit serial number, unit PCB firmware and MICOM
version, and field programmed unit name/tag viewable on controls
and service software.
HIGH STATIC PRESSURE, CEILING-CONCEALED, DUCTED, INDOOR UNIT
(AM0**FNHDCH/AA)
A. General:
1.
The indoor unit shall be a high-performance, high static pressure
capable, concealed ducted indoor fan coil that mounts above the
ceiling with a fixed horizontal discharge supply and shall have a
modulating linear expansion device (gear type). The high static
pressure capable, concealed ducted indoor unit shall be compatible
with DVM S HR (Heat Recovery) outdoor units and MCU (Mode
Change Unit) or DVM S HP (Heat Pump) outdoor units. The high
static pressure capable, concealed ducted indoor unit shall support
individual control using SAMSUNG DVM S NASA Control Network
Solution (Control systems). Indoor model numbers shall be:
AM036FNHDCH/AA, and AM048FNHDCH/AA.
2.
Each system shall perform in accordance to the ratings shown in the
table below. Performance shall be based on nominal cooling
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
32
SAMSUNG Electronics HVAC
conditions of 80F DB, 67F WB for the indoor unit and 95F DB for
the outdoor unit and nominal heating conditions of 70F DB for the
indoor unit and 47F DB, 43F WB for the outdoor unit.
System Model Number
Btu/h
Cooling*
Btu/h
Heating*
AM036FNHDCH/AA
36,000
40,000
AM048FNHDCH/AA
*Nominal Capacity
48,000
54,000
B. Indoor Unit.
1.
The indoor unit shall be factory assembled, wired and run tested.
Contained within the unit shall be all factory wiring, piping, electronic
modulating linear expansion device, control circuit board and fan
motor. The unit shall have a self-diagnostic function, 3-minute time
delay mechanism, and an auto restart function. Indoor unit and
refrigerant pipes shall be charged with dehydrated air (Nitrogen gas)
before shipment from the factory.
2.
The indoor unit shall have a discharge air temperature sensor.
3.
The indoor unit discharge temperature sensor shall allow
configuration to control unit operation based on target cooling and
heating discharge air temperatures (cooling: 46~64º F, heating:
86~109º F).
4.
The indoor unit discharge temperature sensor reading shall be visib
le on central control options (MIM-D00AN, MIM-B16N, MIMB17N) and manufacturer provided service software.
C. Unit Cabinet:
1.
The cabinet shall be space saving, ceiling-concealed ducted.
2.
The cabinet shall be constructed of insulated galvanized steel.
D. Fan:
1.
The indoor unit fan assembly shall have two Sirocco fans direct
driven by a single motor.
2.
Standard external static pressure is 0.39” WC. Acceptable range:
0.197” – 0.788” WC for 36,000 – 48,000 btu/h high static pressure
concealed ducted indoor units.
3.
Standard external static pressure is 0.59” WC. Acceptable range:
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
33
SAMSUNG Electronics HVAC
0.20” – 0.98” WC for 72,000 btu/h high static pressure concealed
ducted indoor units.
4.
Standard external static pressure is 0.59” WC. Acceptable range:
0.20” – 1.10” WC for 96,000 btu/h high static pressure concealed
ducted indoor units.
5.
The indoor fan shall be statically and dynamically balanced to run on
a motor with permanently lubricated bearings.
6.
The indoor fan shall consist of three (3) speeds, High, Mid, and Low.
7.
The indoor unit shall have a ducted air outlet system and ducted
return air system (field provided).
8.
The fan speed shall be adjustable by optional remote controller
according to external static pressure.
E. Filter:
1.
Field provided filtration must be used within bounds of external
pressure drop.
F. Coil:
1.
The indoor coil shall be of nonferrous construction with slit fins on
copper tubing.
2.
The tubing shall have inner grooves for high efficiency heat
exchanger.
3.
All tube joints shall be brazed with phos-copper or silver alloy.
4.
The coils shall be pressure tested at the factory.
5.
A condensate pan and drain shall be provided under the coil
6.
The coil fins are coated with hydrophilic paint.
7.
The condensate shall be gravity drained as standard (optional,
internally mounted, field installed, manufacturer provided
condensate pumps available).
G. Optional SAMSUNG Condensate Pump
1.
DRAFT: 07/29/2014
Condensate pump model: MDP-M075SGU2D for high static
pressure ducted units 36,000 – 48,000 btu/h.
www.SamsungDVM-S.com
Specifications are subject to change without notice.
34
SAMSUNG Electronics HVAC
2.
Condensate pump model: MDP-N047SNC1D for high static pressure
ducted units 72,000 – 96,000 btu/h.
H. Electrical:
I.
1.
The unit electrical power shall be 208/230 volts, 1 phase, 60 hertz.
2.
The system shall be capable of satisfactory operation within voltage
limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz).
3.
The control circuit between the indoor units, MCU (Mode Change
Unit) and the outdoor unit shall be 0.5VDC - 7VDC completed using
stranded, annealed copper conductor, two-core, 16 AWG, shielded
cable to provide total integration of the system
4.
The indoor unit shall have a thermal fuse under high-voltage terminal
block to disable unit in the event of overheating due to electrical
malfunction/poor connection.
Controls:
1.
This unit shall use controls provided by SAMSUNG Electronics to
perform functions necessary to operate the system. Please refer to
Part 5 of this guide specification for details on controllers and other
control options.
2.
The indoor unit shall have a removable EEPROM on its PCB to store
all unit data. All data on the indoor unit EEPROM shall be viewable
from the manufacturer provided service software. The indoor unit
main EEPROM shall be removable allowing replacement of indoor
unit PCB without losing digital, field programmed data. The indoor
unit removable EEPROM shall store the following unit data: unit
model number, unit serial number, unit PCB firmware and MICOM
version, and field programmed unit name/tag viewable on controls
and service software.
Part 5 – Controls
5.01
OVERVIEW
A.
General:
1.
DRAFT: 07/29/2014
The DVM Controls Network Solution shall be capable of supporting
remote controllers, schedule timers, system controllers, centralized
controllers, an integrated web based interface, graphical user
workstation, and system integration to Building Management
Systems via BACnet® and LonWorks®.
www.SamsungDVM-S.com
Specifications are subject to change without notice.
35
SAMSUNG Electronics HVAC
5.02
ELECTRICAL CHARACTERISTICS
A.
General:
1.
B.
C.
5.03
The DVM S Controls Solution shall operate at 12V DC (excluding
MCM-A202DN ON/OFF Controller). Controller power and
communications shall be via a common communications bus.
Wiring:
1.
Main system control wiring (COM1, F1/F2) shall be installed in a
system daisy chain configuration from the indoor equipment to
outdoor unit. Control wiring to wired remote controllers shall be run
from the indoor unit terminal block to the controller associated with
that unit. This cable shall be 16 AWG X 2, shielded cable.
2.
Control wiring for system controllers and centralized controllers
(upper level) shall be installed in a daisy chain configuration from
outdoor unit to outdoor unit (R1/R2), to system controllers.
3.
Communication wire connection (OF1/OF2) between outdoor unit
modules (systems greater than 168,000 btu/h) must be connected
from the MAIN unit to SUB1 and SUB2 (where applicable). This wire
shall be 2-conductor, 16 AWG X 2, shielded cable.
4.
MST-P3P (S-Net3 software) shall be capable of being networked
with up to 16: MIM-D00AN (DMS2), MIM-B17N (BACnet gateway),
and/or MIM-B18 (LonWorks gateway) system controllers for
web/LAN based control for consolidated control.
Wiring type:
1.
COM1 and COM2 control wiring shall be 2-conductor, 16 AWG X 2,
shielded cable.
2.
Network wiring shall be CAT-5e with RJ-45 connection.
DVM CONTROL NETWORK SOLUTION
A.
The SAMSUNG DVM S NASA Control Network Solution consists of remote
controllers, system controllers, centralized controllers, and/or integrated
web based interface communicating over a high-speed communication bus.
The SAMSUNG DVM S NASA Control Network Solution shall support
operation monitoring, scheduling, error monitor, power distribution,
personal browsers, tenant billing, online maintenance support, and
integration with Building Management Systems (BMS) using either
LonWorks® or BACnet® interfaces.
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
36
SAMSUNG Electronics HVAC
5.04
MULTI-FUNCTION CONTROLLER – INDIVIDUAL WIRED CONTROLLER (MWRWE10N)
A.
Connection:
1.
B.
Dimensions:
1.
C.
The wired controller shall control up to 16 SAMSUNG indoor units or
SAMSUNG ERV’s (defined and controlled as one group).
The wired controller shall be approximately 4 5/8” x 4 7/8” in size and
white in color
The wired controller shall control indoor units and SAMSUNG ERV as
follows:
1.
Air handler and ERV unified controller (can only control SAMSUNG
ERV’s)
2.
Air handler operation ON/OFF
3.
Air handler operation mode, set temperature, air flow direction, fan
speed, individual louver control (with supported indoor units),
discharge air temperature (with supported indoor units)
4.
Quiet and sleep modes
5.
Error display
6.
Filter replacement alarm display and reset
7.
Single indoor unit control or multiple unit control (maximum 16 units)
8.
Energy saving operation:
9.
DRAFT: 07/29/2014
a.
Upper/lower temperature setting
b.
Automatic operation stop function
c.
Energy saving operation mode
Weekly operating schedule setting:
a.
Weekly operating schedule (A/C only, ERV only, A/C + ERV)
b.
Options to set: desired A/C operation mode, setting
temperature, power mode (ON/OFF), and fan speed to
operate based on weekly or daily schedules
www.SamsungDVM-S.com
Specifications are subject to change without notice.
37
SAMSUNG Electronics HVAC
c.
D.
E.
Optional schedule exception day setting
Other wired controller features:
1.
Different button permission levels
2.
Partial button lock option (on/off, selection, temperature setting, fan
speed, and schedule setting buttons can be locked individually)
3.
Backlight
4.
Daylight savings clock advance option
5.
Temperature limit setting option
6.
Real-time clock function - current time/day display function
7.
Built-in room temperature sensor
8.
Indoor unit operation state display
9.
Service mode support (Indoor unit addressing, indoor unit cycle data
monitoring, option code monitoring and setting, and option
setting/monitoring)
Specifications:
1.
2 conductor connection, PLC, (F3/F4).
2.
DC 12V (power supplied by indoor unit via F3/F4 connection).
3.
RS485 communication (F3/F4).
4.
Can sense temperature via internal sensor, temperature sensor
inside the air handler, or use the average temperature between
controller and air handler temperature sensors.
5.
The wired controller shall have two screw terminals for wiring
connections. Wire is not included with controller.
6.
16AWG X 2 shielded cable is necessary for proper operation.
7.
The wired controller shall allow up to 328 feet of wire from the farthest
connected indoor unit to the controller.
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
38
SAMSUNG Electronics HVAC
Multi-Function Controller
Item
Description
Operation
Display
ON/OFF
Run and stop operation for a single group
Including Samsung ERV operation
Each Group
Each Group
Operation Mode
Switches between Auto/Cool/Dry/ Fan/Heat
Each Group
Each Group
Temperature
Setting
1. Sets temperature for a single group.
2. Range of temperature setting
a. Auto/Cool/Dry: 65°F-86°F
b. Heat: 61°F-86°F
3. Setting discharge outlet air temperature for
supported indoor units.
Each Group
Each Group
Discharge Air
Temperature
Setting
Sets temperature for supported ducted units
Each Group
Each Group
Fan Speed
Setting
Models with 3 air flow speed settings: High
/Mid/Low/Auto
Each Group
Each Group
Air Flow
Direction Setting
1. Air flow 2-step direction (Swing/Stop)
2. Direct setting at a specific angle.
3. Air flow operation varies depending on the
model.
Each Group
Each Group
Each Group
Each Group
Each Group
Each Group
Each Group
Each Group
Weekly
Schedule
Button lock
Specified
Function
DRAFT: 07/29/2014
1. ON/OFF/Temperature setting can be done
at most 10 schedules may be set for each
day.
2. Real-time clock function: current time, day
display function
1. Button permission level setting (On/Off /
Temperature setting / Mode button / Fan
speed)
2. Temperature limit setting
3. After power reset, the setting value is
restored
4. Various restriction capabilities
1. Automatic stop setting (setting time range:
0-12 hours)
2. Energy saving operation mode (IDU+ERV
or ERV operation only depending on
outdoor temperature)
www.SamsungDVM-S.com
Specifications are subject to change without notice.
39
SAMSUNG Electronics HVAC
Multi-Function Controller
Item
Description
Operation
Display
Service Mode
Viewing/Setting indoor unit option code
Viewing/setting indoor unit MAIN address
Viewing/setting indoor unit RMC address
Viewing indoor unit cycle data
Setting/Viewing
temperature
sensor
compensation of the wired remote
controller (-9°F~ +9°F)
6. Viewing RPM compensation
7. Viewing/setting EEV stop step when indoor
unit is thermo-off during heating mode
8. Viewing/setting filter reminder time interval
(1000 hours, 2000 hours)
9. Viewing/setting indoor unit temperature
sensor compensation during Heating
(+2°F or +5°F)
10. Viewing the H/W option setting
11. Viewing wired remote controller software
version
12. Viewing/setting individual louver lock
Each Unit
Each Unit
Blade
Setting individual blade positions on 4-Way
Cassette (AM0**FN4DCH/AA)
Each Unit
Each Unit
Error
When an error is currently occurring in the
system, the afflicted unit and the error code
are displayed
Each Group
Each Group
Permit / Prohibit
Local Operation
Setting/releasing of simplified locking of
remote control buttons
Each Group
N/A
Quiet Mode
Select the quiet mode to lower the fan noise
level.
Each Group
N/A
1.
2.
3.
4.
5.
Room
Actual room temperature or set temperature
Each Group Each Group
Temperature
can be displayed
*Some features may not be available depending on the model of connected air handler(s).
5.05
SIMPLIFIED WIRED CONTROLLER (MWR-SH00N)
A. Connection:
1.
The wired controller shall control up to 16 SAMSUNG indoor units
(defined and controlled as one group).
B. Dimensions:
1.
DRAFT: 07/29/2014
The wired controller shall be approximately 4 13/16” x 3” x 5/8” in
size and white in color.
www.SamsungDVM-S.com
Specifications are subject to change without notice.
40
SAMSUNG Electronics HVAC
C. The wired controller shall have the following features and control capability:
1.
Indoor unit operation ON/OFF
2.
Indoor unit operation mode, set temperature, and fan speed
3.
Error display
4.
Filter replacement alarm display and reset
5.
Single indoor unit control or multiple unit control (maximum 16 units)
6.
Partial controller button lock (operation mode button, temperature
setting buttons, fan speed button, timer button, and lock mode button)
7.
Upper and lower temperature setting restriction
8.
Auto mode skip
9.
Heat mode skip (cooling only)
10.
Restrict wireless controller signal (optional)
11.
Louver position setting (cassette and wall units)
12.
Single event timer function (ON/OFF control, 30 minutes ~ 18 hours
timer setting options)
13.
System/indoor unit function and operation indication (defrost, error,
restricted controller, SPi status)
14.
Quiet Mode setting (for supported units)
15.
Service mode for connected indoor unit operation monitoring,
addressing, and setup
16.
Can be used to specify "Mode Master" while connected to a single
indoor unit when used with heat pump systems.
D. Specifications:
1.
2 conductor connection, PLC, (F3/F4).
2.
DC 12V (power supplied by indoor unit via F3/F4 connection).
3.
RS485 communication (F3/F4).
4.
The wired controller shall have two screw terminals for wiring
connections. Wire is not included with controller.
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
41
SAMSUNG Electronics HVAC
5.
16AWG X 2 shielded cable is necessary for proper operation.
6.
The wired controller shall allow up to 328 feet of wire from the farthest
connected indoor unit to the controller.
Simplified Controller
Item
Description
Operation
Display
ON/OFF
Run and stop operation for a single group
Including Samsung ERV operation
Each Group
Each Group
Operation Mode
Switches between Auto/Cool/Dry/ Fan/Heat
Each Group
Each Group
Temperature
Setting
1. Sets temperature for a single group.
2. Range of temperature setting
a. Auto/Cool/Dry: 65°F-86°F
b. Heat: 61°F-86°F
3. Setting discharge outlet air temperature for
supported indoor units.
Each Group
Each Group
Fan Speed
Setting
Models with 3 air flow speed settings: High
/Mid/Low/Auto
Each Group
Each Group
Air Flow
Direction Setting
1. Air flow 2-step direction (Swing/Stop)
2. Air flow operation varies depending on the
model.
Each Group
Each Group
Each Group
Each Group
Each Group
Each Group
Each Group
Each Group
Each Unit
Each Unit
Each Group
Each Group
ON/OFF Timer
Button lock
Specified
Function
Service Mode
Error
DRAFT: 07/29/2014
1. ON/OFF single event timer
2. Can set to turn unit ON and/or OFF between
30 minutes ~ 18 hours.
1. Button permission level setting (On/Off /
Temperature setting / Mode button / Fan
speed)
2. Temperature limit setting
3. After power reset, the setting value is
restored
4. Various restriction capabilities
1. Energy saving operation mode (IDU+ERV
or ERV operation only depending on
outdoor temperature)
1.
2.
3.
4.
5.
Viewing/Setting indoor unit option code
Viewing/setting indoor unit MAIN address
Viewing/setting indoor unit RMC address
Viewing indoor unit cycle data
Viewing/setting indoor unit temperature
sensor compensation during Heating
(+2°F or +5°F)
When an error is currently occurring in the
system, the afflicted unit and the error code
are displayed
www.SamsungDVM-S.com
Specifications are subject to change without notice.
42
SAMSUNG Electronics HVAC
Simplified Controller
Item
Description
Operation
Display
Permit / Prohibit
Local Operation
Setting/releasing of simplified locking of
remote control buttons
Each Group
N/A
Quiet Mode
Select the quiet mode to lower the fan noise
level.
Each Group
N/A
5.06
WIRELESS CONTROLLER (MWR-DH00U)
A. Function:
1. The wireless controller shall support the following control options via
soft-touch buttons: ON/OFF, set temperature, mode, fan speed, filter
reminder reset, independent louver control (4-way cassette only),
airflow direction, and single event timer setting.
2. The wireless controller shall have a wide, easy to read display.
3. The wireless controller shall support indoor unit option code setting,
indoor unit addressing, and indoor unit option setting.
4. The wireless controller shall include a holder to secure remote to wall.
B. Dimensions:
1. Width Height X Depth: 1 11/16” X 5 7/16” X 1 1/8”
5.07
WIRELESS SIGNAL RECEIVER FOR DUCT-TYPE INDOOR UNITS (MRK-A10N)
A.
Connection:
1.
B.
The wireless signal receiver shall be capable of connection to 1 duct
unit.
Function:
1.
The wireless signal receiver shall control: power, fan speed, set
temperature, and timer via wireless controller (MRW-DH00U).
2.
The wireless signal receiver shall display operation indication and
blinking LED indication in the event of system operation and
abnormality/error.
3.
The wireless signal receiver shall connect using included receiver
wire (32.8’).
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
43
SAMSUNG Electronics HVAC
C.
5.08
Dimensions:
1.
The wireless signal receiver shall be approximately 2.7” x 4.7” in size
and white in color with a LED display.
2.
The wireless signal receiver shall be recessed mount.
EXTERNAL ROOM TEMPERATURE SENSOR (MRW-TA)
A. Connection:
1.
The external remote room sensor shall connect to 1 indoor unit.
2.
The external remote room sensor shall plug directly into PCB of
indoor unit with supplied adapter.
B. Function:
5.09
The external remote room sensor shall be used to measure the exact
room temperature.
2.
The external remote room sensor shall support wire length of
maximum 39 feet.
EXTERNAL CONTACT CONTROL – INDIVIDUAL UNIT, ON/OFF CONTROL AND
MONITORING (MIM-B14)
A.
5.10
1.
Function:
1.
Control option to enable/disable and monitor individual indoor units
2.
Direct indoor unit control by external contact, 0 volts OPEN/CLOSE
signal
3.
Emergency control with simple contact input
4.
Indoor unit operation (thermo or operation)/error state output through
relay contacts (5VDC)
5.
Installation location: inside a single indoor unit
6.
Connection to indoor unit with included wire harnesses
ON/OFF CONTROLLER (MCM-A202DN)
A.
Connection:
1.
DRAFT: 07/29/2014
The On/Off Controller shall be capable of controlling up to 128 indoor
units (defined as 16 groups).
www.SamsungDVM-S.com
Specifications are subject to change without notice.
44
SAMSUNG Electronics HVAC
B.
C.
Dimensions:
1.
The On/Off Controller shall be approximately 2.3” x 4.7” in size and
white in color with 17 LED displays.
2.
The On/Off Controller shall install recessed in wall.
approved box shall be required for installation.
An NEC
Function:
1.
The On/Off Controller shall be capable of turning ON/OFF up to
sixteen groups of indoor units (1 – 16 units per group), for a
maximum of 128 indoor units.
2.
Each of the 16 individual groups shall have ON/OFF control separate
from other groups.
3.
All of the indoor units shall be turned ON/OFF using the main ALL
ON/ALL OFF power button.
4.
An LED for each group of indoor units, up to 16 groups, shall be
indicated if there is a failure within each group by flashing.
5.
An All LED shall be ON if all the indoor units controlled by MCMA202DN are turned ON.
6.
An LED for each group of indoor units shall indicate the ON/OFF
status of the group.
7.
208/230VAC 50/60 Hz. power. Must install in an NEC approved box.
ON/OFF Controller
Item
Description
Operation
Display
ON/OFF
Run and stop operation for the air conditioner
units
Group or
Collective
Group or
Collective
Operation Mode
Setting
Auto/Cooling/Heating mode control using
mode switch + ALLO ON/ALL OFF button
N/A
All Unit
Groups LED
Error
LED flashes during failure.
N/A
Each Group
Schedule
Operation
Not Available
N/A
N/A
Connection
Position
Outdoor Unit Communication Line (R1/R2)
N/A
N/A
Permit / Prohibit
Local Operation
Wireless/wired remote control restriction
Each Group
N/A
5.11
INTEGRATED MANAGEMENT SYSTEM – DATA MANAGEMENT SERVER (MIM-
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
45
SAMSUNG Electronics HVAC
D00AN)
A.
Function:
1.
Easy control and monitoring through web browser (optimized for
Internet Explorer). Individual/Group control of up to 256 indoor units
including SAMSUNG ERV and air handlers.
2.
The Data Management Server shall have basic operation controls
which can be applied to an individual indoor unit, a group of indoor
units (up to 256 indoor units), or all indoor units (collective batch
operation). This basic controls for the MIM-D00AN shall include
on/off, operation mode selection (auto, cool, heat, dry, and fan),
temperature setting, fan speed setting, airflow direction setting, error
email notification, temperature limitations, operation mode limitation,
and online maintenance.
3.
The Data Management Server shall support system error notification
via email. The Data Management Server emailed errors shall include:
error occurrence time, error code with description of error, effected
equipment address, and current error status.
4.
The Data Management Server shall support: system configuration,
1-day/daily/weekly scheduling, monitoring of operation status, online
maintenance tool, operation superseding of the remote controllers,
editable user defined control logic, and malfunction monitoring.
5.
The Data Management Server shall allow maximum current setting
control of each outdoor unit (DVM S Series AM***FX*A**/AA only).
6.
Schedule control function through web browser. Up to 256 schedule
settings, weekly and daily schedule setting, wireless/wired remote
controller restriction setting. Digital Outputs can be incorporated into
scheduling.
7.
Convenient digital display allows for easy set up.
8.
SD memory card slot for data storage and software updating.
9.
Available programmable logic to control the system based on preset
monitor points.
10.
Web server function with remote control (with a public IP address)
via internet connection. No management software required – PCindependent management through web browser.
11.
10 DI (Digital Input) ports available. Two digital output ports shall be
for emergency shutdown with external contact control interface and
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
46
SAMSUNG Electronics HVAC
8 for other monitoring options (OPEN/CLOSE status). Full indoor
unit control with simple contact input (Emergency/Lock). Digital
inputs can be incorporated into control logics.
12.
B.
8 DO (Digital output) terminals for monitoring and control options. 2
state output (Operation/Error) for synchronous control and
monitoring. 6 general purpose outputs to control other components
(on: 12VDC out; off: no voltage). Digital Inputs and Digital Outputs
can be incorporated into control logics and scheduling.
Connection:
1.
DC 12V, 3A power provided by AC/DC adapter (input 110-240VAC
50/60Hz, provided with MIM-D00AN).
2.
LAN connection for web browser or SNET3 software connection.
3.
16 AWG X 2 shielded cable between SAMSUNG equipment and
controls is necessary for proper operation.
4.
Maximum number of RS485 connections to 1 MIM-D00AN:
a.
75 ON/OFF Controllers (MCM-A202DN)
b.
80 DVM S Series Systems (AM***FX*A**/AA and
AM0**FXMDCH/AA) connected direct (5 ports, 16 systems
per port)
c.
Maximum 256 indoor units (air handler and/or SAMSUNG
ERV)
5.
Upper level device connections : S-NET 3, web client.
6.
The Data Management Server shall provide functions to monitor and
control status of SAMSUNG DVM S Series systems
(AM***FXVA**/AA and AM0**FXMDCH/AA) as standard.
7.
The Data Management Server shall support provide functions to
monitor and control status of SAMSUNG DVM Plus II, Samsung
DVM Plus III, Mini DVM, Free Joint Multi, and CAC
(CH070/105/140CAV, DH105/140CAV single zone systems) with
installation of communication converter interface module per system.
8.
Dimensions:
a.
DRAFT: 07/29/2014
The Data Management Server shall be approximately 9.4” x
10” x 2.6” in size with stainless steel front and LCD displays.
www.SamsungDVM-S.com
Specifications are subject to change without notice.
47
SAMSUNG Electronics HVAC
VRF Data Management Server (DMS2)
Item
Description
Operation
Display
ON/OFF
Run and stop operation for a single group
Each Group
Each Group
Operation Mode
Switches between Auto/Cool/Dry/ /Fan/Heat
Each Group
Each Group
Temperature
Setting
1. Sets the temperature for a single group.
Range of temperature setting
a. Auto/Cool/Dry: 65°F-86°F
b. Heat: 61°F-86°F
Each Group
Each Group
Fan Speed
Setting
Models with 3 air flow speed settings: High
/Mid/Low
Each Group
Each Group
Air Flow
Direction Setting
1. Air flow 2-step direction (Swing/Stop)
2. Direct setting at a specific angle.
3. Air flow operation varies depending on the
model.
Each Group
Each Group
Web Server
Function
1. Remote control with the public IP address
2. No management software required – PCindependent management
Each Group
Each Group
Accessible level
/ Dynamic user
security
Management
1. Wireless/wired remote controller restriction
setting
2. Specify the scope of control and monitoring
unit on a per-user
3. 3 accessible levels -Admin/Manager/User
Each Group
Each Group
Error
1. When an error is currently occurring in the
system(s), the afflicted unit and the error
code are displayed
2. Error notification via email
Each Group
Each Group
Schedule
Operation
Up to 256 schedule settings
Weekly and daily schedule setting
Each Group
Each Group
Power distribution to 256 indoor units.
Remote data query in 1-day units
File saving in Microsoft Excel format.
Power distribution data storage for one
year
5. MIM-B16 or MIM-B16N required for power
use measurements
Each Group
Each Group
1. Full indoor unit control with simple contact
input (Emergency/Lock)
2. State
output
(Operation/Error)
for
synchronous control
3. 10 digital outputs (2 reserved) / 8 digital
inputs (2 reserved)
Each
Channel
Each
Channel
Power
Distribution
System
External Contact
Interface
DRAFT: 07/29/2014
1.
2.
3.
4.
www.SamsungDVM-S.com
Specifications are subject to change without notice.
48
SAMSUNG Electronics HVAC
VRF Data Management Server (DMS2)
Item
Description
Operation
Display
Control & monitoring zone edition
Wireless/wired remote control restriction
Temperature limit setting
Operation mode restriction
Each Group
Each Group
Smart Central
Management
1.
2.
3.
4.
User editable
control logic
1. User can edit control logic with
arithmetic/conditional
operators
and
parameters.
2. Efficient energy saving realization for
various operation conditions.
3. EHP/ERV/AHU parameters + AND/OR +
Arithmetic equation Function
Each Group
Each Group
Data
backup/useful
history
management
1. Important data is stored in SD memory
card (settings, schedules, errors, operation
data, energy data, user settings, etc.)
2. Record the operation history and error
history
Each Group
Each Group
5.12
INTEGRATED MANAGEMENT SYSTEM – S-NET3 SYSTEM MANAGEMENT
SOFTWARE (MST-P3P)
A. Connection:
The integrated management software shall be capable of controlling up to
4,096 indoor units.
B. Dimensions:
S-Net3 shall be system software installed by a CD USB security key.
C. Function:
3.
The Integrated System Software shall enable the user to control
multiple indoor units and shall provide additional functions.
4.
The integrated management software shall be capable of connecting
up to 16 of the following controllers: MIM-D00A, MIM-D00AN, MIMB17, MIM-B17N, MIM-B18, MIM-B18N.
5.
The integrated management software shall be required if the user
wants to simultaneously control 16 X MIM-D00A, MIM-D00AN, MIMB17, MIM-B17N, MIM-B18, and/or MIM-B18N from a single PC using
a single software session.
6.
The integrated management software shall support operation
superseding that of the remote controllers, system configuration,
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
49
SAMSUNG Electronics HVAC
daily/weekly/annual scheduling, monitoring of operation status, error
email notification, online maintenance tool and malfunction
monitoring.
7.
The integrated management software shall have basic operation
controls which can be applied to an individual indoor unit, a group of
indoor units (up to 4,096 indoor units), or all indoor units (collective
batch operation). This basic control set of operation controls for the
integrated management software shall include on/off, operation
mode selection (cool, heat, auto, dry and fan), temperature setting,
fan speed setting, airflow direction setting and online maintenance.
8.
The integrated management software provides centralized control, it
shall be able to enable or disable operation of local remote
controllers via PC.
9.
The integrated management software shall also include a high-level
security USB key.
10.
In terms of scheduling, the integrated management software shall
allow the user to define daily, weekly, and annual schedules with
operations consisting of ON/OFF, mode selection, temperature
setting, and permit/prohibit of remote controllers.
VRF Integrated Management Software (S-Net3)
Item
Description
Operation
Display
ON/OFF
Run and stop operation for a single group/unit
Each Group
Each Group
Operation Mode
Switches between Auto/Cool/Dry/Fan/Heat
Each Group
Each Group
Temperature
Setting
1. Sets the temperature for a single group.
Range of temperature setting
1. Auto/Cool/Dry: 65°F-86°F
2. Heat: 61°F-86°F
Each Group
Each Group
Fan Speed
Setting
Models with 3 air flow speed settings:
High /Mid/Low
Each Group
Each Group
Air Flow
Direction Setting
1. Air flow 2-step direction (Swing/Stop)
2. Direct setting at a specific angle.
3. Air flow operation varies depending on the
model
Each Group
Each Group
Accessible level
1. Wireless/wired remote controller restriction
setting
2. Specify the scope of control and monitoring
unit on a per-user
Each Group
Each Group
Error
When an error is currently occurring on the
system(s), the afflicted unit and the error code
are displayed
Each Group
Each Group
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
50
SAMSUNG Electronics HVAC
VRF Integrated Management Software (S-Net3)
Item
Description
Schedule
Operation
Display
Graphical schedule settings
Weekly, Daily schedule control
Exception date setting
Each Group
Each Group
Power distribution to 4,096 indoor units.
Remote data query in 1-day increments
File saving in Microsoft Excel format.
Power distribution data storage for one
year in 1-day units.
5. MIM-B16 or MIM-B16N required for power
distribution.
6. PDF report generation with electrical
operational costs.
Each Group
Each Group
Each Group
Each Group
1.
2.
3.
4.
Power
Distribution
System
Smart Central
Management
5.13
Operation
1.
2.
3.
4.
Control & monitoring zone edition
Wireless/wired remote control restriction
Temperature limit setting
Operation mode restriction
LonWorks® Gateway (MIM-B18N)
A. Function:
1.
Easy control and monitoring through web browser (optimized for
Internet Explorer) and LonWorks® TP/FT-10A (free topology 78kbs).
Individual/Group control of up to 128 indoor units including
SAMSUNG ERV’s and air handlers (indoor quantity will vary based
on number of control points necessary, see table below).
Control and Monitoring Items*
Maximum Number of
Connectable Indoor Units
27 Items (all)
22
20 Items
30
15 Items
40
12 Items
50
9 Items
64
6 Items
100
4 Items
128
*20 items can be processed per second; data inquiry interval is 30 seconds.
2.
DRAFT: 07/29/2014
The LonWorks® shall have basic operation controls which can be
applied to an individual indoor unit, a group of indoor units (up to 128
indoor units), or all indoor units (collective batch operation). This
www.SamsungDVM-S.com
Specifications are subject to change without notice.
51
SAMSUNG Electronics HVAC
basic control set of operation controls for the LonWorks® gateway
shall include on/off, operation mode selection (auto, cool, heat, dry,
and fan), temperature setting, fan speed setting, airflow direction
setting, error email notification, temperature limitations, operation
mode limitation, and online maintenance.
B.
3.
The LonWorks® gateway shall support system error notification via
email. The Data Management Server emailed errors shall include:
error occurrence time, error code with description of error, effected
equipment address, and current error status.
4.
The LonWorks® gateway shall support: system configuration, 1day/daily/weekly scheduling, monitoring of operation status, online
maintenance tool, operation superseding of the remote controllers,
editable user defined control logic, and malfunction monitoring.
5.
The LonWorks® gateway shall allow maximum current setting
control of each outdoor unit (DVM S Series AM***FX****/AA only).
6.
Schedule Control Function through web browser. Up to 256 schedule
settings, weekly and daily schedule setting, wireless/wired remote
controller restriction setting. Digital Outputs can be incorporated into
scheduling.
7.
Convenient digital display allows for easy set up.
8.
SD memory card slot for data storage and software updating.
9.
Available programmable logic to control the system based on preset
monitor points.
10.
Web Server Function with remote control (with a public IP address)
via internet connection. No management software required – PCindependent management through web browser.
11.
10 DI (Digital Input) ports available. Two digital output ports shall be
for emergency shutdown with external contact control interface and
8 for other monitoring options (OPEN/CLOSE status). Full indoor
unit control with simple contact input (Emergency/Lock). Digital
inputs can be incorporated into control logics.
12.
8 DO (Digital Output) terminals for monitoring and control options. 2
state output (Operation/Error) for synchronous control and
monitoring. 6 general purpose outputs to control other components
(on: 12VDC out; off: no voltage). Digital Inputs and Digital Outputs
can be incorporated into control logics and scheduling.
Connection:
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
52
SAMSUNG Electronics HVAC
C.
1.
DC 12V, 3A power provided by AC/DC adapter (input 110-240VAC
50/60Hz, provided with the LonWorks® gateway)
2.
LAN connection for BMS, web browser, SNET3 software connection
3.
Communication connection: ON/OFF Controller(s) (MCM-A202DN)
4.
16 AWG X 2 shielded cable between SAMSUNG equipment and
controls is necessary for proper operation
5.
Maximum number of RS485 connections to 1 LonWorks® gateway:
a.
75 ON/OFF Controllers (MCM-A202DN)
b.
80 DVM S Series Systems (AM***FX****/AA and
AM0**FXMDCH/AA) connected direct (5 ports, 16 systems
per port)
c.
Maximum 128 indoor units (air handler and/or SAMSUNG
ERV)
6.
Upper level device connections:
(LonWorks®), web client
S-NET 3, BMS system
7.
The LonWorks® gateway shall support LonWork®s TP/FT-10A (free
topology 78kbs) and provide functions to monitor and control status
of SAMSUNG DVM S Series systems (AM***FX****/AA and
AM0**FXMDCH/AA).
8.
The LonWorks® gateway shall support LonWorks® TP/FT-10A (free
topology 78kbs) and provide functions to monitor and control status
of SAMSUNG DVM Plus II, SAMSUNG DVM Plus III, Mini DVM, Free
Joint Multi, and CAC (CH070/105/140CAV, DH105/140CAV single
zone systems) with installation of communication converter interface
module per system (MIM-N01).
Dimensions:
1.
The LonWorks® gateway shall be approximately 9.4” x 10” x 2.6” in
size with stainless steel front and LCD displays.
VRF LonWorks® Gateway
Item
Description
Operation
Display
ON/OFF
Run and stop operation for a single group
Each Group
Each Group
Operation Mode
Switches between Auto/Cool/Dry/ /Fan/Heat
Each Group
Each Group
Each Group
Each Group
Temperature
Setting
DRAFT: 07/29/2014
1. Sets the temperature for a single group.
Range of temperature setting
www.SamsungDVM-S.com
Specifications are subject to change without notice.
53
SAMSUNG Electronics HVAC
VRF LonWorks® Gateway
Item
Description
a. Auto/Cool/Dry: 65°F-86°F
b. Heat: 61°F-86°F
Operation
Display
Fan Speed
Setting
Models with 3 air flow speed settings:
High /Mid/Low
Each Group
Each Group
Air Flow
Direction Setting
1. Air flow 2-step direction (Swing/Stop)
2. Direct setting at a specific angle.
3. Air flow operation varies depending on
the model.
Each Group
Each Group
Web Server
Function
1. Remote control with the public IP address
2. No management software required – PCindependent management
Each Group
Each Group
Accessible level
/ Dynamic user
security
Management
1. Wireless/wired
remote
controller
restriction setting
2. Specify the scope of control and
monitoring unit on a per-user
3. 3 accessible levels:
Admin/Manager/User
Each Group
Each Group
When an error is currently occurring on
the System(s), the afflicted unit and the
error code are displayed
Error notification via email
Each Group
Each Group
Each Group
Each Group
Power distribution to 128 indoor units.
Remote data query in 1-day units
File saving in Microsoft Excel format.
Power distribution data storage for one
year
5. MIM-B16 or MIM-B16N required for
power use measurements
Each Group
Each Group
External Contact
Interface
1. Full indoor unit control with simple contact
input (Emergency/Lock)
2. State output (Operation/Error) for
synchronous control
3. 10 digital outputs (2 reserved) / 8 digital
inputs (2 reserved)
Each
Channel
Each
Channel
Smart Central
Management
1.
2.
3.
4.
Each Group
Each Group
1.
Error
2.
Schedule
Operation
Power
Distribution
System
DRAFT: 07/29/2014
Up to 256 schedule settings
Weekly and daily schedule setting
1.
2.
3.
4.
Control & monitoring zone edition
Wireless/wired remote control restriction
Temperature limit setting
Operation mode restriction
www.SamsungDVM-S.com
Specifications are subject to change without notice.
54
SAMSUNG Electronics HVAC
VRF LonWorks® Gateway
Item
Description
Operation
Display
User editable
control logic
1. User can edit control logic with
arithmetic/conditional operators and
parameters.
2. Efficient energy saving realization for
various operation conditions.
3. EHP/ERV/AHU parameters + AND/OR +
Arithmetic equation Function
Each Group
Each Group
Data backup/
useful history
management
1. Important data is stored in SD memory
card
2. Record the operation history and error
history
Each Group
Each Group
VRF LonWorks® Gateway
Input Variables (Control)
Output Variables (Monitor)
On/Off control
On/Off state
In/out contact state
Operation mode
Operation mode
Emergency Stop
Temperature setting
Set/Room temperature
Error code
Fan speed/direction
Fan speed/direction
Indoor time duration
ERV operation mode
ERV operation mode
ERV fan speed
ERV fan speed
Filter alarm reset
Filter alarm
User control restriction
User control restriction
Operation mode lock
Thermo Off/On
Set temperature limit
Power distribution
Emergency stop
Operation mode lock
Output contact control
Set temperature limit
5.14
BACnet® GATEWAY (MIM-B17N)
A. Function:
1.
Easy control and monitoring through web browser (optimized for
Internet Explorer). Individual/Group control of up to 256 indoor units
(indoor quantity will vary based on number of control points
necessary, see table below) including SAMSUNG ERV’s and air
handlers.
2.
The BACnet® gateway shall have basic operation controls which can
be applied to an individual indoor unit, a group of indoor units (up to
256 indoor units), or all indoor units (collective batch operation). This
basic control set of operation controls for the BACnet® gateway shall
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
55
SAMSUNG Electronics HVAC
include on/off, operation mode selection (auto, cool, heat, dry, and
fan), temperature setting, fan speed setting, airflow direction setting,
error email notification, temperature limitations, operation mode
limitation, and online maintenance.
3.
The BACnet® gateway shall support system error notification via
email. The Data Management Server emailed errors shall include:
error occurrence time, error code with description of error, effected
equipment address, and current error status.
4.
The BACnet® gateway shall support: system configuration, 1day/daily/weekly scheduling, monitoring of operation status, online
maintenance tool, operation superseding of the remote controllers,
editable user defined control logic, and malfunction monitoring.
5.
The BACnet® gateway shall allow maximum current setting control
of each outdoor unit (DVM S Series AM***FX****/AA only).
6.
Schedule Control Function through web browser. Up to 256 schedule
settings, weekly and daily schedule setting, wireless/wired remote
controller restriction setting. Digital Outputs can be incorporated into
scheduling.
7.
Convenient digital display allows for easy set up.
8.
SD memory card slot for data storage and software updating.
9.
Available programmable logic to control the system based on preset
monitor points.
10.
Web Server Function with remote control (with a public IP address)
via internet connection. No management software required – PCindependent management through web browser.
11.
10 DI (Digital Input) ports available. Two digital output ports shall be
for emergency shutdown with external contact control interface and
8 for other monitoring options (OPEN/CLOSE status). Full indoor unit
control with simple contact input (Emergency/Lock). Digital inputs
can be incorporated into control logics.
12.
8 DO (Digital Output) terminals for monitoring and control options. 2
state output (Operation/Error) for synchronous control and
monitoring. 6 general purpose outputs to control other components
(on: 12VDC out; off: no voltage). Digital Inputs and Digital Outputs
can be incorporated into control logics and scheduling.
C. Connection:
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
56
SAMSUNG Electronics HVAC
1. DC 12V, 3A power provided by AC/DC adapter (input 110-240VAC
50/60Hz, provided with the BACnet® gateway)
2. LAN connection for BMS, web browser, SNET3 software connection
3. Communication connection: ON/OFF Controller(s) (MCM-A202DN)
4. 16 AWG X 2 shielded cable between SAMSUNG equipment and controls
is necessary for proper operation
5. Maximum number of RS485 connections to 1 BACnet® gateway:
a.
75 ON/OFF Controllers (MCM-A202DN)
b.
80 DVM S Series Systems (AM***F**A**/AA and
AM0**FXMDCH/AA) connected direct (5 ports, 16 systems
per port)
c.
Maximum 128 indoor units (air handler and/or SAMSUNG
ERV)
6. Upper level device connections: S-NET 3, BMS system (BACnet® IP),
web client
7. MIM-B17N shall provide functions to monitor and control status of
SAMSUNG DVM S Series systems (AM***FX****/AA and
AM0**FXMDCH/AA).
8. MIM-B17N shall support provide functions to monitor and control status
of SAMSUNG DVM Plus II, SAMSUNG DVM Plus III, Mini DVM, Free
Joint Multi, and CAC (CH070/105/140CAV, DH105/140CAV single zone
systems) with installation of communication converter interface module
per system (MIM-N01).
D. Dimensions:
1. The BACnet® gateway shall be approximately 9.4” x 10” x 2.6” in size
with stainless steel front and LCD displays.
VRF BACnet® Gateway
Input Variables (Control)
Output Variables(Monitor)
On/Off control
On/Off state
In/out contact state
Operation mode
Operation mode
Emergency Stop
Temperature setting
Set/Room temperature
Error code
Fan speed/direction
Fan speed/direction
Indoor unit run time
ERV operation mode
ERV operation mode
DO/DI Status
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
57
SAMSUNG Electronics HVAC
VRF BACnet® Gateway
Input Variables (Control)
Output Variables(Monitor)
ERV fan speed
ERV fan speed
Filter alarm reset
Filter alarm
User control restriction
User control restriction
Operation mode lock
Thermo Off/On
Set temperature limit
Power distribution
Emergency stop
Operation mode lock
Output contact control
Set temperature limit
DO ON/OFF
Human Sensor (select units)
5.15
SPI setting
CENTRAL TOUCHSCREEN SYSTEM CONRTOLLER
A.
Function:
1. The central touchscreen controller is only compatible with Samsung
DVM S systems.
2. The central touchscreen controller shall provide control and monitoring
via 7” touchscreen interface.
3. The central touchscreen controller shall provide Individual/Group control
of up to 128 indoor units (16 systems maximum) including SAMSUNG
DVM S ERV’s and air handlers.
4. The central touchscreen controller shall allow control and monitoring of
indoor unit: operation mode, set temperature, room temperature, fan
speed, louver position, remote control restriction, and power.
5. The central touchscreen controller shall 2 X DI (digital input) terminals
to allow quick disable of equipment with a 0 volt contact
6. The central touchscreen controller shall have 1 X DO (digital output) that
will provide 12V DC output interlocked with indoor unit operation
(ON/OFF).
7. The central touchscreen controller shall have an SD card slot for data
backup and future firmware updates.
8. The central touchscreen controller shall provide scheduling capability.
Scheduling shall control of indoor unit: operation mode, set temperature,
fan speed, louver position, remote control restriction, and power.
9. The central touchscreen controller shall have an all ON/OFF button
10. The central touchscreen controller shall allow creation of zones and
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
58
SAMSUNG Electronics HVAC
grouping of indoor units regardless of connected refrigerant system.
11. The central touchscreen controller shall allow grouping of multiple indoor
units to display as a single unit on user interface.
12. The central touchscreen controller shall have customizable group and
zone icons on main interface to allow easy operation for user.
13. The central touchscreen controller shall allow restriction of ON/OFF,
mode, set temperature, fan speed, and remote control use for daily (nonmanagement) touchscreen controller users.
14. The central touchscreen controller shall have menu lock capability
allowing restriction of indoor unit control, schedule setting/changing, and
touchscreen controller settings by daily (non-management) touchscreen
controller users.
15. The central touchscreen controller shall allow screen lock to prevent
unwanted changes by unauthorized users.
16. The central touchscreen controller shall have an LED indicator light on
front of device to display operation and error status.
B.
Connection:
1. The central touchscreen controller shall be powered by 100~240 VAC,
50/60 Hz.
2. The central touchscreen controller can connect to a single DVM S
system via 2 X 16 AWG shielded cable on main system communication
terminals (F1/F2). Connection on F1/F2 will allow control and monitoring
of a single system.
3. The central touchscreen controller can connect to multiple DVM S
systems via 2 X 16 AWG shielded cable on central control connections
(R1/R2).
Maximum 16 system can be daisy chained on this
communication line.
4. Multiple touchscreen controllers can be connected to a single central
control connection (R1/R2, maximum 16) when used with MIM-D00AN,
MIM-B16N, and MIM-B17N.
C.
Dimensions:
1. The central touchscreen controller shall be 8” x 6 5/16” x 1 1/2” (WxHxD).
5.16
ELECTRICITY METER INTERFACE MODULE (MIM-B16)
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
59
SAMSUNG Electronics HVAC
A.
Function:
1. Pulse Input Module (PIM) for SAMSUNG DVM Plus and SAMSUNG
DVM S Series heat pump and heat recovery systems
2. The electricity meter interface module shall support up to 8-channel,
real-time watt-hour consumption display
3. The electricity meter interface module shall support automatic watt-hour
meter tracking and current communication state indication
4. The electricity meter interface module shall communicate to the
following SAMSUNG controllers/gateways: DMS 2 (MIM-D00A), DMS
2.0 (MIM-D00AN), BACnet gateway (MIM-B17 / MIM-B17N), LonWorks
Gateway (MIM-B18 / MIM-B18N) to monitor/record energy consumption.
B.
5.17
Connection:
1.
Energy consumptions data shall be viewed via the following
SAMSUNG controllers/gateways: DMS 2 (MIM-D00A), DMS 2.0
(MIM-D00AN), BACnet gateway (MIM-B17 / MIM-B17N), LonWorks
Gateway (MIM-B18 / MIM-B18N), SNET 3 Software (MST-P3P)
2.
The electricity meter interface module shall support up to 8 watt-hour
meters with pulse output.
3.
DC 12V, 3A power provided by AC/DC adapter (input 110-240VAC
50/60Hz, provided with electricity meter interface module)
COMMUNICATION INTERFACE MODULE (MIM-N01)
A.
B.
Function:
1.
Communication device that interfaces DVM S indoor and outdoor
units with DVM Plus III central control systems (MCM-A202D, MIMD00A, MIM-B17, MIM-B18, MCM-A300N).
2.
Communication device that interfaces DVM Plus III indoor and
outdoor units with DVM S central control systems (MCM-A202DN,
MIM-D00AN, MIM-B17N, MIM-B18N, MCM-A300N).
3.
Communication device that interfaces Samsung single zone and
multi-split systems: CH***CAV, DH***CAV, MH0**FXCA*A (FJM),
AR**HSFSHWK (Whisper), and AQN**VFUAGM (Max) systems with
DVM S central control systems (MCM-A202DN, MIM-D00AN, MIMB17N, MIM-B18N, MCM-A300N).
Connection:
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
60
SAMSUNG Electronics HVAC
1.
DC 12V
2.
RS485 communication (F1/F2) to outdoor unit with supplied
connection wire.
3.
RS485 communication (R1/R2) to DVM Plus III / DVM S central
control system(s).
4.
Mounts in MAIN outdoor unit (single zone, wall mounted units may
require installation at indoor unit with included enclosure).
5.
1 X MIM-N01 for each system (1-3 outdoor modules).
5.16. MODE SELECTOR SWITCH FOR HEAT PUMP SYSTEMS (MCM-C200)
A. Function:
1.
The mode selector switch shall connect to SAMSUNG DVM S
outdoor unit models AM***FX***H/AA to easily switch operation
mode of the connected system
2.
The mode selector switch shall allow for mode change options: Cool,
Heat, and Auto.
B. Connection:
1.
The mode selector switch shall include a connection harness that
connects to MAIN outdoor unit PCB.
2.
The mode selector switch shall install in MAIN outdoor unit as
standard. The connection harness can be extended up to 328’
3.
The mode selector switch shall only connect to and control one
system.
5.17. MOTION DETECTOR (MCR-SMA)
A. Function:
1.
The motion detector shall connect to SAMSUNG DVM S Mini 4-Way
cassette models AM0**FNNDCH/AA.
2.
The motion detector shall monitor occupancy and turn off indoor unit after
motion is not sensed for the specified duration (30, 60, 120, and 180
minutes).
3.
The motion detector shall monitor occupancy and adjust target evaporator
temperature after motion is not sensed for the specified duration (30, 60,
120, and 180 minutes) thus lowering capacity of unit to reduce energy use.
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.
61
SAMSUNG Electronics HVAC
B. Connection:
1.
The motion detector shall install in the corner of the mini 4-way cassette
fascia panel.
2.
The motion detector shall connect to the indoor unit PCB with provided
cable.
DRAFT: 07/29/2014
www.SamsungDVM-S.com
Specifications are subject to change without notice.