Harmonics (continued)

advertisement

Applied Harmonics

Control of Harmonics

1

Harmonic Distortion Evaluations

IEEE Standard 519-1992

• Limit harmonic current injections from end users so that harmonic voltage distortion is tolerable.

• Limit harmonic voltage (responsibility of utility).

2

utility system

PCC other customers

I

L customer under study utility system

PCC

I

L customer under study other customers

3

• End users are limited at PCC in terms of

– individual harmonic components and

– total demand distortion

• Utility is mainly responsible for limiting voltage distortion at PCC

• Evaluations:

– Measurement of currents injected by load

(over one week period)

– Calculation of frequency response of system impedances (using harmonic calculation software)

4

Total harmonic distortion of voltage is normalized with the system nominal rms voltage :

T HD

V n

 h

 1

V n

V h

2

 100 %

Total demand distortion for current (as before) :

TDD  h

 1

I h

2

I

L

 100 %

5

Bus Voltage at PCC, Vn

[kV,LL]

Vn < 69

Individual harmonic voltage distortion

3.00%

69<Vn<161 1.50%

161<Vn 1.00%

Total voltage distortion

THD_Vn

5.00%

2.50%

1.50%

Table 6.1 Harmonic voltage distortion limits in % of nominal fundamentalfrequency voltage

6

Table 6.2 Harmonic current limits

Vn < 69 kV

Isc/IL

0-20 h<11 11<h<17 17<h<23 23<h<35 35<h

4.0% 2.0% 1.5% 0.6% 0.3%

TDD

5.0%

20-50

50-100

100-1000

>1000

7.0%

10.0%

12.0%

15.0%

3.5%

4.5%

5.5%

7.0%

2.5%

4.0%

5.0%

6.0%

1.0%

1.5%

2.0%

2.5%

0.5%

0.7%

1.0%

1.4%

8.0%

12.0%

15.0%

20.0%

69<Vn <161 kV

Isc/IL

0-20 *

20-50

50-100

100-1000

>1000

161 kV<Vn

Isc/IL

0-50

>50 h<11 11<h<17 17<h<23 23<h<35 35<h

2.0% 1.0% 0.75% 0.3% 0.15%

3.5%

5.0%

6.0%

1.75%

2.25%

2.75%

1.25%

2.0%

2.5%

0.5%

0.75%

1.00%

0.25%

0.35%

0.50%

7.5% 3.50% 3.0% 1.25% 0.70% h<11 11<h<17 17<h<23 23<h<35 35<h

2.0% 1.0% 0.75% 0.3% 0.15%

3.0% 1.50% 1.15% 0.5% 0.22%

TDD

2.5%

4.0%

6.0%

7.5%

10.0%

TDD

2.5%

3.8%

* line applies to all power generation equipment regardless of Isc/IL ratio

7

• I h is rms magnitude of individual harmonic current

• I sc is the short-circuit current at PCC

• I

L is the fundamental component of the maximum demand current (average max demand over 12 months)

• Individual limits apply to odd-order harmonics, even order limits are at 25% of indicated value

8

• For power converters with more than 6 pulses, where q = pulse number, multiply limits in table 6.2 by q / 6

2 .

For example, if q  12, then multiply by

I

L

 kWD kWD pf

 3  kV rated average billed demand in kW pf  average billed power factor kV rated

 nominal LL voltage in kV

9

Controlling harmonics

• Control only when harmonics create a problem. Types of problems:

– load harmonic currents are too large

– path for harmonic currents is too long electrically (too much impedance) producing voltage distortion or communication-line interference

– response of system magnifies one or more harmonics

10

Options for control

• Reduce magnitude of harmonic currents from load

• Add filters to do one or more of these:

– short out (siphon off) the harmonic

– block harmonic currents from entering part of the system

– supply the harmonics locally

• Modify the frequency response of the system by filters or other means

11

Reducing load harmonic current

• Sometimes transformer connections can be changed, for example:

– phase shift on some transformers supplying

6-pulse converters

– delta windings block triplen currents

– zig-zag transformers can supply triplens

12

C

A

B

C

B A

N

Zig-zag transformer

N

13

Zig zag transformer

• Place the transformer to supply balanced triplen harmonics (and any other zerosequence currents) to load

• This will unload zero sequence currents on circuits upstream of the ZZ transformer, with little or no effect downstream

• Fault study results may be affected

14

Placement of ZZ transformer

a b c

I

3 n

3I

3

Unloads the neutral conductor upstream

15

Filtering

• Shunt passive filter: short-circuit harmonic currents close to their source

• Series passive filter: block harmonic currents from power delivery system (may cause large load voltage distortion)

• Active shunt filter: electronically supply low-order harmonics to a nonlinear load

(used with simple passive filters for higher frequency components).

16

Passive Filters

• Shunt passive filters are

– notch filters, tuned to a specific harmonic frequency, or

– high-pass filters notch filter high-pass filter

17

Modifying system frequency response

• Add a shunt filter to the system

• Add a reactor (e.g., in series with a pf correction capacitor) to de-tune system

• Change pf correction capacitor size or placement, or remove capacitor bank entirely

18

Where to control harmonics

• On utility system or end-user facility

– utility system is more difficult to filter unless we can move or change the size of or reconnect a capacitor

– end-user system may be easier to filter if we can access the feeder(s) where the harmonic currents are being produced

19

Filters

• In-line reactors (or chokes) for ASD

• Isolation transformers can help

• Isolation transformers can be reconnected with different phase shifts

X s

X t reactor 0-5% on ASD kVA

ASD

M

20

Isolation transformers X~5%

480 V bus

ASD

M

M

ASD

Approximates a 12-pulse converter with 6pulse converters by putting half on Delta-

Delta transformers and the half on Delta-Y.

12-pulse has I h

= 0 for h = 5, 7

21

Harmonic studies

• Perform harmonic studies when

– a problem occurs, to find a solution

– planning large capacitor bank installation on either utility or industrial system

– planning installation of large nonlinear load such as adjustable speed motor drives (ASD)

– designing a harmonic filter or converting a capacitor to a harmonic filter

22

Download