Slides

advertisement

Pumps and Pumping Stations

• Pumps add energy to fluids and therefore are accounted for in the energy equation

• Energy required by the pump depends on:

– Discharge rate

– Resistance to flow (head that the pump must overcome)

– Pump efficiency (ratio of power entering fluid to power supplied to the pump)

– Efficiency of the drive (usually an electric motor) v

2

1

2 g

 p

1

 

1

H pump

 v

2

2

2 g

 p

2 z

2

H

L

H

L

  h f

  h minor

  h f

 

K i v

2

2 g

Pump Jargon

• (Total) Static head – difference in head between suction and discharge sides of pump in the absence of flow; equals difference in elevation of free surfaces of the fluid source and destination

• Static suction head – head on suction side of pump in absence of flow, if pressure at that point is >0

• Static discharge head – head on discharge side of pump in absence of flow

Static discharge head

Total static head

Static suction head

Pump Jargon

• (Total) Static head – difference in head between suction and discharge sides of pump in the absence of flow; equals difference in elevation of free surfaces of the fluid source and destination

• Static suction lift – negative head on suction side of pump in absence of flow, if pressure at that point is <0

• Static discharge head – head on discharge side of pump in absence of flow

Static discharge head

Total static head Static suction lift

Pump Jargon

Static discharge head Static discharge head

Total static head (both)

Static suction head

Static suction lift

Total static h ead

Static discharge head

Static suction head

Static d a

Static suction lif t

Note: Suction and discharge head / lift measured from pump centerline

Pump Jargon

• (Total) Dynamic head, dynamic suction head or lift, and dynamic discharge head – same as corresponding static heads, but for a given pumping scenario; includes frictional and minor headlosses

Energy Line

Total dynamic head

Dynamic discharge head

Dynamic suction lift

Example. Determine the static head, total dynamic head (TDH), and total headloss in the system shown below.

El = 730 ft

El = 640 ft p s

=

6 psig

El = 630 ft p d

=48 psig

Total static head

  

TDH

48

  psi

 

2.31 ft psi

124.7 ft

H

L

TDH Static head

    

24.7 ft

Example. A booster pumping station is being designed to transport water from an aqueduct to a water supply reservoir, as shown below.

The maximum design flow is 25 mgd (38.68 ft 3 /s). Determine the required TDH, given the following:

• H-W ‘ C ’ values are 120 on suction side and 145 on discharge side

• Minor loss coefficients are

0.50 for pipe entrance

0.18 for 45 o bend in a 48-in pipe

0.30 for 90 o bend in a 36-in pipe

0.16 and 0.35 for 30-in and 36-in butterfly valves, respectively

• Minor loss for an expansion is 0.25( v

2

2

 v

1

2 )/2 g

El = 6349 to

6357 ft

30

 to 48

 expansion

El = 6127 to

6132 ft

Short 30

 pipe w/30

 butterfly valve

4000

 of 48

 pipe w/two 45 o bends

8500

 of 36

 pipe w/one

90 o bend and eight butterfly valves

1.

Determine pipeline velocities from v = Q/A .

.

v

30

= 7.88 ft/s, v

36

= 5.47 ft/s, v

48

= 3.08 ft/s

2.

Minor losses, suction side:

Entrance: h

L

0.50

2 v

30

2 g

0.49 ft

Butterfly valve:

Expansion: o

Two 45 bends: h

L

0.16

2 v

30

2 g

0.16 ft h

L

0.25

 v

2

30

 v

2

48

2 g

0.21 ft h

L

2 * 0.18

2 v

48

2 g

0.05 ft

 h

L ,minor

0.91 ft

3.

Minor losses, discharge side:

8 Butterfly valves: o

One 90 bend: h

L

8* 0.35

2 v

36

2 g

1.30 ft h

L

0.30

2 v

36

2 g

 h

L ,minor

0.14 ft

1.90 ft

4.

Pipe friction losses:

S

 h

L f

Q

0.43

CD

2.63

 1.85

 h L f

Q

0.43

CD

2.63

 1.85

h h

 

4000

38.7

  

2.63

 1.85

2.76 ft

 

8500

 

38.7

  

2.63

 1.85

16.77 ft

5.

Loss of velocity head at exit:

Exit: h

L

 v

2

2

36 g

0.46 ft

6.

Total static head under worst-case scenario (lowest water level in aqueduct, highest in reservoir):

Static head

    

230 ft

7.

Total dynamic head required:

TDH

H static

  h

  h f

 h

230

       

252.8 ft

Pump Power

P

Q

TDH

 

E p

 

• P = Power supplied to the pump from the shaft; also called ‘brake power’ (kW or hp)

• Q = Flow (m 3 /s or ft 3 /s)

• TDH = Total dynamic head

= Specific wt. of fluid (9800 N/m 3 or 62.4 lb/ft 3 at 20 o C)

• CF = conversion factor: 1000 W/kW for SI, 550 (ft-lb/s)/hp for US

• E p

= pump efficiency, dimensionless; accounts only for pump, not the drive unit (electric motor)

Useful conversion: 0.746 kW/hp

Example. Water is pumped 10 miles from a lake at elevation 100 ft to a reservoir at 230 ft. What is the monthly power cost at $0.08/kW-hr, assuming continuous pumping and given the following info:

• Diameter D = 48 in; Roughness e

= 0.003 ft, Efficiency P e

• Flow = 25 mgd = 38.68 ft 3 /s

• T = 60 o F

=80%

El = 230 ft 2

• Ignore minor losses

10 mi of 48

 pipe, e

=0.003 ft

El = 100 ft

1 v

1

2

2 g

 p

1

 

1

H pump

 v

2

2

2 g

 p

2

 

2

H

L

H pump

TDH z

2

 

1

H stat

H

L

 h f

TDH

H stat

 h f

El = 230 ft 2

10 mi of 48

 pipe, e

=0.0003 ft

El = 100 ft

1

TDH

H stat

 h f

H

 stat

 h f

 f

L

 v

2

D  2 g 

 

130 ft Find f from Moody diagram

Re

 vD

3.08 ft/s

 

5 2

1.22x10 ft /s

1.01x10

6 v

/

3.08 ft/s e

D

0.003 ft

4 ft

7.5x10

4

El = 100 ft

1

El = 230 ft 2

10 mi of 48

 pipe, e

=0.0003 ft

Re

1.01x10

6 e

D

7.5x10

4 f

0.0185

h f

 

0.0187

 10*5280 ft

4 ft

3.08 ft/s

2 32.2 ft/s

2

2

 

36.4 ft

TDH

H stat

 h f

   

166.4 ft

P

Q

TDH

 

E p

 

3

   

62.4 lb/ft

3

550 ft-lb/s hp

0.80

918 hp

  

Daily cost 918 hp 0.746

kW



$0.08

hp   kW-hr

24 hr d

$1315 / d

Pump Selection

• System curve – indicates TDH required as a function of Q for the given system

– For a given static head, TDH depends only on H

L

, which is approximately proportional to v 2 /2 g

– Q is proportion to v , so H

L

Q 1.85

is approximately proportional to if H-W eqn is used to model h f

)

Q 2

– System curve is therefore approximately parabolic

(or

Example. Generate the system curve for the pumping scenario shown below. The pump is close enough to the source reservoir that suction pipe friction can be ignored, but valves, fittings, and other sources of minor losses should be considered. On the discharge side, the 1000 ft of 16-in pipe connects the pump to the receiving reservoir. The flow is fully turbulent with D-W friction factor of 0.02. Coefficients for minor losses are shown below.

40 ft

6 ft

K values

Suction Discharge

1 @ 0.10

1 @ 0.12

1 @ 0.12

1 @ 0.20

1 @ 0.30

1 @ 0.60

2 @ 1.00

4 @ 1.00

The sum of the K values for minor losses is 2.52 on the suction side and 5.52 on the discharge side. The total of minor headlosses is therefore 8.04 v 2 /2 g .

An additional 1.0 v 2 /2 g of velocity head is lost when the water enters the receiving reservoir.

The frictional headloss is: h f

 f

L v

2

 

0.02

1000 ft

 v

1.33 ft

2

2 g v

2

15

2 g

Total headloss is therefore (8.04+1.0+15.0) v 2 /2 g = 24.04 v 2 /2 g . v can be written as Q / A , and A = p

D 2 / 4 = 1.40 ft 2 . The static head is 34 ft. So:

TDH

 v

2

H stat

H

L

34 ft

24.04

2 g

34 ft

24.04

Q / 1.40 ft

2

2

2

34 ft 0.19

s

2 ft

5

Q

2

180

160

140

120

100

80

60

40

20

0

0

TDH

34ft

0.19

s

2 ft 5

Q

2

5

Static head

10 15

Discharge, Q (ft

3

/s)

System curve

20 25

Pump Selection

• Pump curve – indicates TDH provided by the pump as a function of Q ;

– Depends on particular pump; info usually provided by manufacturer

– TDH at zero flow is called the ‘shutoff head’

• Pump efficiency

– Can be plotted as fcn( Q ), along with pump curve, on a single graph

– Typically drops fairly rapidly on either side of an optimum; flow at optimum efficiency known as “normal” or “rated” capacity

– Ideally, pump should be chosen so that operating point corresponds to nearly peak pump efficiency (‘BEP’, best efficiency point)

Pump Performance and Efficiency Curves

Shutoff head

Rated hp

Rated capacity

Pump Selection

Pump Efficiency

• Pump curves depend on pump geometry (impeller D ) and speed

Pump Selection

• At any instant, a system has a single Q and a single TDH, so both curves must pass through that point;  operating point is intersection of system and pump curves

Pump System Curve

• System curve may change over time, due to fluctuating reservoir levels, gradual changes in friction coefficients, or changed valve settings.

Pump Selection: Multiple Pumps

• Pumps often used in series or parallel to achieve desired pumping scenario

• In most cases, a backup pump must be provided to meet maximum flow conditions if one of the operating (‘duty’) pumps is out of service.

• Pumps in series have the same Q , so if they are identical, they each impart the same TDH, and the total TDH is additive

• Pumps in parallel must operate against the same TDH, so if they are identical, they contribute equal Q , and the total Q is additive

Adding a second pump moves the operating point “up” the system curve, but in different ways for series and parallel operation

Example. A pump station is to be designed for an ultimate Q of 1200 gpm at a TDH of 80 ft. At present, it must deliver 750 gpm at 60 ft.

Two types of pump are available, with pump curves as shown. Select appropriate pumps and describe the operating strategy. How will the system operate under an interim condition when the requirement is for

600 gpm and 80-ft TDH?

120

110

100

90

80

70

60

50

40

30

20

10

0

0

200

70

60

50

40

400 600 800

Flow rate (gpm)

Pump B

Pump A

1000 1200

Either type of pump can meet current needs (750 gpm at 60 ft); pump

B will supply slightly more flow and head than needed, so a valve could be partially closed. Pump B has higher efficiency under these conditions, and so would be preferred.

120

110

100

90

80

70

60

50

40

30

20

10

0

0

200

70

60

50

40

400 600 800

Flow rate (gpm)

Pump B

Pump A

1000 1200

The pump characteristic curve for two type-B pumps in parallel can be drawn by taking the curve for one type-B pump, and doubling Q at each value of TDH. Such a scenario would meet the ultimate need

(1200 gpm at 80 ft), as shown below.

120

110

100

90

80

70

60

50

40

30

20

10

0

0

200

70

60

50

40

400 600 800

Flow rate (gpm)

Pump B

Pump A

1000 1200

A pump characteristic curve for one type-A and one type-B pump in parallel can be drawn in the same way. This arrangement would also meet the ultimate demand. Note that the type-B pump provides no flow at TDH>113 ft, so at higher TDH, the composite curve is identical to that for just one type-A pump. (A check valve would prevent reverse flow through pump B.) Again, since type B is more efficient, two type-B pumps would be preferred over one type-A and one type-B.

120

110

100

90

80

70

60

50

40

30

20

10

0

0

200

70

60

50

40

400 600 800

Flow rate (gpm)

One A and one

B in parallel

Pump B

Pump A

1000 1200

At the interim conditions, a single type B pump would suffice.

A third type B pump would be required as backup.

120

110

100

90

80

70

60

50

40

30

20

10

0

0

One A and one

B in parallel

200

70

60

50

40

400 600 800

Flow rate (gpm)

Pump B

Pump A

1000 1200

Download