Designing a High Efficiency Ventilation System to Meet ASHRAE

advertisement

Implementing Demand

Controlled Ventilation to Meet

ASHRAE Standard 62.1 - 2010

By Klas C. Haglid, P.E., R.A., CEM

1

Klas C. Haglid, P.E., R.A., CEM - Bio

• ASHRAE Distinguished Service Award

• 2011 ASHRAE Handbook, HVAC Applications and Management, Chapter 37,–

Author, Klas C. Haglid P.E. R.A.

• ASHRAE Standard 189.1, Corresponding Member

• GPC 32P - Sustainable, High Performance Operations & Maintenance, Voting

Member, Contributing, Co-Author

• Technical Committee 5.5 - Air-To-Air Energy Recovery, Handbook Subcommittee

Chairman, Past Chairman

• Technical Committee 7.6 - System Energy Utilization, Voting Member

• Technical Committee 7.8 - Owning and Operating Costs of Commercial Buildings,

Past Chairman

• ASHRAE Standard 84-1991R, Voting Member

• Reviewed draft of ASHRAE Standard 84-1991R and provided engineering details for efficiency calculations.

2

Challenge

• Complying with ASHRAE Std. 62.1-2010 to improve IAQ while increasing energy efficiency

ASHRAE Std. 90.1 can be accomplished with:

– Displacement Ventilation

– Demand Controlled Ventilation

– Energy Recovery Ventilator

– Variable Speed Drives

3

ASHRAE Std. 62.1-2010

• Ventilation for Acceptable Indoor Air Quality

– How to determine minimum prescriptive ventilation rates

– How to use Demand Side Ventilation to meet

ASHRAE Standard 62.1-2010

4

Definitions

“acceptable indoor air quality: air in which there are no known contaminants at harmful concentrations as determined by cognizant authorities and with which a substantial majority (80% or more) of the people exposed do not express dissatisfaction .”

–ASHRAE Standard 62.1-2010 pg. 3

5

6.1.1 Ventilation Rate Procedure

• The following procedure for determining the minimum prescriptive ventilation rates can be used on any zone type.

• 6.1.1 Takes into consideration:

– Space type

– Number of Occupants

– Floor Area

– Typical contaminant sources and source strength

6

Ventilation Rate Procedure -

Breathing Zone Outdoor Airflow

• V bz

= R p

P z

+ R a

A z where:

• A z

• P z

= zone floor area

= zone population

• R p

= outdoor airflow rate required per person as determined from Table 6-1*.

• R a

= outdoor airflow rate required per unit area as determined from Table 6-1*.

*Table 6-1 from ASHRAE Standard 62.1-2010

7

Office Example

What is the prescriptive design for outdoor air (cfm) of a 1500 square foot office with 12 occupants?

Eq 6-1 : V bz

= R p

P z

+ R a

A z

Design inputs for office space:

Pz = 12 people

Az = 1,500 square feet of floor area

V bz

= (5x12) + (.06 x 1500) = 60 + 90 = 150 cfm

8

School Example

What is the prescriptive design for outdoor air (cfm) of a 1100 square foot classroom with 30 students?

Eq 6-1 : V bz

= R p

P z

+ R a

A z

From Table 6-1:

R p

R a

= 10 cfm/person

= 0.12 cfm/ft 2

Design inputs from school classroom project for ventilation:

P z

A z

= 30 people

= 1100 square feet

V bz

= (10 x 30) + (.12 x 1100) = 300 + 132 = 432 cfm

9

General Manufacturing Example

(Excludes Heavy Industrial and processes using chemicals)

What is the prescriptive design for outdoor air (cfm) of a 50,000 square foot coat hanger production facility with 20 machinists?

Eq 6-1 : V bz

= R p

P z

+ R a

A z

From Table 6-1:

R p

R a

= 10 cfm/person

= 0.18 cfm/ft 2

Increase

Production facility input data:

P z

A z

= 20 people

= 50,000 square feet of floor area

V bz

= (10 x 20) + (.18 x 50000) = 200 + 9,000= 9,200 cfm

Notice the Area outdoor air rate (Ra) increased for a manufacturing facility.

10

Ventilation Rate Procedure –

Zone Outdoor Airflow

• V oz

= V bz

/E z

• (E z

) The zone air distribution effectiveness shall be determined using ASHRAE Std.

62.1-2010, Table 6-2.

(Partial Table)

11

Methods of Providing Outdoor

Air to Zone

• Dilution Ventilation

• Displacement Ventilation

12

Dilution Ventilation

It’s important to design ventilation system to have maximum air distribution. This will help eliminate dead space and short circuiting of air flow

UV is not properly distributing air across classroom

13

Dilution Ventilation

• Typical in U.S. construction

• Outdoor air is brought into space and dilutes contaminant concentrations in the space.

• Adequate air mixing

14

Displacement Ventilation

Diagram shows good air circulation providing fresh air on one end of room and exhaust pulling air out on the other end to maximize removing contaminant concentrations

15

Displacement Ventilation (DV)

• Uses natural convection to provide “Buoyancyassisted forced ventilation”

• Effectively removes contaminants from people and objects locally

• ASHRAE Std. 62.1-2010 Table 6-2 recognizes DV to be 1.2 times more effective than traditional dilution ventilation

• Some applications measured DV to be 2 to 2.5 more effective than traditional dilution ventilation

16

Displacement Ventilation

• Using displacement ventilation and then measuring air quality of the space is an effective way to improve

IAQ

• Often times, balancing airflow according to how effective the displacement ventilation system is can reduce required airflow by 50%

– This saves energy and reduces latent loads

– Can be achieved with Variable Speed Drives (VSD)

17

Demand Controlled Ventilation

(DCV)

• “any means by which the breathing zone outdoor airflow (Vbz) can be varied to the occupied space or spaces based on the actual or estimated number of occupants and/or ventilation requirements of the occupied zone.”

– ASHRAE Std. 62.1-2010 pg. 4

18

Example of DCV Methods

Fan

Relays

ERV

CO2 Sensor comes on over

700 ppm and turns off under

600 ppm

People

ERV- Energy Recovery

Ventilator

EA- Exhaust Air

SOA- Supply Outside Air

EA

SOA

19

DCV

• CO

2 ppm concentrations in outdoor air generally range from 300 to 500

• ASHRAE std. 62.1 2007 and 2010 recognize 700 ppm of CO

2 above outdoor ambient levels or 1000 to 1200 ppm to be acceptable air quality for an indoor space. Reference page 37 of Appendix C

• Displacement Ventilation with CO

1000 ppm

2

Demand Controlled Ventilation properly engineered and installed will keep CO

2 levels well below

• DCV can reduce runtime from 168 hours per week to 30 hours per week for a classroom. That is an 82% reduction in runtime.

20

Summary of Ventilation Rates

• Determine prescriptive design ventilation rate for zone by using Ventilation Rate Procedure

• Determine Method of Ventilation

– Dilution

– Displacement – up to 2.5 times more effective

• Choose appropriate method to control the ventilation system and monitor the contaminants of concern

– CO2 sensor

– VSD – Variable Speed Drive to reduce fan speed to balance and optimize ERV efficiency

21

Not All ERVs Are the Same

• ERV Features to Compare:

– Airflow Arrangement

• Thermal Effectiveness

– Pressure Drop

– Fan Efficiency

– Maintenance

– Sound Levels

22

Heat Exchanger Airflow Arrangement

ASHRAE states:

• Counter-flow heat exchangers are theoretically capable of achieving 100% Sensible Effectiveness*

• Parallel Flow heat exchangers: 50% (Max)

• Cross-flow heat exchangers and

Enthalpy Wheels: 50-75% (Max)

*Note: Source: 2012 ASHRAE Handbook – HVAC Systems and Equipment,

Chapter 26: Air-to-Air Energy Recovery Equipment.

23

Fan Affinity Laws

• Assuming fan diameter and air density are constant

• Eq (1) : 𝐢𝐹𝑀

2

=

𝑅𝑃𝑀

2

𝑅𝑃𝑀

1 π‘₯ 𝐢𝐹𝑀

1

• Eq (2) : 𝑆𝑃

2

• Eq (3) : 𝐡𝐻𝑃

= (

𝑅𝑃𝑀

2

𝑅𝑃𝑀

1

) 2 π‘₯ 𝑆𝑃

1

2

= (

𝑅𝑃𝑀

2

𝑅𝑃𝑀

1

) 3 π‘₯ 𝐡𝐻𝑃

1

24

Example

• What is the percent difference in BHP required to run a ventilation system if alternative 2 has a 50% increase in static pressure from alternative 1?

• Altenative 1 Conditions:

– CFM = 8,000

– SP = 1” in wg

– BHP = 5

– RPM = 1000

25

Example Continued

• Rearranging Eq (2):

– RPM

2

– RPM

2

= SP

2

/SP

1 x RPM

1

= 1.5/1 x 1000 = 1225

Eq (3):

BHP

2

BHP

2

= BHP

1 x ( RPM

2

/RPM

1

) 3

= 5 x ( 1225/1000) 3 = 9.2 BHP

9.2-5/5 = 84% Increase

A 50% increase in static pressure results in an 84% increase in power consumption

26

High Efficiency Fans

• Typical fan efficiency can range from 5 to 10 W/cfm

• A high efficiency fan can be expected to be approximately 0.2

W/cfm

• The EER of an ERV is formulated by the BTUs recovered divided by the watts of power consumed from the fan energy

EER =

BTUs Recovered

Watts of Fan Power

27

Efficiency is Essential

160

140

120

100

80

60

40

20

0

High Eff. ERV

Typical ERV

Typical ERV has an

EER of around 10.

High efficiency ERV can be well above

120.

Effectiveness (%) Fan Power (W) EER (BTU/W)

Combining premium Efficiency fans with High efficiency ERVs and a low static pressure system can yield great energy savings

28

Maintenance Costs are Essential

• There’s more to a product than its initial costs and efficiency – Maintenance costs can make or break your bottom line

• Look for :

• Corrosion resistant equipment

• Minimal moving parts

• Low static pressure

• Use appropriate filter type for equipment

29

Tools to Meet ASHRAE Std. 62.1 and Improve IAQ

While Increasing Energy Efficiency, ASHRAE Std. 90.1

• Displacement Ventilation

• Demand Controlled Ventilation

– CO2 controls or other contaminant monitoring sensors

• ERV

– Counter flow heat exchanger

– Low Pressure Drops

– High efficiency fans

• Variable Speed Drives

– Air balancing

– Better control

30

Download