TECHNICAL SEMINAR - 2 nd PART - EMC & THD
POWER ELECTRONICS R&D
20 th February2011
Index
01
02
Index
01
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
Index
> INTRODUCTION
> CONDUCTED NOISE
> INPUT
- RFI- EMC Input filter
> OUTPUT
- Common Mode Ferrites
- dV/dt Filter
- Sinusoidal/ LC Filter
> COMPETITORS
> STANDARDS & REGULATIONS
> Directiva OMC 2004/108/CE
> IEC/EN 61800-3
> IEEE 519-1992
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
Introduction
EMC
Electromagnetic Compatibility
EMI
Electromagnetic Interference
EMS
Electromagnetic Susceptibility
COMPATIBILITY MARGIN
Device Immunity level
Minimum Immunity level
Maximum Emission level
Device emission level
Frequency spectrum
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
Introduction
EMC
Electromagnetic Compatibility
Low frequency
F Z> 150 kHz
THD
Flicker
EMI
Electromagnetic Interference
Medium
Frequency
150 kHz< f < 30MHz
Conduced
High
Frequency f < 30MHz
Radiated
EMS
Electromagnetic Susceptibility
Radio Frequency
Conduced
Radiated
Surges
Electrical fast transients
Electrostatic discharges
THD
Voltage dips and interruptions
IEEE 519-1992 IEC61800-3 EMC 2004/108/CE
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC | Radiated & Conduced
The electric noise is produced by the inverter bridge. It is due to the interruption of the current signal when the thyristors commutate their status (switch over ON and OFF and vice versa).
For this reason the electric noise is a high frequency current signal which is coupled to the current that is flowing in the drive to the motor and that additionally can be emitted.
It is necessary to deal with two kind of emissions:
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC | Radiated
The RADIATED electric noise will be attenuated considering:
The use of metallic conductions.
The use of shielded wires.
The own metallic cabinet of the drive will help to minimize this effect.
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
Index
> INTRODUCTION
> CONDUCTED NOISE
> INPUT
- RFI- EMC Input filter
> OUTPUT
- Common Mode Ferrites
- dV/dt Filter
- Sinusoidal/ LC Filter
> COMPETITORS
> STANDARDS & REGULATIONS
> Directiva OMC 2004/108/CE
> IEC/EN 61800-3
> IEEE 519-1992
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC | Conduced | Input
Noise coupled to the INPUT SIGNAL of the drive
Recommended use of RFI Input Filters (Radio Frequency Interferences) as well called
EMC Filters (Electro-Magnetic Compatibility).
Regulation which controls the selection of these filters is UNE-EN 61800-3/A11:2002 .
See details on Annex I.
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC | Conduced | Output
Noise coupled in the CURRENT FLOWING TO THE MOTOR - OUTPUT
Output Common Mode Ferrites , in case of the couple noise is common mode noise, that means, noise signal coupled to the capacitances existing between the phases and the earth and also between the motor windings and the earth. This noise is the responsible of the bearing damages.
dV/dt Output Filters , in case of the coupled noise is differential noise, that means, noise signal coupled to the capacitances existing between phases. This noise will produce isolation drillings and additionally will increase the dV/dt factor. These filters can be:
Output Inductance (output coils in series, one per phase)
Iron Dust Toroids , in all output phases.
Sinusoidal / LC filters , deals with the problem by converting the chopped signal into a sinusoidal signal reducing the noise.
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC | Conduced | Output
It is possible to observe that the output waveform of the drive is as follow:
This is the result of the inverter bridge action.
Show film
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC | Conduced | Output | dV/dt
If the waveform is amplified, it is possible to observe that the angle is not 90º exactly:
132kW 800V/µs 1380W
132kW 4000V/µs 1100W
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC | Conduced | Output | dV/dt
By incrementing the dV/dt ramp is possible to reduce the drive losses, that allows to the drives to dissipate less power and consequently they can be smaller.
132kW 800V/µs
1380W
132kW 4000V/µs 1100W
The main disadvantage of this method is the appearance of brusque over-impulses in the drive output which will be higher at motor input.
It is possible to check this in the measurement realized using a competitor drive:
» Actual measurement on competitor drive of 200A on load
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC | Conduced | Output | dV/dt
To solve this problem, Power Electronics works over the gate resistor of the IGBTs, guaranteeing that those over-impulses do not overcome a concrete value.
» Actual measurement on a drive of 200A on load: COMPETITOR
Rg is the gate resistor and it controls the load of the “capacitor” which conform the
IGBT.
» Actual measurement on a drive of 200A on load:
POWER ELECTRONICS
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC | CONDUCED | Output | dV/dt filter
SD700 dV/dt Filter | Iron Dust Toroids
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC | Conduced | Output | dV/dt
Power Electronics for 690V drives integrates the CLAMP system.
This circuit injects the commutation peak voltage that occurs in the IGBT’s due to the inductance caused by the output cable and the motor.
This system avoids IGBT’s and motor damage and reduce the dv/dt filter overheat.
01.
OMC| CONDUCED | Output | Sinusoidal/LC filter
L
Converts the chopped signal into a sinusoidal signal
C
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
Index
> INTRODUCTION
> CONDUCTED NOISE
> INPUT
- RFI- EMC Input filter
> OUTPUT
- Common Mode Ferrites
- dV/dt Filter
- Sinusoidal/ LC Filter
> COMPETITORS
> STANDARDS & REGULATIONS
> Directiva OMC 2004/108/CE
> IEC/EN 61800-3
> IEEE 519-1992
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC| Competitors
SUPPLIER A
For higher cable lengths additional filters must be used. See next pages.
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC| Competitors
SUPPLIER A
DRIVE
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC| Competitors
SUPPLIER A
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC| Competitors
SUPPLIER B
For higher cable lengths additional output chokes must be used. For further details, see next page.
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC| Competitors
SUPPLIER B
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC| Competitors
SUPPLIER C
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC| SD700
SD700 SERIES
Input chokes (as standard)
Output dV/dt filters (as standard)
Electronic control of the dV/dt of the IGBT
Mechanical construction
Design of PCB’s
Supply Voltage
Frames
Screened (m)
1 2 3 4
400Vac (-20% to +10%)
5 6 7 8 9 10 11
150 150 150 150 150 150 150 150 150 150 150
Unscreened (m) 300 300 300 300 300 300 300 300 300 300 300
Supply Voltage
Frames
Screened (m)
3
100
4
100
5
550Vac to 690Vac (-20% to +10%)
100
6
100
7
100
8
100
9
100
10
100
11
100
Unscreened (m) 200 200 200 200 200 200 200 200 200
» For higher cable length contact with Power Electronics
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC| SD700
Admissible Peak voltage limit curves in AC motors terminals:
2.4
2.0
1.6
1.2
0.8
0.4
50m
IEC 60034-25 Curve B
(without filters for motors up to 690V AC)
2.15kV
NEMA MG1 Pt31 in grids of 600V
100m
IEC 60034-25 Curve A
(without filters for motors up to 500V AC)
IEC 60034-17
NEMA MG1 Pt31 in grids of 400V
Effect of the motor range increase
1.86kV
1.56kV
1.35kV
1.24kV
10m
20m
30m
0.1
0.2
Examples of the test results, using reinforced copper wires at 415V rated voltage.
1.1
1.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
Rise time of the voltage pulse (µs)
1.0
VFITCC0035AI
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC| SD700
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC| SD700
One sample of the tests to the SD700.
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
OMC| SD700
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
Index
> INTRODUCTION
> CONDUCTED NOISE
> INPUT
- RFI- EMC Input filter
> OUTPUT
- Common Mode Ferrites
- dV/dt Filter
- Sinusoidal/ LC Filter
> COMPETITORS
> STANDARDS & REGULATIONS
> Directiva OMC 2004/108/CE
> IEC/EN 61800-3
> IEEE 519-1992
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
:
EMC 2004/108/CE
IEC61800-3
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
First environment
Second environment
IEC61800-3/A11
Classifying Criteria
Non restricted distribution
Restricted distribution
Input current 100A
Input current > 100A
Application Limit
C1
C2
C3
C4
WHERE?
First Environment: Includes domestic or residential use. It includes also, places directly connected, without intermediate transformers, to a power supply distribution system of low energy which additionally gives supply to buildings used for domestic uses (cinemas, theatres, shopping centres, hospitals,…).
Second Environment: (Named also industrial). It includes all places different from those which are directly connected to a power supply distribution system of low energy which additionally gives supply to buildings used for domestic uses (factories and facilities supplied with transformer of medium voltage to low voltage).
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
First environment
Second environment
IEC61800-3/A11
Classifying Criteria
Non restricted distribution
Restricted distribution
Input current 100A
Input current > 100A
Application Limit
C1
C2
C3
C4
WHERE?
Non-Restricted Distribution: Marketing modality where the power supply of the drive does not depend on the customer or user regarding to EMC issues for the application of operation.
Restricted Distribution: Marketing modality where the manufacturer limits the supplying of the drive to those customers or users which, in an independent or together way, have technical competence on the EMC requirements for the application of operation.
01.
ELECTROMAGNETIC COMPATIBILITY (EMC)
C1
1 st Environment
C2
I < 100A
C3
2 nd Environment
I > 100A
C4
EMC PLAN
Quasi pick value Average value
Index
02
02 TOTAL HARMONIC DISTORTION
TOTAL HARMONIC DISTORTION
> Basic principles
> Measurement
> Effects
> Standards & Regulations
> Solutions
- Passive Filters
- FREEMAQ
- Active Filters
- Multipulses drives
> Competitors
02 TOTAL HARMONIC DISTORTION
Basic Principles | What is the Harmonic Distortion?
02 TOTAL HARMONIC DISTORTION
Basic Principles | What is the Harmonic Distortion?
If g
► 50Hz or 60 Hz If
5rd
► 5 · f g
I
T
= I
1
+ I
5
…..+I n
If
7th
► 7 · f g
02 TOTAL HARMONIC DISTORTION
Wave Fourier Transform
THDi Value
02 TOTAL HARMONIC DISTORTION
In variable speed drives applications both the harmonic current distortion and the harmonic voltage distortion are of interest. The harmonic current and voltage distortion have different effects on the power system and it is therefore important to separate them.
The harmonic current distortion is caused by the rectifier part of the variable speed drive, typically a 6-pulse diode rectifier. The harmonic currents can be described as a reactive current adding to the active current. Consequently the harmonic current distortion is increasing the
RMS current and if not taking into account can result in overheating of components such as the supply transformer or cables. The amount of harmonic current distortion is often described in percent of the fundamental current also known as the total harmonic current distortion
(THID).
THID
h
2
I h
2
I
1
02 TOTAL HARMONIC DISTORTION
The harmonic current is normally flowing from the harmonic current generator (e.g. the diode rectifier) into the mains. The voltage drop caused by the harmonic currents over the supply impedance causes then the harmonic voltage distortion. I.e. the harmonic voltage distortion is a product of the harmonic current distortion and the supply impedance, where a grid with the largest impedance yields the highest voltage distortion.
The harmonic voltage distortion can interfere with equipment connected to the same line such as direct on-line motors or electronic equipment and eventually cause this equipment to fail. The amount of harmonic voltage distortion is often described in percent of the fundamental voltage also known as the total harmonic voltage distortion (THVD).
THVD
h
2
U h
2
U
1
02 TOTAL HARMONIC DISTORTION
TOTAL HARMONIC DISTORTION
> Basic principles
> Measurement
> Effects
> Standards & Regulations
> Solutions
- Passive Filters
- FREEMAQ
- Active Filters
- Multipulses drives
> Competitors
02 TOTAL HARMONIC DISTORTION
1) Electrical Grid and Power Transformer overload and heating.
2) Reduction of the Motor Efficiency , non sinusoidal waveforms increases internal heating lost.
3) Resonance effects and power capacitors banks overload , the power factor corrections systems do not work properly increasing the energy bill.
4) Electronic and computers underperformance. Low consumption and single phase devices could be affected and do not work properly.
02 TOTAL HARMONIC DISTORTION
TOTAL HARMONIC DISTORTION
> Basic principles
> Measurement
> Effects
> Standards & Regulations
> Solutions
- Passive Filters
- FREEMAQ
- Active Filters
- Multipulses drives
> Competitors
02 TOTAL HARMONIC DISTORTION
The legislation applicable for drives is that described in the international regulation IEC61800-
3. Included in that general regulation, there are some others regulations which refer to harmonics such us IEC61000-2-4 (Class 3: THD=10%) or IEC61000-2-2 (THD=8%)
Literal description extracted from regulation IEC61800-3 :
“The immunity levels used for the design regarding the THD of voltage and the individual harmonics orders will be as minimum equal to the permanent compatibility levels at the IEC61000-2-2 (class 3: THD=10%) or IEC61000-2-4 (THD=8%), for those situations in permanent service.
For transient situations (duration less than 15 seconds), the immunity levels used for the design will be minimum 1.5 times the permanent levels”.
02 TOTAL HARMONIC DISTORTION
NORMS DESCRIPTION
IEC61000-2-4 The norm establishes the electromagnetic compatibility levels for low frequency conducted distortions at industrial installations.
IEC61000-2-2 The norm establishes the electromagnetic compatibility levels for low frequency distortions at public low voltage supply systems.
IEC61000-2-12 The norm established the electromagnetic compatibility levels for low frequency distortions at public medium voltage supply systems.
02 TOTAL HARMONIC DISTORTION
This regulation refers to conducted distortions at frequency ranges from 0kHz to 9kHz. It establishes the numeric values of compatibility levels for industrial supply distribution systems and no publics at nominal voltages up to 35kV and nominal frequencies of 50Hz or 60Hz.
ELECTROMAGNETIC ENVIRONMENT CLASSES
CLASS 1 To protected distribution systems and has compatibility levels lower than the public power supply systems. It is related to the use of the equipments very sensible to the supply distribution distortions, as the electric instruments of technological laboratories, some kind of automatic equipments and protection equipments, some computers, etc
CLASS 2 This class is generally applied to PCC and PCI in industrial supply distribution systems and some others no public supply systems. The compatibility levels are generally identical to the corresponding to public supply systems. For that reason, the equipments (in our case the VSD) designed to be used in public power supply systems could also be used in this class in industrial environment
CLASS 3 This class is applicable only for PCI at industrial environment.
There should be considered under the following conditions: Most par of the load is supplied with converters, there are welding machines, the big motors are often started, the load varies quickly.
02 TOTAL HARMONIC DISTORTION
Compatibility levels for Total Harmonic Distortions
CLASS 1 CLASS 2 CLASS 3
Total Harmonic Distortion
(THD)
5% 8% 10%
Note: In case of one part of the power supply system is used for important non linear loads, the compatibility levels of class 3 for this par of the supply distribution could be 1,2 times the above mentioned values.
Then it is necessary to take caution for those equipments there connected. Nevertheless, in the CCP (public supply distribution system) the values offered in norms IEC61000-2-2 and IEC61000-2-12 will prevail.
02 TOTAL HARMONIC DISTORTION
This norm refers to the conducted distortions in the frequency range from 0kHz to 9kHz, with amplified option to 148kHz for signals transmission system to the supply distribution system. These numerical values are offered for compatibility levels in case of public supply distribution system of low voltage with nominal voltage of 420V single-phase or
690V 3-phase and nominal frequency of 50Hz or 60Hz.
Compatibility levels for individual harmonics voltages in low voltage distribution systems.
Odd harmonics not multiple of 3
Order of harmonic
(h)
5
Voltage of harmonic (%)
6
Odd harmonics multiple of 3
(note)
Order of harmonic
(h)
Voltage of harmonic
(%)
3 5
Order of harmonic
(h)
2
Even harmonics
Voltage of harmonic (%)
2
7 5 9 1,5 4 1
11
13
17 ≤ h ≤ 49
3,5
3
2,27 x (17/h)-0,27
15
21
21 ≤ h ≤ 45
0,4
0,3
0,2
6
8
10 ≤ h ≤ 50
0,5
0,5
0,25 x (10/h)+0,25
Note: The levels indicated through odd harmonics multiples of three are applied to the homopolar harmonics. So this, in a 3-phase distribution line without neutral cable with no load connected between a phase and ground, the value of the harmonics order 3 and
9 can be lower enough than compatibility levels, depending on the distribution line imbalance.
02 TOTAL HARMONIC DISTORTION
This norm refers to the conducted distortions in the frequency range from 0kHz to 9kHz, with amplified option to
148,5kHz for signals transmission system to the supply distribution system. These numerical values are offered for compatibility levels in case of public supply distribution system of low voltage with nominal voltage between
1kV and 35kV and nominal frequency of 50Hz or 60Hz.
The compatibility levels are specified for electromagnetic distortion of those types that can be expected in the public power supply distribution systems of medium voltage, with the target of helping to define the following: a) The limits to be established for distortions emissions (in our case of study, harmonics) in the public power supply distribution systems.
b) The immunity limits to be established by products committees or for other devices which support conducted emissions in the public power supply distribution lines.
The medium voltage systems covered by this norm are public power supply distribution systems that supply to: a) Particular installations where devices are connected directly or through transformers.
b) Sub-stations that supply to low voltage public power supply distribution lines.
02 TOTAL HARMONIC DISTORTION
Compatibility levels for individual harmonic voltages in distribution lines of medium voltage.
Odd harmonic not multiples of 3
Harmonic order (h)
5
7
11
13
Harmonic voltage (%)
3,5
3
6
5
Odd harmonics multiples of 3 (note)
Harmonic order (h)
Harmonic voltage (%)
15
21
3
9
5
1,5
0,4
0,3
Harmonic order (h)
2
4
6
8
Even harmonics
Harmonic voltage (%)
0,5
0,5
2
1
17 ≤ h ≤ 49 2,27 x (17/h)-0,27 21 ≤ h ≤ 45 0,2 10 ≤ h ≤ 50 0,25 x (10/h)+0,25
Note: The levels indicated through even harmonics multiples of three are applied to the homopolar harmonics.
So this, in a 3-phase distribution line without neutral cable with no load connected between a phase and ground, the value of the harmonics order 3 and 9 can be lower enough than compatibility levels, depending on the distribution line imbalance.
02 TOTAL HARMONIC DISTORTION
SUMMARY
It is necessary to clarify that in order to fulfill standard regulations, it is required to fulfil the following norms:IEC61000-2-2, IEC61000-2-4 or IEC61000-2-12 depending on the location where the equipments are connected.
If those regulations above mentioned are fulfilled and the THD values in current are above the specified ones in document IEEE-519, then it is possible to state that both the installation and the equipments are have compliance with the norms.
Distortion limits in voltage of a low voltage system (THDv):
THD (voltage)
Special applications
3%
General system
5%
In special applications are included hospitals and airports.
Dedicated system
10%
Distortion limits of current for general distribution systems (THDi):
Isc/IL
<20*
20<50
50<100
100<1000
>1000
<11
4.0
7.0
10.0
12.0
15.0
Maximum harmonic current distortion
Order of each harmonic
11≤h<17 17≤h<23 23≤h<35
2.0
1.0
0.6
3.5
4.5
5.5
7.0
2.5
4.0
5.0
6.0
1.0
1.5
2.0
2.5
35≤h
0.3
0.5
0.7
1.0
1.4
Isc: Maximum short circuit current in the PCC
IL : Maximum demanded current by the load in the PCC
TDD
5.0
8.0
12.0
15.0
20.0
02 TOTAL HARMONIC DISTORTION
TOTAL HARMONIC DISTORTION
> Basic principles
> Measurement
> Effects
> Standards & Regulations
> Solutions
- Passive Filters
- FREEMAQ
- Active Filters
- Multipulses drives
> Competitors
02 TOTAL HARMONIC DISTORTION
PASSIVE FILTERS
th
th
HIGH INPUT IMPEDANCE NOTCH FILTER
ACTIVE FILTERS.
MULTIPULSES DRIVES
02 TOTAL HARMONIC DISTORTION
Passive Filter Input Coils – Choque Inductances
These passive filters can be placed in the rectifier bridge input , realizing a double mission:
• First of all, they protect to the rectifier from voltage variation of the mains.
• On the other hand, they filter the produced harmonics making softer the sinusoidal wave of current.
They can also be placed in the DC bus . The rectifier bridge will not be as protected as in the previous configuration, but this is always a low cost option.
SD700 Frames 3 on SD700 Frame 1 & 2
02 TOTAL HARMONIC DISTORTION
VSD
Zg
L1
L2
C1 C2 f 5th f 7th
1) LC Filters designed for an Specific
Harmonic and Grid Impedance ( Zg)
2) Variation on Zg → Increase THDi
3) Variation on Zg → May cause Resonance
4) Valid for original installations, not compatible with new Grid Loads
1 st 5 th 7 th
Grid Impedance (Zg) Variation
1 st 5 th 7 th
02 TOTAL HARMONIC DISTORTION
L1
Zg
L2
L3
C1
1 st 5 th 7 th
1) LCL Filters designed for General Harmonic attenuation and Independent from the
Grid Impedance ( Zg)
2) Variation on Zg → Do NOT affect to THDi . Z
L1
>> Zg
3) Built in with robust electric components
4) Never cause resonance
02 TOTAL HARMONIC DISTORTION
Zg
C1
L2
L1 1) Works as a Current source.
2) LCL Filter in Parallel.
3) Smaller size of L1 and L2 , designed for switching frequency.
4) Built in with Semiconductors and control software - reduce robustness
CONTROLLED BRIDGE RECTIFIER
02 TOTAL HARMONIC DISTORTION
L1 L2
VSD
Zg
C1
1) Regenerates the braking energy 4 quadrants drive . Increase the overall efficiency
2) Serie LCL Filter
3) Smaller size of L1 and L2 , designed for switching frequency.
4) Built in with Semiconductors and control software reduce robustness
02 TOTAL HARMONIC DISTORTION
The 12 , 18, 24 pulses drive have two, three or four rectifier bridges and the input voltage of each rectifier bridge is 30º / 15º / 7,5º diphase each other
PULSES
6
12
18
24
THDi (%)
< 40 %
< 15 %
< 9 %
< 5%
To do that, it is needed a special transformer with multiple secondary windings is required.
02 TOTAL HARMONIC DISTORTION
12 PULSES ELECTRIC SCHEME
02 TOTAL HARMONIC DISTORTION
12 PULSES RECTIFYING BRIDGE
We can suppose a quasi ideal system applied to the rectifier, considering squared wave signal as reference. Having into consideration that the double secondary, explained before, enters a 30º phase shift in the currents applied to each rectifier, the result is a waveform much more sinusoidal in the inverter bridge:
02 TOTAL HARMONIC DISTORTION
FILTER
TECHNOLOGY
Passive 5th & 7th
Notch Filter
Low Harmonic
FREEMAQ
Active Filter
VSD
Active Front End
LOAD
60%
7% (*)
≈6.5%
≈10%
≈10%
LOAD
75%
6% (*)
≈5%
≈8%
≈8%
LOAD
100%
≤5% (*)
≤5%
≤5%
≤5%
(*) : Depending on the Grid Impedance Zg. Notch filter Re-design for grid load changes .
02 TOTAL HARMONIC DISTORTION
FILTER
TECHNOLOGY
Passive 5th & 7th
Notch Filter
Low Harmonic
FREEMAQ
Active Filter
VSD Active Front
End
LOAD
60%
≥ 96.5
≥ 96.5
≥ 96.5
≥ 96
LOAD
75%
≥ 97
≥ 97
≥ 97
≥ 96.5
LOAD
100%
≥ 97.5
≥ 97
≥ 97
≥ 97
02 TOTAL HARMONIC DISTORTION
XMV660 is multi-cell VFD with series multi-cell VFD with series-connect units, high voltage input, high voltage output.
VFD is composed of transformer, power cells and control system.
Communication between power cells and control system is performed by optic fibre that can handle the problem of separation between heavy current and light current as well as electric magnetic harassment.
3kV
3.3kV
24 PULSES
TRANSFORMER
FAN FAN
3 FANS
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
GND
PC: Power Cell
02 TOTAL HARMONIC DISTORTION
Structure and power cell working principle
Each power cell is AC-DC-AC voltage source and low voltage transformer with 3-phase input, single phase output.
The rectifying side of power cell is rectified by diode 3-phase full bridge in the mode of not-controllable full wave.
Electrolytic capacitor is used to filter wave and store energy in the middle, the output side is formed by 4 pieces of
IGB in the form of H bridge.
Diode does not control rectification, power factor of single power cell is 0.97. Capacitor can buffer power supply impact. Equipment can keep on working in case of insufficient voltage or power off within short time.
02 TOTAL HARMONIC DISTORTION
Control over Output Voltage of Power Cell
At any moment, there are 3 types of possible output voltage. If A+ is on with B-, the output voltage from U to V is +Ud, if B+ is on with A, output voltage from U to V is –Ud, if A+ is on with B+ or A- is on with
B-, output voltage from U to V is 0V.
In the end, equal amplitude PWM wave form can be obtained from U,
V output terminal through control on/off on the IGBT A+ 、 A、 B+ 、
B-.
02 TOTAL HARMONIC DISTORTION
Frequency and Voltage Varying principle of Power Cell
Forma de onda salida PWM durante Frecuencia de Alta Conmutación
Frequency of output voltage of power cell is changed by altering the cycled period between positive voltage and negative voltage of PWM wave form.
Size of AC basic wave of output voltage from the power cell is changed by altering duty ratio between positive and negative voltage of PWM wave form.
Forma de onda de salida PWM durante Frecuencia de Baja Conmutación
02 TOTAL HARMONIC DISTORTION
Output Connection of Power Cell
Output of neighboring power cells are connected in series in “Y” form, which can realize high voltage output. Each power cell undertakes 1/n phase voltage, 100% motor current, 1/3n output efficiency.
For 6KV VFD , if 5 steps in each phase are connected in series, each power cell can output 693V , phase voltage is 3464V , wire voltage is 6000V . Unit DC Bus voltage is lower than 980V. IGBT resisting 1700V can be adopted.
3kV
3.3kV
24 PULSES
TRANSFORMER
FAN FAN
3 FANS
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
R
S
T
PC
GND
PC: Power Cell
02 TOTAL HARMONIC DISTORTION
Q1 Q3
Q2 Q4
En cualquier momento, la tensión de salida que cada célula puede ofrecer es:
Tensión= +600V en caso de que Q1 y Q4 estén en ON.
Tensión= -600V en caso de que Q2 y Q3 estén en ON.
Tensión= 0V en caso de que Q1 y Q3 estén en ON ó si Q2 y Q4 están en ON.
02 TOTAL HARMONIC DISTORTION
Multi-level Signal Generation
Detail Level 1 :
Power cell A2 offers 600V at the output, power cells A1 and A3 offer
0V. Therefore, the voltage is +600V .
02 TOTAL HARMONIC DISTORTION
Multi-level Signal Generation
.
Detail Level 2:
Power cells A1 and A3 offer 600V at the output, power cell A2 offers 0V.
Therefore, the voltage is +1200V.
02 TOTAL HARMONIC DISTORTION
Multi-level Signal Generation
.
Detail Level 3:
.
The three power cells A1, A2 and A3 offer 600V at the output each one.
Therefore, the voltage is +1800V.
02 TOTAL HARMONIC DISTORTION
Producing mechanism of Multi-cell and Phase-shifting PWM
CP1
CP2
CP3
Power cell in the same phase outputs basic wave voltage with the same amplitude and phase position. But the carrier wave of serial connected cells are separated at certain electric angle.
Phase shifting of triangle carrier wave is 360 ° /n electric angle of carrier wave.
CP1+CP2+CP3
02 TOTAL HARMONIC DISTORTION
Phase Voltage and wire Voltage of Multi-cell Phase shifting Output
Wave form of phase voltage and wire voltage (take 3 grade as example).
As for n grade system, there are 2n+1 cells in the phase voltage and 4n+1 cells in the wire voltage. If the modulating frequency of power cell is “f”, the equivalent on/off frequency of output wire voltage is 2nf. The on/off frequency of IGBT is smaller (the on/off loss is also small), the equivalent on/off frequency of output is very high. As there is wave filtration of induction in the motor, current content of output harmonic is very low.
N
U
V
W
02 TOTAL HARMONIC DISTORTION
TOTAL HARMONIC DISTORTION
> Basic principles
> Measurement
> Effects
> Standards & Regulations
> Solutions
- Passive Filters
- FREEMAQ
- Active Filters
- Multipulses drives
> Competitors
02 TOTAL HARMONIC DISTORTION
SUPPLIER A
1.
DC CHOKES.
38% of drives standard built in
62% of drives external option
2.
LINE CHOKES.
100% of drives external option
OTHER SUPPLIER
DRIVE
02 TOTAL HARMONIC DISTORTION
SUPPLIER B
1.
DC CHOKES.
100% of drives external option
2.
LINE CHOKES.
100% of drives external option
02 TOTAL HARMONIC DISTORTION
SUPPLIER C
1.
DC CHOKES.
100% of drives external option
2.
LINE CHOKES.
100% of drives external option