UPS SG-CE Series 160-300 kVA
Sales presentation
PRODUCT HIGHLIGHT
2
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Product portfolio
CE Marked, 3x380/400/415V In & Out, 50/60Hz
_01
S1_UPS
60-200_
SGSE_1
UPS SG-CE Series 160kVA
UPS SG-CE Series 200kVA
144 kW Thyristor
180kW rectifier
UPS SG-CE Series 160kVA PurePulseTM
144kW
UPS SG-CE Series 200kVA PurePulseTM
180kW
160 – 200 kVA
IGBT
rectifier
PS_01
-300_S1_U
SGSE_250
Thyristor
rectifier
UPS SG-CE Series 250kVA
UPS SG-CE Series 300kVA
225kW
270kW
IGBT
rectifier
UPS SG-CE Series 250kVA PurePulseTM
225kW
250 – 300 kVA
UPS SG-CE Series 300kVA PurePulseTM SG-CE Series 160-300 kVA S1
Sales presentation
270kW
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
3
Double conversion parallelable
Designed for Mission Critical Applications
Bypass
supply
True On-Line Double Conversion
VFI technology
(Voltage and Frequency
Independent)
Inverter output transformer for load
galvanic separation
Static bypass
Rectifier
AC
Rectifier
supply
Inverter
DC
Load
AC
DC
Battery bank
Redundant Parallel Architecture™
RPA™ up to 6 UPS units
Increase system reliability and
security
Expanded UPS installed power
SGSE_16
0-200_S1_
1
position_0
RPA dis
UPS
3-4-5-6
UPS 1
4
UPS 2
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
High power concentration
New technology for actual and future trend
_01
S1_UPS
60-200_
SGSE_1
Reduced footprint
Compact design saving space in
installation:
- 160-200 kVA:
1900
1350 x 850 x
1900 mm
- 250-300 kVA:
1500 x 850 x
1900 mm
Full active power available
Full power capability to supply
- inductive loads
- resistive loads
- capacitive loads
Suitable for actual loads
applications, e.g. capacitive loads in
new datacentre
5
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Performances for actual and future trend
High efficiency and clean input technologies for modern applications
Efficiency
100%
94%
80%
Efficiency %
High efficiency at any load
High efficiency at full and partial
loads for real benefit in operating
conditions
60%
Typical
Operation
40%
20%
0%
10%
25%
50%
75%
100%
Load
6
Total Input Harmonic Distortion
5%
4%
THDi
Clean input UPS by PurePulse™
technology
No input current distortion:
THDi =
2%
at 100%
load
2.5%at 75% load
3% at 50% load
Input power factor: PF=0.99
3%
2%
1%
0%
0%
20%
40%
60%
Load
80%
100%
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Superior output dynamic stiffness
Technology for actual and future trend
Output voltage with non-linear load
No output voltage distortion
Real sinewave output voltage with
linear and non-linear loads
Reduced stress for load power supply
equipments
current
output voltage
Voltage variation at 0–100% load step
Voltage stability at loads steps
Capability to supply critical loads with
high and fast loads steps
(pulsating loads)
No oversize required for pulsating
loads
output voltage
current
load step 0-100%
load step
0-100%
output voltage
output voltage
7
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
TYPICAL
APPLICATIONS
8
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Typical applications
Designed for mission critical applications, with highest levels of protection and
reliability
Data centers
Medical equipment & healthcare
facilities
Transportation & Infrastructure
Call centres
Security system
and more ...
9
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
IEC 62040-3
CLASSIFICATION
10
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Performance IEC 62040-3 – Level 1
Output voltage dependancy
Level 1: Output voltage dependency from utility (XXX YY ZZZ)
VFI – Voltage & Frequency Independent
~
Utility
Topology: Double conversion/on-line
-
-
Rectifier
Load
~
Inverter
Battery
VI - Voltage Independent
~
~
Utility
Impedance
Load
Converter
Topology: UPS-Utility-Parallel operation /
Single conversion / Line-interactive
-
~
Inverter &
Charger
Battery
VFD – Voltage & Frequency DependentUtility
Topology: Off-line
Load
-
~Charger
11
Battery
~
Inverter
Switch
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Performance IEC 62040-3 – Level 2
Output voltage quality
Level 2: Output voltage quality depending on load (XXX YY ZZZ)
S
S
Sine wave: THD < 8% (IEC 61000-2-2/-4) for all linear and nonlinear loads
X
X
Non-sine wave: THD > 8 % with non-linear load
Y
Y
Non-sine wave: out of tolerance of IEC 61000-2-2/ -4
Battery operation
Normal operation
12
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Performance IEC 62040-3 – Level 3
Dynamic output voltage
Level 3: Dynamic output voltage behaviour (XXX YY ZZZ)
Class 1
Class 2
Class 3
Z
Z
Z
Dynamic load changes with non-linear load (0% – 100%– 0%)
Dynamic load changes with linear load (0% – 100% – 0%)
Change of operation mode (Utility – battery / Inverter - By-pass)
13
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
SG CE classification
Exeeding IEC 62040-3 standard requirements
SG CE classification: VFI – SSS – 111
VFI Voltage & Frequency Independent
Frequency Converter operation
available
SS Output voltage THD < 8% for all
loads
THDv < 1.5%
linear loads
THDv < 3% non-linear loads
111 Class 1 performance
Exceeding Class 1
‘’Best in Class’’ dynamic
response:
+/- 3% at load step: 0-100%-0
+/- 2% at load step: 0-50%-0
Class 1
SG-CE
Series
14
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
CHARACTERISTICS
&
PERFORMANCES
15
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
UPS configuration
Double conversion with inverter output isolation transformer
Q2
MANUAL BYPASS
SSM
K6
Q4
RECTIFIER
INVERTER
Q1
K7
LOADS
INPUT MAINS
AUTOMATIC BYPASS
INVERTER
TRANSFORMER
K3
BATTERY
Double conversion (VFI) technology with output isolation transformer
Automatic bypass for overloads, short circuit and UPS disturbances
conditions
Manual bypass for UPS maintenance operations without load interruption
Protection safety devices integrated (back feed protection k6 standard)
SG-CE Series 160-300 kVA S1
16
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Compact design
True front access for operation and maintenance, saving installation space
_01
S1_UPS
60-200_
SGSE_1
Reduced footprint
Compact design saving space in
installation
- 160-200 kVA: 1350 x 850 x 1900 mm
- 250-300 kVA: 1500 x 850 x 1900 mm
Easier to handle in narrow space
True front access
Installation against a wall
More space available for other
equipments
1900
UPS
850
1.600
Reduced weigh
Easier to handle into installation site
(e.g. transportation though floors by lift)
Reduced installation time and cost
17
1.350
Footprint SG 200kVA
UPS
: 1.350 x 0.850 = 1.15 sqm
Operational : 1.350 x 1.600 = 2.16 sqm
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Highest UPS output power capability
Capability to supply Inductive, Resistive and Capacitive loads
Full range power capability
Designed to supply real power for
any type of application
- inductive loads
- resistive loads
- capacitive loads
E.g. SG 300kVA load capabilities:
Inductive load PF=0.9 270 kW / 300 kVA
Resistive load PF=1
270 kW / 270 kVA
Capacitive load PF=0.9 270 kW / 300 kVA
No over-sizing required to supply
resistive and capacitive loads
Suitable for modern power supply
application with unit or capacitive
power factor (e.g. new servers
generation), crest factor up to 3:1
18
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Input rectifier performances
Wide input window to preserve battery autonomy and lifetime
Input window
Wide input voltage and frequency
windows
Limited use of battery
Preserve battery autonomy for real
input mains failures
Increase battery lifetime
Input
frequency
+10%
50 Hz
-10%
-15%
400V
+15%
Input voltage
Soft start
Rectifier can be activated gradually,
controlling the input current
Preventing instable situation for
GenSet
Avoids false trip of upfront protection
devices
Sequential softstart for parallel UPS
19
Soft start
UPS input current
UPS 1
100%
UPS 2
0%
time
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Backfeed protection
IEC 62040-1 : ……“For fixed installation UPS, backfeed protection may be
provided internally or externally to the UPS in the a.c. input line”
Standard feature inside UPS
cabinet
No additional cost required
No addition installation required
Backfeed contactor
static bypass
Input
mains
Fully compliant with IEC 62040-1
Compliance to UPS installation
safety requirements
Rectifier
Inverter
DC
AC
DC
Load
AC
Battery bank
Safer operating condition
Safer operation for end users and
service engineers
preventing feedback to the mains from the
inverter in case of mains failure and a fault
in the bypass circuit
20
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
IGBT technology for clean input
Pure Pulse configuration for highest input performances
PurePulse technology for IGBT rectifier
UPS input performances
Total Current Harmonic Distortion
THDi=2%
UPS input power factor: 0.99
Constant behavior at all loads
Negligible harmonics contents at full and
partial loads
Total Input Harmonic Distortion
5%
4%
THDi
Benefit on input mains
Saving in the sizing of upfront equipments
e.g. GenSet, cablings, circuit breakers, …
No disturbances to nearby equipment
Saving cost due to additional filters
3%
2%
1%
0%
0%
21
20%
40%
60%
Load
80%
100%
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Perfect integration with GenSet
No GenSet oversizing required
GenSet integration
Compatible with GenSet design
Saving GenSet size
(suggested GenSet vs. UPS ratio ~ 1.1*)
Reducing GenSet installation space
Saving GenSet investment
GenSet system integration
GenSet integration via Customer
Interface (dedicated auxiliary contact)
Programmable functions based on
GenSet working condition (Gen on/off)
_UPS_01
SGSE_16
0-200_S1
Example
Load
UPS
300 kVA; PF=0.8; 240 kW
SG 300 kVA Pure Pulse;
input PF = 0.99
GenSet data reactance subtr. X“d=12%
GenSet size min. size required 332 kVA
GenSet/UPS = 332/300 =
1.1
SG-CE Series 160-300 kVA S1
* Pure Pulse configuration and GenSet able to
manage large load steps
22
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Superior Battery Management
Safe and protected battery management to preserve investment and UPS
reliability
Charging voltage = f (battery temperature)
2.36
2.33
Volt per cell
Flexible applications
Different battery technologies
applicable:
PB sealed (VRLA) - PB
vented – NiCd
Wide autonomy range
(from few minutes to some hours)
2.30
2.27
2.24
2.21
2.18
0
User friendly information
Prediction of true back-up time, based
on load status
Alarm for “stop operation” to prevent
any unknown shut-down
5
10
15
20
25
30
35
40
Battery tem perature [°C]
Voltage temperature compensation
V
Monitoring and control
Battery test (programmable or manual)
; preserve UPS system reliability
Battery earth fault detection; safer
operation for service engineer & end
user
23
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
No output voltage distortion
Best in class inoutput dynamic stiffness
Output voltage with linear + non-linear
load
No output voltage distortion with linear
and non-linear loads
Voltage distortion
- linear loads:
THDv <1.5%
- non-linear loads:
THDv < 3%
Enhanced customer productivity
Improved quality of application,
reducing
stress for loads
supplied
Increased uptime and MTBF of
customer
Reduced service intervention
(e.g. medical applications: ~60% labor
hour & spare parts reduction)
24
output voltage
current
Output voltage with non-linear load
output voltage
current
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Output Dynamic Stiffness
Best in class inoutput dynamic stiffness
Best in class in output voltage variation
with load steps:
Static
: < + 1%
Dynamic at load steps 0-50-0% : < + 2%
Dynamic at load steps 0-100-0%
:
< + 3%
Enhanced customer unit productivity
Improved quality of application
(i.e. medical images)
Capability to supply critical loads with
high and fast loads steps (pulsating
loads)
Increased uptime and MTBF of customer
Reduced service intervention
25
Medical scanner - dynamic current
absorbtion
1
ms
Voltage variation at 0–100% load step
load step 0-100%
output voltage
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
EFFICIENCY
26
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
High Efficiency at all loads
Reduced customer operation costs and cost saving in air conditioning design
Energy cost saving
Reduced cost of customer equipment
operation at all loads
SG CE Thyristors rectifier –
Efficiency*
100%
94%
80%
Efficiency %
High efficiency performances at any
load
High efficiency at full and partial loads
for real benefit in operating conditions
60%
Typical
Operation
40%
20%
Air conditioning cost saving
Reducing size and cost of air condition
system
Reducing consumption and related
operating cost
27
0%
10%
25%
50%
75%
100%
Load
* SG CE PurePulse (IGBT rectifier) 1%
less
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Super Eco Mode - functionality
Improving UPS efficiency
Normal mode
Normal mode
The output voltage is newly
generated, independently from the
input voltage
Heat losses are present in rectifier
and inverter
Bypass
supply
Static bypass
Rectifier
Rectifier
supply
AC
Inverter
DC
Load
AC
DC
Battery bank
Super Eco Mode
Super Eco Mode
Load is supplied via the bypass
UPS rectifier keeps the battery
charged
UPS inverter switched off
(no heat losses)
Bypass
supply
Static bypass
Rectifier
Rectifier
supply
AC
Inverter
DC
DC
Transf.
Load
AC
Battery bank
28
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Super Eco Mode - benefit
High efficiency, preserving protection to critical load
<
2ms
High efficiency: 98%
prevents heat losses
saving customer utility bill
Fast transfer time to inverter: <2 ms
Guaranteed safe energy for the
application
Configurable according to load
requirement
Adjustable bypass supply tolerance
- voltage: +/- 10% (adjustable)
- frequency: +/- 5% (adjustable)
29
Output voltage
Bypass
on/off
Inverter
current
Inverte
r
control
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
RPA
30
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Reduntant Parallel Architecture
True redundancy with no single point of failure
Modular design
Future system expansion
Saving investment
Input mains
rectifier
AC
True redundancy
No single point of failure
Decentralized bypass
Distributed parallel management
system
bypass
rectifier
AC
DC
battery
DC
battery
DC
DC
AC
Increased system reliability
Safe and reliable power supply for
“mission critical applications”
Increase productivity
True redundancy with no single point
of failure
31
bypass
AC
critical load
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Reduntant Parallel Architecture
Increase system reliability for Mission Critical Applications
Configurable up to 6 units in parallel
Future expansion
Safe and reliable power supply
Redundant Communication Bus
Easy to install and maintain
Easy system upgrade/downgrade
Maintenance operation without
load interruption
utility supply
S_01
200_S1_UP
SGSE_160-
redundant
communication
buses
32
S_01
200_S1_UP
SGSE_160-
S_01
SGSE_160-
200_S1_UP
critical load
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
EMC
33
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
EMC - Electro Magnetic Compatibility
immunity
IEC 62040-2 standard defines the limits of maximum allowable levels of emission of
Emission
electromagnetic disturbances for UPS systems
Any electronic devices emits
electromagnetic disturbances - radio
frequency waves - through:
- cables
(conducted emissions)
- air
(radiated emissions)
Immunity
All electronic equipment is sensitive for
electromagnetic waves.
These waves can disturb the functions of
these equipments
Electro Magnetic Compatibility
Disturbances tolerance among different
types of equipment when running in the
same environment.
34
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
EMC Category C2 (Class A), optional feature*
Compensation of radio-frequency emission to avoid distrurmabces on nearby equipments
No interference with other equipments
Avoid any interferences with critical
applications sensitive to radio frequency
emission (e.g. telecom, broadcasting, …)
No additional investment required for
EMC investigation.
Protected unit quality enhancement
Increased quality and productivity
(e.g. Image quality in medical application)
*Additional EMC cabinet
required
35
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
SERVICEABILITY
36
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Designed for serviceability
Saving time and cost in service
Easy maintenance interventention
Reducing time and cost on maintenance intervention
Reducing down-time, increasing availability
37
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Fan failure detection
Ventilation monitoring for highest reliability
fan
failure
Ventilation monitoring
Alert before overheating occurs
Continuos monitoring of cooling
system
 Repairing time reduction
 Fault level decreasing
detectio
n
alar
m
38
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
POWER QUALITY
SYSTEMS
39
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Power Quality Systems
Integretion with other Power Quality euipments for Mission Critical Applications
UPS: Uninterruptible Power Supply
ISM: Intelligent Synchronization
Module
STS:
Static Transfer Switch
BatteryB
BatteryA
ion_01
PA disposit
ISM_Cabinet_GE_01
ISM
SGSE_
SGSE_160
UPS-B
-200_S1_R
TM
osition_01
1_RPA disp
160-200_S
UPS-A
UPS
3-4-5-6
UPS
3-4-5-6
UPS 1
UPS 1
UPS 2
STS-B
UPS 2
STS-A
Load-B
Load-A
40
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
INTEGRATION WITH BMS
41
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
Customer interface
Easy integration with Building Management System (BMS)
UPS supervision capability
1x RS232 Serial Communication Port
6 programmable potential free alarm
contacts:
- D plug
- Terminals blocks
1x Emergency Power OFF contact
1x Gen-ON Input contact
1x Control Input contact
Customer interface
Additional interface:
SNMP Interface Card
(10/100Mbps auto-select)
MODBUS RTU Interface (RS232 or
RS485)
42
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
CONNECTIVITY
43
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
IRIS - Intelligent Remote Information System
Remote monitoring and diagnostics solution
SNMP/Modem/GPRS topologies
available
Flexible, safe and customer-friendly
solution for remote monitoring
Secure communication via:
e-mail, SMS, fax
GPRS
Web/PDA
Data
Acquisition
Communication
Medium
44
IRIS
Infrastructure
User
Interface
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt
45
SG-CE Series 160-300 kVA S1
Sales presentation
SAP_SGS_XCE_M16_M30_1GB_V020.ppt