The Life Safety Surveyor How Should I Prepare for the Life Safety Surveyor Documentation Session? Healthcare Engineering Consultants The LSS Document Review Documents likely to be reviewed include: Fire system detection and extinguishing test documents Electrical system test documentation including emergency generators, battery lights and SEPPS units Medical gas and vacuum system test results and new installation certifications Interim life safety measures policy and documentation Pre-Construction Risk Assessment (PCRA) policy and documentation Statement of Conditions (SOC), unless already reviewed during the Preliminary Planning Session Healthcare Engineering Consultants The Life Safety Surveyor (LSS) It is likely that the LSS will arrive with the team on the first or second day, less likely later in the survey The LSS will be scheduled for at least two days “on-site”, with extra days for >1.5 million square feet and three or more surveyable healthcare occupancy buildings (could be up to 5 days “on-site”!) The LSS will spend several hours on dedicated documentation review, but much more time on the facility tour Other responsibilities assigned to the LSS will depend on the survey team member preferences and responsibilities – they will probably conduct the Physical Environment Interview and Emergency Management review The other survey team members will also observe life safety issues, but not as detailed as the LSS – it is not likely that the nurse and physician will request a ladder and flashlight! If the LSS observes deficiencies outside of their defined responsibility (example: medical records privacy or medication security), they will report it to the other team members Healthcare Engineering Consultants Fire System Tests Points to Remember: Every fire system device must be individually inventoried, with each test result documented as “PASS” or “FAIL” Test records should be sorted by device type, not as a combination of devices, and placed in a binder that is tabbed by each device type Written test procedures and references to the NFPA standards should be readily available Documentation should be available to indicate the resolution of all identified deficiencies A method should be used to track when fire system tests are scheduled and when they have been completed, such as a monitoring grid or “dashboard” Healthcare Engineering Consultants Fire System Tests Fire System Component Test Schedule Standard Element of Performance Points to Remember The chart on the right indicates the probable order in which the surveyor will review the documentation – put the test records in this order, either in a binder or in folders The test interval may vary (example: flow devices, fire pump churn tests), depending upon adoption of the CMS “Categorical Waivers” Be sure to indicate on the documentation (or chart) the NFPA code reference for each test, as required in standard EC.02.03.05, EP 25 EC. 02.03.05 1 Scoring Category Test Interval NFPA Reference Fire Component Tests Supervisory switches C Q NFPA 72 2 Tamper switches, flow devices C S/A NFPA 72 3 Duct detectors, door releasing devices Smoke and heat detectors, pull boxes Audible and visual alarms C A NFPA 72 C A NFPA 72 C A NFPA 72 A Q NFPA 72 6 Off-premises transmission equipment Fire pump churn test C W NFPA 25 7 Water tank level alarms C S/A NFPA 25 8 C M NFPA 25 C A NFPA 25 10 Water tank level alarms (cold weather only) Main drain tests on system risers Fire department connections A Q NFPA 25 3 4 5 9 11 Fire pumps (flow test) A A NFPA 25 12 Standpipe test C 5 yr NFPA 25 13 Kitchen extinguishing systems A S/A NFPA 96 14 A A NFPA 2001 C M NFPA 10 C A NFPA 10 17 Carbon dioxide/ gaseous extinguishing systems Portable fire extinguishers (visual check) Portable fire extinguishers (preventive maintenance) Occupant hoses C NFPA 25, 1962 18 Smoke/ fire dampers C 3 yr–hydro 5 yr–new 6 years 19 HVAC smoke detectors w/ shutdown Horizontal/ vertical fire doors A A NFPA 90A C A NFPA 80 15 16 20 Healthcare Engineering Consultants NFPA 80, 105 Fire System Test Descriptions Supervisory Devices Test interval: Quarterly Be prepared to explain which devices are considered “supervisory” (not including tamper switches!) Supervisory signals are defined in the 2000 Life Safety Code in section 9.7.2 as: “…monitoring shall include, but shall not be limited to, monitoring of control valves, fire pump power supplies and running conditions, water tank levels and temperatures, tank pressure, and air pressure on dry-pipe valves” Typically, the surveyor will ask about documented test results for power off and phase loss conditions for the fire pump and low air pressure on dry sprinkler systems Code Reference: NFPA 72, 1999 edition, Table 7.3.2 Healthcare Engineering Consultants Fire System Test Descriptions Waterflow Devices Test interval: Quarterly, unless the CMS “Categorical Waiver” has been adopted, which then requires semi-annual tests Time delay documentation on device activation recommended “Categorical Waiver” applies to vane-type and pressure switch-type waterflow alarm devices Code References: NFPA 25, 1998 edition, section 2-3.3 without the waiver; NFPA 25, 2011 edition, sections 5.3 and 8.3 with the waiver Healthcare Engineering Consultants Fire System Test Descriptions Duct Detectors Test interval: Annually Must be tested to ensure that the device will sample the airstream Tests must be in accordance with the manufacturer’s instructions Physical verification of damper closure and/ or air handler shutdown must performed (EC.02.03.05, EP19) and is required by NFPA 90A, 1999 edition, section 4-4.1 Failure to test and document the damper closure and/ or air handler shutdown will result in a Direct Impact finding Code References: NFPA 72, 1999 edition, Tables 7-2.2 and 7-3.2, and NFPA 90A Healthcare Engineering Consultants Fire System Test Descriptions Smoke Detectors Test interval: Annually; Sensitivity: AHJ Must be tested in place to ensure smoke entry into the sensing chamber and alarm activation Tests must be in accordance with the manufacturer’s instructions, including type of test smoke and/ or aerosol Smoke detector sensitivity tests must use a calibrated test method, manufacturer’s approved instrument, or other test method acceptable to the AHJ Code References: NFPA 72, 1999 edition, Tables 7-2.2 and 7-3.2 Healthcare Engineering Consultants Fire System Test Descriptions Off-Premises Transmission Equipment Test interval: Quarterly Two tests required: 1. Receipt of signal by off-site “responders” (local fire department) – Joint Commission requirement 2. Receipt of signal by “receiving station” (can be off-site stations such as ADT, Simplex, etc. or fire department) within 90 seconds (reference to NFPA 72) Code References: NFPA 72, 1999 edition, Tables 7-2.2 and 7-3.2 Healthcare Engineering Consultants Fire System Test Descriptions Fire Pumps Test interval: Annual flow test; weekly churn test Weekly churn test unless CMS “Categorical Waiver” is accepted, which requires a monthly test (electric pumps) Churn test must be activated by dropping water pressure Electric pump: 10 minute test; Diesel pump: 30 minutes Annual flow test should include a graph of test results Code References: NFPA 25, 1998 edition, sections 5-3.2.1, 3.2.2; with CMS waiver, NFPA 25, 2011 edition Healthcare Engineering Consultants 5- Fire System Test Descriptions Main Drain Test Test interval: Annual Either test the system low point or all system risers Perform the test using the following steps: 1. Record the initial static pressure 2. Open the main drain valve, record residual pressure 3. Slowly close the main drain valve 4. Record the time to return to initial static pressure Changes in the return time indicate possible obstructions Code References: NFPA 25, 1998 edition, sections 9-2.6 and Appendix A-9.2.6 Healthcare Engineering Consultants Fire System Test Descriptions Fire Department Connections Test interval: Quarterly Perform and document the following checks: 1. Connections and ID signs are visible and accessible 2. Couplings and swivels rotate smoothly 3. Plugs, gaskets and caps are in place and undamaged 4. Check valve is not leaking 5. Automatic drain valve operates properly Intended to be outside fire department connections Code Reference: NFPA 25, 1998 edition, section 9-7.1 Healthcare Engineering Consultants Fire System Test Descriptions Standpipe Waterflow Test Test interval: Every Five Years Perform and document the following checks: 1. Flow the system at the highest design pressure to the hydraulically most remote or highest hose connection of each standpipe system 2. Consult the local AHJ for the appropriate test location Code Reference: NFPA 25, 1998 edition, section 3-3.1.1 Healthcare Engineering Consultants Fire System Test Descriptions Kitchen Extinguishing Systems Test interval: Semi-annually Perform and document the following checks: 1. Inspect the extinguishing system and hoods 2. Test all actuation components (pull stations, detectors, dampers, mechanical and electrical devices, etc.) 3. Replace fusible links and sprinkler heads annually 4. Service and/ or replace detection according to manufacturer recommendations Discharge of the system is not required Code Reference: NFPA 96, 1998 edition, section 8-2 Healthcare Engineering Consultants Fire System Test Descriptions Gaseous Extinguishing Systems Test interval: Annual Perform and document the following checks: 1. Inspection and tests (4-1) 2. Clean agent containers (4-2) 3. System hose inspection (1-year), test (5-years) (4-3) 4. System maintenance (4-5) 5. Training of staff who inspect (4-6) Discharge of the system is not required Code Reference: NFPA 2001, 1996 edition, section 4-1 Healthcare Engineering Consultants Fire System Test Descriptions Portable Fire Extinguishers Test intervals: Monthly, Annual and 6-Year Monthly checks require the following: 1. Proper location, no restriction to access or visibility 2. Instructions for use legible and seals/ indicators OK 3. Fullness determined by “hefting” or weighing 4. Evidence of physical damage and gauge reading 5. Documentation with date/ month/ year/ initials Annual preventive maintenance required 6-Year extinguisher recharge Code Reference: NFPA 10, 1998 edition, sections 4-3 and 4-4 Healthcare Engineering Consultants Fire System Test Descriptions Smoke and Fire Dampers Test intervals: Initially, 1-year and 6 years thereafter All smoke and fire dampers must be tested initially and one year after installation Re-testing is every four years except 6 years for hospitals Inaccessible dampers should be placed on a PFI with a 6-year timeframe for re-evaluation (document ILSM!) The 1-year test after installation only applies to dampers installed after January 1, 2008 Code References: NFPA 80, 2007 edition, section 19.4.1.1; NFPA 105, 2007 edition, section 6.5.2 Healthcare Engineering Consultants Fire System Test Descriptions Sliding and Rolling Fire Doors Test interval: Annual Test must include proper operation and full closure Re-setting the release mechanism must be done according to manufacturer specifications Fusible links and other release devices must not be painted or prevented from operating by sealing gaps with intumescent materials Code Reference: NFPA 80, 1999 edition, section 15-2.4 Healthcare Engineering Consultants Fire System Test Monitoring Best Practice for Monitoring Compliance Regulatory Compliance Dashboard for Fire System Tests Description JAN Supervisory Devices Tamper Switches Water Flow Devices Duct Detectors 1/15 X X X 1/15 X X X 1/15 X X X Door Releasing Devices Smoke Detectors Pull Boxes FEB MAR APR AUG SEP OCT NOV DEC W W W X X X X X X X 1/18 X Visual Alarms X Kitchen Systems JUL X X Fire Pump Flow Test Water Tank Level Alarms Main Drain Riser Test Fire Dept. Connections Standpipe Test JUN 1/22 Audible Alarms Signal Time to FD Fire Pump Churn Test MAY 1/6 4, 11 25 X W W W X W W W X W W X N/A X X X X 1/12 X X 5 yr X X Healthcare Engineering Consultants Comments Fire System Test Monitoring Regulatory Compliance Dashboard for Fire System Tests (continued) Description CO2/ Gaseous Systems Portable Extinguishers Portable Extinguishers Occupant Hoses JAN APR MAY JUN JUL AUG SEP OCT NOV DEC X X Comments X 1/23 X X X X X X X X X X X 3 yr Smoke/ Fire Dampers HVAC Shutdown Horiz/ Vertical Fire Doors FEB MAR X 6 yr 1/25 X X Key to dashboard symbols: X – Indicates that action is required during the month indicated; W – Indicates that weekly action is required A/R – Indicates that action is required when applicable Key to colored boxes: Red boxes indicate non-compliance (tests were not performed); Yellow boxes indicate partial compliance (tests have been delayed or not fully completed); Green boxes indicate full compliance (tests satisfactorily completed). Healthcare Engineering Consultants Emergency Power Systems EC.02.05.07: Emergency Generators Perform and document weekly generator visual checks Code reference: NFPA 110, 2005 edition, section 8.4.1 Perform and document monthly generator tests with at least 30% of the rated load for 30 minutes Document that all automatic transfer switches are exercised monthly Conduct 2-hour annual load bank tests if the 30% load is not achieved and manifold temperatures are not sufficient If the CMS “Categorical Waiver” is adopted by the hospital, then the 2010 edition of NFPA 110 will require a 1.5 hour annual load bank test with a 50% load for 30 minutes, and a 75% load for 60 minutes Healthcare Engineering Consultants Emergency Power Systems EC.02.05.07: Emergency Generators Combining the annual and trienniel tests can be performed by starting the load at 30% of nameplate for the first 30 minutes of the test, then continuing with: 50% of load for 30 minutes; 75% load for 60 minutes, and; any load greater than 30% for the remaining 2 hours Note: If the CMS “Categorical Waiver” is adopted, then the combined tests require a 50% load for 30 minutes, a 75% load for 1.5 hours and any load greater than 30% for the remaining 2.5 hours Document the static or dynamic 4-hour trienniel test for all generators Test fuel oil quality annually per ASTM D-975, unless fuel is consumed from the entire tank over the course of 12 months Code Reference: NFPA 110, 2005 edition, section 8.3.8 Utilize “Interim Emergency Power Measures” (IEPM) when necessary Healthcare Engineering Consultants Emergency Power Systems EC.02.05.07: Emergency Battery Lights Required in all anesthetizing locations (NFPA 70: 517.63 ) “administration of nonflammable inhalation anesthetic agents in the course of examination or treatment” Note: Grandfathering usually permitted in existing OR’s w/o lights Required in “Level 1 or Level 2 EPS equipment locations”, which is normally interpreted as transfer switch locations (NFPA 110: 7.3.1) Required in some business occupancies for egress lighting where emergency power is not required or not available (NFPA 101: 7.9.1.1) Monthly 30-second push-to-test and annual 90-minute discharge test required for all battery installations, whether for task or egress lighting Annual battery replacement is acceptable in lieu of 90-minute discharge test, but 10% of lights must be tested for 90 minutes annually, even if the batteries are changed Healthcare Engineering Consultants Emergency Power Systems EC.02.05.07: Stored Emergency Power Supply Systems (SEPSS) Standard applies to Level 1 systems (NFPA 111: 4.5.1) Level 1: “failure of the equipment to perform could result in loss of human life or serious injuries” Testing requires: 1. Quarterly functional test (5 minutes or class specification) 2. Annual full-load test for 60% of SEPSS class duration Note 1: NFPA 111 requires a monthly inspection, quarterly functional test and annual full load test for full class duration for Level 1 systems Note 2: The Joint Commission references exit lighting, life support ventilation, fire detection and alarm systems, and public communications systems as Level 1 systems, but most are not SEPSS systems, since they are backed up with emergency generators; non-SEPSS UPS systems should be tested per manufacturer specifications Healthcare Engineering Consultants The LSS Documentation Review EC.02.05.09: Medical Gas and Vacuum Systems Medical gas and vacuum system preventive maintenance program is required (facility must define PM) and must include: - Bulk medical gas and vacuum system components and source valve - Master signal panels and area alarms - Automatic pressure switches and shutoff valves - Flexible connectors and outlets Healthcare Engineering Consultants The LSS Documentation Review EC.02.05.09: Medical Gas and Vacuum Systems Testing per NFPA 99 is required for new installation, modification or repair (cross-connections, purity, pressure) Main supply valves and area shut-off valves must be accessible and clearly labeled Utilize “Interim Medical Gas Measures” (IMGM) when necessary Note: Significant changes for testing have been included in NFPA 99, the 2012 edition, but it has not yet been adopted by CMS or the Joint Commission, except for the “Categorical Waiver” tht permits one master alarm monitor location to be a computer Healthcare Engineering Consultants The LSS Documentation Review EC.02.05.09: Medical Gas and Vacuum Systems Certification of installers and verifiers per ASSE 6000 series is required Medical air quality must meet NFPA 99 requirements below: Parameter Limit Value Pressure dew point 39 degrees F Carbon monoxide 10 ppm Carbon dioxide 500 ppm Gaseous hydrocarbons 25 ppm (as methane) Halogenated hydrocarbons 2 ppm Healthcare Engineering Consultants The LSS Documentation Review Medical Gas and Vacuum System PM Recommendations Component Description Note 1: The recommendations provided in the chart to the right are from NFPA 99, the 2005 edition, Appendix C, section 5.2. Tests that are required due to new system installations, renovations or repair are listed in Chapter 5 of NFPA 99 Note 2: Significant changes for medical gas system tests have been added to NFPA 99, the 2012 edition, but have not yet been adopted by either CMS or the Joint Commission, except for the single master alarm panel “Categorical Waiver” Recommended Test Frequency Gas cylinder manifold pressure Daily Gas cylinder manifold changeover signal Daily Liquid cylinder manifold pressure Daily Liquid cylinder manifold changeover signal Daily Liquid cylinder reserve/ in-use signal Annually Bulk liquid system contents gauge Daily Bulk system pressure gauges “Regularly” (weekly) Bulk system master signal “Periodically” (monthly) Main line vacuum system gauge Daily Medical air intake location Quarterly Medical air pressure gauge Annually Medical air high level water sensor Annually Medical air receiver drain Daily Medical compressed air alarms Annually Medical air compressors/ vacuum pumps Per manufacturer specifications Dew point sensor/ CO monitor Annually Warning system components Annually Audible/ visual alarms Monthly Shut-off valve leak test “Periodically” (annually) Outlet leakage and flow “Periodically” (annually) Medical air purity As determined by facility Healthcare Engineering Consultants The LSS Documentation Review Interim Utility System Measures Interim Utility System Measures Best Practice! Project Number: _________________ Affected System: Fire System: _____ Date: ____________________ Emergency Power _____ Medical Gas: _____ Description of Project: ______________________________________________________ Strongly recommended to document that interim measures have been implemented to compensate for utility systems that are taken out of service __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ Interim Measures Required: _____ Affected staff notified Comments: ______________________________________ _____ Additional Equipment Required Specify: _________________________________ _____ Back-up Procedures in Place Specify: ___________________________________ _____ Emergency Procedures Reviewed Comments: ____________________________ _____ Other: ______________________________________________________________ _____ Other: ______________________________________________________________ _____ Other: ______________________________________________________________ Additional Comments: ______________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ Date Project Completed: ___________________ Reviewed By: ____________________ Healthcare Engineering Consultants Interim Life Safety Measures Interim Life Safety Measures Requirement Standard LS.01.02.01 from the Joint Commission Accreditation Manual: “The hospital protects occupants during periods when the Life Safety Code is not met or during periods of construction” Healthcare Engineering Consultants Interim Life Safety Measures The Interim Life Safety Measures Process Includes the Following Steps: 1. Is an ILSM evaluation required? Y or N 2. If Yes, does the ILSM evaluation require the implementation of ILSM? Y or N 3. If Yes, which interim measures apply? 4. Implement and document the required measures Note: An interim life safety measures policy must be written and address each of the four steps listed above Healthcare Engineering Consultants Interim Life Safety Measures Step 1: Is an ILSM evaluation required? The need for an interim life safety measure evaluation is normally required whenever there is a life safety deficiency that is found, or renovation or construction activities create life safety deficiencies. Be sure to do an ILSM evaluation for PFI’s! Include in the ILSM policy “exclusions” for evaluations, such as “routine work orders” or “superficial projects” Healthcare Engineering Consultants Interim Life Safety Measures Example Interim Life Safety Measures Policy Purpose Interim life safety measures evaluation exception for “routine work orders or superficial projects that do not impact life safety” The purpose of this interim life safety measures (ILSM) policy is to address situations during periods of construction or renovation, or whenever Life Safety deficiencies exist and cannot be immediately corrected, so that an equivalent level of Life Safety is maintained. This policy also includes criteria for evaluating when and to what extent the hospital follows special, temporary measures to compensate for increased life safety risk. Policy This policy provides information and guidelines for evaluating and implementing interim life safety measures during times when a Life Safety deficiency is present due to construction or whenever an existing building deficiency is identified. Procedure When the hospital identifies Life Safety deficiencies during surveillance rounds, during periods of construction or renovation, or through other means, and the deficiency cannot be immediately corrected, the hospital performs an analysis to determine whether the implementation of interim life safety measures is necessary. This analysis is documented using the Interim Life Safety Applicability Form (ILSAF) attached to Appendix A of this policy. Completion of the ILSAF form is not required for routine work orders, or superficial projects that do not impact life safety in the hospital. If the completion of the ILSAF indicates that interim life safety measures are not required, then the completed form is maintained in a document file for reference purposes. If the ILSAF indicates that interim life safety measures are required to be implemented, then the Interim Life Safety Measures Chart (ILSMC) form is completed (refer to Appendix B) to determine which interim measures must be implemented and documented. The ILSMC form should be completed by referring to the following “Typical Triggers” for each of the possible interim measures listed below. Note: The following list of “Typical Triggers” are suggestions only and may be revised on the ILSAF form based on the judgment of hospital personnel. Measure 1: Notify the fire department, and initiate and document a fire watch. Typical Trigger Criteria: When the fire alarm or sprinkler system is out of service for more than 4 hours in a 24-hour period in an occupied building, as defined by the fire watch decision grid in Appendix C. Measure 2: Inspect exits in affected areas on a daily basis and document the inspection. Healthcare Engineering Consultants Interim Life Safety Measures Step 2: Are interim life safety measures necessary, based on the evaluation? Interim life safety measure “trigger points” include the following: Egress is compromised, and alternative exits are necessary Compartmentation is breached,and is considered serious Part or all of the fire detection or extinguishing system has been taken out of service “Hot Work” is being performed Large quantities of combustible materials are present Other conditions determined by the organization Healthcare Engineering Consultants Interim Life Safety Measures Appendix A - Interim Life Safety Applicability Form Description of Project or Deficiency: _________________________________________ ________________________________________________________________________ Location: ________________________________________________________________ Check which “triggers” (if any) apply for the project Add other “triggers, as desired If none of the “triggers” are marked “Yes”, then no additional action is required Instructions: Determine whether any of the “ILSM Triggers” listed in the chart below apply to or will occur during this project. Description of ILSM Trigger Applicable? Hot work Y N Blocked exit Y N Alternate egress Y N Excessive combustible materials Y N Removal of part or all of the fire detection system Y N Removal of part or all of the extinguishing system Y N Significant breach of smoke or fire wall Y N Significant breach of smoke or fire door Y N Y N Y N Y N If one or more of the ILSM triggers listed above are marked “Yes”, then interim life safety measures apply and must be evaluated using Appendix B, Interim Life Safety Measures Chart ______ ILSM measures do not apply _____________________________ Signed ______ ILSM measures do apply _________________________ Title Healthcare Engineering Consultants ______________ Date Interim Life Safety Measures Step 3: Which interim life safety measures apply? The use of an ILSM “applicability matrix” that helps to determine which interim measures apply is helpful. The matrix can either be “pre-filled” for specific conditions or left blank until the evaluation process occurs. The ILSM policy should describe how the interim measures are selected, based on criteria developed by the hospital Healthcare Engineering Consultants Interim Life Safety Measures Possible Interim Life Safety Measures Include: Fire watch Alternative exit signage Daily inspection of exits Temporary, but equivalent fire alarm and detection systems Additional fire fighting equipment Temporary, smoke-tight, noncombustible partitions Increased surveillance of buildings, grounds and equipment Storage, housekeeping and debris removal practices Additional staff training for staff who use fire equipment Healthcare Engineering Consultants Interim Life Safety Measures Possible Interim Life Safety Measures Include (continued): Additional fire drills Inspect and test temporary systems monthly Additional staff training related to the interim measures Additional training to compensate for impaired fire or building features Note: Implementation of any or all of the interim life safety measures noted in the list above are based on criteria developed by the hospital and should be listed in the hospital interim life safety measures policy Healthcare Engineering Consultants Interim Life Safety Measures (ILSM) X Breach compartmentation X X X X Impair fire detection, alarm, suppression X Hot work Large quantities of combustibles X X X X X X X X X X X X X X X X X X X X X X Healthcare Engineering Consultants X Other X X Fire watch X Fire drills Prohibit smoking Surveillance X Staff training Compromise egress Reduce combust. Fire equipment Barriers Deficiency Operational LS Measure Notify Fire Dept Interim Ensuring Egress Applicability Grid Example for Interim Life Safety Measures Interim Life Safety Measures Example for Interim Life Safety Measures Chart Appendix B - Interim Life Safety Measures Chart Description of Project or Deficiency: _________________________________________ ________________________________________________________________________ One or more of the interim measures listed on the chart may be selected, based on the scope of the project and the type of deficiency that exists Location: ________________________________________________________________ Instructions: Based on the project or deficiency described above, determine and document which of the following interim life safety measures apply in the chart below. Description of Interim Measure Applicable? Fire watch (see Appendix C) Y N Signage signifying alternative exits Y N Daily inspections in affected area Y N Temporary and equivalent fire alarm and detection systems Y N Additional portable fire extinguishers Y N Temporary construction partitions (non- or limited combustibility) Increased surveillance of buildings, grounds or equipment Y N Y N Additional storage, housekeeping and debris removal Y N Additional staff training for portable fire extinguishers Y N Additional fire drills Y N Monthly tests and inspections of temporary systems Y N Additional staff training for construction hazards, temporary measures Additional staff training for impaired fire safety features Y N Y N Additional comments related to required measures: ____________________________ ______________________________________________________________________ _____________________________ Signed _________________________ Title Healthcare Engineering Consultants ______________ Date Interim Life Safety Measures Step 4: Implement and document the required measures Whichever interim measures are selected must be implemented and documented Remember: Failure to implement or document interim life safety measures, when required, can result Contingent Accreditation from the Joint Commission! Healthcare Engineering Consultants Interim Life Safety Measures Healthcare Engineering Consultants Fire Watch Requirements LS.01.02.01: EP 1 “The hospital notifies the fire department (or other emergency response group) and initiates a fire watch when a fire alarm or sprinkler system is out of service more than 4 hours in a 24-hour period in an occupied building. Notification and fire watch times are documented” Question: What constitutes when “a fire alarm or sprinkler system is out of service”? Healthcare Engineering Consultants Fire Watch “Decision Grid” Appendix C – Fire Watch Decision Grid Description of Project or Deficiency: _________________________________________ The requirement for a fire watch is determined by the hospital staff. NFPA 101, section A.9.6.1.6 states: “it is not the intent of the Code to require notification of the AHJ for a single non-operating device or appliance” ________________________________________________________________________ Location of Project or Deficiency: ____________________________________________ Fire Watch Notification: ______ Fire Department ______ Insurance Company ______ Other Responders ______ Internal Hospital Staff ______ Other Instructions: Based on the “Out of Service” description listed in the chart below, the requirement for a fire watch is indicated. Circle each “Yes” below, as applicable. Description of Fire Alarm or Sprinkler System “Out of Fire Watch Required? Service” Condition Multiple fire alarm or sprinkler system components out-ofNo service for less than 4 hours in a 24-hour period Fewer than 6 smoke detectors in the same area out-ofNo service for more than 4 hours in a 24-hour period Extinguishing system in less than a single smoke compartNo ment out-of-service for more than 4 hours in a 24-hour period Fire alarm system in “bypass” mode due to testing No More than 5 smoke detectors in the same area out-of-service for more than 4 hours in a 24-hour period Extinguishing system in more than a single smoke compartment out-of-service for more than 4 hours in a 24-hour period Any combination of fire detection and extinguishing devices out of service > 4 hours in a 24-hour period at the same time Failure of the fire alarm annunciator panel (any time period) Yes Failure of the entire fire detection system (any time period) Yes Failure of the entire extinguishing system (any time period) Yes Failure of the fire pump (any time period) Yes _____________________________ Signed Yes Yes Yes Y N Y N _________________________ Title Healthcare Engineering Consultants ______________ Date Functional Environment Issue: Pre-Construction Risk Assessment (PCRA) Biggest Pitfall: Only ICRA and ILSM are evaluated Best Practice: Include all seven of the items listed below in the PCRA evaluation ● Noise ● Emergency procedures ● Vibration ● Utility failures ● Air quality ● Interim life safety measures ● Infection control Healthcare Engineering Consultants Infection Control Risk Assessment (ICRA) – Best Practice Grid Risk Criteria for Infection Control Patient Risk Construction Type Type A Type B Type C Type D Group 1 (lowest) I II II III Group 2 (medium) I II III IV Group 3 (medium high) II III III IV Group 4 (highest) III IV IV IV Healthcare Engineering Consultants Functional Environment Issue: Documentation of PCRA Achieving Compliance: • Evaluate measures to reduce risk and minimize the impact of the construction activities • Perform daily monitoring in all construction areas • Use a monitoring checklist • Post required permits, such as hot work, ICRA, above-the-ceiling work, ILSM, etc. on door entrance to construction area Healthcare Engineering Consultants Functional Environment Issue: Pre-Construction Risk Assessment (PCRA) Best Practice: Include MCRA changes during the project Pre-Construction Risk Assessment Timeline Chart Project number: __________________________ Date: _____________________ Completed by: ____________________________ PCRA Category Week 1 Week 2 Week 3 Week 4 Week 5 Week 6 Week 7 Week 8 Noise Vibration Air Quality Infection Control Risk Assessment (ICRA) Interim Life Safety Measures (ILSM) Emergency Procedures Utility Failures Healthcare Engineering Consultants Week 9 Week 10 Comments The Life Safety Surveyor Document Review Questions? Healthcare Engineering Consultants