Energy Efficient Buildings Outdoor Air Control Homework 1) ASHRAE 62.1 - 2004 reduces the occupancy-based ventilation requirement from 15 cfm/person to 7.5 cfm/person. Determine the difference in CO2 concentration (ppm) between outdoor and indoor air to meet this requirement for occupancy-based ventilation. 2) Consider the VAV system with multiple CO2 sensors shown below. The peak sensible cooling loads on the three zones are: 24,000 Btu/hr, 40,000 Btu/hr and 60,000 Btu/hr. The peak number of occupants in the three zones are: 20, 30 and 30. The supply air temperature is 55 F and the return air temperature is 72 F. Code requires 15 cfm of outdoor air per person. Determine the design volume flow rate Vsa and outdoor air flow rate Voa at these conditions for three zones, and the total fraction outdoor air, foa, supplied by the air handler. Zone 1 Design Vsa (cfm) VOA (cfm) foa Z1 Zone 2 Zone 3 Z2 Z3 Total Next, consider an actual operating condition. The actual sensible cooling loads on the three zones are: 22,000 Btu/hr, 30,000 Btu/hr and 15,000 Btu/hr. The actual number of occupants in the three zones are: 18, 10 and 5. Determine the volume flow rate Vsa, outdoor air flow rate Voa, and required foa for each zone at these conditions. Determine the critical (maximum) foa. Determine the actual outdoor air supplied to each zone, and the actual total outdoor air supplied by the air handler. Design Vsa (cfm) VOA,REQUIRED (cfm) foa VOA,ACTUAL (cfm) Z1 Z2 Z3 Total 3) Determine annual cooling energy use (mmBtu/year) for a HVAC system in Chicago, IL with and without a temperature-based economizer. The volume air flow rate over the cooling coil is 1,000 cfm and the air density is 0.075 lb/ft3. The supply air leaves the cooling coil at 55 F with an enthalpy of 23.3 Btu/lb. The return air leaves the zone at 72 F with an enthalpy of 28.3 Btu/lba. The minimum required fraction outdoor air is 0.20. To do so, create a temperature bin file from the Chicago IL TM3 file using WeaTran, and open it into excel. Remove extraneous columns. It may be helpful to match the results shown below for Dayton, Ohio, and then paste the Chicago IL bin data into the first 5 columns. Note that in Dayton, Ohio, the economizer cut annual cooling energy use in half. No Economizer psa = 0.075 lb/ft3 StrTemp EndTemp T(F) h(Btu/lba) hrs1-24 Tsa(F) has(Btu/lba)Tra(F) hra(Btu/lba)foa,min foa Tma(F) hma(Btu/lba) Vsa(cfm) Qcc (mmBtu/yr) ======================================================================================================================== 105 109 107 -99 0 55 23.3 72 28.3 0.2 0.20 79.0 2.8 1000 0.00 100 104 102 -99 0 55 23.3 72 28.3 0.2 0.20 78.0 2.8 1000 0.00 95 99 97 -99 0 55 23.3 72 28.3 0.2 0.20 77.0 2.8 1000 0.00 90 94 91 38.8 5 55 23.3 72 28.3 0.2 0.20 75.8 30.4 1000 0.16 85 89 87.4 38 123 55 23.3 72 28.3 0.2 0.20 75.1 30.2 1000 3.84 80 84 82.2 34.9 451 55 23.3 72 28.3 0.2 0.20 74.0 29.6 1000 12.83 75 79 76.9 32.7 563 55 23.3 72 28.3 0.2 0.20 73.0 29.2 1000 14.90 70 74 72.4 31.2 706 55 23.3 72 28.3 0.2 0.20 72.1 28.9 1000 17.73 65 69 68.1 28.6 794 55 23.3 72 28.3 0.2 0.20 71.2 28.4 1000 18.08 60 64 62.4 24.2 863 55 23.3 72 28.3 0.2 0.20 70.1 27.5 1000 16.23 55 59 57 21.1 657 55 23.3 72 28.3 0.2 0.20 69.0 26.9 1000 10.53 50 54 51.8 18.7 670 55 23.3 72 28.3 0.2 0.20 68.0 26.4 1000 9.29 45 49 47.5 16.6 487 55 23.3 72 28.3 0.2 0.20 67.1 26.0 1000 5.83 40 44 43.2 14.8 683 55 23.3 72 28.3 0.2 0.20 66.2 25.6 1000 7.07 35 39 37.5 12.6 693 55 23.3 72 28.3 0.2 0.20 65.1 25.2 1000 5.80 30 34 32.3 10.8 641 55 23.3 72 28.3 0.2 0.20 64.1 24.8 1000 4.33 25 29 27.4 8.8 390 55 23.3 72 28.3 0.2 0.20 63.1 24.4 1000 1.93 20 24 23.1 7.5 371 55 23.3 72 28.3 0.2 0.20 62.2 24.1 1000 1.40 15 19 17.8 5.7 302 55 23.3 72 28.3 0.2 0.20 61.2 23.8 1000 0.65 10 14 12.1 4 152 55 23.3 72 28.3 0.2 0.20 60.0 23.4 1000 0.10 5 9 7.2 2.6 105 55 23.3 72 28.3 0.2 0.20 59.0 23.2 1000 0.00 0 4 2.5 1.3 53 55 23.3 72 28.3 0.2 0.20 58.1 22.9 1000 0.00 -5 -1 -2 0 40 55 23.3 72 28.3 0.2 0.20 57.2 22.6 1000 0.00 -10 -6 -6.4 -1.1 11 55 23.3 72 28.3 0.2 0.20 56.3 22.4 1000 0.00 -15 -11 -13 -99 0 55 23.3 72 28.3 0.2 0.20 55.0 2.8 1000 0.00 -20 -16 -18 -99 0 55 23.3 72 28.3 0.2 0.20 54.0 2.8 1000 0.00 -25 -21 -23 -99 0 55 23.3 72 28.3 0.2 0.20 53.0 2.8 1000 0.00 -30 -26 -28 -99 0 55 23.3 72 28.3 0.2 0.20 52.0 2.8 1000 0.00 Total 130.68 Temperature-based Economizer psa = 0.075 lb/ft3 StrTemp EndTemp T(F) h(Btu/lba) hrs1-24 Tsa(F) has(Btu/lba)Tra(F) hra(Btu/lba)foa,min foa Tma(F) hma(Btu/lba) Vsa(cfm) Qcc (mmBtu/yr) ======================================================================================================================== 105 109 107 -99 0 55 23.3 72 28.3 0.2 0.20 79.0 2.8 1000 0.00 100 104 102 -99 0 55 23.3 72 28.3 0.2 0.20 78.0 2.8 1000 0.00 95 99 97 -99 0 55 23.3 72 28.3 0.2 0.20 77.0 2.8 1000 0.00 90 94 91 38.8 5 55 23.3 72 28.3 0.2 0.20 75.8 30.4 1000 0.16 85 89 87.4 38 123 55 23.3 72 28.3 0.2 0.20 75.1 30.2 1000 3.84 80 84 82.2 34.9 451 55 23.3 72 28.3 0.2 0.20 74.0 29.6 1000 12.83 75 79 76.9 32.7 563 55 23.3 72 28.3 0.2 0.20 73.0 29.2 1000 14.90 70 74 72.4 31.2 706 55 23.3 72 28.3 0.2 0.20 72.1 28.9 1000 17.73 65 69 68.1 28.6 794 55 23.3 72 28.3 0.2 1.00 68.1 28.6 1000 18.94 60 64 62.4 24.2 863 55 23.3 72 28.3 0.2 1.00 62.4 24.2 1000 3.50 55 59 57 21.1 657 55 23.3 72 28.3 0.2 1.00 57.0 21.1 1000 0.00 50 54 51.8 18.7 670 55 23.3 72 28.3 0.2 0.84 55.0 20.2 1000 0.00 45 49 47.5 16.6 487 55 23.3 72 28.3 0.2 0.69 55.0 20.2 1000 0.00 40 44 43.2 14.8 683 55 23.3 72 28.3 0.2 0.59 55.0 20.3 1000 0.00 35 39 37.5 12.6 693 55 23.3 72 28.3 0.2 0.49 55.0 20.6 1000 0.00 30 34 32.3 10.8 641 55 23.3 72 28.3 0.2 0.43 55.0 20.8 1000 0.00 25 29 27.4 8.8 390 55 23.3 72 28.3 0.2 0.38 55.0 20.9 1000 0.00 20 24 23.1 7.5 371 55 23.3 72 28.3 0.2 0.35 55.0 21.1 1000 0.00 15 19 17.8 5.7 302 55 23.3 72 28.3 0.2 0.31 55.0 21.2 1000 0.00 10 14 12.1 4 152 55 23.3 72 28.3 0.2 0.28 55.0 21.4 1000 0.00 5 9 7.2 2.6 105 55 23.3 72 28.3 0.2 0.26 55.0 21.6 1000 0.00 0 4 2.5 1.3 53 55 23.3 72 28.3 0.2 0.24 55.0 21.7 1000 0.00 -5 -1 -2 0 40 55 23.3 72 28.3 0.2 0.23 55.0 21.8 1000 0.00 -10 -6 -6.4 -1.1 11 55 23.3 72 28.3 0.2 0.22 55.0 21.9 1000 0.00 -15 -11 -13 -99 0 55 23.3 72 28.3 0.2 0.20 55.0 2.8 1000 0.00 -20 -16 -18 -99 0 55 23.3 72 28.3 0.2 0.20 54.0 2.8 1000 0.00 -25 -21 -23 -99 0 55 23.3 72 28.3 0.2 0.20 53.0 2.8 1000 0.00 -30 -26 -28 -99 0 55 23.3 72 28.3 0.2 0.20 52.0 2.8 1000 0.00 Total 71.88 4) Consider a building that uses 100% outdoor, is maintained at 72 F, and exhausts and intakes 20,000 cfm of outside air. The supply air passes over a heating coil and then a cooling coil before being transported to the zones in the building. The temperature of the air after the cooling coil is maintained at 58 F. Using hourly bin data from WeaTran for Chicago IL, determine the annual sensible heating energy use (mmBtu/year) and sensible cooling energy use (mmBtu/year). Next, consider the case where the building uses an air-to-air heat exchanger between the intake and exhaust air streams with effectiveness = 0.80. Determine annual sensible heating energy use (mmBtu/year) and sensible cooling energy use (mmBtu/year). [Answers: Qhc(no heat recovery) = 2,531 mmBtu/yr, Qcc(no heat recovery) = 935 mmBtu/yr, Qhc(heat recovery) = 2 mmBtu/yr, Qcc(heat recovery) = 1,802 mmBtu/yr. To receive credit, show your bin calculations.] 5G) Graduate students only. Determine annual cooling energy use (mmBtu/year) for a HVAC system in Chicago, IL with an enthalpy-based economizer. The volume air flow rate over the cooling coil is 1,000 cfm and the air density is 0.075 lb/ft3. The supply air leaves the cooling coil at 55 F with an enthalpy of 23.3 Btu/lb. The return air leaves the zone at 72 F with an enthalpy of 28.3 Btu/lba. The minimum required fraction outdoor air is 0.20.