Fuel Oil Piping Systems - MD Anderson Cancer Center

advertisement
MDACC Project No. XX-XXXX
A/E Name
A/E Project No.
MD ANDERSON PROJECT NAME
Issue Description
Month, 00, 0000
SECTION 23 11 13 – FUEL OIL PIPING SYSTEMS
PART 1 - GENERAL
1.01
RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General Conditions and Division
01 Specification Sections, apply to this Section.
B. Specifications throughout all Divisions of the Project Manual are directly applicable to this
Section, and this Section is directly applicable to them.
1.02
SUMMARY
A. Perform all Work required to provide and install fuel oil piping systems.
B. Provide a complete integrated emergency fuel system for all diesel driven equipment as
shown in the Contract Documents. This specification requires system coordination,
equipment, installation guidance, programming, startup, training and fuel stabilization
treatment to be the responsibility of a single specialized fuel system supplier. This
specification section includes Contractor responsibility for all materials, labor, design, code
compliance, permits, inspections, piping, specialty components, fuel leak detection, fuel
monitoring, and control systems installation. The system shall be in accordance with design
standards and shall be designed and built for reliability. Fuel equipment supplier shall be
responsible for all field control wire and conduit associated with the fuel system to ensure a
fully functional and coordinated system and maintain a single point of system responsibility.
C. Equipment and related material included:
1. Main fuel storage tank(s) and accessories
2. Day tank(s) and accessories
3. Fuel distribution pipe, valves and fittings including automatic tank selection valves and
related controls
4. Painting (primer) and above and below grade labels of pipe system
5. Re-Fueling equipment, controls, alarms and related operations
6. Fuel transfer and control from main tank(s) to Day tank(s)
7. Fuel maintenance/filtration system
8. Automatic Tank gauge level and leak monitoring system
9. Fuel piping leak detection sensors and monitoring system
10. Integrated control and monitoring.
11. Control system interface with building management system.
12. Control system interface with building fire alarm system.
The University of Texas
M. D. Anderson Cancer Center
MS082812
FUEL OIL PIPING SYSTEMS
23 11 13
1 OF 14
MDACC Project No. XX-XXXX
A/E Name
A/E Project No.
MD ANDERSON PROJECT NAME
Issue Description
Month, 00, 0000
13. Spill kits and signage in each room containing fuel.
14. Field required device control conduit and wire equipment and labor
15. Function testing and commissioning labor
16. Owner Training
1.03
REFERENCE STANDARDS
A. The latest published edition of a reference shall be applicable to this Project unless identified
by a specific edition date.
B. All reference amendments adopted prior to the effective date of this Contract shall be
applicable to this Project.
C. All materials, installation and workmanship shall comply with the applicable requirements and
standards addressed within the following references:
1. ANSI B31.1 - Power Piping.
2. ANSI B31.4 - Pipeline Transportation Systems for Liquid Hydrocarbons and Other
Liquids.
3. ANSI B31.9 - Building Service Piping.
4. ANSI / ASME A13.1 Labeling Guide (General Pipe Marking Standards).
5. API 2000 - Venting Atmospheric and Low Pressure Storage Tanks.
6. ASME RTP1 - Reinforced Thermal Plastic Corrosion-Resistant Equipment.
7. ASME Section 9 - Welding and Brazing Qualifications.
8. ASME B16.3 - Malleable Iron Threaded Fittings.
9. ASME B36.10 - Welded and Seamless Wrought Steel Pipe.
10. ASTM A53 - Pipe, Steel, Black and Hot-Dipped Zinc Coated, Welded and Seamless.
11. ASTM A234 - Pipe Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and
Elevated Temperatures.
12. ASTM D4021-Standard Specification for Glass-Fiber-Reinforced Polyester Underground
Petroleum Storage Tanks
13. NFPA 30 - Flammable and Combustible Liquids Code.
14. NFPA 31 - Installation of Oil Burning Equipment.
15. NFPA 37 – Installation and Use of Stationary Combustion Engines and Turbines.
16. NFPA 70 - National Electric Code.
The University of Texas
M. D. Anderson Cancer Center
MS082812
FUEL OIL PIPING SYSTEMS
23 11 13
2 OF 14
MDACC Project No. XX-XXXX
A/E Name
A/E Project No.
MD ANDERSON PROJECT NAME
Issue Description
Month, 00, 0000
17. NFPA 99 – Standard for Healthcare Facilities.
18. NFPA 110 – Standard for Emergency and Standby Power Systems.
19. UL 508 - The UL Safety Standard for Industrial Control Equipment.
20. International Fire Code
21. UL 1316 - Glass-Fiber-Reinforced Plastic Underground Tanks for Petroleum Products.
22. TNRCC, Chapter 334 - Underground and Aboveground Storage Tanks.
23. Conform to applicable EPA, State of Texas and Local Regulations for installation of fuel
oil systems.
1.04
QUALITY ASSURANCE
A. Manufacturer: Equipment, controls and all fuel specialty devices shall be provided by a single
supplier to ensure a complete functional and coordinated system with single source
responsibility. Supplier shall give guidance to equipment and device installation and shall
complete all programming, commissioning and owner training. The supplier shall be a firm
with 5 years of documented experience in the installation of emergency fuel systems. .
B. Installer: Company specializing in performing the work of this Section with minimum three (3)
years documented experience. Bidding contractor shall hold license(s) as required by the
AHJ.
C. Pollution Liability Insurance: Required by both Subcontractor and system Supplier.
Subcontractor and Supplier may provide the required coverage as part of their general liability
insurance coverage. If Subcontractor’s and Suppliers general liability insurance excludes such
coverage, then Subcontractor must maintain a pollution Liability policy that includes coverage
for fuel spillage/contamination events, such as system failures, or leaks, in a minimum
amount of $l,000,000 per occurrence and in aggregate. Such policy must name Owner,
Owner's Lender(s), and Contractor as additional insureds and contain a waiver of subrogation
in favor of Owner, Owner's Lender(s), and Contractor
D. Professional Liability Insurance: If Subcontractor’s and Suppliers scope includes any design
or system recommendations, then the Subcontractor and Supplier must carry Professional
Liability: $1,000,000 per claims made and in aggregate. If Subcontractor's or Suppliers
general liability insurance excludes such coverage, then Subcontractor or Supplier must
maintain a professional liability policy that includes coverage for design work related to fuel oil
systems and the related design and specification work. This coverage must protect the
Subcontractor, Contractor, Owner and Owner's Lender(s) from liability arising out of errors
and omissions in the performance of design and/or engineering services provided by
Subcontractor, its employees or consultants.
E. Valves: Manufacturer’s name and pressure rating marked on valve body.
F. Welding Materials and Procedures: Conform to ASME Code.
G. Welders Certification: In accordance with ASME Section 9.
H. Maintain one copy of each document at the Project Site.
The University of Texas
M. D. Anderson Cancer Center
MS082812
FUEL OIL PIPING SYSTEMS
23 11 13
3 OF 14
MDACC Project No. XX-XXXX
A/E Name
A/E Project No.
1.05
MD ANDERSON PROJECT NAME
Issue Description
Month, 00, 0000
SUBMITTALS
A. Supplier & Contractor Documentation
1. Both Supplier and Contractor shall submit list of recently completed projects and proof of
insurance coverage as indicted herein.
B. Shop Drawings:
1. The drawing(s) need to indicate system layout with the location and elevation of the
tank(s) dimensions, accessories, including manholes and hold down straps and / or rods.
2. The drawings shall also indicate the location, elevation with slope of piping, pipe sizes,
instrumentation tubing for the piping leak detection system, and conduit requirements and
routing for electrical power and for protection of control wiring and tubing.
C. Product Data:
1. Provide data on pipe materials, pipe fittings, valves and accessories. Provide
manufacturers catalog information. Indicate valve class, material, dimensional data and
ratings.
2. Provide manufacturer's products installation instructions and calibration charts.
D. Record Documents:
1. Record documents shall include as built drawings, pressure test actual location of piping
system, storage tank(s) and system components.
2. As built drawings shall show actual tank(s) location of
conduit for power, control wiring and elevations.
pipe sizes, valves, sensors,
3. Provide hydrostatic test procedure for engineering review and approval.
4. Provide a detailed commissioning plan with prefunctional, functional in integrated test to
prove fuel oil storage and delivery system instrumentation that provides fuel level, level
alarms, and leak detection alarms are operable.
E. Operation and Maintenance Data:
1. Include installation instructions, spare parts lists, exploded assembly views.
1.06
REGULATORY REQUIREMENTS
A. Submit and comply with all the requirements of the EPA, state and local authorities having
jurisdiction. Include installation permit/fees for fuel storage tank and all accessories and
appurtenances.
B. Comply with “National Electric Code” for equipment, wiring, and conduit installed under this
section.
The University of Texas
M. D. Anderson Cancer Center
MS082812
FUEL OIL PIPING SYSTEMS
23 11 13
4 OF 14
MDACC Project No. XX-XXXX
A/E Name
A/E Project No.
1.07
MD ANDERSON PROJECT NAME
Issue Description
Month, 00, 0000
DELIVERY, STORAGE AND HANDLING
A. Deliver, store, protect and handle products to the Project Site under provisions of Division 01
and Division 20.
B. Provide temporary protective end caps and closures on tank openings piping and fittings to
preclude damage to threads, and the intrusion unwanted fluids or materials. These protective
measures shall be maintained in place until installations are complete.
PART 2 - PRODUCTS
2.01
GENERAL
A. All materials shall meet or exceed all applicable referenced standards, federal, state and local
requirements, and conform to codes and ordinances of authorities having jurisdiction.
B. Country of Origin: All material and equipment specified in this section shall be made in the
USA of domestic materials.
2.02
FUEL OIL AND TANK VENT PIPING, ABOVE GROUND
A. Steel Pipe: ASTM A53 or ASME B36.10, Schedule 40 black.
1. Fittings: ASTM B16.3, black malleable iron, Class 150 (300 lb. WOG), threaded.
2. Joints: NFPA 30, threaded ANSI B31.4.
3. Thread Sealant: Make up all threaded connections utilizing sealant that is compatible with
intended sevice.
4. Pipe shall be labeled with plastic wrap around labels in accordance with ANSI A13.1. The
labels shall have proper identification for supply piping (Fuel Oil DS) and for return piping
(Fuel Oil DR) Fuel Oil Vent, Fuel Oil Fill and Fuel Oil Drain, etc.
2.03
FUEL OIL PIPING (DS AND DR), BELOW GRADE
A. Provide R.T. (Red Thread) II double-wall secondary containment piping of fiberglass
reinforced epoxy piping and fittings with UL label as manufactured by A.O. Smith Inland, Inc.
1. Fiberglass pipe and fittings shall be joined together with A.O. Smith Adhesive Kit No.
DS-7014.
2. Primary and secondary piping shall be of the same specified material. The secondary
piping shall be minimum one pipe size larger than primary piping.
3. Secondary containment piping shall be joined with two-piece fittings assembled with
standard bolts, nuts and flat washers along with A.O. Smith Inland adhesive.
4. Pipe labels shall be the same as specified in 2.02. and durable to withstand the
environment of being placed on the piping below grade. The plastic wrap labels for piping
below grade shall have metal copper wire integrated within the plastic label material, in
order to detect and locate the pipe with a metal detector.
The University of Texas
M. D. Anderson Cancer Center
MS082812
FUEL OIL PIPING SYSTEMS
23 11 13
5 OF 14
MDACC Project No. XX-XXXX
A/E Name
A/E Project No.
2.04
MD ANDERSON PROJECT NAME
Issue Description
Month, 00, 0000
FLANGES, UNIONS AND COUPLINGS
A. Pipe Size 3 Inches and Under:
1. Ferrous pipe: Class 300 all malleable iron threaded unions.
2. Thread Sealant: Same as specified for fuel oil piping above ground.
2.05
BALL VALVES
A. Forged carbon steel, two piece body, complying with API 607, threaded ends, rated 1500 psi
WOG cold non-shock and 29 inches Hg, Federal Specification WW-V-35C, Type: II,
Composition: CS, Style 3., provide locking handles for field locations, RPTFE Seats and
Packing, blow-out proof stem and adjustable packing gland
2.06
CHECK VALVES
A. Provide carbon or stainless steel spring-loaded check valve with NPT connections.
2.07
PRESSURE REGULATING
A. Pressure regulating valve: Carbon or SS body, steel disc, teflon seat, steel stem and springs,
automatic, direct, acting pressure actuated, threaded ends.
2.08
RELIEF VALVES
A. Provide overpressure relief valve carbon or stainless steel body, steel disc, teflon seat, steel
stem and springs, automatic, direct, acting pressure actuated, threaded ends.
2.09
ANTI-SIPHON VALVES
A. Anti-Siphon Valve: Aluminum, Bronze or Brass body, brass plug, spring loaded, normally
closed, threaded ends, size to resist static siphon head. Locate on all suction lines where fuel
level is at a higher elevation that the equipment and where shown on the drawings
2.10
STRAINERS
A. 150 lb. carbon steel, threaded connections, stainless steel basket, Buna-N or other fuel
compatible gasket
2.11
DAY TANK FUEL FILL SYSTEM
A. Provide a packaged day tank assembly that is Factory assembled and tested for Project
application. Assembly shall maintain adequate flow to each generator regardless of system
demand. A system matched return pump shall be provided to ensure proper pump
performance in order to evacuate the fuel from day tank during an overfill condition. System
shall include at a minimum:
1. Fire Safety Valve: Provide a fusible link carbon steel Emergency Shut-Off Valve
constructed per API 607 at pump set supply and at all equipment supply connections and
as indicated on drawings. Provide fusible link package and limit switch assembly to
monitor the valve position. Switches shall be tied into the fuel control/monitoring system
The University of Texas
M. D. Anderson Cancer Center
MS082812
FUEL OIL PIPING SYSTEMS
23 11 13
6 OF 14
MDACC Project No. XX-XXXX
A/E Name
A/E Project No.
MD ANDERSON PROJECT NAME
Issue Description
Month, 00, 0000
2. Electric Soleniod Fill Valve: Direct Acting, carbon steel or stainless steel body, “0” PSIG
pressure differential, normally closed, NEMA 4, watertight, threaded pipe and conduit
connections. Provide manual over-ride switches for the solenoid fill valve and fuel return
pump in the control panel.
3. Deadman By-pass Valve: Provide a carbon steel spring-return valve constructed per API
607 at each day tank fill valve as a manual bypass and as indicated on drawings.
4. Pipeline Specialties: Isolation valves, unions, strainer, sight flow indicator, check valve
and return pump.
2.12
FLOW INDICATOR
A. Flow Indicator: Carbon steel body, 150 psi rated glass, nylon wheel, as manufactured by
Ernst, OPW or McMaster Carr. Furnish on each day tank supply and return line and each
pump and relief valve discharge and on lines serving main tank and tank selector valves and
at other locations required to properly assess the flow of fuel within the system
2.13
FLEXIBLE CONNCECTOR
A. Flexible Connector: Stainless steel inner hose and braided exterior sleeve, suitable for
minimum 200 psi WOG and 250 degrees F. All flexible connectors must have welded (not
swaged or crimped) ends. All flexible connectors must be vacuum rated.
2.14
FLAME ARRESTOR
A. Flame Arrestor: Each main tank shall include a flame arrestor on the normal vent connection
with Cast Iron body, Cast Iron cover, Brass cap and Stainless Steel arrestor plates.
2.15
OVERFILL PREVENTION VALVE
A. Overfill Prevention Valve: Each main tank compartment shall include an overfill prevention
valve in the re-fueling connection port to automatically stop the flow of fuel into the tank at
90% of maximum tank capacity. The valve shall be a two stage, float operated and suitable
for either above grade or below grade tanks as required by project conditions. Tanks 3,000
gallons and smaller shall have a 2” valve, larger tanks shall have a 3” valve. Valve assembly
shall be UL listed and include a drop tube extended to within 6” of tank bottom
2.16
REMOTE FILL SYSTEM
A. Below Grade System:
1. Fill/spill container shall include a composite top-seal, tight fill adapter and locking fill cap.
To prevent damage from frost heave, normal settling, or roadway traffic, the spill
compartment shall incorporate a flexible bellows protected by a ribbed gravel shroud.
The noncorrosive resin spill compartment shall be readily removable to allow soil testing
directly through the spill container without breaking the concrete. An integral hand pump
for removal of spilled fuel shall be provided.
The University of Texas
M. D. Anderson Cancer Center
MS082812
FUEL OIL PIPING SYSTEMS
23 11 13
7 OF 14
MDACC Project No. XX-XXXX
A/E Name
A/E Project No.
MD ANDERSON PROJECT NAME
Issue Description
Month, 00, 0000
2. Provide a UL 508a listed local and remote fill alarm panel with audible and visual warning
devices, digital display of tank level (percent) for each tank and alarm silence button.
Alarm/Operations panel shall incorporate a “dead front” design to prevent tampering and
shall include a locking hasp, NEMA 4X weather protection, 85% audible/visual warning
and 90% audible/visual warning. Panel shall be interfaced with main tank monitoring
system.
3. Provide a placard with description of electronic warning features for the filling operations
and a tank gauging charge inside cabinet.
2.17
UNDERGROUND FUEL STORAGE TANKS
A. Manufacturers:
1. Containment Systems, Inc.
2. Other acceptable manufacturers offering equivalent products.
a. Xerxes.
B. Tank: Materials shall meet ASTM D4021, and the shall be UL listed and labeled. Tank shall
be constructed as a double wall reinforced glass fiber polyester primary and secondary
containment wall type, capable of containing liquid storage with a specific gravity of 1:1 at
temperatures up to 150 degrees F (65 degrees C), Approved anchor straps and attachments,
fittings, lifting lugs and tapings for accessories shall be included by the tank manufacturer.
C. Capacity:
1. Tank material, volume, diameter and overall length, sizes and the number of tank NPT
fittings, filler cap, manways, and equipment enclosure are indicated on the equipment
schedule of the Owner's Drawings.
2. If the tank(s) deviates from dimensions indicated on the Owner’s Drawings, the
Contractor shall be responsible for all coordination and related cost associated with
required Structural coordination and changes.
2.18
PACKAGED ENCLOSED FUEL TRANSFER PUMP SET (DP-1 AND DP-2)
A. Manufacturers:
1. Veeder-Root, Red Jacket products and design is an approved supplier.
2. Other acceptable manufacturers offering equivalent products may be considered with
proper submission of prior approval request..
B. Fuel Pump Performance and Construction:
1. Fuel pump flowrate, head pressure, motor type, horsepower and voltage is indicated on
the Owner’s Drawings.
The University of Texas
M. D. Anderson Cancer Center
MS082812
FUEL OIL PIPING SYSTEMS
23 11 13
8 OF 14
MDACC Project No. XX-XXXX
A/E Name
A/E Project No.
MD ANDERSON PROJECT NAME
Issue Description
Month, 00, 0000
2. Positive Displacement Pumps: Provide and mount two (2) positive displacement rotary
type pumps, with cast iron housing and self-adjusting mechanical, Carbon ring seals.
Pumps that have aluminum, brass, or bronze housings or rotors are not acceptable.
Packing gland equipped pumps, close-coupled pumps, Carbonator shaft mounted pumps
or centrifugal pumps are not acceptable.
C. Piping and Mounting
1. Provide a 100% redundant duplex pump set that is factory assembled with components
piped and mounted within a continuously welded metal enclosure. Provide a containment
basin with drain connection and factory installed drain valve and plug. The enclosure
shall have an integral basin contain and capture potential internal leaks from all factory
installed piping and components. All package pipe shall be schedule 40 ASTM A-53
Grade “A” with ANSI B16.3 Class 150 malleable iron threaded fittings.
2. Pump Isolation and Check Valves Provide and mount four (4) pump isolation valves.
Locate one (1) valve on the suction and discharge side of each pump. Isolation valves
will allow off-line pump maintenance without system loss of availability. Isolation valves
shall be API 607 carbon steel ball type valves to provide full flow while open and positive
shutoff when closed. Additionally, two (2) carbon steel check valves shall be provided
and mounted, one (1) located on the discharge of each pump.
D. Package Enclosure for Class II Liquid shall be constructed of minimum 12 gauge stainless
steel and feature double doors and locking/latching handle, a spill enclosure for 5 gallons of
fuel, lifting eyes, self supporting stand and have a internal support structure for pumps and
components and if noted, painted with a durable powder coat finish.
E. Fuel transfer package shall include inlet strainer to each pump, isolations valves each pump,
unions at each device, flow switch, pressure relief valves each pump, system pressure
regulating valve, inlet and outlet gauges, sight flow indicators on discharge and safety relief
line and basin leak switch. All materials shall comply with NFPA 30.
2.19
TRANSFER SYSTEM
A. System: Interconnect fuel pumps (DP-1 and DP-2) with emergency generators to
automatically energize transfer pumps when generators start. This in turn will fill day tanks
from main storage tank. The pumps shall automatically stop when generators stop.
1. Alarm: Provide flow switch and timer which shall sound audible alarm if pump DP-1
and/or DP-2 fails to start/stop within one minute after generator starts/stops, respectively.
2. Alarm Reports: Provide low fuel, high fuel, high water and product loss monitor reports.
3. Control Panel: Provide a UL 508a Listed control panel in a NEMA 4 enclosure, complete
with fused disconnect switches, magnetic starters with overload and low voltage
protection, Hand-On Automatic selector switches, an pump alternator, reset buttons,
running lights and alarm bell with alarm silencing switch.
4. Provide and wire to accessible terminal strip the following dry contacts for remote
monitoring by the building automation system (BAS): One set of contacts to activate when
control panel alarms and one set of contacts to activate when fuel flow is present. BAS
Provider shall connect to the building automation system and alarm as directed.
The University of Texas
M. D. Anderson Cancer Center
MS082812
FUEL OIL PIPING SYSTEMS
23 11 13
9 OF 14
MDACC Project No. XX-XXXX
A/E Name
A/E Project No.
MD ANDERSON PROJECT NAME
Issue Description
Month, 00, 0000
5. The control system shall include these functions: day tank panel interface, generator
interface, duplex pump operation with pump status using CTs, electronic fuel flow
indicator, main tank overfill protection and tank inventory and leak monitoring system,
remote fueling operations, automatic tank selection and filtration unit interface. The panel
shall be capable of manual control and override of each transfer pump and solenoid
valve.
6. Control modules shall be UL listed, UL Canada listed, or CE stamped as appropriate for
the location.
7. Monitoring Panel: The monitoring panel shall display the tank volume in gallons. The
panel shall have a touch screen display to graphically indicate all real-time operating and
alarm conditions. All device status and alarms shall be color-coded.
8. Overfill Alarm and Acknowledgement for Re-Fueling Operation: Interface with the remote
fill system for remote alarms, tank and valve status and control all tank selection valves
and position indication when applicable.
9. Interface with the fuel filtration and maintenance system when applicable.
10. The control panel shall display the tank volume in gallons. The panel shall have a touch
screen display to graphically indicate all real-time operating and alarm conditions. Screen
shall UL Listed, minimum 12” color display, 32-Bit CPU, internal memory, battery back-up,
non-volatile memory and historical memory of recent alarm conditions.
11. The HMI display shall graphically depict the main tanks, pumps, selector valves,
generators, day tanks and other system equipments to give operator visual indication of
system operations.
12. Panel shall be Ethernet ready for accessing control system via the internet.
13. Panel shall incorporate an incoming UL Type 98 disconnect or UL Type 489 molded
circuit breaker for incoming power isolation. Each motor shall have an independent
means of disconnect. Where applicable, panel shall incorporate a fused control
transformer and each field termination point shall be readily identified adjacent to each
such terminal.
2.20
FUEL FILTRATION UNIT
A. Manufacturers: STS Automatic Fuel Filtration System meeting the performance requirements
listed herein shall be accepted with proper submission of prior approval request.
B. General: Supply a self contained, Automatic Fuel Oil Transfer and Monitoring System to
ensure a reliable supply of fuel oil to the emergency generators or boilers included in this
project. The system shall include automatic tank selection and valve control when multiple
tank are served by a single unit.
C. Size: As specified within the Contract Documents or based on the manufacturers
recommendations.
The University of Texas
M. D. Anderson Cancer Center
MS082812
FUEL OIL PIPING SYSTEMS
23 11 13
10 OF 14
MDACC Project No. XX-XXXX
A/E Name
A/E Project No.
MD ANDERSON PROJECT NAME
Issue Description
Month, 00, 0000
D. Controls: The Control Cabinet shall be UL 508a Listed. The control cabinet and filtration
package shall be the product of one manufacturer for single source responsibility. Controller
shall be able to automatically start system and run through its’ operation without the need of
human engagement. Controller shall monitor all system functions, integrate with main fuel
system controller via a communications interface and control tank selection valves as
required. Run time and duration shall be field selectable and system shall interface with the
BAS system. System shall have a manual start feature that would allow an operator to initial a
full run cycle.
E. Unit shall include an inlet basket strainer, circulation pump, multi-stage filtration, water
removal, particulate removal to 1 microns, water detection switch and basin leak switch.
F. Unit shall be fully enclosed in a weather tight stainless steel housing
G. Each filter and assembly shall be rated for minimum of 25 GPM for Diesel fuel, have a
pressure rating of 150 PSI, temperature rating of 240˚F, have a manual drain valve, manual
vent, sight glass and water probe on coalescer housing. Each filter shall have a differential
pressure gauge to indicate which element needs to be replaced.
H. Unit shall feature a sight flow indicator, system relief valve (relief valve integral to pump are
NOT acceptable) and integral isolation valves for system maintenance.
I.
2.21
Provide (1) One full replacement set of filters for Owner stock.
FUEL TREATMENT
A. Manufacturers: Power Service or Pre-Approved Equal
B. General: Fuel system supplier shall provide fuel treatment additive required for stabilization of
new fuel based on the following:
1. Clear Diesel – Application rate per manufacturers recommendation.
2. Diesel Kleen – Application rate per manufacturers recommendation.
2.22
FUEL SPILL KIT
A. Manufacturers: Use Fuel Purification Systems, Inc., or Pre-Approved Equal
B. General: Provide a spill kit contained in 2 barrels in each room (or adjacent room) that has
diesel fuel storage.
C. Barrel one of the spill kit shall contain a minimum of: 40 pounds of particulate absorbent, 2
packages of absorbent “socks” 12 feet long and 100 absorbent pads. Barrel two of the spill
kit shall contain 12 gallon wet/dry shop vacuum, 100 foot extension cord, 2 tarpaulins, dust
pan and broom, disposal bags and ties, 1 box contractor towels, 1 box of rubber gloves, 4 pair
protective glasses. Each barrel shall have an easily removable top
PART 3 - EXECUTION
3.01
PREPARATION
A. Verify that excavations are excavated to required grade, are dry, and not over-excavated.
The University of Texas
M. D. Anderson Cancer Center
MS082812
FUEL OIL PIPING SYSTEMS
23 11 13
11 OF 14
MDACC Project No. XX-XXXX
A/E Name
A/E Project No.
MD ANDERSON PROJECT NAME
Issue Description
Month, 00, 0000
B. Ream pipe and tube ends. Remove burrs.
C. Remove scale and dirt, on inside and outside, before assembly.
D. Prepare piping connections to equipment with threaded unions.
3.02
INSTALLATION
A. Installation shall meet or exceed all applicable federal, state and local requirements,
referenced standards and conform to codes and ordinances of authorities having jurisdiction.
B. All installation shall be in accordance with manufacturer’s published recommendations.
C. Piping Installation:
1. Use compatible sealant when assembling all threaded joints and fittings.
2. Route piping in orderly manner and maintain gradient.
3. Install piping to conserve building space and not interfere with use of space.
4. Group piping whenever practical at common elevations.
5. Install piping to allow for expansion and contraction without stressing pipe, joints, or
connected equipment.
6. Provide clearance for access to valves and fittings.
7. Provide access where valves and fittings are not exposed.
8. Prepare pipe, fittings, supports and accessories not prefinished, ready for finish painting.
9. Identify piping systems including underground piping.
10. Install valves with stems upright or horizontal, not inverted.
11. Protect piping systems from entry of foreign materials by temporary covers, completing
sections of the work and isolating parts of completed system.
12. Slope underground fuel supply and vent piping back to storage tank.
13. Secondary containment pipe shall be positioned over product pipe prior to bonding the
product piping. After testing the product pipe, the containment fittings shall be assembled.
The containment system shall then be tested.
D. Fuel Tank Installation:
1. Clean underground tanks prior to delivery to the Project Site. Seal until pipe connections
are made.
2. Install underground tanks on concrete ballast pad with mass equal to tank capacity and
secure with hold down straps and turnbuckles.
3. Backfill underground tanks with material and procedures per manufacturer's instructions.
Do not bed on timbers, beams or cradles.
The University of Texas
M. D. Anderson Cancer Center
MS082812
FUEL OIL PIPING SYSTEMS
23 11 13
12 OF 14
MDACC Project No. XX-XXXX
A/E Name
A/E Project No.
MD ANDERSON PROJECT NAME
Issue Description
Month, 00, 0000
4. Provide piping connections to tanks with unions and swing joints. Provide venting to API
2000.
5. Extend fill line and spill container to grade. Where fill container is installed in soft
conditions (i.e. soil, gravel, asphalt) provide minimum 24 x 24 x 6 inch (600 x 600 x 150
mm) concrete pad.
6. Fill tanks at Project completion with appropriate fuel, including generator day tanks.
3.03
ELECTRICAL SYSTEM
A. Electrical branch circuits from panel board and feeder from main distribution panel shall be
provided by Div 16. Panel to be equipped with means of disconnecting all fueling system
circuits per NFPA 70.
B. All required field control wiring and conduit for the fuel system shall be provided by the
equipment supplier to ensure a complete and coordinated system and maintain a single
source of responsibility. All field control wiring shall be labeled in conjunction with system
devices and shall be verified has required to ensure all devices and equipment are properly
terminated.
C. Tank shall be grounded by Div. 16.
3.04
TESTING
A. Pneumatically test tanks in accordance with manufacturer's recommendations upon arrival at
the Project Site and after tank installation to assure tank integrity.
B. Primary (Product) Piping Test: Hydrostatically test system at 100 psi and carefully check for
leaks. Repair all leaks and retest until proven watertight. Flush system thoroughly with diesel
fuel until all moisture or debris is removed and diesel is clear. Fill system with clean diesel
fuel, close end valves and allow system to remain full. Legally dispose of flush diesel.
C. Secondary Containment Piping Test: Seal secondary containment piping to primary piping at
both ends with concentric termination fittings as recommended by the manufacturer. Provide
test gauge and pipe connection at this point for pneumatic testing. Pneumatically test system
at 10 psi for ten (10) minutes, then soap all joints and check for leaks. Retest until there are
no leaks and system is proven tight.
3.05
FUNCTIONAL TESTING
A. Before witness testing and/or commissioning the system perform these steps to ensure the
system is ready for final acceptance test as required:
1. Ensure all devices are in place and operational.
2. Ensure all controls are operational.
3. Move fuel through system filling and returning to/from day tanks to verify control
sequences.
4. Clean all strainers.
The University of Texas
M. D. Anderson Cancer Center
MS082812
FUEL OIL PIPING SYSTEMS
23 11 13
13 OF 14
MDACC Project No. XX-XXXX
A/E Name
A/E Project No.
MD ANDERSON PROJECT NAME
Issue Description
Month, 00, 0000
B. Perform a complete system commissioning in accordance with the approved commissioning
plan.
3.06
FUEL TREATMENT
A. Coordinate with project testing schedules. Upon completion of all generator load testing and
prior to final fueling of system, fuel system treatment shall be added to storage tanks as
required.
3.07
DEMONSTRATION
A. Train Owner’s personnel on system layout, operational procedures and schedules related to
start-up and shutdown, troubleshooting, servicing, and preventive maintenance as required by
system equipment
END OF SECTION 23 11 13
The University of Texas
M. D. Anderson Cancer Center
MS082812
FUEL OIL PIPING SYSTEMS
23 11 13
14 OF 14
Download