pump consist sourse distribution storage sistem withing transporting circuit evaporator liquid compressed increases Furnace smokestack engine apply steam approaches fire tube as shown here wood bursts explosion rack positioned following much more complicated extract bit improve examination erection adjustment foreign complete supply sootblower suppliersсoal millsdraft plantsturboblowers- http://www.engineeringtoolbox.com/hvac-terms-d_246.html http://www.bergquistcompany.com/fans-blowers/glossary.php ABSOLUTE HUMIDITY - The weight of water vapor in a given amount of air. ABSOLUTE PRESSURE - Pressure measured with the base of zero. ABSOLUTE TEMPERATURE - A temperature scale expressed in degrees oF or oC using absolute zero as a base. Referred to as the Rankin or Kelvin scale. ABSOLUTE ZERO - The temperature at which molecular activity theoretically ceases. 456.69 oF or -273.16 oC. AIR CONDITIONING - The process of controlling the temperature, humidity, cleanliness and distribution of the air. AIR, Standard Conditions - Conditions at which capacity ratings for air conditioning equipment is rated. AMBIENT - Refers to the temperature surrounding a body or unit under test. ATMOSPHERIC PRESSURE - The weight of a 1 unit column of the earth's atmosphere. BIMETAL - Two metals with different rates of expansion fastened together. When heated or cooled they will warp and can be made to open or close a switch or valve. BOILING POINT - The temperature at which the addition of any heat will begin a change of state from a liquid to a vapor. BRITISH THERMAL UNIT (BTU) - The amount of heat necessary to change the temperature of 1 pound of pure water 1 degree Fahrenheit (oF). CAPILLARY TUBE - A refrigerant control consisting of a small diameter tube which controls flow by restriction. They are carefully sized by inside diameter and length for each particular application. CENTIGRADE - A temperature scale with the freezing point of water 0 oC and the boiling point 100 oC at sea level. CHECK VALVE - A valve designed to permit flow in one direction only. COMPRESSION - The reduction of volume of a vapor or gas by mechanical means. COMPRESSION RATIO - The ratio determined by dividing the discharge pressure, in PSI (Pa), by the suction pressure in PSI (Pa). COMPRESSOR - A mechanical device used to compress gases. Three main types reciprocating, centrifugal and rotary. CONDENSATION POINT - The temperature at which the removal of any heat will begin a change of state from a vapor to a liquid. CONDENSING MEDIUM - The substance, usually air or water, to which the heat in a condenser is transferred. CONDENSING UNIT - The portion of a refrigeration system where the compression and condensation of refrigerant is accomplished. Sometimes referred to as the 'high side'. CONDUCTION - The transfer of heat from molecule to molecule within a substance. CONTACTOR - An electromagnetic actuated relay. Usually used to refer to the relay which closes the circuit to a compressor. CONVECTION - The transfer of heat by a moving fluid. COOLING ANTICIPATOR - A resistance heater (usually not adjustable) in parallel with the cooling circuit. It is 'on' when the current is 'off", adding heat to shorten the off cycle. COP - Ratio of work performed or accomplished as compared to the energy used. CUBIC FEET PER MINUTE - A common means of assigning quantitative values to volumes of air in transit, usually abbreviated CFM. CYCLE - The complete course of operation of a refrigerant back to a selected starting point in a system. DENSITY - Mass or weight per unit of volume. DISCHARGE LINE - A tube used to convey the compressed refrigerant vapor from the compressor to the condenser inlet. DISCHARGE PRESSURE - The pressure read at the compressor outlet. Also called head pressure or high side pressure. DRY AIR - Air which contains no moisture vapor. DRY BULB TEMPERATURE - Temperature read with an ordinary thermometer. EFFECTIVE TEMPERATURE - An arbitrary concept which combines into a single value the effect of temperature, humidity, and air movement as sensed by the human body. ENTHALPY - Total amount of heat in one pound (kg) of a substance calculated from accepted temperature base, expressed in BTU's per pound mass (J/kg). EQUIVALENT LENGTH - That length of straight tubing which has the same pressure drop as the fitting, valve or accessory (of the same nominal size) being considered. EVAPORATIVE COOLING - The cooling effect of vaporization of a liquid in a moving air stream. EVAPORATOR - A device in which a liquid refrigerant is vaporized. Some superheating usually takes place. EVAPORATOR SUPERHEAT - The actual temperature of the refrigerant vapor at the evaporator exit as compared to the saturated vapor temperature indicated by the suction pressure. EXTERNAL STATIC PRESSURE - The sum of the static and velocity pressures of a moving air system at the point of measurement. FAHRENHEIT - A temperature scale with the freezing point of water 32 oF and the boiling point 212 oF at sea level. FEET PER MINUTE - A term assigned to a velocity of a moving air stream, usually express FPM. FILTER-DRIER - A device that removes moisture, acid and foreign matter from the refrigerant. FLASH GAS - Instantaneous evaporation of some liquid refrigerant at the metering device due to pressure drop which cools the remaining liquid refrigerant to desired evaporation temperature. FREEZING POINT - The temperature at which the removal of any heat will begin a change of state from a liquid to a solid. GAUGE PRESSURE - Pressure measured with atmospheric pressure as a base. HEAT - A form of energy causing the agitation of molecules within a substance. HEAT EXCHANGER - A device for the transfer of heat energy from the source to the conveying medium. HEAT FLOW - Heat flows from a warmer to a cooler substance. The rate depends upon the temperature difference, the area exposed and the type of material. HEAT OF COMPRESSION - The heat added to a vapor by the work done on it during compression. HEAT OF THE LIQUID - The increase in total heat (Enthalpy) per pound of a saturated liquid as its temperature is increased above a chosen base temperature. (Usually - 40 oF for refrigerants). HEAT TRANSFER - The three methods of heat transfer are conduction, convection and radiation. INCHES OF MERCURY - Atmospheric pressure is equal to 29.92 inches of mercury. LATENT HEAT - Heat that produces a change of state without a change in temperature; i.e., ice to water at 32 oF or water to steam at 212 oF. LATENT HEAT OF CONDENSATION - The amount of heat energy in BTU's that must be removed to change the state of one pound of a vapor to one pound of liquid at the same temperature. LATENT HEAT OF FUSION - The amount of heat energy, in BTU's required to change the state of one pound of a liquid to one pound of solid at the same temperature. LATENT HEAT OF MELTING - The amount of heat energy, in BTU'S, that must be removed to change the state of one pound of solid to one pound of liquid at the same temperature. LATENT HEAT OF VAPORIZATION - The amount of heat energy in BTU's required to change the state of one pound of a liquid to one pound of vapor at the same temperature. LIFT - To elevate a fluid from one level to a higher level. LIQUID LINE - A tube used to convey the liquid refrigerant from the condenser outlet to the refrigerant control device of the evaporator. MANOMETER - A tube filled with a liquid used to measure pressures. MBH - One MBH is equivalent to 1,000 BTU's per hour. MEAN TEMPERATURE DIFFERENCES - The mean of difference between the temperature of a fluid receiving and a fluid yielding heat. MELTING POINT - The temperature at which the addition of any heat will begin a change of state from a solid to a liquid. MERCURY MANOMETER - Used to measure vacuum in inches of mercury. MICRON - A unit used to measure high vacuums. One micron equals 1/25,400 of one inch mercury. MOLLIER CHART - A psychrometric chart. How-to convert between Mollier and Psyhrometric charts? MUFFLER - Device installed in hot gas line to silence discharge surges. OIL SEPARATOR - A device for separating out oil entrained in the discharge gas from the compressor and returning it to the crankcase. PARTIAL PRESSURE - The pressure exerted by any individual gas in a mixture. PITCH - The slope of a pipe line for the purpose of improving drainage. PITOT TUBE - A device comprising a small diameter orifice projecting directly into an air stream measuring total pressure and surrounded by an annular section with small diameter entrances normal to the flow, measuring static pressure; both sections are usually connected to a manometer to indicate velocity pressure. PRECHARGED LINES - Refrigerant line's which are filled with refrigerant and are sealed at both ends. The seals are broken when the lines are installed and the line charge becomes part of the total system charge. PRESSURE DROP - The decrease in pressure due to friction of a fluid or vapor as it passes through a tube or duct or/and lift. PRESSURE - TEMPERATURE RELATIONSHIP - The change effected in temperature when pressure is changed or vice versa. Only used at saturated conditions. An increase in pressure results in a temperature increase. A decrease in temperature results in a pressure decrease. PUMPDOWN - Process of pumping refrigerant out of the evaporator and suction line at the end of the on- cycle by closing a solenoid valve in the liquid line and letting the compressor shut-off by the low pressure control. PSYCHROMETER - A devices having both a dry and wet bulb thermometer. It is used to determine the relative humidity in a conditioned space. Most have an indexed scale to allow direct conversion from the temperature readings to the percentage of relative humidity. PSYCHROMETRIC CHART - A chart on which can be found the properties of air under varying conditions of temperature, water vapor content, volume, etc. QUICK CONNECT - Name given to the end connections on precharged lines which screw on to mated fittings of the outdoor and indoor sections. Tightening the quick connections ruptures the seals on the fittings and the line charge becomes part of the total system charge. RADIATION - The transfer of heat without an intervening medium. It is absorbed on contact with a solid surface. RECEIVER - A vessel for holding refrigerant liquefied by the condenser. REFRIGERANT - A substance which produces a refrigerating effect while expanding or vaporizing. REFRIGERANT CONTROL - A device used to meter the amount of refrigerant to an evaporator. It also serves as a dividing point between the high and low pressure sides of the system. REFRIGERANT DISTRIBUTOR - A device which meters equal quantities of refrigerant to independent circuits in the evaporator coil. REFRIGERANT MIGRATION - The movement of refrigerant through the system to the compressor crankcase during the off-cycle, caused by its attraction to oil. REFRIGERANT OPERATING CHARGE - The total amount of refrigerant required by a a system for correct operation. REFRIGERANT VELOCITY - The rate at which refrigerant is moving at a given point in a system, usually given in feet per minute (FPM). REFRIGERATION - The transfer of heat from a place where it is not wanted to a place where its presence is not undesirable. REFRIGERATION EFFECT - The amount of heat a given quantity of refrigerant will absorb in changing from a liquid to a vapor at a given evaporating pressure. RELATIVE HUMIDITY - The percentage of water vapor present in a given quantity air compared to the amount it can hold at its temperature. RELAY - A device used to open and close an electrical circuit. The relay may may be actuated by a bimetal electrically heated strip, a rod wrapped with a fine resistance wire causing expansion when energized, a bellows actuated by expansion of a fluid or gas or an electromagnetic coil. REVERSING VALVE - A device in a heat pump that is electrically controlled to reverse the flow of refrigerant as the system is switched from cooling to heating; also called a four-way valve. RISER - A vertical tube or pipe which carries refrigerant in any form from a lower to a higher level. SATURATED VAPOR - Vapor in contact with a liquid. SATURATION - A condition of stable equilibrium of a vapor and a liquid. SENSIBLE HEAT - Heat that can be measured or felt. Sensible heat always causes a temperature rise. SIGHT GLASS - A glass installed in the liquid line permitting visual inspection of the liquid refrigerant for the purpose of detecting vapor in the liquid. They also generally have a device included to monitor moisture content of the refrigerant. SLUGGING - A condition in which a quantity of liquid enters the compressor causing hammering and possible compressor damage. SPECIFIC HEAT - The amount of heat necessary to change the temperature of one pound of a substance 10 F. SPECIFIC VOLUME - The volume of a substance per unit of mass; i.e., standard air 13.33 cubic feet per pound. The reciprocal of density. STANDARD AIR DENSITY - 0.075 pounds per cubic foot. Equivalent to dry air at 70 oF and at sea level pressure. STATE CONDITION - Substances can exist in three states - solid, liquid or vapor. STATIC PRESSURE - The normal force per unit area at a small hole in the wall of a duct. STATIC TAP - A means by which static pressures of a duct system may be read directly, usually consisting of a small diameter hole in the side of the duct connected to a manometer. SUB COOLING - Cooling of a liquid, at a constant pressure, below the point at which it was condensed. SUBLIMATION - A condition where a substance changes from a solid to a gas without becoming a liquid. SUCTION LINE - A tube used to convey the refrigerant vapor from the evaporator outlet to the suction inlet of compressor. SUCTION LINE ACCUMULATOR - A device located in the suction line that intercepts quantities of a liquid refrigerant and thereby prevents damage to the compressor. SUPERHEAT - Heat added to a vapor after all liquid has been vaporized. TEMPERATURE - A measurement of heat intensity. THERMISTOR - Basically a semiconductor which has electrical resistance that varies inversely with temperature. THERMOSTAT - A bimetal actuated switch to close and open a circuit to indicate or terminate operation of a heating or air conditioning system. THERMOSTATIC EXPANSION VALVE - Refrigerant control which monitors the flow rate according to the superheat at the evaporator outlet. TON OF REFRIGERATION - The amount of heat of fusion absorbed by melting 1 short ton (0.893 long ton or 0.907 t) of pure ice at 0 °C (32 °F) in 24 hours. Equivalent to the consumption of one ton of ice per day during the transition from stored natural ice to mechanical refrigeration. TOTAL HEAT (Enthalpy) - Total heat energy in a substance. The sum of sensible and latent heat. TOTAL PRESSURE - The sum of all partial pressures in a mixture of gases. TRAP - A depression or dip in refrigerant piping in which oil will collect. A trap may be placed at the base of a suction or hot gas riser to improve oil return up the riser. VACUUM - Any pressure below atmospheric pressure. VAPOR BARRIER - The term applied to an impervious layer of material superimposed upon a layer of insulation. Vapor barriers are always applied on the warm side of the insulation layer. VAPOR PRESSURE - The pressure exerted by vapor. VELOCITY PRESSURE - In a moving fluid, the pressure capable of causing an equivalent velocity as applied to move the same fluid through an orifice such that all pressure energy expanded is converted into kinetic energy. WATER MANOMETER - Used to measure pressure in inches of water. WET BULB TEMPERATURE - Temperature read with a thermometer whose bulb is encased in a wetted wick. Glossary heating and cooling systems Glossary heating and cooling systems All A B C D E F G H I J K L M N O P Q R S T U V W X Y Z Actuator The actuator is an active component of the so-called control circuit. It is controlled through an adjusting command (see Control variable) from the controller (see Temperature controller) and triggers a measure that counteracts the control deviation. Ambient temperature range This is the admissible temperature range in which the unit can be operated in accordance with the regulations. ATEX Directive 94/9/EC, also known as ATEX 100a, has been issued by the EC in order to harmonize fundamental safety and health requirements for devices, protection systems and components that are provided for use in accordance with the regulations for hazardous areas. This definition includes devices for safety, test and control which are required for use outside hazardous areas with regard to their explosion risks. Directive 94/9/EC is applicable to electrical and non-electrical devices, protection systems and components (electrical and non-electrical operating supplies). Bus system see Interface. Cascade control see External control. Component tested safety facilities As a rule all temperature control units fall within the pressure equipment directive (see DGRL 97/23 EC). Depending on the heat transfer medium and the temperature, the installations have to be equipped with special safety devices, for example safety valves, pressure, temperature or level switches. These devices serve as a protection for the temperature control unit when the admissible limits of the application are exceeded. Compressor control see injection control. Condenser see coolant. Control circuit The control circuit is the control section (see Control section) and controller. Sensors and signals, their processing and transmission also form part of the control circuit. For example, transformers, clamps and electric lines. Control deviation is the deviation of the actual value from the preset setpoint (see control circuit and controller caracteristic). Control section Control section is the part of the control circuit to be influenced according to its application. Pipework, sensors and heat transfer areas with their walls and coatings also form part of the control section. Through distances from the test point to the final control element and through inertia at the heat transfer for example, a characteristic response time of a control section arises. Depending on the response time, a control section is classified from ‘good’ to ‘difficult’. Controller characteristic Different controllers are distinguished according to their so-called controller characteristic: proportional response (P-controller), integral response (I-controller) and differential response (Dcontroller). As for temperature controllers, combined characteristics have stood the test. Modern PID-controllers can be perfectly adapted to difficult control sections through freely eligible parameters. They are therefore widely used. Cooling output With medium-cooled heat exchangers the cooling output always depends on the temperature difference between the cooling medium and heat transfer fluid. The cooling output reduces at falling outflow temperature and tends to zero when it reaches the cooling medium temperature. With machine-aided cooling the characteristics are similar. The cooling output thus always relates to a definite outflow temperature. At LAUDA the performance data of refrigeration machines is based on cooling water or air with a temperature of 20 °C. Cooling process see coolant. Cooling system see coolant. Delivery head The delivery head is a theoretical value which is used within the pump characteristics (see Pump characteristic) instead of the feed pressure (see Feed pressure). The advantage is that the delivery head is valid for any given liquid. The feed pressure is then calculated for the respective feed medium by multiplying the density by the delivery head (see Feed pressure). Evaporator see refrigerant Expansion volume/Expansion tank When heating up the heat transfer medium to the desired operating temperature, the heat transfer medium expands. This expansion volume results from the expansion coefficient, the temperature change and the contents of the unit. The expansion tank installed in the temperature control unit has to collect the expansion volume safely. The assessment of the dimensions of the expansion tank for thermal oils depends on the medium The following applies for hot water: about 0.8 percent per ∆T = 10 K. The following applies to mineral oils: about 1 percent per ∆T = 10 K. The following applies to silicone oils: about 2 percent per ∆T = 10 K. External control If the outflow temperature is not the controlled variable, but it is instead a temperature measured outside the thermostatic unit, then the outflow temperature of the heat transfer fluid is tracked in such a way that the setpoint is reached at the external point. In practice this is achieved via a so-called cascade control (see Cascade control). The so-called “master controller“ produces as the control variable (see Control variable) the setpoint for the following slave controller (see Slave controller), which in turn controls the outflow temperature of the heat transfer medium liquid. Feed pressure Feed pressure is the manometric pressure measured at the outlet nozzle of a pump or a compressor. With pumps the feed pressure is also given from the pump characteristic (see Delivery head) and the density of the feed medium. Filling volume In connection with a LAUDA system, the recommended filling amount of the system (volume) which is required in order to guarantee trouble-free operation, and to allow for expansion or contraction of the system throughout its operating temperature range. Film temperature The maximum film temperature, which the manufacturer indicates with reference to organic heat transfer media, describes the temperature at which the heat transfer media begin to decompose. Especially when organic heat transfer media are heated up with the help of electric heaters, attention must be paid to the heat flux values because otherwise the heat transfer medium is destroyed by a high surface or film temperature. Flow rate Volume flow of a pump or a compressor. The flow rate depends on the respective operating point and the characteristics (see Pump characteristic) of each component. GMP/FDA In processes in which the reaction temperature or the respective temperature control represent a critical quantity, the temperature control unit has to be qualified and validated. Qualification takes place according to the “Good Manufacturing Practice“ (GMP). If, for example, pharmaceutical products are produced for the American market, the manufacturing process – and with it the process equipment including the temperature control unit – is subject to the requirements of the American “Food and Drug Administration“ (FDA). Hazard evaluation (HAZOP) As far as hazard evaluation is concerned, which has to be generated by the operating company, the information relevant for safety from the operating manual of the manufacturer has to be considered. This especially includes: mounting and integration of the temperature control unit into the total system, commissioning, operation, maintenance and inspection and indications for possible improper use, as far as such an application has not already been prevented by the rating/technical measures. Heat transfer fluid These are liquids which supply or dissipate energy at the consumer. The heat carrier is transported to the consumer by the circulating pump on the thermostatic unit. The larger the circulating quantity, the lower the temperature difference at the consumer. The less the temperature difference, the better the control accuracy. Heater power With electric heating, the heater power is identical to the power consumption of the built-in electric heaters. It is always the maximum possible heater power and, in the case of electric heating, it remains invariable at all operating temperatures. With medium-heated heat exchangers, the heater power always depends on the temperature difference between heating medium and heat transfer fluid. The heater power reduces at increasing outflow temperatures, and tends to zero when it reaches the heating medium temperature. The applied pump output is helpful but not taken into account. Injection control With LAUDA process cooling units, the cooling power (see Cooling power) is permanently controlled by adjusting the injection flow (0 - 100 percent). The final control element is a continuously working control valve that is placed in the refrigerant feed line before the evaporator. If several compressors are operated in parallel, an automatic step switch (see Compressor control) ensures energy-saving partial-load operation. Interface (electrical) Always serves to exchange data and may be set up on an analogue basis (mostly standard signal 4-20 mA or 0-10 V) or on a digital basis. In the digital area you find the simple serial interfaces (RS 232) or the more powerful, parallel addressable systems for many users (RS 485 or the different industrial bus systems). Master controller see External control. Modular engineering This describes the modular kit from which any conceivable thermostatic system can be planned and assembled according to a recurring pattern. It saves costs in the planning, implementation, commissioning, documentation and servicing, because each module is itself well-proven. By using modular engineering, a maximum safety standard is achieved. Monofluid (single fluid) system This is a heat transfer system which works with only one heat transfer liquid. It is useful when heating, cooling and freezing must be done simultaneously and heating and cooling units are working together. Overlay pressure/Inert gas covering Through an inert gas covering (nitrogen) on the expansion tank, oxidation of the heat transfer medium and seeping of water vapor from the air can be prevented. If the heat transfer medium is operated below its evaporation point, overlay pressure should be as low as possible (about 0.1 bar), so that when heating up through the reduction of the gas space the pressure increase is not too high. If the heat transfer medium is operated above its evaporation point and atmospheric pressure (1.013 bar), an overlay pressure of at least the respective vapor pressure is necessary in order to safely prevent cavitation. In both cases a safety valve has to be installed on the expansion tank. Peripheral wheel pump Peripheral wheel pump is a centrifugal pump with a running wheel that has a so-called ‘peripheral’ shape. The almost linear characteristics of a peripheral wheel differ fundamentally from the characteristics of a radial running wheel. At highest feed pressure and lowest feed flow rate the highest drive energy is required with the peripheral shape. Peripheral wheel pumps are especially suited for small feed flow rates and high pressures. Permanent control deviation In the case of a purely proportional controller there is always a „remaining control deviation“. The control variable will always be proportional to the deviation. There is no adjusting command without a deviation. Plug & Play modules Temperature control units and modules arrive at the construction site with clearly defined interfaces, ready for connection, complete with pipework and insulated. They only have to be docked (see Modular engineering). Pressure Equipment Directive (DGRL 97/23 EC) Temperature control units are in the control of the pressure equipment directive considered as modules, which are assembled from several pressure devices (expansion tank, pipelines, fittings, safety valve, etc). The fundamental safety requirements for this are described in Annex I of the pressure equipment directive (DGRL). The process of conformity assessment for the module to be applied depends on the category in which the module is classified. This category is determined through the highest category of the respective built-in pressure device. In this connection, parts of equipment with a safety function are ignored. The category that describes the hazard potential depends on the maximum operating pressure, heat transfer medium, content and type of the built-in pressure device. Before the temperature control unit is commissioned, the manufacturer has – according to the operating conditions – to classify the module into a category and to submit it to a process of conformity assessment. The temperature control unit has to be labeled with the CE label and, starting from category II, has to be labeled with the identification number of the named testing laboratory. Primary side Denominates primary energy carriers such as vapor, cooling water, air, brine, liquid nitrogen, etc., that have to be connected to the temperature control unit by the customer. These primary energies can be gaseous, vaporous or fluid. Protection type IP Pursuant to EN 60529 two numerals assess the electric degree of protection. The first numeral represents the quality of the touch and foreign body protection (dust). The second numeral assesses the protection against water. For example, IP 54 protection signifies dust protection and sealing against splashed water on all sides. Pump characteristic This is a diagram that shows the function of the delivery head in relation to the flow rate. Radial pumps Radial pumps are centrifugal pumps with a running wheel that has a so-called ‘radial’ shape. The non-linear characteristics of a radial wheel differ fundamentally from the characteristics of a peripheral wheel. At lowest feed pressure and highest feed flow rate the highest drive energy is required with the radial shape. Standard pumps for the chemica industry are radial pumps. Radial pumps are especially suited for small feed pressures and high flow rates. Refrigerant Operating material of the cooling process that is located in the closed refrigeration system. The compressor sucks it from the evaporator, where it changes to the gaseous condition under heat absorption. On the warmer side of the evaporator the medium cools down due to heat extraction. On the high pressure side of the compressor the cooling medium is liquefied in the condenser/ heat exchanger under heat transfer. The condenser/heat exchanger is water or air-cooled. Risk analysis The risk analysis has to be generated by the manufacturer of the temperature control unit. The analysis serves to determine the dangers in connection with the unit with reference to the provided operating conditions. Rating and construction of the temperature control unit take place in consideration of the risk analysis. As to the remaining dangers which cannot be covered through technical solutions, as well as measures required from the operator, the manufacturer has to inform the operator through indications in the operating manual, and if necessary through mounting alert labels on the temperature control unit. Secondary side/Heat transfer medium side Designates the side of the temperature control unit from which the heat transfer medium flows. Heat transfer media (thermal oil, water) are chosen according to the operating temperature range and their respective application. Set value Adjusting command of the controller that acts on the so-called actuator. Slave controller see External control. Sound pressure level Quantity for the acoustic emission according to DIN EN ISO 11200. In contrast to the acoustic power level, the pressure level is always assigned to a defined distance. In practice both quantities are stated in dbA. System pressure This is the pressure which is produced by pump pressure, vapor pressure at operating temperature and overlay pressure in the heat transfer medium system. Please pay special attention to the maximum system pressure because all components that have the heat transfer medium flowing through them have to be suitable for the maximum system pressure (see Pressure equipment directive). Temperature control Temperature control is taken to mean the controlled supply or extraction of heating or cooling energy to achieve a constant temperature on the consumer. Temperature control unit (TCU) This is a comprehensive term for differently designed heating and cooling systems which in a defined working temperature range can control temperature of the consumer by means of a liquid. Temperature controller A temperature controller is an active component which compares at least one actual temperature value with one setpoint, and depending on the deviation (see Control deviation) outputs an adjusting command (see Control variable). This so-called “adjusting command“ acts on the so-called ‘final control element’ which also actively triggers a measure that acts against the deviation. Temperature controllers can be of purely mechanical design (for example the so-called ‘radiator thermostat’) or electronic, i.e. analog or digital. Often several operating modes are combined. Through-flow cooler A through-flow cooler is an electrically cooled or otherwise cooled heat exchanger, where a fluid is forced to flow through the system. The cooler mainly serves as a cooler for the fluid that is flowing through. Usually the forced flow is generated by a pump. Through-flow heater A through-flow heater is an electrical or otherwise heated heat exchanger, where a fluid flow is forced through the system. The heater mainly serves as a heater for the fluid that is flowing through. Usually the forced flow is generated by a pump. Two-circuit cascade refrigeration This is a cascade connection of two refrigeration systems with cooling mediums (see refrigerant) of different thermodynamic properties. Two-circuit cascades with compression refrigerating processes are used at working temperatures below -50 °C. The first cascade (high-temperature stage) produces temperatures of about -35 °C in the evaporator. On the warm side of the evaporator the cooling medium of the second stage (low-temperature stage) condenses at about -30 °C and vaporizes at about -90 °C, and cools the heat transfer fluid to about -80 °C. Interactive Engineering Tools Unit ConversionFan Law CalculatorAltitude & Temp EffectsGlossary Get definitions of Fan, Heat Transfer, and HVAC Terms A B C D E F G H I/J K L M/N/O P/Q R S T U-Z A Absolute Pressure The total of the indicated gage pressure plus the atmospheric pressure. Abbreviated "psia" for pounds per square inch absolute. Absolute Temperature Temperature measured from absolute zero using an absolute temperature scale (e.g. Kelvin). Absolute Zero Temperature at which all molecular motion ceases (-460 °F, -273.15 °C, and 0 K.) ACH, Air Changes Per Hour The number of times that air in a house is completely replaced with outdoor air in one hour. Aeration Act of combining substance with air. AFUE - Annual Fuel Utilization Efficiency The ratio of annual output of useful energy or heat to the annual energy input to the furnace. AHU (Air Handling Unit) The inside part of the A/C system that contains the blower, cooling (evaporator) coil, and heater. Air Change The amount of air required to completely replace the air in a room or building; not to be confused with recirculated air Air Coil Coil on some types of heat pumps used either as an evaporator or condenser. Air conditioner Equipment that conditions air by cleaning, cooling, heating, humidifying, or dehumidifying it. A term often applied to comfort cooling equipment. Air conditioning A process that maintains comfort conditions in a defined area. Air Cooler Mechanism designed to lower temperature of air passing through it. Air Diffuser Air distribution outlet or grille designed to direct airflow into desired patterns. Air Diffusion Distribution of the air in a space, called the treated space, by means of devices, called air terminal devices, in a manner so as to meet certain specified conditions, such as air change rate, pressure, cleanliness, temperature, humidity, air velocity and noise level. Air Distribution The transportation of a specified air flow to or from the treated space or spaces, generally by means of ductwork. Air Gap The space between magnetic poles or between rotating and stationary assemblies in a motor or generator. Air Handler Fan/blower, filter and housing parts of a system. Air Infiltration Leakage of air into rooms through cracks, windows doors and other openings. Air Sensor A device that registers changes in air conditions such as pressure, velocity, temperature, or moisture content. Air Source Equipment Heat pumps or air conditioners that uses the outdoor air to transfer heat to and from the refrigerant in the unit. Air Terminal Device A device located in an opening provided at the boundaries of the treated space to ensure a predetermined motion of air in this space. Air Vent A fitting used to vent air manually or automatically from a system. Air-Cooled Condenser Heat of compression, plus the heat of absorption, is transferred from refrigerant within coil to surrounding air, either by convection or fan or blower. Airflow The volume of air moving through a blower or duct. Units of measure are cubic feet per minute (CFM), liters per second (LPS) or cubic meters per hour (m3h). Anemometer An instrument used to measure air velocities. ARI (Air-Conditioning and Refrigeration Institute) Air-Conditioning and Refrigeration Institute is a nonprofit, voluntary organization comprised of heating, air conditioning and refrigeration manufacturers. ARI publishes standards for testing and rating heat pumps and air conditioners to provide you with a standardized measure of comparison. So, ARI ensures a level of performance within the industry. ASHRAE A leading HVAC/R Association - American Society of Heating, Refrigerating and Air Conditioning Engineers - http://www.ashrae.org/ ASTM American Society for Testing and Materials. Automatic Control Controls that react to a change in conditions to cause the condition to stabilize. Automatic Expansion Valve A refrigerant control valve that maintains a constant pressure in an evaporator. Atmospheric Pressure The pressure exerted upon the earth's surface by the air because of the gravitational attraction of the earth. Standard atmosphere pressure at sea level is 14.7 pounds per square inch (psi). Measured with a barometer. Axial Fan A device that propels air in an axial direction. B Balance Point The lowest outdoor temperature at which the refrigeration cycle of a heat pump will supply the heating requirements without the aid of a supplementary heat source. Balancing Process of adjusting the flow of air in duct systems, or water flow in hot-water heating systems. Barometer An instrument for measuring atmospheric pressure. Blower An enclosed air-moving device which redirects the airflow by 90 degrees towards one or more exit points. BTU (British Thermal Unit) Quantity of heat required to raise the temperature of one pound of water one degree Fahrenheit. Burner A device used to prepare and burn fuel. C Carbon Dioxide A by-product of natural gas combustion that is not harmful. Carbon Monoxide A colorless, odorless, highly poisonous gas produced when carbon burns without sufficient air nearby. Centrifugal Fan A device that draws air in axially and discharges it radially. CFC (Chlorofluorocarbon) A class of refrigerants. Generally refers to the Chlorofluorocarbon family of refrigerants. Sometimes called Freon. CFM (Cubic Feet per Minute) A standard measurement of airflow that indicates how many cubic feet of air pass by a stationary point in one minute. The higher the number, the more air is being forced through the system. Charge Amount of refrigerant placed in a refrigerating unit. Circuit Breaker A device that opens an electric circuit when an overload occurs. Combustion A reaction called rapid oxidation or burning produced with the right combination of a fuel, oxygen, and heat. Comfort Zone The range of temperatures, humidities and air velocities at which the greatest percentage of people feel comfortable. Compressor Pump of a refrigerating mechanism which draws a low pressure on cooling side of refrigerant cycle and squeezes or compresses the gas into the high pressure or condensing side of the cycle. Condensate The moisture collected on an evaporator coil. Condensate Pump A small pump used to pump condensate to a higher level. Condenser Coil Part of the outdoor portion of a split-system air conditioner or heat pump. By converting refrigerant that is in a gas form back to a liquid, the coil transfers heat carried by the refrigerant to the outside air. Condensing Temperature The temperature at which a vapor changes to a liquid. Condensing Unit Part of a refrigerating mechanism which pumps vaporized refrigerant from the evaporator, compresses it, liquefies it in the condenser and returns it to the refrigerant control. Conduction The transfer of heat through a solid material. Conformal Coating Material coating to protect fan from harsh environmental conditions. Convection The movement of heat by fluid flow(e.g. air, water). COP (Coefficient Of Performance) COP compares the heating capacity of a heat pump to the amount of electricity required to operate the heat pump in the heating mode. D Damper A device that is located in ductwork to adjust air flow. DB Dry Bulb Temperature dB (Decibel) A decibel describes the relative loudness of a sound on a logarithmic scale. Defrost Cycle The process of removing ice or frost buildup from the outdoor coil during the heating season. Dehumidification The reduction of water vapor in air by cooling the air below the dew point; removal of water vapor from air by chemical means, refrigeration, etc. Dew point The exact temperature at which moisture begins to form. Direct Gas-Fired Heater The burner fires directly in the air stream being heated, rather than through a heat exchanger. 100% of available BTUs are delivered to the heated space because no flue or heat exchanger is required. This results in no wasted energy. DOE (Department of Energy) The Department of Energy is a federal agency in charge of setting industry efficiency standards and monitoring the consumption of energy sources. Duct A pipe or closed conduit made of sheet metal, fiberglass board, or other suitable material used for conducting air to and from an air handling unit. E EER (Energy Efficiency Ratio) A ratio calculated by dividing the cooling capacity in Btu's per hour (Btuh) by the power input in watts at any given set of rating conditions, expressed in Btuh per watt (Btuh/watt). EER & SEER can not be compared equally. Air source equipment is rated by SEER and geothermal equipment is rated by EER. EER changes with the inside and outside conditions, falling as the temperature difference between inside and outside gets larger. Efficiency A rating on comfort equipment is similar to the miles per gallon rating on your car. Energy Recovery Ventilator (ERV) This device preheats incoming outside air during the winter and pre-cools incoming air during the summer to reduce the impact of heating and or cooling the indoor air. EPA (Environmental Protection Agency) Environmental Protection Agency - http://www.epa.gov/ Evaporation The condition that occurs when heat is absorbed by liquid and it changes to vapor. Evaporator Coil Part of a split-system air conditioner or heat pump located indoors. The evaporator coil cools and dehumidifies the air by converting liquid refrigerant into a gas, which absorbs the heat from the air. The warmed refrigerant is then carried through a tube to the outdoor unit (condenser coil). Exfiltration Uncontrolled air leakage out of a building. Exhaust The air flow leaving the treated space. F Fahrenheit Scale The temperature scale that places the boiling point of water at 212°F and the freezing point at 32°F. Fan A device that produces a pressure difference in air to move it. Fan Cycling The use of a pressure control to turn a condenser fan on and off to maintain a correct pressure within the system. Fan Laws A family of mathematical relationships that allows the calculation of new operating characteristics from known system conditions. Filter A device for removing dust particles from air or unwanted elements from liquids. Flow Coefficient A dimensionless parameter relation air velocity to fan tip velocity. It's used to determine approximate fan width for centrifugal impellers. G Gage An instrument for measuring pressure. Geothermal Equipment Heat pumps that uses the ground to transfer heat to and from the refrigerant in the unit. The unit circulates water through a heat exchanger in the to a closed loop buried in the ground or by pumping water from a well through the unit. H HCFC (Hydrochlorofluorocarbon) A class of refrigerants. Generally refers to Halogenated Chlorofluorocarbon family of refrigerants. Heat Exchanger This is a device that enables furnaces to transfer heat from combustion safely into breathable air. The primary heat exchanger transfers heat from combustion gases to the air blowing through the ductwork. Heat Gain The amount of heat gained, measured in BTU's, from a space to be conditioned, at the local summer outdoor design temperature and a specified indoor design condition. Heat Loss The amount of heat lost, measured in BTU's from a space to be conditioned, at the local winter outdoor design temperature and a specified indoor design condition. Heat Pump Compression cycle system used to supply heat to a temperature controlled space. Same system can also remove heat from the same space. Heat Recovery Ventilator (HRV) This device bring fresh, outside air into a home while simultaneously exhausting stale indoor air outside. In the process of doing this, an HRV removes heat from the exhaust air and transfers it to the incoming air, pre-heating it. HFC (Hydrofluorocarbon) A class of refrigerants. Generally refers to Hydrofluorocarbon family of refrigerants Humidifier A device that adds moisture to warm air being circulated or directed into a space. Humidity Sensor A device designed to regulate humidity input by reacting to changes in the moisture content of the air. Humidity The amount of moisture in the air. Air conditioners remove moisture for added comfort. HVAC Heating, Ventilating and Air Conditioning I/J Inches of Water Gage or Column (IN WG or IN WC) A unit of air pressure measurement equal to the pressure exerted by a column of water 1 inch high. IAQ Indoor Air Quality IGBT Insulated Gate Bipolar Transistor. Impedance The resistance or opposition to airflow in a system. Same as back pressure or static pressure. Impeller The component of a fan assembly that is composed of a number of contoured blades. Induction Process by which the primary air sets into motion an air volume, called secondary air, in the room. K KW Kilowatt, equals 1000 Watts. KWh Kilowatt hour is the amount of kilowatts of electricity used in one hour of operation of any equipment. L Latent Cooling Load The net amount of moisture added to the inside air by plants, people, cooking, infiltration, and any other moisture source. The amount of moisture in the air can be calculated from a combination of dry-bulb and wet-bulb temperature measurements. Latent Heat Heat, that when added or removed, causes a change in state - but no change in temperature. Linear Feet per Minute (LFM) A unit of measurement. The velocity of the air. M/N/O Manometer An instrument that measures air pressure differences between locations. Tubes are usually attached to a manometer and run to the spaces where pressures are measured. Essentially a Utube partly filled with a liquid, usually water, mercury or a light oil. The pressure exerted on the liquid is indicated by the liquid displaced. A manometer can be used as a differential pressure gage. Motor A device that converts electrical energy into mechanical energy. A motor can operate on direct current (DC) or alternating current (AC) voltage supply, not both. P/Q PCB Printed Circuit Board. Pascals (Pa) A small unit of air pressure. Pitot Tube A sensing device used to measure total pressures in a fluid stream. It was invented by a French physicist, Henri Pitot, in the 1700's. Plenum An air flow passage. Pressure Coefficient A dimensionless parameter relating the static pressure potential of a fan to its tip velocity pressure equivalent. It's used to determine approximate fan diameter. R Radiation The transfer of heat directly from one surface to another. (No intermediate air acting as a transfer mechanism required). Refrigerant Substance used in refrigerating mechanism. It absorbs heat in evaporator by change of state from a liquid to a gas, and releases its heat in a condenser as the substance returns from the gaseous state back to a liquid state. RH Relative Humidity RPM Revolutions per minute, the measurement of fan blade speed. Rotor The rotating part of the motor which includes the propeller assembly. S Saturation Temperature Also referred to as the boiling point or the condensing temperature. This is the temperature at which a refrigerant will change state from a liquid to a vapor or visa versa. SEER (Seasonal Energy Efficiency Ratio) The total cooling of a central unitary air conditioner or unitary heat pump in BTU's during its normal annual usage period for cooling divided by the total electric energy input in watt-hours during the same period. Sensible Cooling Load The heat gain of the home due to conduction, solar radiation, infiltration, appliances, people, and pets. Burning a light bulb, for example, adds only sensible load to the house. This sensible load raises the dry-bulb temperature. Sensible Heat Heat, that when added or removed, causes a change in temperature but not in state. Sound Attenuators Components which are inserted into the air distribution system and designed to reduce airborne noise which is propagated along the ducts. Specific Speed A dimensionless parameter based on fan rotational speed, flow rating and pressure rating. It's a tool used to select the type of fan for a specific application. Each Different fan type achieves peak efficiency at a unique specific speed range. Split System Refrigeration or air conditioning installation, which places condensing unit outside or away from evaporator. These unit are connected together by a supply and return refrigerant lines. Standard Cubic Feet Per Minute (SCFM) The volumetric rate of airflow at standard air conditions. Static Efficiency A measure of an air mover's efficiency based on its air horsepower in terms of flow and static pressure vs. required shaft input power. Static Pressure The difference in air pressure between the suction side and pressure side of the blower. Unit of measure is inches of water column (in. wc) or Pascals (Pa). Stator The part of the motor that is fixed, typically found in the hub of the fan. Subcooled Liquid Liquid refrigerant which is cooled below its saturation temperature. Superheated Vapor Refrigerant vapor which is heated above its saturation temperature. If a refrigerant is superheated, there is no liquid present. System Impedance The resistance to air flow when moving air through an airflow system. Examples: air filters, air grilles and abrupt changes in flow direction. System Operating Point The point of operation of the air mover on its air performance curve. It is described by an airflow and static pressure point. The operating point is that point on the air mover performance curve where the system resistance curve crosses the air performance curve. T Thermometer An instrument used to detect differences in the level of heat. Thermostat A device that senses temperature change and changes some dimension or condition within to control an operating device. Ton A unit of measure for cooling capacity. One ton = 12,000 BTUs per hour. Total Efficiency A measure of an air movers efficiency based on its air horsepower in terms of flow and total pressure vs. required shaft input power. U-Z Ventilator Captures heating or cooling energy from stale indoor air and transfers it to fresh incoming air. Venturi The housing or frame of the fan. W Watt, the SI unit of power. In electricity it is Volts x Amps. WB Wet Bulb WC (Water Column) Common measure of air pressure used in HVAC systems. Wet-bulb Temperature When a wet wick is placed over a standard thermometer and air is blown across the surface, the water evaporates and cools the thermometer below the dry-bulb temperature. This cooler temperature (called the wet-bulb temperature) depends on how much moisture is in the air Glossary of Useful Terms AFUE - Annual Fuel Utilization Efficiency This is the rating that all heating systems are given by the federal government, and rates the efficiency of each manufacturers system. It is similar to the EPA ratings for gas mileage on your car. The higher the AFUE rating, the higher the efficiency, and therefore, the lower your heating bill. Gas systems run as high as 96% and oil as high as 86% AFUE. Boiler A boiler produces hot water to heat a home using hot water baseboard, radiant floor heat, European style panel radiators, or to circulate hot water to hydro-air air handlers. BTU’s - British Thermal Units A measurement of heat and cooling used in the heating and cooling business. All equipment is rated in BTU’s. The higher the number, the more heating or cooling you have. One BTU is equal to the heat a single wood match produces when burning. Condensing Unit This is the outdoor unit that contains the a/c compressor (just like your refrigerator), that produces the cooling for your central a/c system. Dehumidifier This device, located in the basement, dries out a humid basement in spring, summer and fall. Ideally, it should be installed to allow a hose to drain the moisture into a sump in the basement, precluding daily emptying of the dehumidifier bucket. ERV - Energy Recovery Ventilator This device is similar to an HRV except it also recovers the moisture in winter that would ordinarily be lost to the outside. In summer, it brings in fresh air while rejecting the excess moisture to the outside. This allows your central a/c system to work easier by not having to dehumidify the hot humid air being introduced by the ventilator. Warm Air Furnace This is a popular system that produces warm air to heat the home. Metal ductwork distributes warm air from the furnace to floor and ceiling registers throughout the house. Geothermal Heat Pumps These are used for heating and cooling. They use a series of 400 foot bore holes with HDPE piping containing a mixture of water and non toxic gycol to either reject heat to the earth in summer or extract heat from the earth in the winter. HEPA - High Efficiency Particulate Filter This is similar to the air filters that hospitals use, but on a smaller scale for homes. They can be free standing devices in a room, or whole house devices attached to a warm air heating system. This allows all rooms to get the benefit of the filtration it produces. HRV - Heat Recovery Ventilator This device, located in attics and basements, brings fresh air in to the home while exhausting the same volume of air, and recovering 75 to 80% of the heat. It is more efficient and comfortable than opening windows in winter. Humidifier This is the device that is attached to the basement warm air furnace or hydro-air air handler, and produces moisture for the home in winter. Typically, 30% to 35% relative humidity is comfortable in the winter. Hydro Air This is a system whereby a hot water boiler produces hot water, and pumps it into a special air handler with both heating and cooling coils inside (they look like car radiators inside the air handlers). It looks like the indoor air handler of a central a/c system and produces both warm air from hot water to heat the home in winter and cooling in summer. Media Filters These are used on all warm air heating and central cooling systems to filter the air to a high level. They are ideal for families with allergies. Registers, Grilles and Diffusers These are the “grilles” on your floor, walls and ceilings that bring warm or cool air into each room. SEER - Seasonal Energy Efficiency Ratio This is the ratio of electricity consumed by the a/c or heat pump system compared to the energy it produces. The federal government rates the equipment. The higher the SEER number, the more energy efficient the system is. Currently the minimum for a/c systems is 13 SEER. Glossary of HVAC terms From Wikipedia, the free encyclopedia Jump to: navigation, search HVAC (heating, ventilation, and air conditioning) is a major subdiscipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other factors such as installation cost, ease of maintenance, and energy efficiency. The discipline of HVAC includes a large number of specialized terms and acronyms, many of which are summarized in this glossary. air changes per hour Main article: Air changes per hour The hourly ventilation rate divided by the volume of a space. For perfectly mixed air or laminar flow spaces, this is equal to the number of times per hour that the volume the space is exchanged by mechanical and natural ventilation. Also called air change rate or air exchange rate. Abbreviated ACH or ac/hr. air conditioner Main article: Air conditioner An appliance, system, or mechanism designed to dehumidify and extract heat from an area. Usually this term is reserved for smaller self contained units such as a residential system. air handler air handling unit Main article: Air handler A central unit consisting of a blower, heating and cooling elements, filter racks or chamber, dampers, humidifier, and other central equipment in direct contact with the airflow. This does not include the ductwork through the building. Abbreviated AH or AHU. British thermal unit (BTU) Main article: British thermal unit Any of several units of energy (heat) in the HVAC industry, each slightly more than 1 kJ. One BTU is the energy required to raise one pound of water one degree Fahrenheit, but the many different types of BTU are based on different interpretations of this “definition”. In the United States the power of HVAC systems (the rate of cooling and dehumidifying or heating) is sometimes expressed in BTU/hour instead of watts. Abbreviated BTU or Btu. chiller Main article: Chiller A device that removes heat from a liquid via a vapor-compression or absorption refrigeration cycle. This cooled liquid flows through pipes in a building and passes through coils in air handlers, fan-coil units, or other systems, cooling and usually dehumidifying the air in the building. Chillers are of two types; air-cooled or water-cooled. Air-cooled chillers are usually outside and consist of condenser coils cooled by fan-driven air. Water-cooled chillers are usually inside a building, and heat from these chillers is carried by recirculating water to a heat sink such as an outdoor cooling tower. coil Equipment that performs heat transfer to air when mounted inside an air handling unit or ductwork. It is heated or cooled by electrical means or by circulating liquid or steam within it. condenser Main article: Condenser (heat transfer) A component in the basic refrigeration cycle that ejects or removes heat from the system. The condenser is the hot side of an air conditioner or heat pump. Condensers are heat exchangers, and can transfer heat to air or to an intermediate fluid (such as water or an aqueous solution of ethylene glycol) to carry heat to a distant sink, such as ground (earth sink), a body of water, or air (as with cooling towers). constant air volume Main article: Constant air volume A system designed to provide a constant air flow. This term is applied to HVAC systems that have variable supply-air temperature but constant air flow rates. Most residential forced-air systems are small CAV systems with on/off control. Abbreviated CAV. controller Main article: Controller (control theory) A device that controls the operation of part or all of a system. It may simply turn a device on and off, or it may more subtly modulate the set point of components. Most controllers are automatic but have user input such as temperature set points, e.g. a thermostat. Controls may be analog or digital. damper Main article: Damper (flow) A plate or gate placed in a duct to control air flow by increasing friction in the duct. deep lake water cooling Main article: Deep lake water cooling The heat is rejected to deep lake regions to cool homes and offices, reducing the energy costs. ΔT (Also delta T) a reference to a temperature difference. It is used to describe the difference in temperature of a heating or cooling medium as it enters and as it leaves a system. duct Main article: Duct (HVAC) Specialized housing for the air flow. Dehumidifier A dehumidifier is the equipment that extracts and removes humidity from the air. It works by cooling air to the point where water turns to liquid from vapor form and then the liquid is removed. Diffuser A diffuser is placed over ductwork, and it separates air with vanes going in differing directions. It evenly distributes air flow in the desired directions. Dry Bulb Temperature Dry bulb temperature is the temperature of air measured by a thermometer which is freely exposed to the air while it is shielded from radiation and moisture. It is usually thought of as air temperature, and it is the true thermodynamic temperature. It is a measurement of heat intensity independently of humidity and a dry bulb thermometer is used to measure it. Dry Bulb Thermometer A dry bulb thermometer is a device that measures air temperature independently of humidity. It is freely exposed to the air it is measuring and is protected from the radiation and moisture. economizer Main article: Economizer An HVAC component that uses outside air, under suitable climate conditions, to reduce required mechanical cooling. When the outside air’s enthalpy is less than the required supply air during a call for cooling, an economizer allows a building’s mechanical ventilation system to use up to the maximum amount of outside air. enthalpy Main article: Enthalpy For a given sample of air, a measure of the total heat content (the sum of the heat energy of the dry air and heat energy of the water vapor within it). It is typically used to determine the amount of fresh outside air that can be added to recirculated air for the lowest cooling cost. evaporator Main article: Evaporator A component in the basic refrigeration cycle that absorbs or adds heat to the system. Evaporators can be used to absorb heat from air or from a liquid. The evaporator is the cold side of an air conditioner or heat pump. fan coil unit Main article: Fan coil unit A small terminal unit that is often composed of only a blower and a heating and/or cooling coil, as is often used in hotels, condominiums, or apartments. Abbreviated FCU. flow A transfer of fluid volume per unit time. fresh air intake An opening through which outside air is drawn into the building. This may be to replace air in the building that has been exhausted by the ventilation system, or to provide fresh air for combustion of fuel. Abbreviated FAI. furnace Main article: Furnace A component of an HVAC system that adds heat to air or an intermediate fluid by burning fuel (natural gas, oil, propane, butane, or other flammable substances) in a heat exchanger. gas furnace heat exchanger A gas furnace heat exchanger is responsible for the transfer of heat from inside the furnace into the air outside the furnace. The duct system then transfers this exchanged air to different rooms in the building or space. grille A facing across a duct opening, often rectangular in shape, containing multiple parallel slots through which air may be delivered or withdrawn from a ventilated space. The grille directs the air flow in a particular direction and prevents the passage of large items. heating coil A heating coil is the part of the system that conducts heat. It allows electricity to act as fire. heat exchanger A heat exchanger is the part of the system that transfers heat from the hot parts of the machine or a system to the cold parts of the machine or system. heat gain heat load heat loss Terms for the amount of cooling (heat gain) or heating (heat loss) needed to maintain desired temperatures and humidities in controlled air. Regardless of how well-insulated and sealed a building is, buildings gain heat from sunlight, conduction through the walls, and internal heat sources such as people and electrical equipment. Buildings lose heat through conduction during cold weather. Engineers use heat load calculations to determine the HVAC needs of the space being cooled or heated. heat pump A heat pump is a compressor that cycles hot or cold air. It is a device that is designed to move thermal energy in the opposite direction of heat flow by absorbing heat from a cold space which is released to a warmer space. heat transfer Heat transfer happens when heat moves from one area to another. It is an important and vital step in the process of cooling a space. hspf - (Heating Seasonal Performance Factor) Heating Seasonal Performance Factor is the measurement of heat efficiency over the period of a heating season. intermediate fluid A liquid or gas used to transfer heat between two heat exchangers. An intermediate fluid is used when the hot and cold fluids are too bulky (such as air) or difficult to handle (such as halocarbon refrigerant) to directly transfer the heat. louver 1. Components made of multiple smaller blades, sometimes adjustable, placed in ducts or duct entries to control the volume of air flow. When used inside of ducts, their function is similar to that of a damper, but they can be manufactured to fit larger openings than a single-piece damper. 2. Blades in a rectangular frame placed in doors or walls to permit the movement of air. makeup air unit An air handler that conditions 100% outside air. Typically used in industrial or commercial settings, or in "once-through" (blower sections that only blow air one-way into the building), "low flow" (air handling systems that blow air at a low flow rate), or "primary-secondary" (air handling systems that have an air handler or rooftop unit connected to an add-on makeup unit or hood) commercial HVAC systems. Abbreviated MAU. minimum outside air The lowest amount of fresh air flow that can be allowed into a recirculating system. This limit is sent to ensure that the interior air remains safe and comfortable to breathe. outside air damper An automatic louver or damper that controls the fresh air flow into an air handler and modulates to the most energy efficient setting. outside air temperature A measure of the air temperature outside a building. The temperature and humidity of air inside and outside the building are used in enthalpy calculations to determine when outside air can be used for free heating or cooling. Abbreviated OAT. packaged terminal air conditioner An air conditioner and heater combined into a single, electrically powered unit, typically installed through a wall and often found in hotels. Abbreviated PTAC. packaged unit Main article: Air handler An air-handling unit, defined as either "recirculating" or "once-through" design, made specifically for outdoor installation. They most often include, internally, their own heating and cooling devices. Very common in some regions, particularly in single-story commercial buildings. Also called a rooftop unit (RTU) plenum space Main article: Plenum space An enclosed space inside a building or other structure, used for airflow. Often refers to the space between a dropped ceiling and the structural ceiling, or a raised floor and the hard floor. Distinct from ductwork as a plenum is part of the structure itself. Cable and piping within a plenum must be properly rated for its fire and smoke indices. See also: plenum chamber psychrometric Main article: Psychrometrics The study of the behavior of air-water vapor mixtures. Water vapor plays an important role in energy transfer and human comfort in HVAC design. rooftop unit (RTU) Same as Air handler. radiant ceiling panels Usually metal panels suspended under the ceiling, insulated from the building structure. The primary cooling/heating agent temperature is close to the room's temperature. radiant floor A type of radiant heating system where the building floor contains channels or tubes through which hot fluids such as air or water are circulated. The whole floor is evenly heated. Thus, the room is heated from the bottom up. Radiant floor heating eliminates the draft and dust problems associated with forced air heating systems. radiation The transfer of heat directly from one surface to another (without heating the intermediate air acting as a transfer mechanism). smoke damper A damper or adjustable louver designed to augment the ventilation of a space during a fire. split system A split system is the combination of an outdoor unit and an indoor unit. This is the most common type of system. superheat A The number of degrees a vapor is above its boiling point at a specific pressure. subcooling A The condition where liquid refrigerant is colder than the minimum temperature required to keep it from boiling which would change it from a liquid to a gas phase. Subcooling is the difference between its saturation temperature and the actual liquid refrigerant temperature. system General term used to refer to the set or a subset of components that perform a specific HVAC function within a building. terminal unit A small component that contains a heating coil, cooling coil, automatic damper, or some combination of the three. Used to control the temperature of a single room. Abbreviated TU. thermal zone An individual space or group of neighboring indoor spaces that the HVAC designer expects will have similar thermal loads. Building codes may require zoning to save energy in commercial buildings. Zones are defined in the building to reduce the number of HVAC subsystems, and thus initial cost. For example, for perimeter offices, rather than one zone for each office, all offices facing west can be combined into one zone. Small residences typically have only one conditioned thermal zone, plus unconditioned spaces such as garages, attics, and crawlspaces, and basements. thermostat A thermostat is a system that monitors and regulates a heating or cooling system. It can be used to set the desired temperature at which it keeps the environment either heated or cooled. two-stage (cooling and heating) A two-stage air conditioner is designed to operate on high and low settings during different weather conditions and seasons. The high setting is used during extreme weather, and the low setting is used during moderate weather. This type of air conditioner produces a balanced temperature and is in use for a longer period of time. txv - Thermostatic Expansion Valve A thermostatic expansion valve is a piece of equipment that meters the flow of liquid refrigerant into the evaporator while measuring the vapor refrigerant leaving the evaporator. It thereby controls the superheating at the outlet of the evaporator. underfloor air distribution Main article: Underfloor air distribution A method for providing ventilation and space conditioning by using the air plenum below a raised floor to distribute conditioned air through diffusers directly to the occupied zone. Abbreviated UFAD. variable air volume Main article: Variable air volume An HVAC system that has a stable supply-air temperature, and varies the air flow rate to meet the temperature requirements. Compared to constant air volume systems, these systems conserve energy through lower fan speeds during times of lower temperature control demand. Most new commercial buildings have VAV systems. VAVs may be bypass type or pressure dependent. Pressure dependent type VAVs save energy while both types help in maintaining temperature of the zone that it feeds. Abbreviated VAV. zoning system A zoning system sections a building or a space into zones which are controlled independently of each other. This is beneficial when different areas or rooms of a building have different temperatures as well as when the desired temperatures in different rooms are different. Temperature is controlled by different thermostats. References[edit] Modern Refrigeration and Air Conditioning (August 2003) by Althouse, Turnquist, and Bracciano, Goodheart-Wilcox Publisher; 18th edition International Mechanical Code (March 6, 2006) by the International Code Council, Thomson Delmar Learning; 1 edition ASHRAE Handbook: Fundamentals, Atlanta, GA, 2009. Green Building and Controls Glossary, by KMC Controls, New Paris, IN, 2013. ASHRAE Terminology www.ashrae.org/ASHRAEterms [1] External links[edit] HVAC Components Infographics (Sanhua - HVAC manufacturer) HVAC industry terminology Service Champions [hide] v t e HVAC (Heating, Ventilation, and Air Conditioning) Fundamental concepts Technology Air changes per hour Building envelope Convection Dilution (equation) Domestic energy consumption Enthalpy Fluid dynamics Gas compressor Heat pump and refrigeration cycle Heat transfer Infiltration (HVAC) Noise control Psychrometrics Stack effect Thermal comfort Thermal destratification Thermodynamics Vapor pressure of water Absorption refrigerator Air barrier Air conditioning Antifreeze Automobile air conditioning Autonomous building Building insulation materials Central heating Central solar heating Chilled beam Chilled water Constant air volume Coolant Components Dedicated outdoor air system Deep water source cooling Demand-controlled ventilation Displacement ventilation District cooling District heating Electric heating Energy recovery ventilation Forced-air Forced-air gas Free cooling Heat recovery ventilation Hydronics HVAC Ice storage air conditioning Kitchen ventilation Mixed-mode ventilation Microgeneration Natural ventilation Passive cooling Passive house Radiant cooling Radiant heating Radon mitigation Refrigeration Renewable heat Room air distribution Solar air heat Solar combisystem Solar cooling Solar heating Thermal insulation Thermal mass Underfloor air distribution Underfloor heating Vapor barrier Vapor-compression refrigeration Variable air volume Variable refrigerant flow Ventilation (architecture) Air conditioner inverter Air filter Air handler Air ionizer Air-mixing plenum Air purifier Air source heat pumps Back boiler Barrier pipe Blast damper Boiler Centrifugal fan Chiller Condensate pump Condenser (heat transfer) Condensing boiler Convection heater Cooling tower Damper (flow) Dehumidifier Duct (flow) Durable elbow support Economizer Electrostatic precipitator Evaporative cooler Evaporator Exhaust hood Expansion tank Fan coil unit Fan heater Fire damper Fireplace Fireplace insert Firestop Freeze stat Flue Freon Fume hood Furnace Furnace room Gas compressor Gas heater Geothermal heat pump Grease duct Grille Ground-coupled heat exchanger Heat exchanger Heat pipe Heat pump Heating system High efficiency glandless circulating pump High-efficiency particulate air (HEPA) High pressure cut off switch Humidifier Hybrid heat Infrared heater Inverter compressor Louver Mechanical fan Mechanical room Oil heater Packaged terminal air conditioner Plenum space Pressurisation ductwork Measurement and control Professions, trades, and services Radiator (heating) Radiator reflector Recuperator Refrigerant Register Reversing valve Run-around coil Scroll compressor Solar chimney Space heater Smoke exhaust ductwork Thermal expansion valve Thermal wheel Thermosiphon Thermostatic radiator valve Trickle vent Trombe wall Turning vanes (HVAC) Ultra-low particulate air (ULPA) Whole-house fan Windcatcher Wood-burning stove Air flow meter Aquastat BACnet Blower door Building automation Clean Air Delivery Rate (CADR) Gas sensor Home energy monitor Humidistat HVAC control system Intelligent buildings LonWorks Minimum efficiency reporting value (MERV) OpenTherm Programmable communicating thermostat Programmable thermostat Psychrometrics Room temperature Smart thermostat Thermostat Thermostatic radiator valve Architectural acoustics Architectural engineering Architectural technologist Building services engineering BIM Deep energy retrofit Industry organizations Health and safety See also Duct leakage testing Environmental engineering Hydronic balancing Kitchen exhaust cleaning Mechanical engineering Mechanical, electrical, and plumbing Mold growth, assessment, and remediation Refrigerant reclamation Testing, adjusting, balancing ACCA AMCA ASHRAE ASTM International BRE BSRIA CIBSE LEED SMACNA Indoor air quality Passive smoking Sick building syndrome ASHRAE Handbook Building science Fireproofing Glossary of HVAC terms Template:Home automation Template:Solar energy Efficiency Terms In 1992, the Federal Government established minimum efficiency requirements for all heating and air conditioning equipment. If your present HVAC equipment — a furnace, heat pump, or air conditioning system — was purchased and installed before that date, it could be highly inefficient by today’s standards. Efficiency ratings are important to understand because installing a new unit could achieve significant energy cost reductions. And that could save you from the higher operating expenses of some pre-1992 equipment. AFUE% = Furnace Efficiency “AFUE” is a measure of a furnace’s heating efficiency. It stands for Annual Fuel Utilization Efficiency. The higher the AFUE%, the more efficient the product. The government’s established minimum rating for furnaces is 78%. HSPF = Heat Pump Heating Efficiency HSPF stands for Heating Seasonal Performance Factor. The higher the HSPF rating, the more efficient a heat pump is at heating your home. There is no legislated minimum rating. SEER = Cooling Efficiency “SEER” is a measure of cooling efficiency for air conditioning products. SEER stands for Seasonal Energy Efficiency Ratio. The higher the SEER rating number, the more energy efficient the unit. The government’s established minimum rating for air conditioning is 13. Basic Heating and Air Conditioning Definitions Air Handler The portion of a central air conditioning or heat pump system that moves heated or cooled air throughout a home’s ductwork. In some systems, a furnace handles this function. Heat Source A body of air or liquid from which heat is collected. In an air source heat pump, the air outside the house is used as the heat source during the heating cycle. Indoor Coil The portion of a heat pump or central air conditioning system that is located in the house and functions as the heat transfer point for warming or cooling indoor air. Outdoor Coil/Condensing Unit The portion of a heat pump or central air conditioning system that is located outside the home and functions as a heat transfer point for collecting heat from or dispelling heat to the outside air. Single Package A year ’round heating and air conditioning system that has all the components completely encased in one unit outside the home. Split System A heat pump or central air conditioning system with components located both inside and outside of a building — the most common types installed in homes. Supplemental Heat The auxiliary or emergency heat provided at temperatures below a heat pump’s balance point. It is usually electrical resistance heat. Technical Heating and Air Conditioning Definitions Balance Point An outdoor temperature — usually between 30°F to 45°F — at which a heat pump’s output exactly equals the heating needs of the house. Below the balance point, supplementary electric resistance heat is needed to maintain indoor comfort. British Thermal Unit (Btu) The amount of heat required to raise the temperature of one pound of water (about one pint) by one degree Fahrenheit. Coefficient of Performance (COP) A ratio calculated by dividing the total heating capacity provided by the heat pump, including circulating fan heat but excluding supplementary resistance heat (Btu’s per hour), by the total electrical input (watts) x 3.412. (See Heating Seasonal Performance Factor, above.) Energy Efficiency Ratio (EER) A ratio calculated by dividing the cooling capacity in Btu’s per hour (Btuh) by the power input in watts at a given set of rating conditions, expressed in Btuh per watt (Btuh/watt). (See Seasonal Energy Efficiency Ratio, above.) eating & Cooling Glossary AHRI: American Heating and Refrigeration Institute (responsible for rating heating and cooling equipment). Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment that simultaneously controls air temperature, relative humidity, purity, and motion. Air Diffuser: An air distribution outlet or grille that directs airflow into desired patterns. Air Handler: The part of the central air conditioning or heat pump system that circulates heated or cooled air throughout a home’s ductwork. Some furnaces perform this function. Annual Fuel Utilization Efficiency (AFUE): A rating that measures the amount of heating your equipment delivers for every dollar spent on fuel; the higher the better. A higher rating indicates more efficient equipment. Balance Point: An outdoor temperature, usually between 30 °F and 45 °F, at which a heat pump’s output equals the exact heating needs of the home. Below the balance point, supplementary electric resistance heat must maintain indoor comfort. Blower: An air-handling device for moving air in a distribution system. BTU (British Thermal Unit): The standard of measurement used for the amount of heat required to raise the temperature of one pound of water by one degree (Fahrenheit). BTUh = the number of BTUs per hour. Capacity: The ability of a heating or cooling system to function in a given amount of space. Heating = BTUs. Cooling = tons. Central Air Conditioner System: Where air is treated at a central location and carried to and from the rooms by one or more fans and a system of ducts. CFM (Cubic Feet per Minute): Commonly used to measure the rate of an air conditioning system’s airflow. Compressor: In an air conditioner this is known as “the heart of the system” because it circulates the refrigerant through the loop. The compressor is the pump that moves the refrigerant from the indoor evaporator to the outdoor condenser then back to the evaporator. Condenser Coil: A series or network of refrigerant tubes, typically placed outside the home, which removes heat from hot, gaseous refrigerant and re-liquefies it. Condensing Unit: Part of a refrigerating mechanism that pumps in vaporized refrigerant from the evaporator, compresses it, liquefies it in the condenser, and returns it to the refrigerant control. Coefficient of Performance: The COP, or Coefficient of Performance of a heat pump, measures the ratio of the rate of useful heat output that the pump delivers (exclusive of supplementary heating) to the corresponding rate of energy input. In short, it is partly a measure of the efficiency of a heat pump. For example: A heat pump with a COP of 3.5 provides 3.5 units of heat for each unit of energy consumed as compared to electric only heat source. The higher the number the more efficient the heat pump. Cooling Load: Heat that flows into a space from outdoors and/or indoors. Damper: Found in ductwork, this movable plate opens and closes to control airflow and is used in zoning to regulate airflow to certain rooms. Defrost Cycle: The removal of ice or frost buildup from the outdoor coil during the heating season. Dehumidification: The reduction of water vapor by cooling the air below the dew point, as well as the removal of water vapor from air by chemical means, refrigeration, etc. Downflow Furnace: Draws in return air from the top and expels warm air at the bottom. Duct: Used for conducting air to and from an air-handling unit via a pipe or closed conduit made of materials such as sheet metal or fiberglass board. Ductwork: Building-wide air delivery conducted through pipes or channels. Efficiency: A comfort-equipment and fuel-efficiency rating similar to the miles-per-gallon rating for automobiles. Emergency Heat (Supplemental or Auxiliary Heat): The backup heat built into a heat pump system. Energy Efficiency Ratio (EER): The ratio of an air conditioning unit’s cooling capacity in British Thermal Units (BTUs) per hour to the total electrical input in watts. Evaporator: Absorbs heat or liquid from the surrounding air and then moves it outside the refrigerated area by means of a refrigerant. Also known as a cooling coil, blower coil, chilling unit, or indoor coil. Evaporator Coil: Located inside the home, a series or network of tubes filled with refrigerant that remove heat and moisture from indoor air as liquid refrigerant evaporates. Filter: A device that removes dust and other air particles to comfort the respiratory system and protect the heating and cooling equipment. The higher the MERV rating, the better the filter. Freon: Refers to hydrocarbons containing fluorine, chlorine, or bromine, which are used as refrigerants. Furnace: The part of an environmental system that converts natural gas, oil, electricity, or other fuel into heat for distribution within a structure. Heat Exchanger: Transfers heat energy from its source to the conveying medium. Heat Gain: As measured in BTUs, the amount of heat gained from a space to be conditioned, at the local summer outdoor design temperature and a specified indoor design condition. Heat Loss: As measured in BTUs, the amount of heat lost from a space to be conditioned, at the local summer outdoor design temperature and a specified indoor design condition. Heat Pump: An air conditioner with a valve that permits alternate heating and cooling. Heat Source: A body of air or liquid from which heat is collected. With any heat pumps, the air outside the home is the source for the heating cycle. Heat Transfer: The movement of heat from one place to another, between two substances, or within a substance. Heating Capacity: The rate at which a specific device can add substantial heat to a substance, expressed in BTUh (British Thermal Units per hour). Heating Seasonal Performance Factor (HSPF): The total heating output of a heat pump in BTUs during its normal usage period for heating, as divided by the total electrical energy input in watt-hours during the same period. Horizontal Furnace: A sideways furnace that draws in return air from one side and expels warm air from the other. HVAC: Heating, ventilation, and air conditioning. Humidification: The process of adding moisture to the air within a space. Humidistat: Regulates humidity input by reacting to moisture content changes in the air. Humidity: The amount of moisture in the air; air conditioners remove moisture for added comfort. Indoor Unit: Usually located inside the house, it houses the indoor coil, fan, motor, and filtering device, sometimes called the air-handler. Indoor Coil: A refrigerant containing a portion of a fan coil unit similar to a car radiator, typically made of several rows of copper tubing with aluminum fins. Infiltration: Airflow into a space usually through walls and leaks around doors and windows. Insulation: Any material that reduces the speed of heat transfer. Integrally Controlled Motor (ICM): A variable-speed motor that operates at low RPM when possible for efficiency and quiet operation. More than 90% efficiency vs. 60% for conventional motors. Kilowatt (kW): Equal to 1,000 watts of electricity, a kilowatt-hour (kWh) is a common unit of electrical consumption measured by the total energy that one kilowatt creates in an hour. Latent Cooling Capacity: An air conditioning system’s capability to remove moisture from the air. Latent Heat: The heat energy needed to change the state of a substance (e.g., from a liquid to a gas) but not its temperature. Load Calculation: Determines a building’s heat gain and heat loss to ensure installation of properly sized air conditioning and heating equipment. Matched System: A heating and cooling system consisting of products certified to perform at promised comfort and efficiency levels when used together in accordance with design and engineering specifications. Natural-Draft Furnace: A furnace whose natural airflow around the furnace supports combustion. It depends on the pressure that heat creates in the flue gases to force them out through the vent system. Operating Cost: The day-to-day cost of running your home comfort equipment, based on daily energy use. Outdoor Coil/Condensing Unit: The portion of a heat pump or central air conditioning system located outside the home. Functions as a heat transfer point for collecting heat from and dispelling heat to the outside air. Payback Analysis: A general measure of your home comfort system’s efficiency and value. By combining your purchase price with ongoing operating costs, it determines the number of years required before monthly energy savings offset the purchase price. Refrigerant: A substance that produces a refrigerating effect while expanding or vaporizing. Refrigerant Lines: Set of two copper lines connecting the outdoor unit and the indoor unit. Register: Combination grille and damper assembly covering an air opening or end of an air duct. Relative Humidity: The ratio of the amount of vapor contained in the air to the maximum amount the air could hold at that temperature, usually expressed as a percentage. Return Air: Air drawn into a heating unit after having been circulated from the heater’s output supply to a room. Reversing Valve: A device in a heat pump that reverses the flow of refrigerant as the system switches from cooling to heating. SEER (Seasonal Energy Efficiency Ratio): A rating that denotes the efficiency of air conditioning equipment in terms of the amount of cooling your equipment delivers for every dollar spent on electricity. The higher the SEER, the more efficient the unit and the lower the operating cost. Sensible Cooling Capacity: An air conditioning system’s capability to reduce the temperature by removing heat from the air. Sensible Heat: Heat energy that raises or lowers the temperature of a gas, liquid, or solid when added to or removed from that material. Setpoint: The temperature at which a thermostat is set for desired comfort level. Single Package: A year-round heating and air conditioning system with all components encased in one unit outside the home. Split System: The most common type of home central air conditioner, it consists of a compressor (the unit and condenser, installed outside the building) and a non-compressor (the air-handling unit installed within the building). Supplementary Heat: Auxiliary or emergency heat, usually electrical resistance heat, provided at temperatures below a heat pump’s balance point. Thermostat: A temperature control device, typically found on an inside wall, that consists of a series of sensors and relays for monitoring and controlling a heating and cooling system. Tonnage: The unit of measure used in air conditioning to describe the cooling capacity of a system. One ton of cooling is based on the amount of heat needed to melt one ton (2,000 lbs.) of ice in a 24-hour period, and equals 12,000 BTUs per hour. Upflow: A type of air conditioning system that discharges air into the conditioned space via a top-mounted discharge plenum or through an overhead duct system. Upflow Furnace: A furnace that pulls return air in from the bottom and expels warm air from the top. Vapor Barrier: A moisture-resistant layer applied to the surfaces of humid spaces that prevents moisture from traveling to a point where it can condense due to lower temperature. Vapor Seal: A barrier essential to prevent moisture from infiltrating into, or migrating from, a data processing center or other “critical space” that contains sensitive electronic instrumentation. Vapor barriers may be created using plastic film, vapor-retardant paint, vinyl wall coverings, and vinyl floor systems, in combination with careful sealing of all openings (doors and windows) into the room. Ventilation: The process of supplying or removing air, by natural or mechanical means, to or from any space. Such air may or may not have been conditioned. Watt: A unit of power that equals one joule per second, named after the Scottish inventor and mechanical engineer, James Watt. Zone System: A method of dividing a home into zones that makes it possible to control the amount of comfort provided to each. Zoning: The practice of providing independent heating and/or cooling to different areas within a structure.