9/5/2013 HEAT PIPE CONTROLS FOR EXHAUST AIR HEAT RECOVERY APPLICATIONS Tom Brooke MBA, PE, CEM, Member ASHRAE INTRODUCTION Heat Pipes belong to the class of HVAC air‐to‐air heat exchangers that transfer only sensible (heat) energy. By design, they trade off the ability to transfer latent energy (moisture) to be the simplest, most reliable, most economical, and easiest to maintain of all heat exchangers, and they also have the least ability of transferring any contamination between air streams of all heat exchangers used in residential, commercial and industrial HVAC systems. But they share the same industry standards for their testing1, use2 and certification3 as energy wheels and plate heat exchangers which also transfer latent energy. This paper provides an intermediate level of instruction on all aspects of commercial heat pipe HVAC systems used to recover and exchange energy from a building’s return air (RA) at Point C to precondition a building’s incoming outside air (OA) at Point A in Figures 1 and 2. The heat pipes straddle two different airstreams (sometimes called a parallel application4) and the psychrometrics show heating of the winter OA and subsequent cooling of the EA. Of course, it is also active in summer by cooling the OA from heating the EA. In this example, note that as the Return condensation per hour per 1000 CFM from the RA/EA airstream. It is evident Point A Outside Air 40.0 ºF DB 25.2 ºF DP 12.6 Btu/lb. Point D Exhaust Air 50.7 ºF DB 50.7 ºF DP 20.7 Btu/lb. HEAT PIPES Air (RA) gives up heat to the incoming OA, it is also cooled below its dew‐point (DP). Therefore, there are 2.1 lbs. of 63.7 ºF DB 25.2 ºF DP 18.3 Btu/lb. 72.0 ºF DB 52.2 ºF DP 26.4 Btu/lb. Point B Supply Air Point C Return Air Figure 1 1 ASHRAE Standard 84 “Method of Testing Air‐to‐Air Heat Exchangers” AHRI Standard 1060 “Performance Rating of Air‐to‐Air Heat Exchangers for Energy Recovery Ventilation Equipment” 3 AHRI OM 1060 “Operations Manual for Air‐to‐Air Energy Recovery Ventilation Equipment” 4 The use of the word “parallel” in this context follows AHRI convention that “parallel” airflows provide conditioning of the OA from the separate EA while “series” airflows provide conditioning of the air downstream of the cooling coil from the same air upstream of the cooling coil. It has no connection to its meaning in the context of parallel, counter flow or cross flow air streams. 2 HEAT PIPE CONTROLS FOR EXHAUST AIRHEAT RECOVERY APPLICATIONS 65 60 PSYCHROMETRIC CHART 60 POINT C RA Normal Temperature I-P Units SEA LEVEL BAROMETRIIC PRESSURE:: 29.921 i n.. HG 65 POINT D EA 55 55 50 45 This paper does not include a description of the controls for the 40 pumped heat pipes because they’re POINT A OA completely different from all other heat pipes and deserve their own discussion. Otherwise, the reader is expected to already understand the 35 40 45 basic physical and psychrometric aspects of heat pipes used for Exhaust Air (EA) energy recovery. Considerable further basic technical information may be found at http://heatpipe.com/HomePage/mktg_materials/Papers.html. 50 45 40 POINT B SA 35 D E W P O IN T T E M P E R A T U R E - ° F that drain pans (to be covered in a future paper) and controls to prevent frosting and freezing (see page 4) must be addressed in the system design. However, unlike other types of air‐to‐air heat exchangers, there is no chance that this moisture removal by heat pipes carries a contamination risk. 30 25 20 10 0 50 Chartt by:: HANDS DOWN SOFTWARE,, www.. handsdownsoff t ware.. com 55 60 65 DRY BULB TEMPERATURE - °F 70 75 80 Figure 2 GENERAL HEAT PIPE CONTROL CONSIDERATIONS The heat pipes’ simplicity extends to their controls which can be categorized into either air‐side type or fluid‐side type, the fluid being the two phase heat transfer fluid at the heart of all heat pipes. As shown in Figure 3, air‐side control is used for both frost/freezing control, and ventilating/economizer control; however, fluid‐side control is only appropriate for frosting/freezing control. The reader should also consult the latest locally approved building codes5 for the minimum requirements of these controls. Air‐side control consists of using standard HVAC system modulating actuators and control dampers. The actuators may be pneumatic, electric or electronic and the dampers are usually opposed blade type because of their control characteristics, and may be standard, low leakage, industrial grade, etc. When used, face and bypass dampers are usually oppositely linked. The actuators and dampers may be either factory furnished and installed or field furnished and installed in smaller systems; they are usually field furnished and installed in larger systems. 5 Particularly relevant is ASHRAE Standard 90.1‐2010 “Energy Standard for Buildings Except Low‐Rise Residential Buildings”, including paragraphs 6.4.3 and 6.5.1.1. ©Heat Pipe Technology, Inc. Page 2 of 8 HEAT PIPE CONTROLS FOR EXHAUST AIRHEAT RECOVERY APPLICATIONS Heat Pipe Size All Large Control Type Air‐ Side Fluid‐ Side Range 0‐ 100% 0‐ 100% Control Application Frosting/ Freezing Ventilation/ Economizer Frosting/ Freezing Figure 3 Description Increments Dampers Medium Depends on Preheater Stages Preheater Dampers Medium Stepper Valves Fine The last column of Figure 3 highlights the different levels of incremental control that would be appropriate for different types of facilities. But there are two other important decision criteria for the system designer considering air‐side controls. The first is to consider the volume of space needed for the air bypass. While 5,000 CFM only requires 2.5 ft2 of cross sectional duct area6, easily found in most projects, 40,000 CFM requires 20.0 ft2 of cross sectional duct area, not so easily available. When also considering the necessary duct lengths and turning radii, few mechanical spaces have that much volume available without expressly allowing for it. The second criteria that should be taken into account is the control system’s response when the face velocity is reduced across a heat pipe (say, from a bypass damper opening) and its Effectiveness therefore increases, and vice versa. That is, the percentage of available heat transferred from the high temperature source to the lower temperature sink increases (e.g., in winter, a greater percentage of available heat transfers from the warmer exhaust air stream to the colder outside air stream). The winter increase in temperature across the heat pipe could then be noted by monitoring temperature sensors as abnormally high; however, recall that the absolute value of the BTUH transferred does actually decrease because of the lower CFM. The point is that there can be a natural variability in the air temperature change across a heat pipe. Fluid‐side control inherently eliminates both of the above air‐side control considerations. Fluid‐side control means the refrigerant flow is controlled by valve(s) positioned in the heat pipes’ refrigerant circuits. Depending on its size, application, and need for “fineness” of control, a given EA energy recovery heat pipe system may have up to six refrigerant circuits in it, and each circuit may have a stepper valve. For example, it’s not unusual for a heat pipe system to only have valves on half the circuits because of either the budget or there simply is no need to go beyond that breath of control. They are also available in a variety of voltages and frequencies, do not draw current except when the valve position changes and are often controlled by microprocessors in banks of two. The reader may still occasionally find reference to tilt control of heat pipes. That goes back to early heat pipe designs that, no matter how large they were, had to be physically repositioned (tilted) to enable either summer or winter operation; this of course causes air leakage at the two transitions over time. 6 While design duct velocities range from 500 to 3,000, 2,000 fpm is used here. ©Heat Pipe Technology, Inc. Page 3 of 8 HEAT PIPE CONTROLS FOR EXHAUST AIRHEAT RECOVERY APPLICATIONS Beyond the on/off aspect, further tilting has minimal effect on the capacity and as a result, tilting is now seldom used. Modern heat pipe systems do not have to use tilting for either modulation or on‐off control. SPECIFIC CONTROL FOR FROSTING/FREEZING PROTECTION Figures 1 and 2 depict a moderate winter condition, and the EA heat pipe will not have frost or freezing. But frost and freezing will occur anytime the EA is cooled below its dew point and subjected to below freezing temperatures. Not only does that reduce the heat transfer and EA airflow, but in extreme cases can even completely ice over and block airflow through the RA/EA section of the heat pipe. In commercial heat pipe applications where constant ventilating OA is required, there are three methods of control used to prevent this, but all inherently reduce the energy available for recovery when operating: A. Reduce the Effectiveness of the air‐to‐air heat exchanger. For heat pipes, use valves for fluid‐ side control and the stepper valves are ideally suited for this in larger systems. They have the finest (smallest) control increment and are controlled by an analog output (AO) signal to maintain the set‐point (the actual set‐point is discussed below). Each stepper valve may be controlled individually or they may be controlled in banks of two. B. Add a heat source (preheater) upstream of either the OA heat pipe or the EA heat pipe. If the former, the heat source should only be enabled enough to exactly allow there to be enough heat transferred to the EA stream so it won’t freeze. Or, if the latter, heat (even direct fire) is added directly to the EA so freezing doesn’t occur at the heat pipe. Whether the heat source is single stage, multi‐stage or variable dictates the use of a digital output (DO) or AO signal respectively to maintain the set point. It may appear somewhat backwards to add heat while full heat recovery is operating, but energy recovery does take a back seat to operational considerations like coil freezing. HEAT PIPES C. Bypass Dampers are installed Bypass Supply Air Outside Air around the OA heat pipe as in Damper Figure 4. As more air is bypassed around the OA heat pipe, the Exhaust Air Return Air heat sink of the OA heat pipe is T reduced and less heat can transfer from the EA heat pipe Figure 4 to the OA heat pipe. This keeps the EA at a higher temperature and frosting and freezing are prevented. Dropping below the EA set‐point triggers an AO signal to the bypass damper actuator. ©Heat Pipe Technology, Inc. Page 4 of 8 HEAT PIPE CONTROLS FOR EXHAUST AIRHEAT RECOVERY APPLICATIONS The control strategy should be one which minimizes the reduction of recovered energy, incorporating a defined risk of frosting. Higher set‐points that initiate the freezing strategy sooner (as the temperature drops) do not save as much energy as a lower set‐point. Thus, one has to balance the desire for energy savings against the risk of the EA heat pipe section freezing up. The author believes most HVAC designers would want to absolutely prevent any chance of freezing (with perhaps another degree or two included for further safety) and give up extreme energy savings. In any event, the absolute lowest recommended set point is the dry bulb temperature at which frosting begins to occur in the heat pipe core. Since the relative humidity of the EA affects that temperature, there is, in one sense, some automatic conservatism “built in” to a dry bulb temperature set point. Another approach is to consider manually adjusting the set‐point until frosting is observed during near design winter conditions and extrapolating from that. Another consideration to save energy is to use air blenders to extend the set point as low as possible. As more of a supplement and/or backup strategy, the final alternative to consider is to use a differential pressure sensor across the heat pipe instead of using temperature sensors. An improvement over the single point sensor is to use upstream and downstream grids of pitot tubes. As frost builds up in the heat pipe fins, the pressure drop will increase triggering the freeze control strategy. The advantage of this control is that it only responds to actual frost buildup, eliminating if you will the exhaust humidity variable, other variables, and all the safety factors. Thus, it can be expected to provide the highest energy savings. However, it can’t be used on systems with variable flow EA and the standard pressure drop must be established individually for each specific application.7 On the other hand, recognize that there is a unique BIN distribution of hours for every location. Baton Rouge, LA has .3% of its annual hours at the 25/30 BIN and below while Bismarck, ND has 30%. So, depending on location, it may or may not be worthwhile to stretch for the greatest energy savings. In any event, since “for frosting or icing to occur, an airstream must be cooled to a dew point below 32ºF”8, a 32ºF set point may be considered the starting point. Determining how much below requires some careful analysis and balancing the frosting risk against the desire and potential for energy savings. So, given a set‐point and a design Effectiveness of the heat pipe, which of the freeze control strategies is best? Phillips et al9 analyzed these three strategies, and others more for residential applications that stopped the ventilating OA; the latter are not discussed here since they aren’t appropriate for commercial buildings and ASHRAE Standard 62.1. They found that in moderate climates with less than 7,500 Degree Days ºF which includes much of the US, the freeze control strategy has little impact on energy savings. However, parts of Canada have twice that figure and in those colder climates, the energy savings from highest to lowest are: A. Variable preheat B. Valve control; Bypass dampers (same results) 7 Airxchange. 2005. Frost control strategies for Airxchange enthalpy wheels. 2012 ASHRAE Handbook – HVAC Systems and Equipment. p26.7. 9 Phillips, E.G., D.R. Fisher, R.E. Chant, and B.C. Bradley. 1992. Freeze‐control strategy and air‐to‐air energy recovery performance. ASHRAE Journal 34(12):44‐49. 8 ©Heat Pipe Technology, Inc. Page 5 of 8 HEAT PIPE CONTROLS FOR EXHAUST AIRHEAT RECOVERY APPLICATIONS C. Staged preheat D. Fixed preheat At this point, a “caution” must be mentioned for the case of bypass dampers being used in very cold climates. Because the heat pipe’s Effectiveness increases at lower face velocities, the operating face of the outside air heat pipe (even though reduced in total BTUH transfer) may still receive enough heat so that the exhaust air heat pipe will freeze even with the bypass wide open (and no face dampers). The exact details of when that may happen are an intricate interplay of many variables including: exhaust air temperature and humidity, the Effectiveness of the heat pipe, the pressure drop characteristics of the bypass damper, the temperature of the outside air, and the relative airflow amounts of the outside air and exhaust air. Depending on the criticality and airflows of the application, installing interlocked face dampers would eliminate that potential freezing problem. For further assistance on this subject, please contact your local authorized Heat Pipe Technology sales representative. SPECIFIC CONTROL FOR VENTILATION/ECONOMIZER OPERATION Fan Motor Cooling Preheat The other need for control in EA energy recovery systems is during ventilation and/or E Supply Air economizer operations. While Outside Air they are linked, specifically the former refers to the commercial building code requirement10 that a certain minimum amount of OA must be introduced into a facility with human occupancy. The latter recognizes that for both the minimum OA and an E incremental OA amount up to Return Air Exhaust Air the system maximum unconditioned air above the minimum amount may be introduced into a facility to save Dampers central plant energy as long as the unconditioned air falls Figure 5 within certain dry bulb and dew point temperature extremes. It is apparent then that, given only the envelope of satisfactory ambient conditions, the uncontrolled use of any air‐to‐air energy recovery device will certainly not provide the energy savings of which the device Heat Pipes 10 ASHRAE Standard 62.1 – 2010 “Ventilation for Acceptable Indoor Air Quality” ©Heat Pipe Technology, Inc. Page 6 of 8 HEAT PIPE CONTROLS FOR EXHAUST AIRHEAT RECOVERY APPLICATIONS is capable. This paper will provide the proper control methodology for all recovery devices that, by design, only transfer sensible energy from the RA/EA to the incoming OA. E Fan Motor Cooling Preheat Supply Air Dampers E Return Air Exhaust Air Figure 6 70 70 OA Example 1 65 PSYCHROMETRIC CHART 65 OA Example 2 Normal Temperature I-P Units 60 60 SEA LEVEL BAROMETRIC PRESSURE: 29..921 in.. HG 55 RA Summer SA Summer 50 55 50 45 7 OA Example 4 DEW POINT TEMPERATURE - °F The psychrometric chart in Figure 7 shows both types of systems, their summer RA and SA state conditions, and four example OA conditions. Similar logic to that below should be used for other summer and winter ambient conditions. Outside Air Heat Pipes Figures 5 and 6 show the correct location of the EA to OA energy recovery heat pipes in both a simple 100% OA systems and a simple Mixed Air (MA) System respectively. An underlying requirement for both systems is that the minimum OA per ASHRAE Standard 62.1 (or other site specific criteria requiring more OA) be met at all times by the correct settings for all balancing dampers (not shown). 40 % If the OA is at the condition in 35 Example 1, heat should flow 30 25 through the heat pipes in the 20 10 100% OA system to heat the 0 RA and be exhausted to 45 50 55 60 65 70 75 80 85 90 DRY BULB TEMPERATURE - °F ambient. Since maximum heat removal from the OA is desired, the heat pipe bypass Figure 7 dampers should be closed. In the MA system, since it is desired to use minimum compressor energy to cool the OA, the RA damper should be at its maximum open position. OA Example 3 Chartt by:: HANDS DOWN SOFTWARE,, www.handsdownsoftware.com ©Heat Pipe Technology, Inc. Page 7 of 8 HEAT PIPE CONTROLS FOR EXHAUST AIRHEAT RECOVERY APPLICATIONS A cautionary note: in the latter system, it may appear that as the OA dry bulb further decreases, at some point its value as reduced by the heat pipes will become lower than the RA. While that’s true, the heat pipe by design only transfers sensible heat so the absolute value of the OA humidity will not be reduced. The ensuing heat pipe reduced OA enthalpy is virtually certain to be above the RA enthalpy, which again points to a maximum damper open position for maximum RA. If the OA is at the condition in Example 2, the heat pipe bypass dampers in the 100% OA system should be open to save fan energy and prevent the OA temperature (and enthalpy) from increasing. In the MA system, it’s more probable that the OA enthalpy increased by the heat pipe will be less than the RA enthalpy. While the OA dry bulb will be increased by the heat pipe, its final enthalpy should be the decision criteria. Enthalpy sensors or separate linked dry bulb and humidity sensors should monitor both air streams and control the dampers to use the airstream with the lowest enthalpy. If the OA is at the condition in Example 3, it is a certainty that the OA enthalpy in the 100% OA system will be less than the RA enthalpy, and heat pipe operation should be prevented. Thus, the heat pipe bypass dampers should be opened and the dampers in the MA system should be set to maximum closed position for full economizer operation. With both Examples 2 and 3 in the MA system, the thought process should be to always compare the heat pipe reduced OA enthalpy to the RA enthalpy and choose the lower as long as it is above the summer SA enthalpy. If the OA is at the condition in Example 4, the sequence of operations for both systems will shift to winter mode and the SA set point will increase. But in the 100% OA system we still want to take advantage of the heat pipe raising the OA temperature, so the heat pipe bypass dampers should be closed. In the MA system, we need to minimize the OA airflow because it has a lower dry bulb (and enthalpy). That means we open the dampers to maximum position. CONCLUSIONS AND SUMMARY It is clear that air‐to‐air sensible energy recovery has a well‐deserved place in the many HVAC comfort and process applications that either can not allow any chance of cross contamination from a facility’s exhaust air stream to its incoming fresh outside air, must have ultrahigh reliability, and/or require absolute minimum maintenance. This paper provides detailed control guidance for both the freezing and ventilation requirements of those systems. Please give us your feedback or questions. ©Heat Pipe Technology, Inc. Page 8 of 8