Active beams versus VAV with Reheat Analysis of May 2013 ASHRAE Journal article Ken Loudermilk Vice President, Technology & Developement Active Chilled Beams Pre-treated Primary Air 0.4 to 0.7 in. SP 1 Part Air handling unit Entrained Room Air 2 to 4 Parts Supply Air to Room 3 to 5 Parts Comparison of water to air as a heat transfer medium 14“ x 14“ Air Duct 1“ Dia. Water Pipe Cost to transport cooling with water 15 to 20% that of air Typical active beam cooling operation Pre-treated primary air Primary airflow requirement is the greater of: • Volume flow rate needed to maintain mandated ventilation to space • Volume flow rate needed to offset space sensible heat gains • Sensible cooling contribution • Drive induction of room air through coil • Volume flow rate needed to maintain space dew point temperature Typical active beam cooling operation ACB with 55˚F primary air 33% of space sensible heat removed by primary air 67% of space sensible heat removal by water Active beams with a DOAS vs. VAV with reheat ASHRAE Journal, May 2013 • Office/classroom building at UC Davis • 56,500 ft2 building • Sensible loads average 19.5 Btu/h-ft2 • Occupancy is one person per 275 ft2 • Compares VAV + reheat to ACB system with DOAS • Analyzes and compares • System first cost • System energy use • Other benefits of VAV + R Active beams with a DOAS vs. VAV with reheat ASHRAE Journal, May 2013 • Sensible design (outdoor air) • 100˚F DB/70˚F WB (54˚F dew point) • Humidity ratio W = 62.2 grains/lbm-DA • Enthalpy h = 33.8 Btu/h-lbm • Off peak operation (outside air) • 50% indoor sensible load • 77˚F DB/59˚F WB (46˚F dew point) • Humidity ratio W = 46.3 grains/lbm-DA • Enthalpy h = 25.8 Btu/h-lbm Active beams with a DOAS vs. VAV with reheat ASHRAE Journal, May 2013 ACB system • 100% OA (DOAS) air handling unit VAV + reheat system • Mixing AHU with VFD • No energy recovery! • Equipped with airside economizer • Primary air 63˚F, 54˚ DP (W = 2.7 grains) • Primary air 55˚F, 52˚ DP (ΔW = 8 grains) • 0.15 CFM/ft2 for ventilation • 0.15 CFM/ft2 for ventilation • 0.53 CFM/ft2 for latent cooling!! • 0.18 CFM/ft2 for latent cooling • Primary airflow • Primary airflow • 30,000 CFM (0.53 CFM/ft2) • • Constant air volume, no set back • Normal VAV turndown ratio of 6:1 • No DCV provisions • Interior terminals DCV (allows shut off) 50,000 CFM (0.88 CFM/ft2) Active beams with a DOAS vs. VAV with reheat ASHRAE Journal, May 2013 Performance comparison of systems as described Primary air conditions and flow rates as described by authors Design airflow rates in CFMPA per square foot VAV System ACB System 55˚ DB/52˚ DP ΔW = 7.9 grains 63˚ DB/54˚ DP ΔW = 2.7 grains Interior Space Perimeter Space Interior Space Perimeter Space Ventilation 0.15 0.15 0.15 0.15 Dehumidification 0.18 0.18 0.53 0.53 Sensible Cooling 0.60 1.75 0.22 0.53 Resultant Airflow 0.60 1.75 0.53 0.53 Avg. 0.88 CFM/ft2 Avg. 0.53 CFM/ft2 Air handling unit configurations as described OA Heating Coil Filters Cooling Coil Fan Array Filters (0.15 to 0.88 8,300 CFM CFM/Ft2) 63⁰F 30,000 CFM 30,000 CFM Cooling Fan Array Coil 55⁰F 8,475 to 50,000 CFM (0.53 CFM/Ft2) Bypass Damper 8,300 CFM 30,000 CFM VFD 30,000 CFM Note: 100% OA, no energy recovery! Relief Fan 0 to 41,700 CFM recirculation 8,475 to 50,000 CFM Note: OA requirement only 0.15 CFM/Ft2, 16% of design airflow rate! Authors‘ performance conclusions SAT OA RA OA AHU cooling Beam cooling Fan Pumps Total energy ˚F CFM CFM % kW kW BHP BHP kW VAVR system as described 55 8,475 41,525 17% 49.9 0.0 45.6 5.5 88.0 ACB system as described 63 30,000 0 100% 40.5 23.5 26.0 8.7 89.9 SAT OA RA OA AHU cooling Beam cooling Fan Pumps Total energy ˚F CFM CFM % kW kW BHP BHP kW VAVR system as described 55 8,475 16,525 34% 13.0 0.0 6.6 2.0 19.4 ACB system as described 63 30,000 0 100% 15.6 5.1 26.0 1.4 41.2 Sensible design conditions (100% sensible & latent space loads) Shoulder season operation (50% sensible, 80% latent space load) Energy use comparable ACB system more than double Authors‘ performance conclusions 2 kBtu/ft -year 30 25 0.1 2.3 20 5.1 0.0 1.0 1.5 15 10 Pumps Fans Heating District cooling 17.9 12.8 5 0 ACB Design as Described VAV Reheat Authors‘ performance conclusions SAT OA RA OA AHU cooling Beam cooling Fan Pumps Total energy ˚F CFM CFM % kW kW BHP BHP kW VAVR system as described 55 8,475 41,525 17% 49.9 0.0 45.6 5.5 88.0 ACB system as described 63 30,000 0 100% 40.5 23.5 26.0 8.7 89.9 SAT OA RA OA AHU cooling Beam cooling Fan Pumps Total energy ˚F CFM CFM % kW kW BHP BHP kW VAVR system as described 55 8,475 16,525 34% 13.0 0.0 6.6 2.0 19.4 ACB system as described 63 30,000 0 100% 15.6 5.1 26.0 1.4 41.2 Sensible design conditions (100% sensible & latent space loads) Shoulder season operation (50% sensible, 80% latent space load) Energy use comparable ACB system more than double Actual performance comparisons 100 88.0 89.9 80 79.2 70 60 52.0 50 41.2 40 30 19.4 20 10 Sensible Design Performance Latent Design Performance as designed ACB system VAVR system as designed ACB system VAVR system as designed ACB system 0 VAVR system Operational Energy use, kW 90 Shoulder Season Performance What’s wrong with this picture? Waterside sensible cooling Primary Air Sensible Cooling System Design TPA (˚F) Btu/h-ft2 Btu/hCFM CFM/ft % Space Sensible Cooling Btu/hCFM % Space Sensible Cooling 2 Latent Cooling Requirement (all airside) Btu/h- ΔW grains ft2 Ventilation Btu/hCFM CFM/ft2 CFM/ft2 VAVR system as described 55.0 19.5 22.0 0.89 100% NA NA 2.2 11.0 7.5 0.30 0.15 ACB system described 63.0 19.5 13.2 0.53 36% 23.6 64% 2.2 6.0 4.1 0.53 0.15 • • • ACB system primary airflow rate as designed is driven by space latent load combined with low ΔW Primary airflow rate is 75% greater than that typically required by properly designed ACB systems Beam water side cooling capacities (23.6 Btu-h-CFM) as designed are far lower than those (40 to 50 Btu/h-CFM) in properly designed ACB systems Active beams with a DOAS vs. VAV with reheat ASHRAE Journal, May 2013 Performance comparison with properly designed ACB system Air handling unit modifications for ACB system OA Heating Coil Filters Cooling Coil Fan Array Filters 55⁰F Cooling Fan Array Coil 8,475 CFM (0.3 CFM/Ft2) 16.667 CFM 30,000 CFM (0.3 55⁰F 16.667 CFM CFM/Ft2) Bypass Damper 8,300 CFM 16,667 CFM VFD 16,667 CFM Reduce SAT to 55˚F Lower PA dew point allows primary airflow reduction of 45% and an associated fan energy reduction of 70%! Relief Fan 8,192 CFM recirculation Introduce mixing at AHU Mixing results in an additional 30% reduction in chiller energy! 16,667 CFM Leveling the playing field Waterside sensible cooling Primary Air Sensible Cooling System Design 2 TPA (˚F) Btu/h-ft Btu/hCFM CFM/ft % Space Sensible Cooling Btu/hCFM % Space Sensible Cooling 2 Latent Cooling Requirement (all airside) Btu/h- ΔW grains ft2 Ventilation Btu/hCFM CFM/ft2 CFM/ft2 VAVR system as described 55.0 19.5 22.0 0.89 100% NA NA 2.2 11.0 7.5 0.30 0.15 ACB system described 63.0 19.5 13.2 0.53 36% 23.6 64% 2.2 6.0 4.1 0.53 0.15 Properly designed ACB system 55.0 19.5 22.0 0.30 33% 44.0 67% 2.2 11.0 7.5 0.30 0.15 • Same primary air conditions used for both systems • ACB system primary airflow rate reduced from 30,000 CFM to 16,950 CFM! • Beam water side cooling capacity (44 Btu-h-CFM) increased by 86% Primary air conditions and flow rates for modified ACB system Design airflow rates in CFMPA per square foot VAV System ACB System 55˚ DB/52˚ DP ΔW = 7.9 grains 55˚ DB/52˚ DP ΔW = 2.7 grains Interior Space Perimeter Space Interior Space Perimeter Space Ventilation 0.15 0.15 0.15 0.15 Dehumidification 0.18 0.18 0.18 0.18 Sensible Cooling 0.60 1.75 0.20 0.60 Resultant Airflow 0.60 1.75 0.20 0.60 Avg. 0.88 CFM/ft2 Avg. 0.30 CFM/ft2 Actual performance calculations Sensible design conditions (100% sensible & latent space loads) VAVR system as described ACB system as described SAT OA RA OA AHU cooling Beam cooling Fan Pumps Total energy ˚F CFM CFM % kW kW BHP BHP kW 55 63 8,475 30,000 0.0 23.5 45.6 26.0 5.5 8.7 88.0 89.9 100% 28.7 24.4 4.5 7.6 62.1 41,525 17% 49.9 0 100% 40.5 Modified ACB system 30% less than VAVR 54.5 38% less than VAVR Primary air @ 55 ˚ F DB , 53 ˚F DP 55 16,667 0 Mixing at air handling unit 55 8,475 8,192 51% 21.6 24.4 4.5 6.8 SAT OA RA OA AHU cooling Beam cooling Fan Pumps Total energy ˚F CFM CFM % kW kW BHP BHP kW 0.0 14.3 26.0 26.0 2.9 7.0 48.2 79.2 100% 28.5 15.3 4.5 5.9 51.5 6% more than VAVR 31.8 34% less than VAVR Latent design conditions (75% sensible, 90% latent space load) VAVR system as described ACB system as described 55 63 8,475 29,025 23% 26.6 30,000 0 100% 40.2 Modified ACB system Primary air @ 55 ˚ F DB , 53 ˚F DP 55 16,667 0 Mixing at air handling unit 55 8,475 8,192 51% 10.3 15.3 4.5 3.9 SAT OA RA OA AHU cooling Beam cooling Fan Pumps Total energy ˚F CFM CFM % kW kW BHP BHP kW 55 63 8,475 30,000 0.0 5.1 6.6 26.0 2.0 1.4 19.4 41.2 Shoulder season operation (50% sensible, 80% latent space load) VAVR system as described ACB system as described 16,525 34% 13.0 0 100% 15.6 Modified ACB system Same as VAVR Primary air @ 55 ˚ F DB , 53 ˚F DP 55 16,667 0 100% 8.4 6.1 4.5 2.0 19.3 Mixing at air handling unit 55 16,667 0 100% 8.4 6.1 4.5 2.0 19.3 Was more than double * Air handling unit operating in economizer mode Sensible Design Performance Latent Design Performance AHU mixing 22.0 ACB system, 55˚F PA 19.4 ACB system, as designed 40 ACB system 20 VAVR system AHU mixing ACB system, 55˚F PA 52.0 ACB system, as designed 80 ACB system 50 VAVR system AHU mixing ACB system, 55˚F PA 60 ACB system, as designed 88.0 ACB system 90 VAVR system Operational Energy use, kW Actual performance comparisons using modified ACB system 100 89.9 79.2 70 62.1 54.5 51.5 41.2 30 31.8 22.0 10 0 Shoulder Season Performance Active beams with a DOAS vs. VAV with reheat ASHRAE Journal, May 2013 System cost comparisons Authors’ installed cost comparison of the systems as designed Material cost ($) Labor cost ($) Equipment cost ($) Subcontractors ($) Lbs. of ductwork (lbs.) Chilled water piping (LF) Hot water piping (LF) VAV system as designed ACB system as designed Cost or Qty. Cost/CFM Cost or Qty. Cost/CFM $215,179 $584,058 $319,695 $252,067 38,000 310 2,085 $4.30 $11.68 $6.39 $5.04 $576,496 $1,509,349 $608,349 $647,037 28,612 10,244 9,630 $19.22 $50.31 $20.28 $21.57 Total HVAC cost ($) $1,370,999 HVAC cost ($/ft2) $25 $3,341,231 $27 $62 $111 System ductwork configuration 2,000 FPM @ 0.9 CFM/Ft2 900 FPM 0.53 CFM/Ft2 ACB System Mains VAV System Mains AEFF = 50,000/2,000 = 25.0 One supply riser AEFF = 30,000/900 = 33.3 Two supply risers Authors’ conclusion: Average duct cross sectional area 33% greater for the ACB system Ductwork configuration 2,000 FPM 2,000 FPM ACB System Mains VAV System Mains AEFF = 16,667/2,000 = 8.3 AEFF = 50,000/2,000 = 25 VAVR system average duct cross sectional area is triple that of the ACB system when sized for the same maximum velocity Beam requirements VAV system as described Interior zones 2 Perimeter All zones zones ACB system as described Interior zones Perimeter All zones zones Modified ACB system Interior zones Perimeter All zones zones 38,922 17,578 56,500 38,922 17,578 56,500 38,922 17,578 56,500 BTU/H-ft 13.4 33.0 19.5 13.4 33.0 19.5 13.4 33.0 19.5 CFMPA 23,634 26,367 50,000 13,123 16,877 30,000 7,878 8,789 16,667 CFMPA/ft2 0.61 1.50 0.88 0.34 0.96 0.53 0.20 0.50 0.29 BTU/H-CFMPA 22.0 22.0 22.0 39.6 34.4 38.0 66.0 66.0 66.0 ACB Btu/h-LF ACB CFM PA /LF 305 550 398 1,056 1,056 1,056 7.7 16.0 10.9 16.0 16.0 16.0 Linear feet of ACB required 1,706 1,055 2,761 492 549 1,042 Area served, ft 2 • Number of beams reduced by 63% by modifying ACB system • 63% reduction in beam piping and insulation costs Remedies for other cost inequities • Perimeter VAV terminals serve multiple offices • No indication of thermal zoning or condensation prevention in ACB system • Interior VAV terminals have no reheat provisions • Four pipe configuration of interior space beams • Remedy: Eliminate heating provision on interior beams • Eliminates HW piping/insulation and connection to interior beams • Perimeter VAV terminals require only one HW connection per zone • Perimeter beams require individual HW connections • Accomplish perimeter heating by heating primary air • Reduces HW piping/insulation and connections to one per perimeter zone Cost comparison using modified ACB system Material cost ($) Labor cost ($) Equipment cost ($) Subcontractors ($) Lbs. of ductwork (lbs.) Chilled water piping (LF) Hot water piping (LF) VAV system as designed ACB system as designed Modified ACB system Cost or Qty. Cost/CFM Cost or Qty. Cost/CFM Cost or Qty. $215,179 $584,058 $319,695 $252,067 38,000 310 2,085 $4.30 $11.68 $6.39 $5.04 $576,496 $1,509,349 $608,349 $647,037 28,612 10,244 9,630 $19.22 $50.31 $20.28 $21.57 $320,282 $838,544 $337,978 $359,472 15,896 5,691 5,350 Total HVAC cost ($) $1,370,999 HVAC cost ($/ft2) $25 $3,341,231 $27 $62 $1,856,277 $111 $33 Modified ACB system cost assumes the cost per CFM for the ACB system remains constant and thus system costs are proportional to the reduced primary airflow requirements. These costs also do not include any possible reheat piping reduction opportunities discussed before. Installed cost comparison (ACB system with mixing AHU, no ER) Summary Table SYSTEM TYPE Central Equipment Costs Specify AHU configuration All air VAV Active Beams All-air system Total $ $/ft2 Total $ $/ft2 Mixing type without energy recovery $554,608 $9.83 $467,782 $8.29 Beam system (pulldown menu) Mixing type without energy recovery Air handling units and exhaust fans $196,642 $137,201 Chillers $223,253 $169,152 Boilers $37,384 $66,204 Specify perimeter heat method Pumps $97,329 $95,225 All air system (pulldown menu) Air and water distribution costs $851,323 $15.09 $1,060,439 $18.80 Single duct VAV with reheat Beam system (pulldown menu) Ductwork and insulation $389,350 $237,025 Piping and insulation $91,944 $460,106 Air terminal units $150,109 $0 Supply/return grilles and diffusers $92,610 $19,824 Condensation prevention (pulldown menu) Active beams $0 $263,000 Reset each floor chilled water supply temperature Zone controls $127,310 $80,485 Other costs $197,400 $3.50 $206,400 Fire and life safety $84,600 $84,600 Commissioning $112,800 $112,800 $1,603,332 $28.43 2 pipe beams, primary air heating coil $3.66 $9,000 Condensation prevention TOTAL INSTALLED COST OF HVAC SYSTEM $8.16 $1,734,621 $30.76 Gray cells require user input Article in winter 2013 High Performance Buildings • UC Davis Health and Wellness Center • 73,112 ft2 of conditioned space • LEED-NC Gold • Occupied since March 2010 • DOAS air handling strategy • Energy performance • Projected 35% better than LEED baseline • Actual 31% better than projected • 70% less primary air than VAV system And the hands down winner is……… Chilled beams! Questions? Active beams versus VAV with Reheat Analysis of May 2013 ASHRAE Journal article