SAMSUNG Electronics HVAC HVAC Guide Specifications Variable Refrigerant Flow Mini VRF Heat Pump Models with Multiple Indoor Units Size Range: 3 TO 5 TONS NOMINAL SAMSUNG Electronics Mini DVM S Eco 208/230 VAC Model Numbers: AM036FXMDCH/AA AM048FXMDCH/AA AM053FXMDCH/AA Part 1 – General 1.1 SYSTEM DESCRIPTION A. The variable capacity, heat pump air conditioning system shall be a SAMSUNG Electronics MINI DVM S ECO (Variable Refrigerant Flow) System. B. The heat pump system shall consist of an AM0**FXMDCH/AA outdoor unit, multiple indoor units (AM****N*DCH/AA models), and SAMSUNG DVM S NASA Control Network Solution (Control systems). The AM0**FXMDCH/AA outdoor unit shall be a horizontal discharge, 208/230 volt, single phase unit. The AM0**FXMDCH/AA outdoor system model numbers and the associated number of connectable indoor units per AM0**FXMDCH/AA outdoor unit is indicated in the following table. Each indoor unit or group of indoor units shall be independently controlled. Model Number AM036FXMDCH/AA AM048FXMDCH/AA AM053FXMDCH/AA 1.2. 1-6 1-8 1-9 PIPING A. 1.3 Connectable Number of Indoor Units Piping to multiple indoor units requires additional piping components. SAMSUNG Y-joint fittings and/or SAMSUNG HP 4 or 8 port header fittings must be used to branch the main refrigerant lines. QUALITY ASSURANCE A. The units shall be listed by Electrical Laboratories (ETL) and bear the ETL label. DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 1 SAMSUNG Electronics HVAC B. All wiring shall be in accordance with the National Electrical Code (N.E.C.). C. The units shall be manufactured in a facility registered to ISO 9001 and ISO14001 which is a set of standards applying to environmental protection set by the International Standard Organization (ISO). D. A full charge of R-410A for the condensing unit only shall be provided in the condensing unit. Additional refrigerant is required based on diameters and lengths of system liquid refrigerant lines. Part 2 – Warranty 2.01 WARRANTY Applicable Only for SAMSUNG “DVM-S” and “DVM-S ECO” Systems Distributed From January 1, 2014 1. LIMITED WARRANTY – QUIETSIDE CORPORATION (“QUIETSIDE”) warrants to the original end-user (“you”) of SAMSUNG “DVM-S” or “DVM-S ECO” Air-Conditioner and Heat Pump System (“Product”) that, if purchased from and installed by a contractor licensed for HVAC installation under applicable local and state laws within the continental United States, Alaska, Hawaii and Canada, and if it proves defective by reason of defects arising from improper workmanship and/or material: (a) FIVE YEARS ON PARTS. The parts are warranted for a period of five (5) years to the original end-user of this Product. If it should prove defective due to improper workmanship and/or material for a period of five (5) years from the date of installation, QUIETSIDE will replace any defective part without charge for the part. Parts used for replacement may be of like kind and quality and may be new or remanufactured. Defective parts must be made available to QUIETSIDE in exchange for the replacement part and become the property of QUIETSIDE. (b) SEVEN YEAR COMPRESSOR WARRANTY. The compressor is warranted for a total period of seven (7) years to the original end-user of this Product. If it should prove defective due to improper workmanship and/or material for a period of seven (7) years from the date of installation, QUIETSIDE will replace any defective compressor without charge for the compressor. Compressors used for replacement may be of like kind and quality and may be new or remanufactured. Defective compressors must be made available to QUIETSIDE in exchange for the replacement compressor and become the property of QUIETSIDE. (c) NO LABOR. THESE LIMITED WARRANTIES DO NOT INCLUDE LABOR or any other costs incurred for service, maintenance, repair, removing, replacing, installing, complying with local building and electric codes, shipping or handling, or replacement of the Product, compressors or any other parts. For items that are designed to be maintained or replaced by the owner, the owner is solely responsible for all labor and other costs of maintaining, installing, replacing, disconnecting or dismantling the Product and parts (such as filters or belts) in connection with ownerDRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 2 SAMSUNG Electronics HVAC required maintenance. Air filter cleaning and/or replacement for each applicable indoor unit are owner-required maintenance, and labor for this procedure is not covered under warranty. (d) The warranty on the replacement compressor and replacement parts will be limited to the unexpired term of the original warranty for the Product. 2. CONDITIONS – The Limited Warranty applies only if the Product: (a) was initially installed within the continental United States, Hawaii or Canada and remains at the site of its original installation (except for mobile home installations); and (b) was installed and operated and maintained in accordance with all written instructions, all applicable local laws, regulations, permits and building codes, and good industry practices. 3. THIS LIMITED WARRANTY DOES NOT COVER damages caused by: (a) accident, abuse, negligence or misuse; (b) operating the Product in a corrosive atmosphere containing chlorine, fluorine, or any other damaging chemicals; (c) modification, alteration, repair service by any person other than an authorized Product distributor, dealer or HVAC contractor; (d) improper matching or application of the Product or components or loss of refrigerant; (e) failure to provide proper maintenance or service to the Product according to manufacturer’s instructions; (f) failure to apply, install, and operate the Product in compliance with SAMSUNG’s (or QUIETSIDE’s) written instructions, training seminars and recommendations; or (g) fluctuations in electrical power;(h) lightning, flood, fire or other acts of God. This Limited Warranty does not cover if the Product has not been paid for in full. 4. TO OBTAIN WARRANTY SERVICE: a) Contact the licensed contractor who installed the Product or the nearest licensed and authorized contractor, dealer or distributor of any defect within the applicable warranty time period. b) Proof of the installation date by a licensed contractor is required when requesting warranty service. Present the sales receipt, building permit or other document which establishes proof and date of installation. Otherwise, this Limited Warranty shall be deemed to begin one hundred twenty (120) days after the date of manufacture stamped on the System. THE RETURN OF THE OWNER REGISTRATION CARD IS NOT A CONDITION OF COVERAGE UNDER THIS LIMITED WARRANTY. However, please return the Owner Registration Card so that QUIETSIDE can contact you if a question of safety arises. c) To obtain the name of the nearest authorized QUIETSIDE HVAC distributor, dealer or contractor or additional information on warranty program, you may contact: QUIETSIDE CORPORATION 8750 PIONEER BLVD, SANTA FE SPRINGS DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 3 SAMSUNG Electronics HVAC CA 90670. Telephone: 1-562-699-6066 6. This Limited Warranty shall not be enlarged, extended or affected by, and no obligation or liability shall arise or grow out of, QUIETSIDE providing, directly or indirectly, any technical advice, information and/or service to you in connection with the Product. 7. EXCEPT AS OTHERWISE PROVIDED IN THIS LIMITED WARRANTY, QUIETSIDE MAKES NO OTHER WARRANTIES OF ANY KIND WHATSOEVER REGARDING THE PRODUCT. QUIETSIDE DISCLAIMS AND EXCLUDES ALL WARRANTIES NOT EXPRESSLY PROVIDED HEREIN AND ALL REMEDIES WHICH, BUT FOR THIS PROVISION, MIGHT ARISE BY IMPLICATION OR OPERATION OF LAW, INCLUDING, WITHOUT LIMITATION, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND OF FITNESS FOR ANY PARTICULAR PURPOSE. NO ONE IS AUTHORIZED TO CHANGE THIS LIMITED WARRANTY IN ANY RESPECT OR TO CREATE ANY OTHER OBLIGATION OR LIABILITY FOR QUIETSIDE IN CONNECTION WITH THE PRODUCT. QUIETSIDE DISCLAIMS ALL LIABILITY FOR THE ACTS, OMISSIONS AND CONDUCT OF ALL THIRD PARTIES (including, without limitation, the installing contractor) IN CONNECTION WITH OR RELATED TO THE PRODUCT. 8. UNDER NO CIRCUMSTANCES SHALL QUIETSIDE BE LIABLE FOR ANY INCIDENTAL, SPECIAL OR CONSEQUENTIAL DAMAGES INCLUDING, WITHOUT LIMITATION, LOST GOODWILL, LOST REVENUES OR PROFITS, WORK STOPPAGE, SYSTEM FAILURE, IMPAIRMENT OF OTHER GOODS, COSTS OF REMOVAL AND REINSTALLATION OF THE PRODUCT, LOSS OF USE, INJURY TO PERSONS OR PROPERTY ARISING OUT OR RELATED TO THE PRODUCT WHETHER BASED ON BREACH OF WARRANTY, BREACH OF CONTRACT, TORT OR OTHERWISE, EVEN IF QUIETSIDE HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. IN NO EVENT SHALL QUIETSIDE’S LIABILITY EXCEED THE ACTUAL PURCHASE PRICE OF THE PRODUCT WITH RESPECT TO WHICH ANY CLAIM IS MADE. 9. Some states do not allow limitations on warranties or exclusions or limitation of damages, so the above limitations or exclusions may not apply. 10. This Limited Warranty gives the owner specific legal rights and the owner may also have other rights that vary from state to state. 11. This Limited Warranty is valid only in the continental United States, Alaska, Hawaii and Canada, and it is not transferable. 12. This warranty contains the sole express warranty made by QUIETSIDE in connection with the Product. No QUIETSIDE distributor, dealer or contractor or other DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 4 SAMSUNG Electronics HVAC person is authorized to make any other warranties or representations on behalf of QUIETSIDE in connection with the Product. Part 3 – Outdoor Unit Performance 3.01 The heat pump outdoor unit shall perform as indicated below (nominal capacity): Outdoor Units Nominal Cooling Capacity Rated Cooling Capacity (Btu/h) Power Input (kW) AM036FXMDCH/AA 36,000 38,000 3.1 AM048FXMDCH/AA 48,000 48,000 4.2 AM053FXMDCH/AA 53,000 53,000 5.3 Outdoor Units Nominal Heating Capacity Rated Heating Capacity (Btu/h) Power Input (kW) AM036FXMDCH/AA 42,000 42,000 3.4 AM048FXMDCH/AA 54,000 54,000 4.4 AM053FXMDCH/AA 61,000 61,000 5.4 Part 4 – Products HEAT PUMP OUTDOOR UNIT 4.01 A. General: 1. The heat pump outdoor unit shall be specifically used with SAMSUNG DVM S Heat pump components. The SAMSUNG MINI DVM S ECO HP outdoor unit shall consist of AM0**FXMDCH/AA outdoor unit, indoor units (AM***FN*DCH/AA), and SAMSUNG DVM S NASA Control Network Solution (Control systems). AM0**FXMDCH/AA outdoor units shall be equipped with multiple circuit boards that interface to the SAMSUNG DVM S NASA Control Network Solution (Control systems) and shall perform all functions necessary for operation. The outdoor unit shall have a powder coated finish. The outdoor unit shall be completely factory assembled, piped and wired. Each unit shall be run tested at the factory. 2. The sum of connected capacity of all indoor air handlers shall range from 50% to 130% of outdoor rated capacity. DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 5 SAMSUNG Electronics HVAC 3. The heat pump system compressors shall be SAMSUNG, hermetically sealed, inverter driven, Twin BLDC Rotary type. No fixed capacity compressors shall be present in the refrigerant system. 4. The outdoor unit shall have a sound rating no higher than listed in the table below. Outdoor Unit Model Maximum dB(A) AM036FXMDCH/AA 50 AM048FXMDCH/AA 51 AM053FXMDCH/AA 53 5. Both refrigerant lines from the outdoor unit shall be insulated. 6. The heat pump outdoor unit shall have an accumulator 7. The heat pump outdoor unit shall have a high pressure safety switch, over-current protection, thermal fan protection, low pressure protection, compressor overcurrent protection, fan motor voltage protection, current transformer(s), crank case heaters, and intelligent logic to ensure proper operation within unit design limitations and operational parameters. 8. The heat pump outdoor unit shall have the ability to operate with a maximum height difference of 163 feet with the condensing unit installed higher than the indoor units or 131 feet with the condensers installed lower than the indoor units. The greatest length is not to exceed 492 (574 equivalent) feet between outdoor unit and the farthest indoor unit. 9. The heat pump outdoor unit shall be capable of operating in cooling mode between 23°F ~ 120°F outside ambient temperatures. 10. The heat pump outdoor unit shall be capable of operating in heating between -4F ~ 75F ambient temperatures. 11. The heat pump system shall have installer enabled snow blowing settings to prevent snow accumulation in front of idle outdoor units during when below 35º F. 12. The heat pump shall have the ability to adjust cooling and heating temperature/pressure compensation values depending on project conditions thus saving energy. DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 6 SAMSUNG Electronics HVAC 13. The heat pump outdoor unit shall have a high efficiency oil separator plus additional logic controls to ensure adequate oil volume in the compressor is maintained. 14. The heat pump outdoor unit shall have a flat plate type sub-cooler to sub cool liquid refrigerant further to increase capacity and performance with long pipe lengths and to decrease refrigerant sounds at indoor equipment. 15. The heat pump system shall have optional night quite modes to reduce unit sound in evenings. 16. The heat pump system shall have current control to limit current adjustable at outdoor unit. Maximum current limitation shall 3 levels of current limitation from design current. 17. The heat pump outdoor unit shall have a removable EEPROM at the main PCB to store all unit data. All data on the outdoor unit EEPROM shall be viewable from the manufacturer provided service software. The outdoor unit main EEPROM shall be removable allowing replacement of outdoor unit PCB without losing digital, field programmed data. The outdoor unit removable EEPROM shall store the following unit data: unit model number, unit serial number, unit main PCB firmware and MICOM version, sub-PCB firmware and MICOM version, fan PCB firmware and MICOM version, inverter PCB 1 and inverter PCB 2 firmware and MICOM version, auto-trial commissioning startup data, the last 30 minutes of operation data, and field programmed unit name/tag viewable on controls and service software. 18. The heat pump outdoor unit shall have outdoor unit pump-down operation capability allowing storage of refrigerant while opening sealed refrigerant pipe system outside of outdoor unit chassis while performing service. The outdoor unit refrigerant storage shall be greater than the supplied factory R-410A charge. 19. The heat pump outdoor unit shall have individual outdoor module pump-out operation capability allowing the majority of refrigerant in an outdoor unit to be pumped out. The pump-out feature shall allow service of sealed refrigerant system within an outdoor unit chassis. 20. In the event of system error due to outdoor unit failure, the heat pump outdoor unit shall display codes that specify a precise error and which outdoor unit PCB is the cause. 21. The heat pump outdoor unit shall have adjustable defrost operation characteristics (4 total options) adjustable at the outdoor PCB. DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 7 SAMSUNG Electronics HVAC B. Unit Cabinet: 1. C. The chassis shall be fabricated of galvanized steel, bonderized and finished with a powder coated baked enamel. Fan: 1. The heat pump outdoor unit shall be furnished with 2 axial fans with BLDC motors. 2. General: a. All fan motors shall have inherent protection, thermal protection, and have permanently lubricated bearings, and be completely variable speed. b. All fan motors shall be mounted for quiet operation. c. All fans shall be provided with a raised guard to prevent contact with moving parts. d. The outdoor unit shall have horizontal discharge airflow. D. Refrigerant: E. a. R410A refrigerant shall be required for the heat pump system. b. Additional refrigerant is required. Amount is based on installed refrigerant pipe diameters and lengths. Coil: a. The outdoor coil shall be of nonferrous construction with lanced or corrugated plate fins on copper tubing. b. The coil shall be protected with an integral metal guard. c. Refrigerant flow from the outdoor unit shall be controlled by means of capacity modulation capable Twin BLDC Rotary compressor. F. Compressor: 1. The 208/230 VAC heat pump systems shall have the compressor quantity noted in the table below. All compressors shall be modulation capable, DC inverter, Twin BLDC Rotary type. DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 8 SAMSUNG Electronics HVAC 208/230 VAC Nominal System Capacity (btu/h) Compressor Quantity 36,000 48,000 53,000 1 1 1 2. General: a. Crankcase heaters shall be factory mounted on the compressor. b. The outdoor unit compressor shall have a variable modulation technology to modulate capacity. c. The compressor will be equipped with an internal thermal overload. d. The compressor shall be mounted to avoid the transmission of vibration. G. Electrical: a. The outdoor unit electrical power shall be 208/230 volts, 1 phase, 60 hertz. b. The 208/230 VAC unit shall be capable of satisfactory operation within voltage limitations of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). c. The outdoor unit shall be controlled by integral microprocessors. d. The control circuit between the indoor units and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, 16 AWG, shielded, two-core cable to provide total integration of the system. 4.02 ELECTRONIC EXPANSION VALVE KITS (MULTI ZONE) FOR HEAT PUMP OUTDOOR UNITS (MXD) A. General: 1. DRAFT: 07/29/2014 The MXD EEV Kit shall allow a liquid and suction pipe from the condenser to connect and meter refrigerant to 2 or 3 wall (AM0**FNTDCH/AA) or under-ceiling units (AM0**FNCDCH/AA). The MXD units shall be equipped with a circuit board that interfaces to the SAMSUNG DVM S NASA Control Network Solution (Control www.SamsungDVM-S.com Specifications are subject to change without notice. 9 SAMSUNG Electronics HVAC systems) and shall perform all functions necessary for operation. The unit shall have a galvanized steel finish. The MXD EEV kit shall be completely factory assembled, piped and wired. Each unit shall be run tested at the factory. This unit shall be mounted indoors. Only compatible with DVM S heat pump systems (AM****XVA*H/AA and AM0**FXMDCH/AA). The length of pipe between an MXD EEV kit and a single indoor unit cannot exceed 65 actual feet. The MXD EEV kit selection is based on the quantity of units and capacity of each according to the table below. B. C. MXD-E24K132A 2 MXD-E24K200A 2 2 X ≤ 12,000 MXD-E32K200A 2 2 X 18,000 – 24,000 MXD-E24K232A 3 MXD-E24K300A 3 MXD-E32K224A 3 MXD-E32K300A 3 Connectable Capacity (Btu/h) 1 X ≤ 12,000, 1 x 18,000 – 24,000 2 X ≤ 12,000, 1 X 18,000 – 24,000 3 X ≤ 12,000 1 X ≤ 12,000, 2 X 18,000 – 24,000 3 X 18,000 – 24,000 1. The chassis shall be fabricated of galvanized steel. 2. Each cabinet shall house 2 or 3 (depending on model) electronic expansion valves and a common suction connection. Refrigerant: R410A refrigerant shall be required for MXD EEV kits in conjunction with R410A, heat pump unit systems. Integral Drain Pan: 1. E. Number of Connectable Indoor Units MXD EEV Kit Cabinet: 1. D. EEV Kit Model Number An integral condensate pan and drain shall be provided. Drain termination is required upon installation with an appropriate termination. Electrical: 1. DRAFT: 07/29/2014 The unit electrical power shall be 208/230 volts, 1 phase, 60 hertz. www.SamsungDVM-S.com Specifications are subject to change without notice. 10 SAMSUNG Electronics HVAC 2. The unit shall be capable of satisfactory operation within voltage limits of 187-228 volts (208V/60Hz) or 207-253V (230V/60Hz). 3. The MXD EEV kit shall be controlled by integral microprocessors. 4. The control circuit between the indoor units, EEV kit and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two conductor, 16 AWG, shielded cable to provide total integration of the system. Operation is based on communication on this main communication cable. 4.03 ELECTRONIC EXPANSION VALVE KIT (SINGLE ZONE) FOR HEAT PUMP AND HEAT RECOVERY OUTDOOR UNITS A. General: 1. B. MEV-A24SA ≤ 12,000 MEV-A32SA 18,000 – 24,000 The chassis shall be fabricated of galvanized steel and HIPS certified to UL94 V0. For R410A systems only. Electrical: 1. 4.04 Connectable Capacity (Btu/h) Refrigerant: 1. D. EEV Kit Model Number Cabinet: 1. C. The MEV-A**SA device is a single zone electronic expansion valve for Samsung DVM wall-mounted units (AM0***NTDCH/AA) and under-ceiling units (AM0***NCDCH/AA). Compatible with DVM S heat pump systems (AM****XVA*H/AA, AM0**FXMDCH/AA) and DVM S Heat Recovery Systems. The MEV-A**SA EEV installs inline on the liquid line for a single unit. It must be located nearby the unit, within 7 feet (of pipe) between the MEV-A**SA and the connected indoor unit. The appropriate expansion valve should be selected based on the capacity of the connected unit per the table below. The single zone EEV is powered and controlled directly from the indoor unit that it is metering refrigerant to via included wire harness. WALL-MOUNTED INDOOR UNIT (AM0**FNTDCH/AA) DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 11 SAMSUNG Electronics HVAC A. B. General: 1. The wall-mounted indoor unit section shall have a slim silhouette and must be installed with an external modulating linear expansion valve (MEV-A**SA) or two/three room EEV (Electronic Expansion Valve) kits. The wall-mounted indoor unit shall be compatible with DVM S HR (Heat Recovery) outdoor units and MCU (Mode Change Unit, MCU-S*NEE1N) or DVM S HP (Heat Pump) outdoor unis. The wallmounted indoor unit shall support individual control using SAMSUNG DVM S NASA Control Network Solution (Control systems). Indoor model numbers shall be: AM007FNTDCH/AA, AM009FNTDCH/AA, AM012FNTDCH/AA, AM018FNTDCH/AA, AM020FNTDCH /AA, AM024FNTDCH/AA. 2. Each system shall perform in accordance to the ratings shown in the table below. Performance shall be based on nominal cooling conditions of 80F DB, 67F WB for the indoor unit and 95F DB for the outdoor unit and nominal heating conditions of 70F DB for the indoor unit and 47F DB, 43F WB for the outdoor unit. Btu/h Cooling* BTU/h Heating* AM007FNTDCH/AA 7,500 8,500 AM009FNTDCH/AA 9,500 10,500 AM012FNTDCH/AA 12,000 13,500 AM018FNTDCH/AA 18,000 20,000 AM020FNTDCH/AA 20,000 23,000 AM024FNTDCH/AA *Nominal capacity 24,000 24,000 Indoor Unit: 1. C. System Model Number The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, control circuit board and fan motor. An optional electronic modulating linear expansion valves is available for accessories. The unit shall have a self-diagnostic function, 3-minute time delay mechanism, an auto restart function. Indoor unit and refrigerant pipes shall be charged with dehydrated air (Nitrogen gas) before shipment from the factory. Unit Cabinet: 1. DRAFT: 07/29/2014 The casing shall have a gloss white finish, HIPS chassis certified to UL94 V0. www.SamsungDVM-S.com Specifications are subject to change without notice. 12 SAMSUNG Electronics HVAC D. E. F. 2. Multi directional drain and refrigerant piping offering four (4) directions for refrigerant piping and four (4) directions for draining shall be standard. 3. There shall be a separate galvanized steel mounting plate which secures the unit firmly to the wall. Fan: 1. The indoor fan assembly shall be a cross-flow fan direct driven by a single motor. 2. The indoor fan shall be statically and dynamically balanced to run on a motor with permanently lubricated bearings. 3. A manual adjustable guide vane shall be provided with the ability to change the airflow from side to side (left to right). 4. A motorized air sweep louver shall provide an automatic change in airflow by directing the air up and down to provide uniform air distribution. 5. The indoor fan shall consist of various speeds, as indicated in below table. Model Number Fan Speed Setting AM007FNTDCH/AA AM009FNTDCH/AA AM012FNTDCH/AA AM018FNTDCH/AA AM020FNTDCH/AA AM024FNTDCH/AA (UL) – Low – Mid – High Filter: 1. Return air shall be filtered by means of an easily removable, washable filter (2). 2. Supplemental antibacterial and anti-odor filters shall be included. Coil: 1. The indoor coil shall be of nonferrous construction with slit fins on copper tubing. 2. The tubing shall have inner grooves for high efficiency heat exchange. DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 13 SAMSUNG Electronics HVAC G. H. 4.05 3. All tube joints shall be brazed with phos-copper or silver alloy. 4. The coils shall be pressure tested at the factory. 5. A condensate pan and drain shall be provided under the coil. 6. The coil fins are coated with hydrophilic paints. 7. Both refrigerant lines to the wall-mounted indoor unit shall be insulated. Electrical: 1. The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz. 2. The system shall be capable of satisfactory operation within voltage limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). 3. The control circuit between the indoor units, MCU (Mode Change Unit) and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system. 4. The indoor unit shall have a thermal fuse under high-voltage terminal block to disable unit in the event of overheating due to electrical malfunction/poor connection. Controls: 1. This unit shall use controls provided by SAMSUNG Electronics to perform functions necessary to operate the system. Please refer to Part 5 of this guide specification for details on controllers and other control options. 2. The indoor unit shall have a removable EEPROM on its PCB to store all unit data. All data on the indoor unit EEPROM shall be viewable from the manufacturer provided service software. The indoor unit main EEPROM shall be removable allowing replacement of indoor unit PCB without losing digital, field programmed data. The indoor unit removable EEPROM shall store the following unit data: unit model number, unit serial number, unit PCB firmware and MICOM version, and field programmed unit name/tag viewable on controls and service software. UNDER CEILING/WALL INDOOR UNIT (AM0**FNCDCH/AA) A. General: DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 14 SAMSUNG Electronics HVAC B. 1. The under-ceiling/wall indoor unit shall be installed under ceiling or on wall (near floor). The under-ceiling/wall indoor unit shall be compatible with DVM S HR (Heat Recovery) outdoor units and MCU (Mode Change Unit) or DVM S HP (Heat Pump) outdoor units. The under-ceiling/wall indoor unit shall support individual control using SAMSUNG DVM S NASA Control Network Solution (Control systems). Indoor model numbers shall be: AM018FNCDCH/AA and AM024FNCDCH/AA. 2. Each system shall perform in accordance to the ratings shown in the table below. Performance shall be based on nominal cooling conditions of 80F DB, 67F WB for the indoor unit and 95F DB for the outdoor unit and nominal heating conditions of 70F DB for the indoor unit and 47F DB, 43F WB for the outdoor unit. D. BTU/h Cooling* BTU/h Heating* AM018FNCDCH/AA 18,000 20,000 AM024FNCDCH/AA *Nominal capacity 24,000 27,000 Indoor Unit: 1. C. System Model Number The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, electronic modulating linear expansion device, control circuit board and fan motor. The unit shall have a self-diagnostic function, 3-minute time delay mechanism, an auto restart function. The unit shall have a single auto-swing louver. Indoor unit and refrigerant pipes shall be charged with dehydrated air (Nitrogen gas) before shipment from the factory. Gravity drain as standard. Unit Cabinet: 1. The cabinet shall be space-saving, under-ceiling type that can also be installed on a wall (near floor). 2. The casing shall be HIPS certified to UL94 V0. 3. The casing shall have a white finish. 4. There shall be separate galvanized steel mounting hangers that will secure the unit firmly to wall (wall-mounted applications only). Fan: DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 15 SAMSUNG Electronics HVAC E. 1. The indoor fan assembly shall be a Sirocco fan (2) direct driven by a single motor. 2. The indoor fan shall be statically and dynamically balanced to run on a motor with permanently lubricated bearings. 3. The indoor fan shall consist of three (3) speeds, Low, Mid, and High. 4. The auto air swing louver shall be capable of automatically swinging up and down for uniform air distribution. Filter: 1. F. G. Return air shall be filtered by means of a long-life washable permanent filter (2). Coil: 1. The indoor coil shall be of nonferrous construction with slit fins on copper tubing. 2. The tubing shall have inner grooves for high efficiency heat exchange. 3. All tube joints shall be brazed with phos-copper or silver alloy. 4. The coils shall be pressure tested at the factory. 5. A condensate pan and drain outlet shall be provided under the coil (gravity drain). 6. The coil fins are coated with hydrophilic paints. 7. Both refrigerant lines to the under-ceiling/wall indoor unit indoor units shall be insulated. Electrical: 1. The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz. 2. The system shall be capable of satisfactory operation within voltage limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). 3. The control circuit between the indoor units, MCU (Mode Change Unit) and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 16 SAMSUNG Electronics HVAC 4. H. 4.06 The indoor unit shall have a thermal fuse under high-voltage terminal block to disable unit in the event of overheating due to electrical malfunction/poor connection. Controls: 1. This unit shall use controls provided by SAMSUNG Electronics to perform functions necessary to operate the system. Please refer to Part 5 of this guide specification for details on controllers and other control options. 2. The indoor unit shall have a removable EEPROM on its PCB to store all unit data. All data on the indoor unit EEPROM shall be viewable from the manufacturer provided service software. The indoor unit main EEPROM shall be removable allowing replacement of indoor unit PCB without losing digital, field programmed data. The indoor unit removable EEPROM shall store the following unit data: unit model number, unit serial number, unit PCB firmware and MICOM version, and field programmed unit name/tag viewable on controls and service software. 4-WAY CEILING CASSETTE WITH GRILLE INDOOR UNIT (AM0**FN4DCH/AA) A. General: 1. The 4-way cassette shall be style indoor unit shall recess into the ceiling with a ceiling grille (ordered separately, part number: PC4NUSKFN) and shall have a modulating linear expansion device. The 4-way cassette shall be compatible with DVM S HR (Heat Recovery) outdoor units and MCU (Mode Change Unit) or DVM S HP (Heat Pump) outdoor units. The 4-way cassette shall support individual control using SAMSUNG DVM S NASA Control Network Solution (Control systems). Indoor model numbers shall be: AM009FN4DCH/AA, AM012FN4DCH/AA, AM018FN4DCH/AA, AM024FN4DCH/AA, AM030FN4DCH/AA, AM036FN4DCH/AA, AM048FN4DCH/AA. 2. Each system shall perform in accordance to the ratings shown in the table below. Performance shall be based on nominal cooling conditions of 80F DB, 67F WB for the indoor unit and 95F DB for the outdoor unit and nominal heating conditions of 70F DB for the indoor unit and 47F DB, 43F WB for the outdoor unit. DRAFT: 07/29/2014 System Model Number BTU/h Cooling* BTU/h Heating* AM009FN4DCH/AA 9,000 10,000 www.SamsungDVM-S.com Specifications are subject to change without notice. 17 SAMSUNG Electronics HVAC B. D. BTU/h Cooling* BTU/h Heating* AM012FN4DCH/AA 12,000 13,500 AM018FN4DCH/AA 18,000 20,000 AM024FN4DCH/AA 24,000 27,000 AM030FN4DCH/AA 30,000 34,000 AM036FN4DCH/AA 36,000 40,000 AM048FN4DCH/AA *Nominal Capacity 48,000 54,000 Indoor Unit: 1. C. System Model Number The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, electronic modulating linear expansion device, control circuit board and fan motor. The unit shall have a self-diagnostic function, 3-minute time delay mechanism, an auto restart function. Indoor unit and refrigerant pipes shall be charged with dehydrated air (Nitrogen gas) before shipment from the factory. Unit Cabinet: 1. The cabinet shall be space-saving ceiling-recessed cassette. 2. Construction shall be HIPS chassis and fascia panel certified to UL94 V0. 3. Each corner portion of the panel cabinet is detachable, which gives easy access to adjust the height. 4. The cabinet shall have provisions for a field installed, filtered, outside air intake. A booster fan is necessary. A 12V DC relay terminal is available to control a booster fan (with separate PCB connector). 5. Branch ducting shall be allowed from cabinet, available on 2 sides to condition an adjacent space. Fan: 1. The indoor fan assembly shall be a turbo fan direct driven by a single motor. 2. The indoor fan shall be statically and dynamically balanced to run on a motor with permanently lubricated bearings. 3. The indoor fan shall consist of three (3) speeds, Low, Mid, and High. DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 18 SAMSUNG Electronics HVAC E. 4. The auto swing air outlet vanes (4) shall be capable of automatically swinging up and down for uniform air distribution. 5. The supply air vanes shall have independent control capability (32° – 65° control range) adjustable with optional wireless or wired controllers. Filter: 1. F. G. Return air shall be filtered by means of a long-life washable permanent filter included with fascia panel. Coil: 1. The indoor coil shall be of nonferrous construction with slit fins on copper tubing. 2. The tubing shall have inner grooves for high efficiency heat exchange. 3. All tube joints shall be brazed with phos-copper or silver alloy. 4. The coils shall be pressure tested at the factory. 5. A condensate pan and drain shall be provided under the coil. 6. The coil fins are coated with hydrophilic paints. 7. The condensate lift mechanism shall be able to raise drain water 29 inches above the condensate pan with built in check valve and float switch. 8. Both refrigerant lines to the 4-way cassette indoor units shall be insulated. Electrical: 1. The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz. 2. The system shall be capable of satisfactory operation within voltage limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). 3. The control circuit between the indoor units, MCU (Mode Change Uni) and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 19 SAMSUNG Electronics HVAC 4. H. 4.07 The indoor unit shall have a thermal fuse under high-voltage terminal block to disable unit in the event of overheating due to electrical malfunction/poor connection. Controls: 1. This unit shall use controls provided by SAMSUNG Electronics to perform functions necessary to operate the system. Please refer to Part 5 of this guide specification for details on controllers and other control options. 2. The indoor unit shall have a removable EEPROM on its PCB to store all unit data. All data on the indoor unit EEPROM shall be viewable from the manufacturer provided service software. The indoor unit main EEPROM shall be removable allowing replacement of indoor unit PCB without losing digital, field programmed data. The indoor unit removable EEPROM shall store the following unit data: unit model number, unit serial number, unit PCB firmware and MICOM version, and field programmed unit name/tag viewable on controls and service software. MINI 4-WAY CEILING (AM0**FNNDCH/AA) A. CASSETTE WITH GRILLE INDOOR UNIT General: 1. The indoor unit shall be a mini four-way cassette style indoor unit that recesses into the ceiling with a ceiling grille (part number: PC4USUMAN, ordered separately) and shall have a modulating linear expansion device. The mini four-way cassette shall be compatible with DVM S HR (Heat Recovery) outdoor units and MCU (Mode Change Unit) or DVM S HP (Heat Pump) outdoor units. The mini four-way cassette shall support individual control using SAMSUNG DVM S NASA Control Network Solution (Control systems). Indoor model numbers shall be: AM009FNNDCH/AA, AM012FNNDCH/AA, AM018FNNDCH/AA, AM020FNNDCH/AA. 2. Each system shall perform in accordance to the ratings shown in the table below. Performance shall be based on nominal cooling conditions of 80F DB, 67F WB for the indoor unit and 95F DB for the outdoor unit and nominal heating conditions of 70F DB for the indoor unit and 47F DB, 43F WB for the outdoor unit. DRAFT: 07/29/2014 System Model Number BTU/h Cooling* BTU/h Heating* AM009FNNDCH/AA 9,500 10,500 www.SamsungDVM-S.com Specifications are subject to change without notice. 20 SAMSUNG Electronics HVAC System Model Number BTU/h Cooling* BTU/h Heating* AM012FNNDCH/AA 12,000 13,500 AM018FNNDCH/AA 18,000 20,000 AM020FNNDCH/AA 20,000 23,000 *Nominal Capacity B. Indoor Unit: 1. C. D. The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, electronic modulating linear expansion device, control circuit board and fan motor. The unit shall have a self-diagnostic function, 3-minute time delay mechanism, an auto restart function. Indoor unit and refrigerant pipes shall be charged with dehydrated air (Nitrogen gas) before shipment from the factory. Unit Cabinet: 1. The cabinet shall be space-saving ceiling-recessed cassette. 2. Construction shall be insulated HIPS chassis and fascia panel certified to UL94 V0. 3. The cabinet panel shall have provisions for a field installed, filtered, outside air intake. A booster fan is necessary. A 12V DC relay terminal is available to control the booster fan (with separate PCB connector). 4. The compact cabinet size can be installed in one standard ceiling tile (24” x 24”). Fan: 1. The indoor fan assembly shall be a turbo fan direct driven by a single motor. 2. The indoor fan shall be statically and dynamically balanced to run on a motor with permanently lubricated bearings. 3. The indoor fan shall consist of three (3) speeds, Low, Mid, and High. 4. The auto air swing vanes (4) shall be capable of automatically swinging up and down for uniform air distribution. DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 21 SAMSUNG Electronics HVAC E. Filter: 1. F. G. H. Return air shall be filtered by means of a long-life washable permanent filter included with fascia panel. Coil: 1. The indoor coil shall be of nonferrous construction with slit fins on copper tubing. 2. The tubing shall have inner grooves for high efficiency heat exchange. 3. All tube joints shall be brazed with phos-copper or silver alloy. 4. The coils shall be pressure tested at the factory. 5. A condensate pan and drain outlet shall be provided under the coil. 6. The coil fins are coated with hydrophilic paints. 7. The condensate lift mechanism shall be able to raise drain water 29 inches above the condensate pan with float switch. 8. Both refrigerant lines to the mini four-way cassette indoor units shall be insulated. Electrical: 1. The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz. 2. The system shall be capable of satisfactory operation within voltage limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). 3. The control circuit between the indoor units, MCU (Mode Change Unit) and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system 4. The indoor unit shall have a thermal fuse under high-voltage terminal block to disable unit in the event of overheating due to electrical malfunction/poor connection. Controls: 1. DRAFT: 07/29/2014 This unit shall use controls provided by SAMSUNG Electronics to perform functions necessary to operate the system. Please refer to Part 5 of this guide specification for details on controllers and other control options. www.SamsungDVM-S.com Specifications are subject to change without notice. 22 SAMSUNG Electronics HVAC 2. 4.08 The indoor unit shall have a removable EEPROM on its PCB to store all unit data. All data on the indoor unit EEPROM shall be viewable from the manufacturer provided service software. The indoor unit main EEPROM shall be removable allowing replacement of indoor unit PCB without losing digital, field programmed data. The indoor unit removable EEPROM shall store the following unit data: unit model number, unit serial number, unit PCB firmware and MICOM version, and field programmed unit name/tag viewable on controls and service software. SLIM 1-WAY, CEILING CASSETTE WITH GRILLE, INDOOR UNIT A. General: 1. The indoor unit shall be a one-way cassette style indoor unit that recesses into the ceiling with a ceiling grille (ordered separately, part number: PC1NUSMAN or PC1NUPMAN) and shall have a modulating linear expansion device. The one-way cassette shall be compatible with DVM S HR (Heat Recovery) outdoor units and MCU (Mode Change Unit) or DVM S HP (Heat Pump) outdoor units. The one-way cassette shall support individual control using SAMSUNG DVM S NASA Control Network Solution (Control systems). Indoor model numbers shall be: AM007FN1DCH/AA, AM009FN1DCH/AA, AM012FN1DCH/AA. 2. Each system shall perform in accordance to the ratings shown in the table below. Performance shall be based on nominal cooling conditions of 80F DB, 67F WB for the indoor unit and 95F DB for the outdoor unit and nominal heating conditions of 70F DB for the indoor unit and 47F DB, 43F WB for the outdoor unit. System Model Number BTU/h Cooling* BTU/h Heating * AM007FN1DCH/AA 7,500 8,500 AM009FN1DCH/AA 9,500 10,500 AM012FN1DCH/AA 12,000 13,500 *Nominal capacity B. Indoor Unit. 1. DRAFT: 07/29/2014 The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, electronic modulating linear expansion device, control circuit board and fan motor. The unit shall have a self-diagnostic function, 3-minute time delay mechanism, an auto restart function. Indoor unit and www.SamsungDVM-S.com Specifications are subject to change without notice. 23 SAMSUNG Electronics HVAC refrigerant pipes shall be charged with dehydrated air (Nitrogen gas) before shipment from the factory. C. D. E. Unit Cabinet: 1. The cabinet shall be space-saving ceiling recessed. 2. Construction shall be HIPS chassis fascia panel certified to UL94. 3. The one-way grille shall be fixed to bottom of cabinet allowing for one-way airflow (PC1NUSMAN or PC1NUPMAN panel). Fan: 1. The indoor fan shall be an assembly with one line-flow fan direct driven by a single motor. 2. The indoor fan shall be statically and dynamically balanced to run on a motor with permanently lubricated bearings. 3. The indoor fan shall consist of three (3) speeds, Low, Mid, and High. 4. Fascia panel PC1NUPMAN shall have a smooth (non-louvered) return air inlet that opens on one side when unit is ON and closes when unit is OFF. 5. Return air shall be filtered by means of a long-life washable permanent filter (2). Coil: 1. The indoor coil shall be of nonferrous construction with slit fins on copper tubing. 2. The tubing shall have inner grooves for high efficiency heat exchange. 3. All tube joints shall be brazed with phos-copper or silver alloy. 4. The coils shall be pressure tested at the factory. 5. A condensate pan and drain shall be provided under the coil. 6. The condensate lift mechanism shall be able to raise drain water 29 inches above the condensate pan with built in check valve and float switch. 7. The coil fins are coated with hydrophilic paints. DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 24 SAMSUNG Electronics HVAC 8. F. G. 4.09 Both refrigerant lines to the one-way cassette indoor units shall be insulated. Electrical: 1. The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz. 2. The system shall be capable of satisfactory operation within voltage limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). 3. The control circuit between the indoor units, MCU (Mode Change Unit) and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system 4. The indoor unit shall have a thermal fuse under high-voltage terminal block to disable unit in the event of overheating due to electrical malfunction/poor connection. Controls: 1. This unit shall use controls provided by SAMSUNG Electronics to perform functions necessary to operate the system. Please refer to Part 5 of this guide specification for details on controllers and other control options. 2. The indoor unit shall have a removable EEPROM on its PCB to store all unit data. All data on the indoor unit EEPROM shall be viewable from the manufacturer provided service software. The indoor unit main EEPROM shall be removable allowing replacement of indoor unit PCB without losing digital, field programmed data. The indoor unit removable EEPROM shall store the following unit data: unit model number, unit serial number, unit PCB firmware and MICOM version, and field programmed unit name/tag viewable on controls and service software. CEILING-CONCEALED, SLIM, DUCTED, INDOOR UNIT (AM0**FNLDCH/AA) A. General: 1. DRAFT: 07/29/2014 The indoor unit shall be a ceiling-concealed ducted indoor fan coil design that mounts above the ceiling with a 2-position, field adjustable return and a fixed horizontal discharge supply and shall have a modulating linear expansion device. The ceiling-concealed ducted unit shall be compatible with DVM S HR (Heat Recovery) outdoor units and MCU (Mode Change Unit) or DVM S HP (Heat Pump) outdoor units. The ceiling-concealed ducted unit shall support individual control using SAMSUNG DVM S NASA Control Network www.SamsungDVM-S.com Specifications are subject to change without notice. 25 SAMSUNG Electronics HVAC Solution (Control systems). Indoor model numbers shall be: AM007FNLDCH/AA, AM009FNLDCH/AA, AM012FNLDCH/AA, AM018FNLDCH/AA, AM024FNLDCH/AA, AM030FNLDCH/AA, AM036FNLDCH/AA, AM048FNLDCH/AA. 2. Each system shall perform in accordance to the ratings shown in the table below. Performance shall be based on nominal cooling conditions of 80F DB, 67F WB for the indoor unit and 95F DB for the outdoor unit and nominal heating conditions of 70F DB for the indoor unit and 47F DB, 43F WB for the outdoor unit. System Model Number Btu/h Cooling* Btu/h Heating * AM007FNLDCH/AA 7,500 8,500 AM009FNLDCH/AA 9,500 10,500 AM012FNLDCH/AA 12,000 13,500 AM018FNLDCH/AA 18,000 20,000 AM024FNLDCH/AA 24,000 27,000 AM030FNLDCH/AA 30,000 34,000 AM036FNLDCH/AA 36,000 40,000 AM048FNLDCH/AA 48,000 54,000 *Nominal capacity B. Indoor Unit: 1. The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, electronic modulating linear expansion device, control circuit board and fan motor. The unit shall have a self-diagnostic function, 3-minute time delay mechanism, and an auto restart function. Indoor unit and refrigerant pipes shall be charged with dehydrated air (Nitrogen gas) before shipment from the factory. 2. The indoor unit shall have a discharge air temperature sensor. 3. The indoor unit discharge temperature sensor shall allow configuration to control unit operation based on target cooling and heating discharge air temperatures (cooling: 46~64º F, heating: 86~109º F). 4. The indoor unit discharge temperature sensor reading shall be visible on central control options (MIM-D00AN, MIM-B16N, MIM-B17N) and manufacturer provided service software. DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 26 SAMSUNG Electronics HVAC C. D. E. Unit Cabinet: 1. The unit shall be space saving, ceiling-concealed, ducted. 2. The cabinet shall be constructed of insulated galvanized steel. Fan: 1. The indoor unit fan assembly shall be two or three (dependent on capacity) Sirocco fans direct driven by a single motor. 2. The indoor fan shall be statically and dynamically balanced and run on a motor with permanently lubricated bearings. 3. The indoor fan shall consist of various speeds, as indicated in below table. Model Number Fan Speed Setting AM007FNLDCH/AA AM009FNLDCH/AA AM012FNLDCH/AA AM018FNLDCH/AA AM024FNLDCH/AA AM030FNLDCH/AA AM036FNLDCH/AA AM048FNLDCH/AA Low – Mid – High 4. The indoor unit shall have a ducted air outlet and ducted return air system (field provided). 5. Standard external static pressure is 0.08” WC (min. 0”, max. 0.16”WC) for slim ducted indoor units up to 24,000 btu/h and 0.12” WC (min. 0”, max. 0.24”) for units 30,000 btu/h and larger. 6. The fan speed shall be adjustable by optional remote controller or manufacturer provided service software according to external static pressure. Filter: 1. Return air shall be filtered by means of a standard factory installed return air filter on rear of unit. 2. Optional return connection through rear or bottom of unit with removal and replacement of return air conversion plate. Other filtration is field provided (recommended). DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 27 SAMSUNG Electronics HVAC F. G. Coil: 1. The indoor coil shall be of nonferrous construction with slit fins on copper tubing. 2. The tubing shall have inner grooves for high efficiency heat exchange. 3. All tube joints shall be brazed with phos-copper or silver alloy. 4. The coils shall be pressure tested at the factory. 5. A condensate pan and drain shall be provided under the coil. 6. The condensate shall be gravity drained from the fan coil. 7. The coil fins are coated with hydrophilic paint. 8. Both refrigerant lines to the ceiling-concealed ducted indoor units shall be insulated. 9. The condensate shall be gravity drained as standard (optional, internally mounted, field installed, manufacturer provided condensate pumps available). Optional SAMSUNG Condensate Pumps 1. Condensate pump model: MDP-M075GU3D H. I. Electrical: 1. The unit electrical power shall be 208/230 volts, 1 phase, 60 hertz. 2. The system shall be capable of satisfactory operation within voltage limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). 3. The control circuit between the indoor units, MCU (Mode Change Unit) and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system 4. The indoor unit shall have a thermal fuse under high-voltage terminal block to disable unit in the event of overheating due to electrical malfunction/poor connection. Controls: 1. DRAFT: 07/29/2014 This unit shall use controls provided by SAMSUNG Electronics to perform functions necessary to operate the system. Please refer to www.SamsungDVM-S.com Specifications are subject to change without notice. 28 SAMSUNG Electronics HVAC Part 5 of this guide specification for details on controllers and other control options. 2. 4.10 The indoor unit shall have a removable EEPROM on its PCB to store all unit data. All data on the indoor unit EEPROM shall be viewable from the manufacturer provided service software. The indoor unit main EEPROM shall be removable allowing replacement of indoor unit PCB without losing digital, field programmed data. The indoor unit removable EEPROM shall store the following unit data: unit model number, unit serial number, unit PCB firmware and MICOM version, and field programmed unit name/tag viewable on controls and service software. MIDDLE STATIC PRESSURE, CEILING-CONCEALED, DUCTED, INDOOR UNIT (AM0**FNMDCH/AA) A. General: 1. The indoor unit shall be a high-performance ceiling-concealed ducted indoor fan coil that mounts above the ceiling with a return and a fixed horizontal discharge supply and shall have a modulating linear expansion device. The ceiling-concealed ducted indoor unit shall be compatible with DVM S HR (Heat Recovery) outdoor units and MCU (Mode Change Unit) or DVM S HP (Heat Pump) outdoor units. The ceiling-concealed ducted indoor unit shall support individual control using SAMSUNG DVM S NASA Control Network Solution (Control systems). Indoor model numbers shall be: AM018FNMDCH/AA, AM024FNMDCH/AA, AM030FNMDCH/AA, AM036FNMDCH/AA, and AM048FNMDCH/AA. 2. Each system shall perform in accordance to the ratings shown in the table below. Performance shall be based on nominal cooling conditions of 80F DB, 67F WB for the indoor unit and 95F DB for the outdoor unit and nominal heating conditions of 70F DB for the indoor unit and 47F DB, 43F WB for the outdoor unit. System Model Number Btu/h Cooling* Btu/h Heating* AM018FNMDCH/AA 18,000 20,000 AM024FNMDCH/AA 24,000 27,000 AM030FNMDCH/AA 30,000 34,000 AM036FNMDCH/AA 36,000 40,000 AM048FNMDCH/AA 48,000 54,000 *Nominal capacity DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 29 SAMSUNG Electronics HVAC B. Indoor Unit: 1. The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, electronic modulating linear expansion device, control circuit board and fan motor. The unit shall have a self-diagnostic function, 3-minute time delay mechanism, and an auto restart function. Indoor unit and refrigerant pipes shall be charged with dehydrated air (Nitrogen gas) before shipment from the factory. 2. The indoor unit shall have a discharge air temperature sensor. 3. The indoor unit discharge temperature sensor shall allow configuration to control unit operation based on target cooling and heating discharge air temperatures (cooling: 46~64º F, heating: 86~109º F). 4. The indoor unit discharge temperature sensor reading shall be visible on central control options (MIM-D00AN, MIM-B16N, MIM-B17N) and manufacturer provided service software. C. D. Unit Cabinet: 1. The cabinet shall be space saving, ceiling-concealed ducted. 2. The cabinet shall be constructed of insulated galvanized steel. Fan: 1. The indoor unit fan shall be an assembly with two Sirocco fans direct driven by 1 or 2 motors depending on capacity. 2. Standard external static pressure for ceiling-concealed, medium static pressure ducted indoor units 18,000 – 24,000 btu/h is 0.157” WC. Acceptable range: 0” – 0.315” WC. 3. Standard external static pressure for ceiling-concealed, medium static pressure ducted indoor units 30,000 – 48,000 btu/h is 0.3” WC. Acceptable range: 0.25” – 0.4” WC. 4. The indoor fan shall be statically and dynamically balanced to run on a motor with permanently lubricated bearings. 5. The indoor fan shall consist of three (3) speeds, High, Mid, and Low. 6. The indoor unit shall have a ducted air outlet system and ducted return air system (field provided). DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 30 SAMSUNG Electronics HVAC 7. E. F. The fan speed shall be adjustable by optional remote controller according to external static pressure. Filter: 1. Return air shall be filtered by means of a standard factory installed return air filter. 2. Field provided filtration can be used within bounds of external pressure drop (recommended). Coil: 1. The indoor coil shall be of nonferrous construction with slit fins on copper tubing. 2. The tubing shall have inner grooves for high efficiency heat exchange. 3. All tube joints shall be brazed with phos-copper or silver alloy. 4. The coils shall be pressure tested at the factory. 5. A condensate pan and drain shall be provided under the coil. 6. The coil fins are coated with hydrophilic paint. 7. Both refrigerant lines to the ceiling-concealed ducted indoor unit shall be insulated. 8. The condensate shall be gravity drained as standard (optional, internally mounted, field installed, manufacturer provided condensate pumps available). G. Optional SAMSUNG Condensate Pumps 1. Condensate pump model: MDP-M075SGU3D for AM018FNMDCH/AA and AM024FNMDCH/AA indoor unit models. 2. Condensate pump model: MDP-M075SGU1D for AM 030FNMDCH/AA and AM036FNMDCH/AA indoor units models 3. MDP-M075SGU2D for AM048FNMDCH/AA indoor unit model. H. Electrical: 1. DRAFT: 07/29/2014 The unit electrical power shall be 208/230 volts, 1 phase, 60 hertz. www.SamsungDVM-S.com Specifications are subject to change without notice. 31 SAMSUNG Electronics HVAC I. 4.11 2. The system shall be capable of satisfactory operation within voltage limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). 3. The control circuit between the indoor units, MCU (Mode Change Unit) and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system 4. The indoor unit shall have a thermal fuse under high-voltage terminal block to disable unit in the event of overheating due to electrical malfunction/poor connection. Controls: 1. This unit shall use controls provided by SAMSUNG Electronics to perform functions necessary to operate the system. Please refer to Part 5 of this guide specification for details on controllers and other control options. 2. The indoor unit shall have a removable EEPROM on its PCB to store all unit data. All data on the indoor unit EEPROM shall be viewable from the manufacturer provided service software. The indoor unit main EEPROM shall be removable allowing replacement of indoor unit PCB without losing digital, field programmed data. The indoor unit removable EEPROM shall store the following unit data: unit model number, unit serial number, unit PCB firmware and MICOM version, and field programmed unit name/tag viewable on controls and service software. HIGH STATIC PRESSURE, CEILING-CONCEALED, DUCTED, INDOOR UNIT (AM0**FNHDCH/AA) A. General: 1. The indoor unit shall be a high-performance, high static pressure capable, concealed ducted indoor fan coil that mounts above the ceiling with a fixed horizontal discharge supply and shall have a modulating linear expansion device (gear type). The high static pressure capable, concealed ducted indoor unit shall be compatible with DVM S HR (Heat Recovery) outdoor units and MCU (Mode Change Unit) or DVM S HP (Heat Pump) outdoor units. The high static pressure capable, concealed ducted indoor unit shall support individual control using SAMSUNG DVM S NASA Control Network Solution (Control systems). Indoor model numbers shall be: AM036FNHDCH/AA, and AM048FNHDCH/AA. 2. Each system shall perform in accordance to the ratings shown in the table below. Performance shall be based on nominal cooling DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 32 SAMSUNG Electronics HVAC conditions of 80F DB, 67F WB for the indoor unit and 95F DB for the outdoor unit and nominal heating conditions of 70F DB for the indoor unit and 47F DB, 43F WB for the outdoor unit. System Model Number Btu/h Cooling* Btu/h Heating* AM036FNHDCH/AA 36,000 40,000 AM048FNHDCH/AA *Nominal Capacity 48,000 54,000 B. Indoor Unit. 1. The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, electronic modulating linear expansion device, control circuit board and fan motor. The unit shall have a self-diagnostic function, 3-minute time delay mechanism, and an auto restart function. Indoor unit and refrigerant pipes shall be charged with dehydrated air (Nitrogen gas) before shipment from the factory. 2. The indoor unit shall have a discharge air temperature sensor. 3. The indoor unit discharge temperature sensor shall allow configuration to control unit operation based on target cooling and heating discharge air temperatures (cooling: 46~64º F, heating: 86~109º F). 4. The indoor unit discharge temperature sensor reading shall be visib le on central control options (MIM-D00AN, MIM-B16N, MIMB17N) and manufacturer provided service software. C. Unit Cabinet: 1. The cabinet shall be space saving, ceiling-concealed ducted. 2. The cabinet shall be constructed of insulated galvanized steel. D. Fan: 1. The indoor unit fan assembly shall have two Sirocco fans direct driven by a single motor. 2. Standard external static pressure is 0.39” WC. Acceptable range: 0.197” – 0.788” WC for 36,000 – 48,000 btu/h high static pressure concealed ducted indoor units. 3. Standard external static pressure is 0.59” WC. Acceptable range: DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 33 SAMSUNG Electronics HVAC 0.20” – 0.98” WC for 72,000 btu/h high static pressure concealed ducted indoor units. 4. Standard external static pressure is 0.59” WC. Acceptable range: 0.20” – 1.10” WC for 96,000 btu/h high static pressure concealed ducted indoor units. 5. The indoor fan shall be statically and dynamically balanced to run on a motor with permanently lubricated bearings. 6. The indoor fan shall consist of three (3) speeds, High, Mid, and Low. 7. The indoor unit shall have a ducted air outlet system and ducted return air system (field provided). 8. The fan speed shall be adjustable by optional remote controller according to external static pressure. E. Filter: 1. Field provided filtration must be used within bounds of external pressure drop. F. Coil: 1. The indoor coil shall be of nonferrous construction with slit fins on copper tubing. 2. The tubing shall have inner grooves for high efficiency heat exchanger. 3. All tube joints shall be brazed with phos-copper or silver alloy. 4. The coils shall be pressure tested at the factory. 5. A condensate pan and drain shall be provided under the coil 6. The coil fins are coated with hydrophilic paint. 7. The condensate shall be gravity drained as standard (optional, internally mounted, field installed, manufacturer provided condensate pumps available). G. Optional SAMSUNG Condensate Pump 1. DRAFT: 07/29/2014 Condensate pump model: MDP-M075SGU2D for high static pressure ducted units 36,000 – 48,000 btu/h. www.SamsungDVM-S.com Specifications are subject to change without notice. 34 SAMSUNG Electronics HVAC 2. Condensate pump model: MDP-N047SNC1D for high static pressure ducted units 72,000 – 96,000 btu/h. H. Electrical: I. 1. The unit electrical power shall be 208/230 volts, 1 phase, 60 hertz. 2. The system shall be capable of satisfactory operation within voltage limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz). 3. The control circuit between the indoor units, MCU (Mode Change Unit) and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system 4. The indoor unit shall have a thermal fuse under high-voltage terminal block to disable unit in the event of overheating due to electrical malfunction/poor connection. Controls: 1. This unit shall use controls provided by SAMSUNG Electronics to perform functions necessary to operate the system. Please refer to Part 5 of this guide specification for details on controllers and other control options. 2. The indoor unit shall have a removable EEPROM on its PCB to store all unit data. All data on the indoor unit EEPROM shall be viewable from the manufacturer provided service software. The indoor unit main EEPROM shall be removable allowing replacement of indoor unit PCB without losing digital, field programmed data. The indoor unit removable EEPROM shall store the following unit data: unit model number, unit serial number, unit PCB firmware and MICOM version, and field programmed unit name/tag viewable on controls and service software. Part 5 – Controls 5.01 OVERVIEW A. General: 1. DRAFT: 07/29/2014 The DVM Controls Network Solution shall be capable of supporting remote controllers, schedule timers, system controllers, centralized controllers, an integrated web based interface, graphical user workstation, and system integration to Building Management Systems via BACnet® and LonWorks®. www.SamsungDVM-S.com Specifications are subject to change without notice. 35 SAMSUNG Electronics HVAC 5.02 ELECTRICAL CHARACTERISTICS A. General: 1. B. C. 5.03 The DVM S Controls Solution shall operate at 12V DC (excluding MCM-A202DN ON/OFF Controller). Controller power and communications shall be via a common communications bus. Wiring: 1. Main system control wiring (COM1, F1/F2) shall be installed in a system daisy chain configuration from the indoor equipment to outdoor unit. Control wiring to wired remote controllers shall be run from the indoor unit terminal block to the controller associated with that unit. This cable shall be 16 AWG X 2, shielded cable. 2. Control wiring for system controllers and centralized controllers (upper level) shall be installed in a daisy chain configuration from outdoor unit to outdoor unit (R1/R2), to system controllers. 3. Communication wire connection (OF1/OF2) between outdoor unit modules (systems greater than 168,000 btu/h) must be connected from the MAIN unit to SUB1 and SUB2 (where applicable). This wire shall be 2-conductor, 16 AWG X 2, shielded cable. 4. MST-P3P (S-Net3 software) shall be capable of being networked with up to 16: MIM-D00AN (DMS2), MIM-B17N (BACnet gateway), and/or MIM-B18 (LonWorks gateway) system controllers for web/LAN based control for consolidated control. Wiring type: 1. COM1 and COM2 control wiring shall be 2-conductor, 16 AWG X 2, shielded cable. 2. Network wiring shall be CAT-5e with RJ-45 connection. DVM CONTROL NETWORK SOLUTION A. The SAMSUNG DVM S NASA Control Network Solution consists of remote controllers, system controllers, centralized controllers, and/or integrated web based interface communicating over a high-speed communication bus. The SAMSUNG DVM S NASA Control Network Solution shall support operation monitoring, scheduling, error monitor, power distribution, personal browsers, tenant billing, online maintenance support, and integration with Building Management Systems (BMS) using either LonWorks® or BACnet® interfaces. DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 36 SAMSUNG Electronics HVAC 5.04 MULTI-FUNCTION CONTROLLER – INDIVIDUAL WIRED CONTROLLER (MWRWE10N) A. Connection: 1. B. Dimensions: 1. C. The wired controller shall control up to 16 SAMSUNG indoor units or SAMSUNG ERV’s (defined and controlled as one group). The wired controller shall be approximately 4 5/8” x 4 7/8” in size and white in color The wired controller shall control indoor units and SAMSUNG ERV as follows: 1. Air handler and ERV unified controller (can only control SAMSUNG ERV’s) 2. Air handler operation ON/OFF 3. Air handler operation mode, set temperature, air flow direction, fan speed, individual louver control (with supported indoor units), discharge air temperature (with supported indoor units) 4. Quiet and sleep modes 5. Error display 6. Filter replacement alarm display and reset 7. Single indoor unit control or multiple unit control (maximum 16 units) 8. Energy saving operation: 9. DRAFT: 07/29/2014 a. Upper/lower temperature setting b. Automatic operation stop function c. Energy saving operation mode Weekly operating schedule setting: a. Weekly operating schedule (A/C only, ERV only, A/C + ERV) b. Options to set: desired A/C operation mode, setting temperature, power mode (ON/OFF), and fan speed to operate based on weekly or daily schedules www.SamsungDVM-S.com Specifications are subject to change without notice. 37 SAMSUNG Electronics HVAC c. D. E. Optional schedule exception day setting Other wired controller features: 1. Different button permission levels 2. Partial button lock option (on/off, selection, temperature setting, fan speed, and schedule setting buttons can be locked individually) 3. Backlight 4. Daylight savings clock advance option 5. Temperature limit setting option 6. Real-time clock function - current time/day display function 7. Built-in room temperature sensor 8. Indoor unit operation state display 9. Service mode support (Indoor unit addressing, indoor unit cycle data monitoring, option code monitoring and setting, and option setting/monitoring) Specifications: 1. 2 conductor connection, PLC, (F3/F4). 2. DC 12V (power supplied by indoor unit via F3/F4 connection). 3. RS485 communication (F3/F4). 4. Can sense temperature via internal sensor, temperature sensor inside the air handler, or use the average temperature between controller and air handler temperature sensors. 5. The wired controller shall have two screw terminals for wiring connections. Wire is not included with controller. 6. 16AWG X 2 shielded cable is necessary for proper operation. 7. The wired controller shall allow up to 328 feet of wire from the farthest connected indoor unit to the controller. DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 38 SAMSUNG Electronics HVAC Multi-Function Controller Item Description Operation Display ON/OFF Run and stop operation for a single group Including Samsung ERV operation Each Group Each Group Operation Mode Switches between Auto/Cool/Dry/ Fan/Heat Each Group Each Group Temperature Setting 1. Sets temperature for a single group. 2. Range of temperature setting a. Auto/Cool/Dry: 65°F-86°F b. Heat: 61°F-86°F 3. Setting discharge outlet air temperature for supported indoor units. Each Group Each Group Discharge Air Temperature Setting Sets temperature for supported ducted units Each Group Each Group Fan Speed Setting Models with 3 air flow speed settings: High /Mid/Low/Auto Each Group Each Group Air Flow Direction Setting 1. Air flow 2-step direction (Swing/Stop) 2. Direct setting at a specific angle. 3. Air flow operation varies depending on the model. Each Group Each Group Each Group Each Group Each Group Each Group Each Group Each Group Weekly Schedule Button lock Specified Function DRAFT: 07/29/2014 1. ON/OFF/Temperature setting can be done at most 10 schedules may be set for each day. 2. Real-time clock function: current time, day display function 1. Button permission level setting (On/Off / Temperature setting / Mode button / Fan speed) 2. Temperature limit setting 3. After power reset, the setting value is restored 4. Various restriction capabilities 1. Automatic stop setting (setting time range: 0-12 hours) 2. Energy saving operation mode (IDU+ERV or ERV operation only depending on outdoor temperature) www.SamsungDVM-S.com Specifications are subject to change without notice. 39 SAMSUNG Electronics HVAC Multi-Function Controller Item Description Operation Display Service Mode Viewing/Setting indoor unit option code Viewing/setting indoor unit MAIN address Viewing/setting indoor unit RMC address Viewing indoor unit cycle data Setting/Viewing temperature sensor compensation of the wired remote controller (-9°F~ +9°F) 6. Viewing RPM compensation 7. Viewing/setting EEV stop step when indoor unit is thermo-off during heating mode 8. Viewing/setting filter reminder time interval (1000 hours, 2000 hours) 9. Viewing/setting indoor unit temperature sensor compensation during Heating (+2°F or +5°F) 10. Viewing the H/W option setting 11. Viewing wired remote controller software version 12. Viewing/setting individual louver lock Each Unit Each Unit Blade Setting individual blade positions on 4-Way Cassette (AM0**FN4DCH/AA) Each Unit Each Unit Error When an error is currently occurring in the system, the afflicted unit and the error code are displayed Each Group Each Group Permit / Prohibit Local Operation Setting/releasing of simplified locking of remote control buttons Each Group N/A Quiet Mode Select the quiet mode to lower the fan noise level. Each Group N/A 1. 2. 3. 4. 5. Room Actual room temperature or set temperature Each Group Each Group Temperature can be displayed *Some features may not be available depending on the model of connected air handler(s). 5.05 SIMPLIFIED WIRED CONTROLLER (MWR-SH00N) A. Connection: 1. The wired controller shall control up to 16 SAMSUNG indoor units (defined and controlled as one group). B. Dimensions: 1. DRAFT: 07/29/2014 The wired controller shall be approximately 4 13/16” x 3” x 5/8” in size and white in color. www.SamsungDVM-S.com Specifications are subject to change without notice. 40 SAMSUNG Electronics HVAC C. The wired controller shall have the following features and control capability: 1. Indoor unit operation ON/OFF 2. Indoor unit operation mode, set temperature, and fan speed 3. Error display 4. Filter replacement alarm display and reset 5. Single indoor unit control or multiple unit control (maximum 16 units) 6. Partial controller button lock (operation mode button, temperature setting buttons, fan speed button, timer button, and lock mode button) 7. Upper and lower temperature setting restriction 8. Auto mode skip 9. Heat mode skip (cooling only) 10. Restrict wireless controller signal (optional) 11. Louver position setting (cassette and wall units) 12. Single event timer function (ON/OFF control, 30 minutes ~ 18 hours timer setting options) 13. System/indoor unit function and operation indication (defrost, error, restricted controller, SPi status) 14. Quiet Mode setting (for supported units) 15. Service mode for connected indoor unit operation monitoring, addressing, and setup 16. Can be used to specify "Mode Master" while connected to a single indoor unit when used with heat pump systems. D. Specifications: 1. 2 conductor connection, PLC, (F3/F4). 2. DC 12V (power supplied by indoor unit via F3/F4 connection). 3. RS485 communication (F3/F4). 4. The wired controller shall have two screw terminals for wiring connections. Wire is not included with controller. DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 41 SAMSUNG Electronics HVAC 5. 16AWG X 2 shielded cable is necessary for proper operation. 6. The wired controller shall allow up to 328 feet of wire from the farthest connected indoor unit to the controller. Simplified Controller Item Description Operation Display ON/OFF Run and stop operation for a single group Including Samsung ERV operation Each Group Each Group Operation Mode Switches between Auto/Cool/Dry/ Fan/Heat Each Group Each Group Temperature Setting 1. Sets temperature for a single group. 2. Range of temperature setting a. Auto/Cool/Dry: 65°F-86°F b. Heat: 61°F-86°F 3. Setting discharge outlet air temperature for supported indoor units. Each Group Each Group Fan Speed Setting Models with 3 air flow speed settings: High /Mid/Low/Auto Each Group Each Group Air Flow Direction Setting 1. Air flow 2-step direction (Swing/Stop) 2. Air flow operation varies depending on the model. Each Group Each Group Each Group Each Group Each Group Each Group Each Group Each Group Each Unit Each Unit Each Group Each Group ON/OFF Timer Button lock Specified Function Service Mode Error DRAFT: 07/29/2014 1. ON/OFF single event timer 2. Can set to turn unit ON and/or OFF between 30 minutes ~ 18 hours. 1. Button permission level setting (On/Off / Temperature setting / Mode button / Fan speed) 2. Temperature limit setting 3. After power reset, the setting value is restored 4. Various restriction capabilities 1. Energy saving operation mode (IDU+ERV or ERV operation only depending on outdoor temperature) 1. 2. 3. 4. 5. Viewing/Setting indoor unit option code Viewing/setting indoor unit MAIN address Viewing/setting indoor unit RMC address Viewing indoor unit cycle data Viewing/setting indoor unit temperature sensor compensation during Heating (+2°F or +5°F) When an error is currently occurring in the system, the afflicted unit and the error code are displayed www.SamsungDVM-S.com Specifications are subject to change without notice. 42 SAMSUNG Electronics HVAC Simplified Controller Item Description Operation Display Permit / Prohibit Local Operation Setting/releasing of simplified locking of remote control buttons Each Group N/A Quiet Mode Select the quiet mode to lower the fan noise level. Each Group N/A 5.06 WIRELESS CONTROLLER (MWR-DH00U) A. Function: 1. The wireless controller shall support the following control options via soft-touch buttons: ON/OFF, set temperature, mode, fan speed, filter reminder reset, independent louver control (4-way cassette only), airflow direction, and single event timer setting. 2. The wireless controller shall have a wide, easy to read display. 3. The wireless controller shall support indoor unit option code setting, indoor unit addressing, and indoor unit option setting. 4. The wireless controller shall include a holder to secure remote to wall. B. Dimensions: 1. Width Height X Depth: 1 11/16” X 5 7/16” X 1 1/8” 5.07 WIRELESS SIGNAL RECEIVER FOR DUCT-TYPE INDOOR UNITS (MRK-A10N) A. Connection: 1. B. The wireless signal receiver shall be capable of connection to 1 duct unit. Function: 1. The wireless signal receiver shall control: power, fan speed, set temperature, and timer via wireless controller (MRW-DH00U). 2. The wireless signal receiver shall display operation indication and blinking LED indication in the event of system operation and abnormality/error. 3. The wireless signal receiver shall connect using included receiver wire (32.8’). DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 43 SAMSUNG Electronics HVAC C. 5.08 Dimensions: 1. The wireless signal receiver shall be approximately 2.7” x 4.7” in size and white in color with a LED display. 2. The wireless signal receiver shall be recessed mount. EXTERNAL ROOM TEMPERATURE SENSOR (MRW-TA) A. Connection: 1. The external remote room sensor shall connect to 1 indoor unit. 2. The external remote room sensor shall plug directly into PCB of indoor unit with supplied adapter. B. Function: 5.09 The external remote room sensor shall be used to measure the exact room temperature. 2. The external remote room sensor shall support wire length of maximum 39 feet. EXTERNAL CONTACT CONTROL – INDIVIDUAL UNIT, ON/OFF CONTROL AND MONITORING (MIM-B14) A. 5.10 1. Function: 1. Control option to enable/disable and monitor individual indoor units 2. Direct indoor unit control by external contact, 0 volts OPEN/CLOSE signal 3. Emergency control with simple contact input 4. Indoor unit operation (thermo or operation)/error state output through relay contacts (5VDC) 5. Installation location: inside a single indoor unit 6. Connection to indoor unit with included wire harnesses ON/OFF CONTROLLER (MCM-A202DN) A. Connection: 1. DRAFT: 07/29/2014 The On/Off Controller shall be capable of controlling up to 128 indoor units (defined as 16 groups). www.SamsungDVM-S.com Specifications are subject to change without notice. 44 SAMSUNG Electronics HVAC B. C. Dimensions: 1. The On/Off Controller shall be approximately 2.3” x 4.7” in size and white in color with 17 LED displays. 2. The On/Off Controller shall install recessed in wall. approved box shall be required for installation. An NEC Function: 1. The On/Off Controller shall be capable of turning ON/OFF up to sixteen groups of indoor units (1 – 16 units per group), for a maximum of 128 indoor units. 2. Each of the 16 individual groups shall have ON/OFF control separate from other groups. 3. All of the indoor units shall be turned ON/OFF using the main ALL ON/ALL OFF power button. 4. An LED for each group of indoor units, up to 16 groups, shall be indicated if there is a failure within each group by flashing. 5. An All LED shall be ON if all the indoor units controlled by MCMA202DN are turned ON. 6. An LED for each group of indoor units shall indicate the ON/OFF status of the group. 7. 208/230VAC 50/60 Hz. power. Must install in an NEC approved box. ON/OFF Controller Item Description Operation Display ON/OFF Run and stop operation for the air conditioner units Group or Collective Group or Collective Operation Mode Setting Auto/Cooling/Heating mode control using mode switch + ALLO ON/ALL OFF button N/A All Unit Groups LED Error LED flashes during failure. N/A Each Group Schedule Operation Not Available N/A N/A Connection Position Outdoor Unit Communication Line (R1/R2) N/A N/A Permit / Prohibit Local Operation Wireless/wired remote control restriction Each Group N/A 5.11 INTEGRATED MANAGEMENT SYSTEM – DATA MANAGEMENT SERVER (MIM- DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 45 SAMSUNG Electronics HVAC D00AN) A. Function: 1. Easy control and monitoring through web browser (optimized for Internet Explorer). Individual/Group control of up to 256 indoor units including SAMSUNG ERV and air handlers. 2. The Data Management Server shall have basic operation controls which can be applied to an individual indoor unit, a group of indoor units (up to 256 indoor units), or all indoor units (collective batch operation). This basic controls for the MIM-D00AN shall include on/off, operation mode selection (auto, cool, heat, dry, and fan), temperature setting, fan speed setting, airflow direction setting, error email notification, temperature limitations, operation mode limitation, and online maintenance. 3. The Data Management Server shall support system error notification via email. The Data Management Server emailed errors shall include: error occurrence time, error code with description of error, effected equipment address, and current error status. 4. The Data Management Server shall support: system configuration, 1-day/daily/weekly scheduling, monitoring of operation status, online maintenance tool, operation superseding of the remote controllers, editable user defined control logic, and malfunction monitoring. 5. The Data Management Server shall allow maximum current setting control of each outdoor unit (DVM S Series AM***FX*A**/AA only). 6. Schedule control function through web browser. Up to 256 schedule settings, weekly and daily schedule setting, wireless/wired remote controller restriction setting. Digital Outputs can be incorporated into scheduling. 7. Convenient digital display allows for easy set up. 8. SD memory card slot for data storage and software updating. 9. Available programmable logic to control the system based on preset monitor points. 10. Web server function with remote control (with a public IP address) via internet connection. No management software required – PCindependent management through web browser. 11. 10 DI (Digital Input) ports available. Two digital output ports shall be for emergency shutdown with external contact control interface and DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 46 SAMSUNG Electronics HVAC 8 for other monitoring options (OPEN/CLOSE status). Full indoor unit control with simple contact input (Emergency/Lock). Digital inputs can be incorporated into control logics. 12. B. 8 DO (Digital output) terminals for monitoring and control options. 2 state output (Operation/Error) for synchronous control and monitoring. 6 general purpose outputs to control other components (on: 12VDC out; off: no voltage). Digital Inputs and Digital Outputs can be incorporated into control logics and scheduling. Connection: 1. DC 12V, 3A power provided by AC/DC adapter (input 110-240VAC 50/60Hz, provided with MIM-D00AN). 2. LAN connection for web browser or SNET3 software connection. 3. 16 AWG X 2 shielded cable between SAMSUNG equipment and controls is necessary for proper operation. 4. Maximum number of RS485 connections to 1 MIM-D00AN: a. 75 ON/OFF Controllers (MCM-A202DN) b. 80 DVM S Series Systems (AM***FX*A**/AA and AM0**FXMDCH/AA) connected direct (5 ports, 16 systems per port) c. Maximum 256 indoor units (air handler and/or SAMSUNG ERV) 5. Upper level device connections : S-NET 3, web client. 6. The Data Management Server shall provide functions to monitor and control status of SAMSUNG DVM S Series systems (AM***FXVA**/AA and AM0**FXMDCH/AA) as standard. 7. The Data Management Server shall support provide functions to monitor and control status of SAMSUNG DVM Plus II, Samsung DVM Plus III, Mini DVM, Free Joint Multi, and CAC (CH070/105/140CAV, DH105/140CAV single zone systems) with installation of communication converter interface module per system. 8. Dimensions: a. DRAFT: 07/29/2014 The Data Management Server shall be approximately 9.4” x 10” x 2.6” in size with stainless steel front and LCD displays. www.SamsungDVM-S.com Specifications are subject to change without notice. 47 SAMSUNG Electronics HVAC VRF Data Management Server (DMS2) Item Description Operation Display ON/OFF Run and stop operation for a single group Each Group Each Group Operation Mode Switches between Auto/Cool/Dry/ /Fan/Heat Each Group Each Group Temperature Setting 1. Sets the temperature for a single group. Range of temperature setting a. Auto/Cool/Dry: 65°F-86°F b. Heat: 61°F-86°F Each Group Each Group Fan Speed Setting Models with 3 air flow speed settings: High /Mid/Low Each Group Each Group Air Flow Direction Setting 1. Air flow 2-step direction (Swing/Stop) 2. Direct setting at a specific angle. 3. Air flow operation varies depending on the model. Each Group Each Group Web Server Function 1. Remote control with the public IP address 2. No management software required – PCindependent management Each Group Each Group Accessible level / Dynamic user security Management 1. Wireless/wired remote controller restriction setting 2. Specify the scope of control and monitoring unit on a per-user 3. 3 accessible levels -Admin/Manager/User Each Group Each Group Error 1. When an error is currently occurring in the system(s), the afflicted unit and the error code are displayed 2. Error notification via email Each Group Each Group Schedule Operation Up to 256 schedule settings Weekly and daily schedule setting Each Group Each Group Power distribution to 256 indoor units. Remote data query in 1-day units File saving in Microsoft Excel format. Power distribution data storage for one year 5. MIM-B16 or MIM-B16N required for power use measurements Each Group Each Group 1. Full indoor unit control with simple contact input (Emergency/Lock) 2. State output (Operation/Error) for synchronous control 3. 10 digital outputs (2 reserved) / 8 digital inputs (2 reserved) Each Channel Each Channel Power Distribution System External Contact Interface DRAFT: 07/29/2014 1. 2. 3. 4. www.SamsungDVM-S.com Specifications are subject to change without notice. 48 SAMSUNG Electronics HVAC VRF Data Management Server (DMS2) Item Description Operation Display Control & monitoring zone edition Wireless/wired remote control restriction Temperature limit setting Operation mode restriction Each Group Each Group Smart Central Management 1. 2. 3. 4. User editable control logic 1. User can edit control logic with arithmetic/conditional operators and parameters. 2. Efficient energy saving realization for various operation conditions. 3. EHP/ERV/AHU parameters + AND/OR + Arithmetic equation Function Each Group Each Group Data backup/useful history management 1. Important data is stored in SD memory card (settings, schedules, errors, operation data, energy data, user settings, etc.) 2. Record the operation history and error history Each Group Each Group 5.12 INTEGRATED MANAGEMENT SYSTEM – S-NET3 SYSTEM MANAGEMENT SOFTWARE (MST-P3P) A. Connection: The integrated management software shall be capable of controlling up to 4,096 indoor units. B. Dimensions: S-Net3 shall be system software installed by a CD USB security key. C. Function: 3. The Integrated System Software shall enable the user to control multiple indoor units and shall provide additional functions. 4. The integrated management software shall be capable of connecting up to 16 of the following controllers: MIM-D00A, MIM-D00AN, MIMB17, MIM-B17N, MIM-B18, MIM-B18N. 5. The integrated management software shall be required if the user wants to simultaneously control 16 X MIM-D00A, MIM-D00AN, MIMB17, MIM-B17N, MIM-B18, and/or MIM-B18N from a single PC using a single software session. 6. The integrated management software shall support operation superseding that of the remote controllers, system configuration, DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 49 SAMSUNG Electronics HVAC daily/weekly/annual scheduling, monitoring of operation status, error email notification, online maintenance tool and malfunction monitoring. 7. The integrated management software shall have basic operation controls which can be applied to an individual indoor unit, a group of indoor units (up to 4,096 indoor units), or all indoor units (collective batch operation). This basic control set of operation controls for the integrated management software shall include on/off, operation mode selection (cool, heat, auto, dry and fan), temperature setting, fan speed setting, airflow direction setting and online maintenance. 8. The integrated management software provides centralized control, it shall be able to enable or disable operation of local remote controllers via PC. 9. The integrated management software shall also include a high-level security USB key. 10. In terms of scheduling, the integrated management software shall allow the user to define daily, weekly, and annual schedules with operations consisting of ON/OFF, mode selection, temperature setting, and permit/prohibit of remote controllers. VRF Integrated Management Software (S-Net3) Item Description Operation Display ON/OFF Run and stop operation for a single group/unit Each Group Each Group Operation Mode Switches between Auto/Cool/Dry/Fan/Heat Each Group Each Group Temperature Setting 1. Sets the temperature for a single group. Range of temperature setting 1. Auto/Cool/Dry: 65°F-86°F 2. Heat: 61°F-86°F Each Group Each Group Fan Speed Setting Models with 3 air flow speed settings: High /Mid/Low Each Group Each Group Air Flow Direction Setting 1. Air flow 2-step direction (Swing/Stop) 2. Direct setting at a specific angle. 3. Air flow operation varies depending on the model Each Group Each Group Accessible level 1. Wireless/wired remote controller restriction setting 2. Specify the scope of control and monitoring unit on a per-user Each Group Each Group Error When an error is currently occurring on the system(s), the afflicted unit and the error code are displayed Each Group Each Group DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 50 SAMSUNG Electronics HVAC VRF Integrated Management Software (S-Net3) Item Description Schedule Operation Display Graphical schedule settings Weekly, Daily schedule control Exception date setting Each Group Each Group Power distribution to 4,096 indoor units. Remote data query in 1-day increments File saving in Microsoft Excel format. Power distribution data storage for one year in 1-day units. 5. MIM-B16 or MIM-B16N required for power distribution. 6. PDF report generation with electrical operational costs. Each Group Each Group Each Group Each Group 1. 2. 3. 4. Power Distribution System Smart Central Management 5.13 Operation 1. 2. 3. 4. Control & monitoring zone edition Wireless/wired remote control restriction Temperature limit setting Operation mode restriction LonWorks® Gateway (MIM-B18N) A. Function: 1. Easy control and monitoring through web browser (optimized for Internet Explorer) and LonWorks® TP/FT-10A (free topology 78kbs). Individual/Group control of up to 128 indoor units including SAMSUNG ERV’s and air handlers (indoor quantity will vary based on number of control points necessary, see table below). Control and Monitoring Items* Maximum Number of Connectable Indoor Units 27 Items (all) 22 20 Items 30 15 Items 40 12 Items 50 9 Items 64 6 Items 100 4 Items 128 *20 items can be processed per second; data inquiry interval is 30 seconds. 2. DRAFT: 07/29/2014 The LonWorks® shall have basic operation controls which can be applied to an individual indoor unit, a group of indoor units (up to 128 indoor units), or all indoor units (collective batch operation). This www.SamsungDVM-S.com Specifications are subject to change without notice. 51 SAMSUNG Electronics HVAC basic control set of operation controls for the LonWorks® gateway shall include on/off, operation mode selection (auto, cool, heat, dry, and fan), temperature setting, fan speed setting, airflow direction setting, error email notification, temperature limitations, operation mode limitation, and online maintenance. B. 3. The LonWorks® gateway shall support system error notification via email. The Data Management Server emailed errors shall include: error occurrence time, error code with description of error, effected equipment address, and current error status. 4. The LonWorks® gateway shall support: system configuration, 1day/daily/weekly scheduling, monitoring of operation status, online maintenance tool, operation superseding of the remote controllers, editable user defined control logic, and malfunction monitoring. 5. The LonWorks® gateway shall allow maximum current setting control of each outdoor unit (DVM S Series AM***FX****/AA only). 6. Schedule Control Function through web browser. Up to 256 schedule settings, weekly and daily schedule setting, wireless/wired remote controller restriction setting. Digital Outputs can be incorporated into scheduling. 7. Convenient digital display allows for easy set up. 8. SD memory card slot for data storage and software updating. 9. Available programmable logic to control the system based on preset monitor points. 10. Web Server Function with remote control (with a public IP address) via internet connection. No management software required – PCindependent management through web browser. 11. 10 DI (Digital Input) ports available. Two digital output ports shall be for emergency shutdown with external contact control interface and 8 for other monitoring options (OPEN/CLOSE status). Full indoor unit control with simple contact input (Emergency/Lock). Digital inputs can be incorporated into control logics. 12. 8 DO (Digital Output) terminals for monitoring and control options. 2 state output (Operation/Error) for synchronous control and monitoring. 6 general purpose outputs to control other components (on: 12VDC out; off: no voltage). Digital Inputs and Digital Outputs can be incorporated into control logics and scheduling. Connection: DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 52 SAMSUNG Electronics HVAC C. 1. DC 12V, 3A power provided by AC/DC adapter (input 110-240VAC 50/60Hz, provided with the LonWorks® gateway) 2. LAN connection for BMS, web browser, SNET3 software connection 3. Communication connection: ON/OFF Controller(s) (MCM-A202DN) 4. 16 AWG X 2 shielded cable between SAMSUNG equipment and controls is necessary for proper operation 5. Maximum number of RS485 connections to 1 LonWorks® gateway: a. 75 ON/OFF Controllers (MCM-A202DN) b. 80 DVM S Series Systems (AM***FX****/AA and AM0**FXMDCH/AA) connected direct (5 ports, 16 systems per port) c. Maximum 128 indoor units (air handler and/or SAMSUNG ERV) 6. Upper level device connections: (LonWorks®), web client S-NET 3, BMS system 7. The LonWorks® gateway shall support LonWork®s TP/FT-10A (free topology 78kbs) and provide functions to monitor and control status of SAMSUNG DVM S Series systems (AM***FX****/AA and AM0**FXMDCH/AA). 8. The LonWorks® gateway shall support LonWorks® TP/FT-10A (free topology 78kbs) and provide functions to monitor and control status of SAMSUNG DVM Plus II, SAMSUNG DVM Plus III, Mini DVM, Free Joint Multi, and CAC (CH070/105/140CAV, DH105/140CAV single zone systems) with installation of communication converter interface module per system (MIM-N01). Dimensions: 1. The LonWorks® gateway shall be approximately 9.4” x 10” x 2.6” in size with stainless steel front and LCD displays. VRF LonWorks® Gateway Item Description Operation Display ON/OFF Run and stop operation for a single group Each Group Each Group Operation Mode Switches between Auto/Cool/Dry/ /Fan/Heat Each Group Each Group Each Group Each Group Temperature Setting DRAFT: 07/29/2014 1. Sets the temperature for a single group. Range of temperature setting www.SamsungDVM-S.com Specifications are subject to change without notice. 53 SAMSUNG Electronics HVAC VRF LonWorks® Gateway Item Description a. Auto/Cool/Dry: 65°F-86°F b. Heat: 61°F-86°F Operation Display Fan Speed Setting Models with 3 air flow speed settings: High /Mid/Low Each Group Each Group Air Flow Direction Setting 1. Air flow 2-step direction (Swing/Stop) 2. Direct setting at a specific angle. 3. Air flow operation varies depending on the model. Each Group Each Group Web Server Function 1. Remote control with the public IP address 2. No management software required – PCindependent management Each Group Each Group Accessible level / Dynamic user security Management 1. Wireless/wired remote controller restriction setting 2. Specify the scope of control and monitoring unit on a per-user 3. 3 accessible levels: Admin/Manager/User Each Group Each Group When an error is currently occurring on the System(s), the afflicted unit and the error code are displayed Error notification via email Each Group Each Group Each Group Each Group Power distribution to 128 indoor units. Remote data query in 1-day units File saving in Microsoft Excel format. Power distribution data storage for one year 5. MIM-B16 or MIM-B16N required for power use measurements Each Group Each Group External Contact Interface 1. Full indoor unit control with simple contact input (Emergency/Lock) 2. State output (Operation/Error) for synchronous control 3. 10 digital outputs (2 reserved) / 8 digital inputs (2 reserved) Each Channel Each Channel Smart Central Management 1. 2. 3. 4. Each Group Each Group 1. Error 2. Schedule Operation Power Distribution System DRAFT: 07/29/2014 Up to 256 schedule settings Weekly and daily schedule setting 1. 2. 3. 4. Control & monitoring zone edition Wireless/wired remote control restriction Temperature limit setting Operation mode restriction www.SamsungDVM-S.com Specifications are subject to change without notice. 54 SAMSUNG Electronics HVAC VRF LonWorks® Gateway Item Description Operation Display User editable control logic 1. User can edit control logic with arithmetic/conditional operators and parameters. 2. Efficient energy saving realization for various operation conditions. 3. EHP/ERV/AHU parameters + AND/OR + Arithmetic equation Function Each Group Each Group Data backup/ useful history management 1. Important data is stored in SD memory card 2. Record the operation history and error history Each Group Each Group VRF LonWorks® Gateway Input Variables (Control) Output Variables (Monitor) On/Off control On/Off state In/out contact state Operation mode Operation mode Emergency Stop Temperature setting Set/Room temperature Error code Fan speed/direction Fan speed/direction Indoor time duration ERV operation mode ERV operation mode ERV fan speed ERV fan speed Filter alarm reset Filter alarm User control restriction User control restriction Operation mode lock Thermo Off/On Set temperature limit Power distribution Emergency stop Operation mode lock Output contact control Set temperature limit 5.14 BACnet® GATEWAY (MIM-B17N) A. Function: 1. Easy control and monitoring through web browser (optimized for Internet Explorer). Individual/Group control of up to 256 indoor units (indoor quantity will vary based on number of control points necessary, see table below) including SAMSUNG ERV’s and air handlers. 2. The BACnet® gateway shall have basic operation controls which can be applied to an individual indoor unit, a group of indoor units (up to 256 indoor units), or all indoor units (collective batch operation). This basic control set of operation controls for the BACnet® gateway shall DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 55 SAMSUNG Electronics HVAC include on/off, operation mode selection (auto, cool, heat, dry, and fan), temperature setting, fan speed setting, airflow direction setting, error email notification, temperature limitations, operation mode limitation, and online maintenance. 3. The BACnet® gateway shall support system error notification via email. The Data Management Server emailed errors shall include: error occurrence time, error code with description of error, effected equipment address, and current error status. 4. The BACnet® gateway shall support: system configuration, 1day/daily/weekly scheduling, monitoring of operation status, online maintenance tool, operation superseding of the remote controllers, editable user defined control logic, and malfunction monitoring. 5. The BACnet® gateway shall allow maximum current setting control of each outdoor unit (DVM S Series AM***FX****/AA only). 6. Schedule Control Function through web browser. Up to 256 schedule settings, weekly and daily schedule setting, wireless/wired remote controller restriction setting. Digital Outputs can be incorporated into scheduling. 7. Convenient digital display allows for easy set up. 8. SD memory card slot for data storage and software updating. 9. Available programmable logic to control the system based on preset monitor points. 10. Web Server Function with remote control (with a public IP address) via internet connection. No management software required – PCindependent management through web browser. 11. 10 DI (Digital Input) ports available. Two digital output ports shall be for emergency shutdown with external contact control interface and 8 for other monitoring options (OPEN/CLOSE status). Full indoor unit control with simple contact input (Emergency/Lock). Digital inputs can be incorporated into control logics. 12. 8 DO (Digital Output) terminals for monitoring and control options. 2 state output (Operation/Error) for synchronous control and monitoring. 6 general purpose outputs to control other components (on: 12VDC out; off: no voltage). Digital Inputs and Digital Outputs can be incorporated into control logics and scheduling. C. Connection: DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 56 SAMSUNG Electronics HVAC 1. DC 12V, 3A power provided by AC/DC adapter (input 110-240VAC 50/60Hz, provided with the BACnet® gateway) 2. LAN connection for BMS, web browser, SNET3 software connection 3. Communication connection: ON/OFF Controller(s) (MCM-A202DN) 4. 16 AWG X 2 shielded cable between SAMSUNG equipment and controls is necessary for proper operation 5. Maximum number of RS485 connections to 1 BACnet® gateway: a. 75 ON/OFF Controllers (MCM-A202DN) b. 80 DVM S Series Systems (AM***F**A**/AA and AM0**FXMDCH/AA) connected direct (5 ports, 16 systems per port) c. Maximum 128 indoor units (air handler and/or SAMSUNG ERV) 6. Upper level device connections: S-NET 3, BMS system (BACnet® IP), web client 7. MIM-B17N shall provide functions to monitor and control status of SAMSUNG DVM S Series systems (AM***FX****/AA and AM0**FXMDCH/AA). 8. MIM-B17N shall support provide functions to monitor and control status of SAMSUNG DVM Plus II, SAMSUNG DVM Plus III, Mini DVM, Free Joint Multi, and CAC (CH070/105/140CAV, DH105/140CAV single zone systems) with installation of communication converter interface module per system (MIM-N01). D. Dimensions: 1. The BACnet® gateway shall be approximately 9.4” x 10” x 2.6” in size with stainless steel front and LCD displays. VRF BACnet® Gateway Input Variables (Control) Output Variables(Monitor) On/Off control On/Off state In/out contact state Operation mode Operation mode Emergency Stop Temperature setting Set/Room temperature Error code Fan speed/direction Fan speed/direction Indoor unit run time ERV operation mode ERV operation mode DO/DI Status DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 57 SAMSUNG Electronics HVAC VRF BACnet® Gateway Input Variables (Control) Output Variables(Monitor) ERV fan speed ERV fan speed Filter alarm reset Filter alarm User control restriction User control restriction Operation mode lock Thermo Off/On Set temperature limit Power distribution Emergency stop Operation mode lock Output contact control Set temperature limit DO ON/OFF Human Sensor (select units) 5.15 SPI setting CENTRAL TOUCHSCREEN SYSTEM CONRTOLLER A. Function: 1. The central touchscreen controller is only compatible with Samsung DVM S systems. 2. The central touchscreen controller shall provide control and monitoring via 7” touchscreen interface. 3. The central touchscreen controller shall provide Individual/Group control of up to 128 indoor units (16 systems maximum) including SAMSUNG DVM S ERV’s and air handlers. 4. The central touchscreen controller shall allow control and monitoring of indoor unit: operation mode, set temperature, room temperature, fan speed, louver position, remote control restriction, and power. 5. The central touchscreen controller shall 2 X DI (digital input) terminals to allow quick disable of equipment with a 0 volt contact 6. The central touchscreen controller shall have 1 X DO (digital output) that will provide 12V DC output interlocked with indoor unit operation (ON/OFF). 7. The central touchscreen controller shall have an SD card slot for data backup and future firmware updates. 8. The central touchscreen controller shall provide scheduling capability. Scheduling shall control of indoor unit: operation mode, set temperature, fan speed, louver position, remote control restriction, and power. 9. The central touchscreen controller shall have an all ON/OFF button 10. The central touchscreen controller shall allow creation of zones and DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 58 SAMSUNG Electronics HVAC grouping of indoor units regardless of connected refrigerant system. 11. The central touchscreen controller shall allow grouping of multiple indoor units to display as a single unit on user interface. 12. The central touchscreen controller shall have customizable group and zone icons on main interface to allow easy operation for user. 13. The central touchscreen controller shall allow restriction of ON/OFF, mode, set temperature, fan speed, and remote control use for daily (nonmanagement) touchscreen controller users. 14. The central touchscreen controller shall have menu lock capability allowing restriction of indoor unit control, schedule setting/changing, and touchscreen controller settings by daily (non-management) touchscreen controller users. 15. The central touchscreen controller shall allow screen lock to prevent unwanted changes by unauthorized users. 16. The central touchscreen controller shall have an LED indicator light on front of device to display operation and error status. B. Connection: 1. The central touchscreen controller shall be powered by 100~240 VAC, 50/60 Hz. 2. The central touchscreen controller can connect to a single DVM S system via 2 X 16 AWG shielded cable on main system communication terminals (F1/F2). Connection on F1/F2 will allow control and monitoring of a single system. 3. The central touchscreen controller can connect to multiple DVM S systems via 2 X 16 AWG shielded cable on central control connections (R1/R2). Maximum 16 system can be daisy chained on this communication line. 4. Multiple touchscreen controllers can be connected to a single central control connection (R1/R2, maximum 16) when used with MIM-D00AN, MIM-B16N, and MIM-B17N. C. Dimensions: 1. The central touchscreen controller shall be 8” x 6 5/16” x 1 1/2” (WxHxD). 5.16 ELECTRICITY METER INTERFACE MODULE (MIM-B16) DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 59 SAMSUNG Electronics HVAC A. Function: 1. Pulse Input Module (PIM) for SAMSUNG DVM Plus and SAMSUNG DVM S Series heat pump and heat recovery systems 2. The electricity meter interface module shall support up to 8-channel, real-time watt-hour consumption display 3. The electricity meter interface module shall support automatic watt-hour meter tracking and current communication state indication 4. The electricity meter interface module shall communicate to the following SAMSUNG controllers/gateways: DMS 2 (MIM-D00A), DMS 2.0 (MIM-D00AN), BACnet gateway (MIM-B17 / MIM-B17N), LonWorks Gateway (MIM-B18 / MIM-B18N) to monitor/record energy consumption. B. 5.17 Connection: 1. Energy consumptions data shall be viewed via the following SAMSUNG controllers/gateways: DMS 2 (MIM-D00A), DMS 2.0 (MIM-D00AN), BACnet gateway (MIM-B17 / MIM-B17N), LonWorks Gateway (MIM-B18 / MIM-B18N), SNET 3 Software (MST-P3P) 2. The electricity meter interface module shall support up to 8 watt-hour meters with pulse output. 3. DC 12V, 3A power provided by AC/DC adapter (input 110-240VAC 50/60Hz, provided with electricity meter interface module) COMMUNICATION INTERFACE MODULE (MIM-N01) A. B. Function: 1. Communication device that interfaces DVM S indoor and outdoor units with DVM Plus III central control systems (MCM-A202D, MIMD00A, MIM-B17, MIM-B18, MCM-A300N). 2. Communication device that interfaces DVM Plus III indoor and outdoor units with DVM S central control systems (MCM-A202DN, MIM-D00AN, MIM-B17N, MIM-B18N, MCM-A300N). 3. Communication device that interfaces Samsung single zone and multi-split systems: CH***CAV, DH***CAV, MH0**FXCA*A (FJM), AR**HSFSHWK (Whisper), and AQN**VFUAGM (Max) systems with DVM S central control systems (MCM-A202DN, MIM-D00AN, MIMB17N, MIM-B18N, MCM-A300N). Connection: DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 60 SAMSUNG Electronics HVAC 1. DC 12V 2. RS485 communication (F1/F2) to outdoor unit with supplied connection wire. 3. RS485 communication (R1/R2) to DVM Plus III / DVM S central control system(s). 4. Mounts in MAIN outdoor unit (single zone, wall mounted units may require installation at indoor unit with included enclosure). 5. 1 X MIM-N01 for each system (1-3 outdoor modules). 5.16. MODE SELECTOR SWITCH FOR HEAT PUMP SYSTEMS (MCM-C200) A. Function: 1. The mode selector switch shall connect to SAMSUNG DVM S outdoor unit models AM***FX***H/AA to easily switch operation mode of the connected system 2. The mode selector switch shall allow for mode change options: Cool, Heat, and Auto. B. Connection: 1. The mode selector switch shall include a connection harness that connects to MAIN outdoor unit PCB. 2. The mode selector switch shall install in MAIN outdoor unit as standard. The connection harness can be extended up to 328’ 3. The mode selector switch shall only connect to and control one system. 5.17. MOTION DETECTOR (MCR-SMA) A. Function: 1. The motion detector shall connect to SAMSUNG DVM S Mini 4-Way cassette models AM0**FNNDCH/AA. 2. The motion detector shall monitor occupancy and turn off indoor unit after motion is not sensed for the specified duration (30, 60, 120, and 180 minutes). 3. The motion detector shall monitor occupancy and adjust target evaporator temperature after motion is not sensed for the specified duration (30, 60, 120, and 180 minutes) thus lowering capacity of unit to reduce energy use. DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 61 SAMSUNG Electronics HVAC B. Connection: 1. The motion detector shall install in the corner of the mini 4-way cassette fascia panel. 2. The motion detector shall connect to the indoor unit PCB with provided cable. DRAFT: 07/29/2014 www.SamsungDVM-S.com Specifications are subject to change without notice. 62