ECE 476 POWER SYSTEM ANALYSIS Lecture 13 Newton-Raphson Power Flow Professor Tom Overbye Department of Electrical and Computer Engineering Announcements Homework 6 is 2.38, 6.8, 6.23, 6.28; you should do it before the exam but need not turn it in. Answers have been posted. First exam is 10/9 in class; closed book, closed notes, one note sheet and calculators allowed. Last year’s tests and solutions have been posted. Abbott power plant and substation field trip, Tuesday 10/14 starting at 12:30pm. We’ll meet at corner of Gregory and Oak streets. Be reading Chapter 6; exam covers up through Section 6.4; we do not explicitly cover 6.1. 1 PV Buses Since the voltage magnitude at PV buses is fixed there is no need to explicitly include these voltages in x or write the reactive power balance equations – – the reactive power output of the generator varies to maintain the fixed terminal voltage (within limits) optionally these variations/equations can be included by just writing the explicit voltage constraint for the generator bus |Vi | – Vi setpoint = 0 2 Two Bus Newton-Raphson Example For the two bus power system shown below, use the Newton-Raphson power flow to determine the voltage magnitude and angle at bus two. Assume that bus one is the slack and SBase = 100 MVA. Line Z = 0.1j One 1.000 pu 0 MW 0 MVR 2 x V2 Ybus Two 1.000 pu 200 MW 100 MVR j10 j10 j 10 j 10 3 Two Bus Example, cont’d General power balance equations Pi Qi n Vi Vk (Gik cosik Bik sin ik ) PGi PDi k 1 n Vi Vk (Gik sin ik Bik cosik ) QGi QDi k 1 Bus two power balance equations V2 V1 (10sin 2 ) 2.0 0 V2 V1 ( 10cos 2 ) V2 (10) 1.0 0 2 4 Two Bus Example, cont’d P2 (x) V2 (10sin 2 ) 2.0 0 Q2 (x) V2 (10 cos 2 ) V2 (10) 1.0 0 2 Now calculate the power flow Jacobian P2 (x) 2 J ( x) Q 2 (x) 2 P2 ( x) V 2 Q 2 ( x) V 2 10 V2 cos 2 10 V2 sin 2 10sin 2 10 cos 2 20 V2 5 Two Bus Example, First Iteration Set v 0, guess x (0) 0 1 Calculate V2 (10sin 2 ) 2.0 f(x ) 2 V2 (10 cos 2 ) V2 (10) 1.0 10sin 2 10 V2 cos 2 (0) J (x ) 10 V2 sin 2 10 cos 2 20 V2 (0) 1 Solve x (1) 0 10 0 2.0 1.0 1 0 10 2.0 1.0 10 0 0 10 0.2 0.9 6 Two Bus Example, Next Iterations 0.9 (10sin(0.2)) 2.0 0.212 f(x ) 2 0.279 0.9(10 cos(0.2)) 0.9 10 1.0 8.82 1.986 (1) J (x ) 1.788 8.199 (1) 1 0.2 8.82 1.986 0.212 0.233 (2) x 0.9 1.788 8.199 0.279 0.8586 0.0145 0.236 (2) (3) f(x ) x 0.0190 0.8554 0.0000906 f(x ) 0.0001175 (3) Done! V2 0.8554 13.52 7 Two Bus Solved Values Once the voltage angle and magnitude at bus 2 are known we can calculate all the other system values, such as the line flows and the generator reactive power output 200.0 MW 168.3 MVR One -200.0 MW -100.0 MVR Line Z = 0.1j 1.000 pu 200.0 MW 168.3 MVR Two 0.855 pu -13.522 Deg 200 MW 100 MVR 8 Two Bus Case Low Voltage Solution This case actually has two solutions! The second "low voltage" is found by using a low initial guess. Set v 0, guess x (0) 0 0.25 Calculate V2 (10sin 2 ) 2.0 f(x ) 2 V2 (10cos 2 ) V2 (10) 1.0 10sin 2 10 V2 cos 2 (0) J (x ) 10 V2 sin 2 10cos 2 20 V2 (0) 2 0.875 2.5 0 0 5 9 Low Voltage Solution, cont'd 1 0 2.5 0 2 0.8 Solve x 0.25 0 5 0.875 0.075 1.462 (2) 1.42 0.921 (2) (3) f (x ) x x 0.534 0.2336 0.220 (1) Low voltage solution 200.0 MW 831.7 MVR One -200.0 MW -100.0 MVR Line Z = 0.1j 1.000 pu 200.0 MW 831.7 MVR Two 0.261 pu -49.914 Deg 200 MW 100 MVR 10 Two Bus Region of Convergence Slide shows the region of convergence for different initial guesses of bus 2 angle (x-axis) and magnitude (y-axis) Red region converges to the high voltage solution, while the yellow region converges to the low voltage solution 11 Using the Power Flow: Example 1 SLA C K3 4 5 A MVA A MVA 1 .0 2 pu 2 1 8 MW 5 4 M var RA Y 3 4 5 sla ck 1 .0 2 pu T IM 3 4 5 A A MVA MVA A SLA C K1 3 8 1 .0 1 pu A MVA RA Y 1 3 8 A 3 3 MW 1 3 M var A MVA A 1 6 .0 M var 1 .0 2 pu MVA 1 8 MW 5 M var MVA MVA 1 .0 2 pu RA Y 6 9 T IM 6 9 P A I6 9 1 .0 1 pu MVA A 2 3 MW 7 M var 1 .0 1 pu 3 7 MW 1 7 MW 3 M var A 1 .0 2 pu A MVA T IM 1 3 8 A Using case from Example 6.13 1 .0 3 pu A MVA 1 .0 0 pu GRO SS6 9 A 1 3 M var MVA A MVA FERNA 6 9 MVA A MVA M O RO 1 3 8 MVA H ISKY 6 9 MVA A 1 2 MW 5 M var A A 2 0 MW 8 M var 1 .0 0 pu A 1 .0 0 pu P ET E6 9 DEM A R6 9 MVA H A NNA H 6 9 5 1 MW 1 5 M var 5 8 MW 4 0 M var 2 9 .0 M var 1 4 .3 M var 1 .0 0 pu A MVA MVA BO B6 9 1 4 0 MW 4 5 M var A MVA 5 6 MW MVA 5 8 MW 3 6 M var MVA 0 .9 9 pu A 1 4 MW 4 M var MVA A MVA MVA 1 .0 1 pu A H A LE6 9 MVA A BLT 6 9 1 .0 1 pu A 1 5 MW 3 M var 1 .0 0 pu BLT 1 3 8 1 .0 0 pu LY NN1 3 8 A 3 3 MW 1 0 M var MVA A A MVA A M A NDA 6 9 1 3 M var 0 MW 0 M var MVA A 0 .9 9 7 pu A MVA 1 .0 2 pu A MVA MVA MVA 1 2 .8 M var A BO B1 3 8 A 4 5 MW 1 2 M var 0 .9 9 pu UIUC 6 9 A H O M ER6 9 WO LEN6 9 4 .8 M var MVA 1 .0 0 pu 1 .0 1 pu 2 1 MW 7 M var A SH IM KO 6 9 7 .4 M var 1 .0 2 pu A MVA MVA MVA 1 0 6 MW 8 M var A 1 5 MW 5 M var A MVA 3 6 MW 1 0 M var A A 6 0 MW 1 2 M var MVA MVA A MVA A 1 .0 0 pu 0 .0 M var 1 .0 1 pu MVA A 7 .2 M var 1 .0 0 pu P A T T EN6 9 MVA MVA A MVA 1 .0 0 pu LA UF6 9 1 .0 2 pu 2 0 MW 3 0 M var 1 .0 0 pu A A MVA MVA 2 3 MW 6 M var 2 2 MW 1 5 M var 0 MW 0 M var LA UF1 3 8 1 .0 1 pu 4 5 MW 0 M var WEBER6 9 1 .0 2 pu BUC KY 1 3 8 RO GER6 9 2 M var 1 4 MW 3 M var A MVA SA V O Y 6 9 1 .0 2 pu A 4 2 MW 2 M var JO 1 3 8 MVA A MVA 1 4 MW 1 .0 1 pu A MVA SA V O Y 1 3 8 JO 3 4 5 A 1 5 0 MW 0 M var MVA A MVA 1 5 0 MW 0 M var A MVA 1 .0 2 pu A MVA 1 .0 3 pu 12 Three Bus PV Case Example For this three bus case we have 2 x 3 V2 P2 (x) PG 2 PD 2 f (x) P3 (x) PG 3 PD3 0 Q2 (x) QD 2 Line Z = 0.1j 0.941 pu One 170.0 MW 68.2 MVR 1.000 pu Line Z = 0.1j Three Two Line Z = 0.1j -7.469 Deg 200 MW 100 MVR 1.000 pu 30 MW 63 MVR 13 Modeling Voltage Dependent Load So far we've assumed that the load is independent of the bus voltage (i.e., constant power). However, the power flow can be easily extended to include voltage depedence with both the real and reactive load. This is done by making PDi and Q Di a function of Vi : n Vi Vk (Gik cos ik Bik sin ik ) PGi PDi ( Vi ) 0 Vi Vk (Gik sin ik Bik cos ik ) QGi QDi ( Vi ) 0 k 1 n k 1 14 Voltage Dependent Load Example In previous two bus example now assume the load is constant impedance, so P2 (x) V2 (10sin 2 ) 2.0 V2 2 0 Q2 (x) V2 (10 cos 2 ) V2 (10) 1.0 V2 0 2 2 Now calculate the power flow Jacobian 10 V2 cos 2 J ( x) 10 V2 sin 2 10sin 2 4.0 V2 10 cos 2 20 V2 2.0 V2 15 Voltage Dependent Load, cont'd Again set v 0, guess x (0) 0 1 Calculate 2 V (10sin ) 2.0 V 2.0 2 2 2 (0) f(x ) 2 2 1.0 V2 (10 cos 2 ) V2 (10) 1.0 V2 10 4 (0) J (x ) 0 12 1 Solve x (1) 0 10 4 2.0 1.0 1 0 12 0.1667 0.9167 16 Voltage Dependent Load, cont'd With constant impedance load the MW/Mvar load at bus 2 varies with the square of the bus 2 voltage magnitude. This if the voltage level is less than 1.0, the load is lower than 200/100 MW/Mvar 160.0 MW 120.0 MVR One -160.0 MW -80.0 MVR Line Z = 0.1j 1.000 pu 160.0 MW 120.0 MVR Two 0.894 pu -10.304 Deg 160 MW 80 MVR 17 Solving Large Power Systems The most difficult computational task is inverting the Jacobian matrix – – – – inverting a full matrix is an order n3 operation, meaning the amount of computation increases with the cube of the size size this amount of computation can be decreased substantially by recognizing that since the Ybus is a sparse matrix, the Jacobian is also a sparse matrix using sparse matrix methods results in a computational order of about n1.5. this is a substantial savings when solving systems with tens of thousands of buses 18 Newton-Raphson Power Flow Advantages – – Disadvantages – – fast convergence as long as initial guess is close to solution large region of convergence each iteration takes much longer than a Gauss-Seidel iteration more complicated to code, particularly when implementing sparse matrix algorithms Newton-Raphson algorithm is very common in power flow analysis 19 Dishonest Newton-Raphson Since most of the time in the Newton-Raphson iteration is spend calculating the inverse of the Jacobian, one way to speed up the iterations is to only calculate/inverse the Jacobian occasionally – – known as the “Dishonest” Newton-Raphson an extreme example is to only calculate the Jacobian for the first iteration Honest: x(v 1) x( v ) - J (x( v ) )-1f (x( v ) ) Dishonest: x(v 1) x( v ) - J (x(0) )-1 f (x( v ) ) Both require f (x(v ) ) for a solution 20 Dishonest Newton-Raphson Example Use the Dishonest Newton-Raphson to solve f ( x) x 2 - 2 0 x (v ) x ( v ) x ( v 1) 1 df ( x ) (v) f ( x ) dx 1 (v) 2 (0) (( x ) - 2) 2x (v) 1 x (0) (( x ( v ) )2 - 2) 2x (0) 21 Dishonest N-R Example, cont’d x ( v 1) x (v) 1 (v) 2 (0) (( x ) - 2) 2x Guess x (0) 1. Iteratively solving we get v 0 1 2 3 4 x (v ) (honest) 1 1.5 1.41667 1.41422 1.41422 x ( v ) (dishonest) 1 1.5 1.375 1.429 1.408 We pay a price in increased iterations, but with decreased computation per iteration 22 Two Bus Dishonest ROC Slide shows the region of convergence for different initial guesses for the 2 bus case using the Dishonest N-R Red region converges to the high voltage solution, while the yellow region converges to the low voltage solution 23 Honest N-R Region of Convergence Maximum of 15 iterations 24 Decoupled Power Flow The completely Dishonest Newton-Raphson is not used for power flow analysis. However several approximations of the Jacobian matrix are used. One common method is the decoupled power flow. In this approach approximations are used to decouple the real and reactive power equations. 25 Decoupled Power Flow Formulation General form of the power flow problem P ( v ) θ Q ( v ) θ P V (v) (v) (v) θ P ( x ) (v ) f ( x ) ( v ) Q ( v ) V Q(x( v ) ) V where P2 (x( v ) ) PD 2 PG 2 (v) P (x ) P (x(v ) ) P P n Dn Gn 26 Decoupling Approximation P ( v ) Q ( v ) Usually the off-diagonal matrices, and V θ are small. Therefore we approximate them as zero: P ( v ) 0 (v ) (v) θ P ( x ) θ (v) f ( x ) ( v ) ( v ) (v ) Q V Q ( x ) 0 V Then the problem can be decoupled θ (v) P θ ( v ) 1 P (x (v) ) V (v) Q V ( v ) 1 (v) Q ( x ) 27 Off-diagonal Jacobian Terms Justification for Jacobian approximations: 1. Usually r x, therefore Gij Bij 2. Usually ij is small so sin ij 0 Therefore Pi Vi Gij cos ij Bij sin ij Vj Qi θ j 0 Vi V j Gij cos ij Bij sin ij 0 28 Decoupled N-R Region of Convergence 29 Fast Decoupled Power Flow By continuing with our Jacobian approximations we can actually obtain a reasonable approximation that is independent of the voltage magnitudes/angles. This means the Jacobian need only be built/inverted once. This approach is known as the fast decoupled power flow (FDPF) FDPF uses the same mismatch equations as standard power flow so it should have same solution The FDPF is widely used, particularly when we only need an approximate solution 30 FDPF Approximations The FDPF makes the following approximations: 1. G ij 0 2. Vi 3. sin ij 0 1 cos ij 1 Then (v ) (v ) P ( x ) Q ( x ) (v) (v ) 1 1 θ B V B (v) (v) V V Where B is just the imaginary part of the Ybus G jB, except the slack bus row/column are omitted 31 FDPF Three Bus Example Use the FDPF to solve the following three bus system Line Z = j0.07 One Two Line Z = j0.05 Three Line Z = j0.1 200 MW 100 MVR 1.000 pu 200 MW 100 MVR Ybus 20 34.3 14.3 j 14.3 24.3 10 10 30 20 32 FDPF Three Bus Example, cont’d Ybus B 1 20 34.3 14.3 24.3 10 j 14.3 24.3 10 B 10 30 20 10 30 0.0477 0.0159 0.0159 0.0389 Iteratively solve, starting with an initial voltage guess (0) 2 0 0 3 2 3 (1) V 2 V 3 (0) 1 1 0 0.0477 0.0159 2 0.1272 0 0.0159 0.0389 2 0.1091 33 FDPF Three Bus Example, cont’d V 2 V 3 (1) 1 0.0477 0.0159 1 0.9364 1 0.0159 0.0389 1 0.9455 PDi PGi Pi (x ) n Vk (Gik cos ik Bik sin ik ) Vi Vi k 1 (2) 2 0.1272 0.0477 0.0159 0.151 0.1361 0.1091 0.0159 0.0389 0.107 0.1156 3 V 2 V 3 (2) 0.924 0.936 0.1384 Actual solution: θ 0.1171 0.9224 V 0.9338 34 FDPF Region of Convergence 35 “DC” Power Flow The “DC” power flow makes the most severe approximations: – completely ignore reactive power, assume all the voltages are always 1.0 per unit, ignore line conductance This makes the power flow a linear set of equations, which can be solved directly θ B 1 P 36 Power System Control A major problem with power system operation is the limited capacity of the transmission system – – – lines/transformers have limits (usually thermal) no direct way of controlling flow down a transmission line (e.g., there are no valves to close to limit flow) open transmission system access associated with industry restructuring is stressing the system in new ways We need to indirectly control transmission line flow by changing the generator outputs 37 Indirect Transmission Line Control What we would like to determine is how a change in generation at bus k affects the power flow on a line from bus i to bus j. The assumption is that the change in generation is absorbed by the slack bus 38 Power Flow Simulation - Before One way to determine the impact of a generator change is to compare a before/after power flow. For example below is a three bus case with an overload 131.9 MW 124% One 200.0 MW 71.0 MVR Two 68.1 MW 68.1 MW 200 MW 100 MVR Z for all lines = j0.1 Three 1.000 pu 0 MW 64 MVR 39 Power Flow Simulation - After Increasing the generation at bus 3 by 95 MW (and hence decreasing it at bus 1 by a corresponding amount), results in a 31.3 drop in the MW flow on the line from bus 1 to 2. 101.6 MW 100% One 105.0 MW 64.3 MVR Two 3.4 MW Z for all lines = j0.1 Limit for all lines = 150 MVA Three 98.4 MW 200 MW 100 MVR 92% 1.000 pu 95 MW 64 MVR 40 Analytic Calculation of Sensitivities Calculating control sensitivities by repeat power flow solutions is tedious and would require many power flow solutions. An alternative approach is to analytically calculate these values The power flow from bus i to bus j is Pij Vi V j So Pij X ij sin( i j ) i j X ij i j X ij We just need to get ij PGk 41 Analytic Sensitivities From the fast decoupled power flow we know θ B 1P (x) So to get the change in θ due to a change of generation at bus k, just set P (x) equal to all zeros except a minus one at position k. P 0 1 Bus k 0 42 Three Bus Sensitivity Example For the previous three bus case with Zline j 0.1 20 10 10 20 10 Ybus j 10 20 10 B 10 20 10 10 20 Hence for a change of generation at bus 3 2 3 1 20 10 0 0.0333 10 20 1 0.0667 0.0667 0 Then P3 to 1 0.667 pu 0.1 P3 to 2 0.333 pu P 2 to 1 0.333 pu 43