Fundamentals of Distance Protection GE Multilin Outline • • • • • • • • Transmission line introduction What is distance protection? Non-pilot and pilot schemes Redundancy considerations Security for dual-breaker terminals Out-of-step relaying Single-pole tripping Series-compensated lines 2/ GE / March 18, 2016 Transmission Lines A Vital Part of the Power System: • Provide path to transfer power between generation and load • Operate at voltage levels from 69kV to 765kV • Deregulated markets, economic, environmental requirements have pushed utilities to operate transmission lines close to their limits. 3/ GE / March 18, 2016 Transmission Lines Classification of line length depends on: Source-to-line Impedance Ratio (SIR), and Nominal voltage Length considerations: Short Lines: SIR > 4 Medium Lines: 0.5 < SIR < 4 Long Lines: SIR < 0.5 4/ GE / March 18, 2016 Typical Protection Schemes Short Lines • Current differential • Phase comparison • Permissive Overreach Transfer Trip (POTT) • Directional Comparison Blocking (DCB) 5/ GE / March 18, 2016 Typical Protection Schemes Medium Lines • Phase comparison • Directional Comparison Blocking (DCB) • Permissive Underreach Transfer Trip (PUTT) • Permissive Overreach Transfer Trip (POTT) • Unblocking • Step Distance • Step or coordinated overcurrent • Inverse time overcurrent • Current Differential 6/ GE / March 18, 2016 Typical Protection Schemes Long Lines • Phase comparison • Directional Comparison Blocking (DCB) • Permissive Underreach Transfer Trip (PUTT) • Permissive Overreach Transfer Trip (POTT) • Unblocking • Step Distance • Step or coordinated overcurrent • Current Differential 7/ GE / March 18, 2016 What is distance protection? Intended REACH point F1 Z I*Z V=I*ZF I*Z - V RELAY (V,I) For internal faults: > IZ – V and V approximately in phase (mho) > IZ – V and IZ approximately in phase (reactance) 8/ GE / March 18, 2016 What is distance protection? F2 Intended REACH point Z I*Z V=I*ZF I*Z - V RELAY (V,I) For external faults: > IZ – V and V approximately out of phase (mho) > IZ – V and IZ approximately out of phase (reactance) 9/ GE / March 18, 2016 What is distance protection? Intended REACH point Z RELAY 10 / GE / March 18, 2016 Source Impedance Ratio, Accuracy & Speed Relay Lin e System Voltage at the relay: VR VN f LOC [ PU ] f LOC [ PU ] SIR Consider SIR = 0.1 Fault location Voltage (%) Voltage change (%) 75% 88.24 2.76 90% 90.00 0.91 100% 90.91 N/A 110% 91.67 0.76 11 / GE / March 18, 2016 Source Impedance Ratio, Accuracy & Speed Relay System Lin e Voltage at the relay: VR VN f LOC [ PU ] f LOC [ PU ] SIR Consider SIR = 30 Fault location Voltage (%) Voltage change (%) 75% 2.4390 0.7868 90% 2.9126 0.3132 100% 3.2258 N/A 110% 3.5370 0.3112 12 / GE / March 18, 2016 Challenges in relay design > Transients: – High frequency – DC offset in currents – CVT transients in voltages 30 voltage, V 20 High Voltage Line C1 6 steady-state output 10 0 -10 3 1 5 CVT output C2 Secondary Voltage Output -20 2 7 -30 0 1 2 power cycles 3 4 4 8 13 / GE / March 18, 2016 Challenges in relay design > Transients: – High frequency – DC offset in currents – CVT transients in voltages 60 voltage, V 40 High Voltage Line C1 6 steady-state output 20 0 -20 3 1 CVT output 5 C2 Secondary Voltage Output -40 2 7 -60 0 1 2 power cycles 3 4 4 8 14 / GE / March 18, 2016 Challenges in relay design 100 vA vB 100 vC 80 20 0 -20 -40 -60 -80 -100 -0.5 0 0.5 1 1.5 50 SPOL Sorry… Future (unknown) 0 -50 5 iA 4 SOP 3 Current [A] Voltage [V] 40 Reactance comparator [V] 60 -100 2 0 0.5 1 1.5 power cycles 1 0 iB, iC -1 -2 -3 -0.5 -0.5 0 0.5 1 1.5 > In-phase = internal fault > Out-of-phase = external fault 15 / GE / March 18, 2016 Transient Overreach • Fault current generally contains dc offset in addition to ac power frequency component • Ratio of dc to ac component of current depends on instant in the cycle at which fault occurred • Rate of decay of dc offset depends on system X/R 16 / GE / March 18, 2016 Zone 1 and CVT Transients Capacitive Voltage Transformers (CVTs) create certain problems for fast distance relays applied to systems with high Source Impedance Ratios (SIRs): > CVT-induced transient voltage components may assume large magnitudes (up to 30-40%) and last for a comparatively long time (up to about 2 cycles) > 60Hz voltage for faults at the relay reach point may be as low as 3% for a SIR of 30 > the signal may be buried under noise 17 / GE / March 18, 2016 Zone 1 and CVT Transients CVT transients can cause distance relays to overreach. Generally, transient overreach may be caused by: > overestimation of the current (the magnitude of the current as measured is larger than its actual value, and consequently, the fault appears closer than it is actually located), > underestimation of the voltage (the magnitude of the voltage as measured is lower than its actual value) > combination of the above 18 / GE / March 18, 2016 Distance Element Fundamentals Z1 End Zone XL R XC 15 34 42 Actual Fault Location 44 Reactance [ohm] 10 30 dynamic mho zone extended for high SIRs Line Impedance 5 18 22 Trajectory (msec) 0 26 -5 -10 -5 0 Resistance [ohm] 5 10 Impedance locus may pass below the origin of the Z-plane this would call for a time delay to obtain stability 20 / GE / March 18, 2016 CVT Transient Overreach Solutions > apply delay (fixed or adaptable) > reduce the reach > adaptive techniques and better filtering algorithms 21 / GE / March 18, 2016 CVT Transients – Adaptive Solution > Optimize signal filtering: – currents - max 3% error due to the dc component – voltages - max 0.6% error due to CVT transients > Adaptive double-reach approach – filtering alone ensures maximum transient overreach at the level of 1% (for SIRs up to 5) and 20% (for SIRs up to 30) – to reduce the transient overreach even further an adaptive double-reach zone 1 has been implemented 22 / GE / March 18, 2016 CVT Transients – Adaptive Solution The outer zone 1: > is fixed at the actual reach > applies certain security delay to cope with CVT transients The inner zone 1: > has its reach dynamically controlled by the voltage magnitude > is instantaneous X Delayed Trip Instantaneous Trip R 23 / GE / March 18, 2016 Desirable Distance Relay Attributes Filters: > Prefiltering of currents to remove dc decaying transients – Limit maximum transient overshoot (below 2%) > Prefiltering of voltages to remove low frequency transients caused by CVTs – Limit transient overreach to less than 5% for an SIR of 30 > Accurate and fast frequency tracking algorithm > Adaptive reach control for faults at reach points 24 / GE / March 18, 2016 Distance Relay Operating Times 25 / GE / March 18, 2016 Distance Relay Operating Times 35ms 25ms 30ms 20ms 15ms 26 / GE / March 18, 2016 Distance Relay Operating Times SLG faults LL faults 3P faults 27 / GE / March 18, 2016 Actual maximum reach curves Relay 4 100 90 Relay 3 80 Maximum Rach [%] 70 60 50 40 Relay 2 30 20 Relay 1 10 0 0 5 10 15 SIR 20 25 30 28 / GE / March 18, 2016 Maximum Torque Angle • Angle at which mho element has maximum reach • Characteristics with smaller MTA will accommodate larger amount of arc resistance 29 / GE / March 18, 2016 Mho Characteristics Traditional Directional angle “slammed” Directional angle lowered and “slammed” Both MHO and directional angles “slammed” (lens) 30 / GE / March 18, 2016 Load Swings +XL + = LOOKING INTO LINE normally considered forward Load Trajectory Operate No Operate area area Typical load characteristic impedance +R 31 / GE / March 18, 2016 Load Swings “Lenticular” Characteristic Load swing 32 / GE / March 18, 2016 Load Encroachment Characteristic The load encroachment element responds to positive sequence voltage and current and can be used to block phase distance and phase overcurrent elements. 33 / GE / March 18, 2016 Blinders • Blinders limit the operation of distance relays (quad or mho) to a narrow region that parallels and encompasses the protected line • Applied to long transmission lines, where mho settings are large enough to pick up on maximum load or minor system swings 34 / GE / March 18, 2016 Quadrilateral Characteristics 35 / GE / March 18, 2016 Quadrilateral Characteristics Ground Resistance (Conductor falls on ground) R Resultant impedance outside of the mho operating region 36 / GE / March 18, 2016 Distance Characteristics Summary Mho Lenticular JX Quadrilatera l R Standard for phase elements Used for phase elements with long heavily loaded lines heavily loaded Better coverage for ground faults due to resistance added to return path 37 / GE / March 18, 2016 Distance Element Polarization The following polarization quantities are commonly used in distance relays for determining directionality: • Self-polarized • Memory voltage • Positive sequence voltage • Quadrature voltage • Leading phase voltage 38 / GE / March 18, 2016 Memory Polarization > Positive-sequence memorized voltage is used for polarizing: – Mho comparator (dynamic, expanding Mho) – Negative-sequence directional comparator (Ground Distance Mho and Quad) – Zero-sequence directional comparator (Ground Distance MHO and QUAD) – Directional comparator (Phase Distance MHO and QUAD) > Memory duration is a common distance settings (all zones, phase and ground, MHO and QUAD) 39 / GE / March 18, 2016 Memory Polarization Static MHO characteristic (memory not established or expired) jX ZL Dynamic MHO characteristic for a reverse fault Dynamic MHO characteristic for a forward fau Impedance During Close-up Faults R ZS 40 / GE / March 18, 2016 Memory Polarization jX ZL Static MHO characteristic (memory not established or expired) Dynamic MHO characteristic for a forward fault RL R ZS Memory Polarization…Improved Resistive Coverage 41 / GE / March 18, 2016 Choice of Polarization • In order to provide flexibility modern distance relays offer a choice with respect to polarization of ground overcurrent direction functions: – Voltage polarization – Current polarization – Dual polarization 42 / GE / March 18, 2016 Ground Directional Elements > Pilot-aided schemes using ground mho distance relays have inherently limited fault resistance coverage > Ground directional over current protection using either negative or zero sequence can be a useful supplement to give more coverage for high resistance faults > Directional discrimination based on the ground quantities is fast: – Accurate angular relations between the zero and negative sequence quantities establish very quickly because: During faults zero and negative-sequence currents and voltages build up from very low values (practically from zero) The pre-fault values do not bias the developing fault components in any direction 43 / GE / March 18, 2016 Distance Schemes Pilot Aided Schemes Non-Pilot Aided Schemes (Step Distance) Communication between Distance relays No Communication between Distance Relays 44 / GE / March 18, 2016 Step Distance Schemes • Zone 1: – Trips with no intentional time delay – Underreaches to avoid unnecessary operation for faults beyond remote terminal – Typical reach setting range 80-90% of ZL • Zone 2: – Set to protect remainder of line – Overreaches into adjacent line/equipment – Minimum reach setting 120% of ZL – Typically time delayed by 15-30 cycles • Zone 3: – Remote backup for relay/station failures at remote terminal – Reaches beyond Z2, load encroachment a consideration 45 / GE / March 18, 2016 Step Distance Schemes Local Z1 Z1 Remote 46 / GE / March 18, 2016 Step Distance Schemes Local End Zone Z1 End Zone Z1 Remote 47 / GE / March 18, 2016 Step Distance Schemes Local Z1 Breaker Tripped Breaker Closed Z1 Remote 48 / GE / March 18, 2016 Step Distance Schemes Local Z2 (time delayed) Z1 Z1 Z2 (time delayed) Remote 49 / GE / March 18, 2016 Step Distance Schemes … Z3 (remote backup) Z2 (time delayed) Z1 50 / GE / March 18, 2016 Step Distance Protection 51 / GE / March 18, 2016 Distance Relay Coordination Over Lap Local Relay – Z2 Remote Relay – Z4 Local Relay Remote Relay Zone 2 PKP Zone 4 PKP 52 / GE / March 18, 2016 Need For Pilot Aided Schemes Local Relay Remote Relay Communication Channel 53 / GE / March 18, 2016 Pilot Communications Channels • Distance-based pilot schemes traditionally utilize simple on/off communications between relays, but can also utilize peer-to-peer communications and GOOSE messaging over digital channels • Typical communications media include: – Pilot-wire (50Hz, 60Hz, AT) – Power line carrier – Microwave – Radio – Optic fiber (directly connected or multiplexed channels) 54 / GE / March 18, 2016 Distance-based Pilot Protection 55 / GE / March 18, 2016 Pilot-Aided Distance-Based Schemes DUTT – Direct Under-reaching Transfer Trip PUTT – Permissive Under-reaching Transfer Trip POTT – Permissive Over-reaching Transfer Trip Hybrid POTT – Hybrid Permissive Overreaching Transfer Trip DCB – Directional Comparison Blocking Scheme DCUB – Directional Comparison Unblocking Scheme 56 / GE / March 18, 2016 Direct Underreaching Transfer Trip (DUTT) • Requires only underreaching (RU) functions which overlap in reach (Zone 1). •Applied with FSK channel – GUARD frequency transmitted during normal conditions – TRIP frequency when one RU function operates • Scheme does not provide tripping for faults beyond RU reach if remote breaker is open or channel is inoperative. • Dual pilot channels improve security 57 / GE / March 18, 2016 DUTT Scheme Zone 1 Bus Bus Line Zone 1 58 / GE / March 18, 2016 Permissive Underreaching Transfer Trip (PUTT) • Requires both under (RU) and overreaching (RO) functions • Identical to DUTT, with pilot tripping signal supervised by RO (Zone 2) 59 / GE / March 18, 2016 PUTT Scheme Zone 2 Zone 1 To protect end of line Bus Bus Line Zone 1 Zone 2 Rx PKP Zone 2 Local Trip & OR Zone 1 60 / GE / March 18, 2016 Permissive Overreaching Transfer Trip (POTT) • Requires overreaching (RO) functions (Zone 2). • Applied with FSK channel: – GUARD frequency sent in stand-by – TRIP frequency when one RO function operates • No trip for external faults if pilot channel is inoperative • Time-delayed tripping can be provided 61 / GE / March 18, 2016 POTT Scheme Zone 2 Zone 1 Bus Bus Line Zone 1 Zone 2 (Z1) Tx Zone 1 (Z1) OR Rx AND Zone 2 Trip Line Breakers t o 62 / GE / March 18, 2016 POTT Scheme POTT – Permissive Over-reaching Transfer Trip End Zone Communication Channel 63 / GE / March 18, 2016 POTT Scheme Local Relay FWD IGND Local Relay – Z2 Remote Relay FWD IGND Remote Relay – Z2 TRIP Communicatio n Channel POTT RX Local Relay ZONE 2 PKP OR Ground Dir OC Fwd POTT TX ZONE 2 PKP Remote Relay OR Ground Dir OC Fwd 64 / GE / March 18, 2016 POTT Scheme POTT RX 2 POTT RX 3 POTT RX 4 Local Relay Communications Channel(s) POTT RX 1 POTT TX 1 A to G POTT TX 2 B to G POTT TX 3 C to G POTT TX 4 Multi Phase Remote Relay 65 / GE / March 18, 2016 POTT Scheme Current reversal example TRIP Local Relay Remote Relay Timer Start Communication Timer Expire Channel GND GNDDIR DIROC OCFWD REV POTT RX POTT TX ZONE 2 OC ORREV GND DIR GND DIR OC FWD 66 / GE / March 18, 2016 POTT Scheme Echo example Remote FWD IGND Open Remote – Z2 OPEN Communication Channel POTT RX Local Relay POTT TX TRIP POTT TX POTT RX Communication Channel Remote Relay 67 / GE / March 18, 2016 Hybrid POTT • Intended for three-terminal lines and weak infeed conditions • Echo feature adds security during weak infeed conditions • Reverse-looking distance and oc elements used to identify external faults 68 / GE / March 18, 2016 Hybrid POTT Zone 2 Zone 1 Remote Local Weak system Bus Bus Line Zone 1 Zone 4 Zone 2 69 / GE / March 18, 2016 Directional Comparison Blocking (DCB) • Requires overreaching (RO) tripping and blocking (B) functions • ON/OFF pilot channel typically used (i.e., PLC) – Transmitter is keyed to ON state when blocking function(s) operate – Receipt of signal from remote end blocks tripping relays • Tripping function set with Zone 2 reach or greater • Blocking functions include Zone 3 reverse and lowset ground overcurrent elements 70 / GE / March 18, 2016 DCB Scheme Zone 2 Zone 1 Remote Local Bus Bus Line Zone 1 Zone 2 71 / GE / March 18, 2016 Directional Comparison Blocking (DCB) End Zone Communication Channel 72 / GE / March 18, 2016 Directional Comparison Blocking (DCB) Internal Faults Local Relay – Z2 FWD IGND TRIP Timer Start Expired TRIP Zone 2 PKP OR NO Local Relay GND DIR OC Fwd Dir Block RX Remote Relay 73 / GE / March 18, 2016 Directional Comparison Blocking (DCB) External Faults Local Relay – Z2 FWD IGND Remote Relay – Z4 TRIP Timer Start No TRIP REV IGND Dir Block RX Local Relay Zone 2 PKP OR DIR BLOCK TX Communication Channel GND DIR OC Fwd Zone 4 PKP Remote Relay OR GND DIR OC Rev 74 / GE / March 18, 2016 Directional Comparison Unblocking (DCUB) • Applied to Permissive Overreaching (POR) schemes to overcome the possibility of carrier signal attenuation or loss as a result of the fault • Unblocking provided in the receiver when signal is lost: – If signal is lost due to fault, at least one permissive RO functions will be picked up – Unblocking logic produces short-duration TRIP signal (150-300 ms). If RO function not picked up, channel lockout occurs until GUARD signal returns 75 / GE / March 18, 2016 DCUB Scheme Forward Bus Bus Line Forward (Un-Block) Tx1 (Block) Tx2 Trip Line Breakers Forward (Block) Rx2 AND AND (Un-Block) t AND o AND Rx1 Lockout 76 / GE / March 18, 2016 Directional Comparison Unblocking (DCUB) End Zone Communication Channel 77 / GE / March 18, 2016 Directional Comparison Unblocking (DCUB) Normal conditions Load Current FSK Carrier GUARD1 RX FSK Carrier GUARD1 TX Local Relay NO Loss of Guard NO Permission Remote Relay GUARD2 TX Communication Channel GUARD2 RX NO Loss of Guard NO Permission 78 / GE / March 18, 2016 Directional Comparison Unblocking (DCUB) Normal conditions, channel failure Load Current Loss of Channel FSK Carrier GUARD1 NO RX RX FSK Carrier GUARD1 TX Local Relay Loss of Guard Block Timer Started Expired Block DCUB until Guard OK Remote Relay GUARD2 TX Communication Channel GUARD2 NO RX RX Loss of Guard Block Timer Expired Started Block DCUB 79 / until Guard OKGE / March 18, 2016 Directional Comparison Unblocking (DCUB) Internal fault, healthy channel Local Relay – Z2 Remote Relay – Z2 TRIP TRIP Z1 FSK Carrier Local Relay Zone 2 PKP FSK Carrier GUARD1 TRIP1 RXRX GUARD1 TRIP1 TX TX GUARD2 TRIP2 TX TX GUARD2 TRIP2 RXRX Remote Relay ZONE 2 PKP Loss of Guard Permission Communication Channel 80 / GE / March 18, 2016 Directional Comparison Unblocking (DCUB) Internal fault, channel failure Local Relay – Z2 Remote Relay – Z2 Loss of Channel TRIP TRIP Z1 FSK Carrier Local Relay Zone 2 PKP FSK Carrier GUARD1 NO RX RX GUARD1 TRIP1 TX TX GUARD2 TRIP2 TX TX GUARD2 NO RX RX Loss of Guard Block Timer Started Duration Timer Started Expired Remote Relay ZONE 2 PKP Loss of Guard Communication Channel 81 / GE / March 18, 2016 Redundancy Considerations • Redundant protection systems increase dependability of the system: Multiple sets of protection using same protection principle and multiple pilot channels overcome individual element failure, or Multiple sets of protection using different protection principles and multiple channels protects against failure of one of the protection methods. • Security can be improved using “voting” schemes (i.e., 2-outof-3), potentially at expense of dependability. • Redundancy of instrument transformers, battery systems, trip coil circuits, etc. also need to be considered. 82 / GE / March 18, 2016 Redundant Communications End Zone AND Channels: POTT Less Reliable DCB Less Secure OR Channels: Communication Channel 1 Communication Channel 2 More Channel Security POTT More Reliable DCB More Secure More Channel Dependability Loss of Channel 2 83 / GE / March 18, 2016 Redundant Pilot Schemes 84 / GE / March 18, 2016 Pilot Relay Desirable Attributes • Integrated functions: weak infeed echo line pick-up (SOTF) • Basic protection elements used to key the communication: distance elements fast and sensitive ground (zero and negative sequence) directional IOCs with current, voltage, and/or dual polarization 85 / GE / March 18, 2016 Pilot Relay Desirable Attributes Pre-programmed distance-based pilot schemes: Direct Under-reaching Transfer Trip (DUTT) Permissive Under-reaching Transfer Trip (PUTT) Permissive Overreaching Transfer Trip (POTT) Hybrid Permissive Overreaching Transfer Trip (HYB POTT) Blocking scheme (DCB) Unblocking scheme (DCUB) 86 / GE / March 18, 2016 Security for dual-breaker terminals • Breaker-and-a-half and ring bus terminals are common designs for transmission lines. • Standard practice has been to: – sum currents from each circuit breaker externally by paralleling the CTs – use external sum as the line current for protective relays • For some close-in external fault events, poor CT performance may lead to improper operation of line relays. 87 / GE / March 18, 2016 Security for dual-breaker terminals Accurate CTs preserve the reverse current direction under weak remote infeed 88 / GE / March 18, 2016 Security for dual-breaker terminals Saturation of CT1 may invert the line current as measured from externally summated CTs 89 / GE / March 18, 2016 Security for dual-breaker terminals • Direct measurement of currents from both circuit breakers allows the use of supervisory logic to prevent distance and directional overcurrent elements from operating incorrectly due to CT errors during reverse faults. • Additional benefits of direct measurement of currents: independent BF protection for each circuit breaker independent autoreclosing for each breaker 90 / GE / March 18, 2016 Security for dual-breaker terminals Supervisory logic should: – not affect speed or sensitivity of protection elements – correctly allow tripping during evolving external-tointernal fault conditions – determine direction of current flow through each breaker independently: • Both currents in FWD direction internal fault • One current FWD, one current REV external fault – allow tripping during all forward/internal faults – block tripping during all reverse/external faults – initially block tripping during evolving external-tointernal faults until second fault appears in forward direction. Block is then lifted to permit tripping. 91 / GE / March 18, 2016 Single-pole Tripping • Distance relay must correctly identify a SLG fault and trip only the circuit breaker pole for the faulted phase. • Autoreclosing and breaker failure functions must be initiated correctly on the fault event • Security must be maintained on the healthy phases during the open pole condition and any reclosing attempt. 92 / GE / March 18, 2016 Out-of-Step Condition • For certain operating conditions, a severe system disturbance can cause system instability and result in loss of synchronism between different generating units on an interconnected system. 93 / GE / March 18, 2016 Out-of-Step Relaying Out-of-step blocking relays – Operate in conjunction with mho tripping relays to prevent a terminal from tripping during severe system swings & out-of-step conditions. – Prevent system from separating in an indiscriminate manner. Out-of-step tripping relays – Operate independently of other devices to detect out-of-step condition during the first pole slip. – Initiate tripping of breakers that separate system in order to balance load with available generation on any isolated part of the system. 94 / GE / March 18, 2016 Out-of-Step Tripping When the inner characteristic is entered the element is ready to trip The locus must stay for some time between the outer and middle characteristics Must move and stay between the middle and inner characteristics 95 / GE / March 18, 2016 Power Swing Blocking Applications: > Establish a blocking signal for stable power swings (Power Swing Blocking) > Establish a tripping signal for unstable power swings (Outof-Step Tripping) Responds to: > Positive-sequence voltage and current 96 / GE / March 18, 2016 Series-compensated lines Benefits of series capacitors: • Reduction of overall XL of long lines • Improvement of stability margins • Ability to adjust line load levels • Loss reduction • Reduction of voltage drop during severe disturbances • Normally economical for line lengths > 200 miles E Xs SC XL Infinte Bus 97 / GE / March 18, 2016 Series-compensated lines SCs create unfavorable conditions for protective relays and fault locators: • Overreaching of distance elements • Failure of distance element to pick up on low-current faults • Phase selection problems in single-pole tripping applications • Large fault location errors E Xs SC XL Infinte Bus 98 / GE / March 18, 2016 Series-compensated lines Series Capacitor with MOV 99 / GE / March 18, 2016 Series-compensated lines 100 / GE / March 18, 2016 Series-compensated lines Dynamic Reach Control 101 / GE / March 18, 2016 Series-compensated lines Dynamic Reach Control for External Faults 102 / GE / March 18, 2016 Series-compensated lines Dynamic Reach Control for External Faults 103 / GE / March 18, 2016 Series-compensated lines Dynamic Reach Control for Internal Faults 104 / GE / March 18, 2016 Distance Protection Looking Through a Transformer • Phase distance elements can be set to see beyond any 3-phase power transformer • CTs & VTs may be located independently on different sides of the transformer • Given distance zone is defined by VT location (not CTs) • Reach setting is in sec, and must take into account location & ratios of VTs, CTs and voltage ratio of the involved power transformer 105 / GE / March 18, 2016 Transformer Group Compensation Depending on location of VTs and CTs, distance relays need to compensate for the phase shift and magnitude change caused by the 106 / power transformer GE / March 18, 2016 Setting Rules • Transformer positive sequence impedance must be included in reach setting only if transformer lies between VTs and intended reach point • Currents require compensation only if transformer located between CTs and intended reach point • Voltages require compensation only if transformer located between VTs and intended reach point • Compensation set based on transformer connection & vector group as seen from CTs/VTs toward reach point 107 / GE / March 18, 2016 Distance Relay Desirable Attributes > Multiple reversible distance zones > Individual per-zone, per-element characteristic: – Dynamic voltage memory polarization – Various characteristics, including mho, quad, lenticular > Individual per-zone, per-element current supervision (FD) > Multi-input phase comparator: – additional ground directional supervision – dynamic reactance supervision > Transient overreach filtering/control > Phase shift & magnitude compensation for distance applications with power transformers 108 / GE / March 18, 2016 Distance Relay Desirable Attributes > For improved flexibility, it is desirable to have the following parameters settable on a per zone basis: – Zero-sequence compensation – Mutual zero-sequence compensation – Maximum torque angle – Blinders – Directional angle – Comparator limit angles (for lenticular characteristic) – Overcurrent supervision 109 / GE / March 18, 2016 Distance Relay Desirable Attributes > Additional functions – Overcurrent elements (phase, neutral, ground, directional, negative sequence, etc.) – Breaker failure – Automatic reclosing (single & three-pole) – Sync check – Under/over voltage elements > Special functions – Power swing detection – Load encroachment – Pilot schemes 110 / GE / March 18, 2016 111 / GE / March 18, 2016