PID Tuning and Controllability Sigurd Skogestad NTNU, Trondheim, Norway Tuning of PID controllers SIMC tuning rules (“Skogestad IMC”)(*) Main message: Can usually do much better by taking a systematic approach One tuning rule! Easily memorized • • k’ = k/τ1 = initial slope step response c ≥ 0: desired closed-loop response time (tuning parameter) For robustness select (1) : c ¸ (gives Kc ≤ Kc,max) For acceptable disturbance rejection select (2) : Kc ≥ Kc,min = ud0/ymax References: (1) S. Skogestad, “Simple analytic rules for model reduction and PID controller design”, J.Proc.Control, Vol. 13, 291-309, 2003 (2) S. Skogestad, ``Tuning for smooth PID control with acceptable disturbance rejection'', Ind.Eng.Chem.Res, 45 (23), 7817-7822 (2006). (*) “Probably the best simple PID tuning rules in the world” Need a model for tuning Model: Dynamic effect of change in input u (MV) on output y (CV) First-order + delay model for PI-control Second-order model for PID-control Step response experiment Make step change in one u (MV) at a time Record the output (s) y (CV) First-order plus delay process RESULTING OUTPUT y (CV) k’=k/1 STEP IN INPUT u (MV) Step response experiment : Delay - Time where output does not change 1: Time constant - Additional time to reach 63% of final change k : steady-state gain = y(1)/ u k’ : slope after response “takes off” = k/1 Model reduction of more complicated model Start with complicated stable model on the form Want to get a simplified model on the form Most important parameter is usually the “effective” delay half rule Approximation of zeros Derivation of SIMC-PID tuning rules PI-controller (based on first-order model) For second-order model add D-action. For our purposes it becomes simplest with the “series” (cascade) PID-form: Basis: Direct synthesis (IMC) Closed-loop response to setpoint change Idea: Specify desired response T = (y/ys)desired and from this get the controller. Algebra: IMC Tuning = Direct Synthesis Integral time Found: Integral time = dominant time constant (I = 1) Works well for setpoint changes Needs to be modified (reduced) for integrating disturbances d c u g y Example. “Almost-integrating process” with disturbance at input: G(s) = e-s/(30s+1) Original integral time I = 30 gives poor disturbance response Try reducing it! Example: Integral time for “slow”/integrating process IMC rule: I = 1 =30 Reduce I to improve performance. This value just avoids slow oscillations: I = 4 (c+) = 8 (see derivation next page) Derivation integral time: Avoiding slow oscillations for integrating process . Integrating process: 1 large Assume 1 large and neglect delay : PI-control: C(s) = Kc (1 + 1/I s) Poles (and oscillations) are given by roots of closed-loop polynomial 1+GC = 1 + k’/s ¢ Kc ¢ (1+1/Is) = 0 or I s2 + k’ Kc I s + k’ Kc = 0 Can be written on standard form (02 s2 + 2 0 s + 1) with To avoid oscillations must require ||¸ 1: G(s) = k e- s /(1 s + 1) ¼ k/(1s) = k’/s Kc ¢ k’ ¢ I ¸ 4 or I ¸ 4 / (Kc k’) With choice Kc = (1/k’) (1/(c+)) this gives I ¸ 4 (c+) Conclusion integrating process: Want I small to improve performance, but must be larger than 4 (c+) to avoid slow oscillations Summary: SIMC-PID Tuning Rules One tuning parameter: c Some special cases One tuning parameter: c Note: Derivative action is commonly used for temperature control loops. Select D equal to time constant of temperature sensor Selection of tuning parameter c Two cases 1. Tight control: Want “fastest possible control” subject to having good robustness • 2. (1) S. Skogestad, “Simple analytic rules for model reduction and PID controller design”, J.Proc.Control, Vol. 13, 291309, 2003 Smooth control: Want “slowest possible control” subject to having acceptable disturbance rejection • (2) S. Skogestad, ``Tuning for smooth PID control with acceptable disturbance rejection'', Ind.Eng.Chem.Res, 45 (23), 7817-7822 (2006). (1) TIGHT CONTROL TIGHT CONTROL Example. Integrating process with delay=1. G(s) = e-s/s. Model: k’=1, =1, 1=1 SIMC-tunings with c with ==1: IMC has I=1 Ziegler-Nichols is usually a bit aggressive Setpoint change at t=0 Input disturbance at t=20 TIGHT CONTROL 1. Approximate as first-order model with k=1, 1 = 1+0.1=1.1, =0.1+0.04+0.008 = 0.148 Get SIMC PI-tunings (c=): Kc = 1 ¢ 1.1/(2¢ 0.148) = 3.71, I=min(1.1,8¢ 0.148) = 1.1 2. Approximate as second-order model with k=1, 1 = 1, 2=0.2+0.02=0.22, =0.02+0.008 = 0.028 Get SIMC PID-tunings (c=): Kc = 1 ¢ 1/(2¢ 0.028) = 17.9, I=min(1,8¢ 0.028) = 0.224, D=0.22 (2) SMOOTH CONTROL Tuning for smooth control Tuning parameter: c = desired closed-loop response time (1) Selecting c= (“tight control”) is reasonable for cases with a relatively large effective delay Other cases: Select c > for slower control smoother input usage less disturbing effect on rest of the plant less sensitivity to measurement noise better robustness Question: Given that we require some disturbance rejection. What is the largest possible value for c ? Or equivalently: The smallest possible value for Kc? (2) Will derive Kc,min. From this we can get c,max using SIMC tuning rule SMOOTH CONTROL Closed-loop disturbance rejection d0 -d0 ymax -ymax SMOOTH CONTROL Kc u Minimum controller gain for PI-and PID-control: Kc ¸ Kc,min = |ud0|/|ymax| |ud0|: Input magnitude required for disturbance rejection |ymax|: Allowed output deviation SMOOTH CONTROL Minimum controller gain: Industrial practice: Variables (instrument ranges) often scaled such that (span) Minimum controller gain is then Minimum gain for smooth control ) Common default factory setting Kc=1 is reasonable ! SMOOTH CONTROL Example c is much larger than =0.25 Does not quite reach 1 because d is step disturbance (not not sinusoid) Response to disturbance = 1 at input SMOOTH CONTROL LEVEL CONTROL Application of smooth control Averaging level control q V LC If you insist on integral action then this value avoids cycling Reason for having tank is to smoothen disturbances in concentration and flow. Tight level control is not desired: gives no “smoothening” of flow disturbances. Derivation of tunings: Minimum controller gain for acceptable disturbance rejection: Kc ¸≥ Kc,min = |ud0|/|ymax| Where in our case |ud0| = |q0| - expected flow change [m3/s] (input disturbance) |ymax| = |Vmax| - largest allowed variation in level [m3] Integral time: From the material balance (dV/dt = q – qout), the model is g(s)=k’/s with k’=1. Select Kc=Kc,min = |q0| |Vmax| . SIMC-Integral time for integrating process: I = 4 / (k’ Kc) = 4 |Vmax| / |q0| = 4 ¢ residence time provided tank is nominally half full (so |Vmax| = V) and q0 is equal to the nominal flow. SMOOTH CONTROL Rule: Kc ¸ |ud0|/|ymax| ( ~1 in scaled variables) Exception to rule: Can have even smaller Kc (< 1) if disturbances are handled by the integral action. Happens when c > I = 1 Applies to: Process with short time constant (1 is small) For example, flow control Kc: Assume variables are scaled with respect to their span SMOOTH CONTROL Summary: Tuning of easy loops Easy loops: Small effective delay ( ¼ 0), so closedloop response time c (>> ) is selected for “smooth control” Flow control: Kc=0.5, I = 1 = time constant valve (typically, 10s to 30s) Level control: Kc=2 (and no integral action) Other easy loops (e.g. pressure control): Kc = 2, I = min(4c, 1) Note: Often want a tight pressure control loop (so may have Kc=10 or larger) Kc: Assume variables are scaled with respect to their span LEVEL CONTROL More on level control Level control often causes problems Typical story: Level loop starts oscillating Operator detunes by decreasing controller gain Level loop oscillates even more ...... ??? Explanation: Level is by itself unstable and requires control. LEVEL CONTROL Integrating process: Level control q V • Level control problem has LC – y = V, u = qout, d=q • Model of level: V(s) = (q - qout)/s – G(s)=k’/s, Gd(s)= -k’/s (with k’=1) • Apply PI-control: u = c(s) (ys-y); c(s) = Kc(1+1/Is) • Closed-loop response to input disturbance: y/d = gd / (1+gc) = I s / (I/k’ s2 + Kc I s + Kc) • The denominator can be rewritten on standard form – (02 s2 + 2 0 s + 1) with 02 = I/k’¢Kc and 2 0 = I – Algebra gives: – To avoid oscillations we must require 1, or Kc¢k’ ¢I > 4 • The controller gain Kc must be large to avoid oscillations! This is the basis for the SIMC-rule for the minimum integral time LEVEL CONTROL How avoid oscillating levels? • Simplest: Use P-control only (no integral action) • If you insist on integral action, then make sure the controller gain is sufficiently large • If you have a level loop that is oscillating then use Sigurds rule (can be derived): To avoid oscillations, increase Kc ¢I by factor f=0.1¢(P0/I0)2 where P0 = period of oscillations [s] I0 = original integral time [s] Actually, 0.1 = 1/π2 LEVEL CONTROL Case study oscillating level We were called upon to solve a problem with oscillations in a distillation column Closer analysis: Problem was oscillating reboiler level in upstream column Use of Sigurd’s rule solved the problem LEVEL CONTROL Identifying the model Model identification from step response General: Need 3 parameters: Delay 2 of the following: k, k’, 1 (Note relationship k’ = k/1) Two approaches for obtaining 1: 1. 2. 1 = 16 min for this case k’ 0.14 k 0.135 0.13 63% Initial response: ( + 1) is where initial slope crosses final steadystate (+1)= 63% of final steady state If disagree: Initial response is usually best, but to be safe use smallest value for 1 (“fast response”) as this gives more conservative PID-tunings BOTTOM V: -0.5 0.125 xB 0.12 0.115 0.11 0.105 0.1 0.095 1=16 min / 19 min 0 50 100 150 200 250 300 Model identification from step response 0.9954 Generally need 3 parameters 0.9953 0.9953 0.9952 BUT For control: Dynamics at “control time scale” (c) are important c = desired response time “Slow” (integrating) process (c< 1/5): May neglect 1 and use only 2 parameters: k’ and g(s) = k’ e- s / s “Delay-free” process (c > 5θ): Need only 2 parameters: k and 1 g(s) = k / (1 s+1) 0.9952 0.9951 1 ¼ 200, 0.9951 0.995 c 0.995 0.9949 0 1 10 20 30 40 50 60 time c < τ1/5 = 40: “Integrating” (neglect τ1) c > 5θ = 5: “Delay-free” (neglect θ) “Integrating” process (c < 1/5): Need only two parameters: k’ and From step response: Response on stage 70 to step in L Example. Step change in u: Initial value for y: Observed delay: At T=10 min: Initial slope: 2.8 u = 0.1 y(0) = 2.19 = 2.5 min y(T)=2.62 2.7 2.6 2.5 y(t) 2.4 2.62-2.19 2.3 7.5 min 2.2 2.1 0 =2.5 t [min] 2 4 6 8 10 “Delay-free” process (c > 5 ) Example: BOTTOM V: -0.5 0.14 First-order model: = 0 k= (0.134-0.1)/(-0.5) = -0.068 (steady-state gain) 1= 16 min (63% of change) 0.135 0.13 63% 0.125 xB 0.12 0.115 0.11 0.105 0.1 0.095 16 min 0 50 100 150 200 250 300 Step response experiment: How long do we need to wait? NORMALLY NO NEED TO RUN THE STEP EXPERIMENT FOR LONGER THAN ABOUT 10 TIMES THE EFFECTIVE DELAY () Conclusion PID tuning SIMC tuning rules 1. Tight control: Select c= corresponding to 2. Smooth control. Select Kc ¸ Note: Having selected Kc (or c), the integral time I should be selected as given above Cascade control Tuning: 1. First tune TC (based on response from V to T) 2. Close TC and tune CC (based on response from Ts to xB) Ts Primary controller (CC) sets setpoint to secondary controller (TC). TC xB CC CC: Primary controller (“slow”): TC: Secondary controller (“fast”): y1 = xB (“original” CV), y2 = T (CV), u1 = y2s (MV) u2 = V (“original” MV) Tuning of cascade controllers • Want to control y1 (primary CV), but have “extra” measurement y2 • Idea: Secondary variable (y2) may be tightly controlled and this helps control of y1. • Implemented using cascade control: Input (MV) of “primary” controller (1) is setpoint (SP) for “secondary” controller (2) • Tuning simple: Start with inner secondary loops (fast) and move upwards • Must usually identify new model experimentally after closing each loop. • One exception: Serial process with “original” input (u) and outputs (y1) at opposite ends of the process, and y2 in the middle. – Inner (secondary-2) loop may be modelled with gain=1 and effective delay=(c+2 Cascade control serial process (“exception”) d=6 ys K1 y2s K2 u2 G2 y2 G1 y1 Cascade control serial process d=6 ys K1 y2s K2 Without cascade With cascade u G2 y2 G1 y1 Tuning cascade control: serial process Inner fast (secondary) loop: Outer slower primary loop: Reduced effective delay (2 s instead of 6 s) Time scale separation P or PI-control Local disturbance rejection Much smaller effective delay (0.2 s) Inner loop can be modelled as gain=1 + 2*effective delay (0.4s) Very effective for control of large-scale systems CONTROLLABILITY Controllability (Input-Output) “Controllability” is the ability to achieve acceptable control performance (with any controller) “Controllability” is a property of the process itself Analyze controllability by looking at model G(s) What limits controllability? CONTROLLABILITY Controllability Recall SIMC tuning rules 1. Tight control: Select c= corresponding to 2. Smooth control. Select Kc ¸ Must require Kc,max > Kc.min for controllability ) max. output deviation initial effect of “input” disturbance y reaches k’ ¢ |d0|¢ t after time t y reaches ymax after t= |ymax|/ k’ ¢ |d0| CONTROLLABILITY Controllability • More general disturbances. Requirement becomes (for c=): Following step disturbance d0: Time it takes for output y to reach max. deviation • Conclusion: The main factors limiting controllability are – large effective delay from u to y ( large) – large disturbances (k’d |d0| / ymax large) • Can generalize using “frequency domain”: |Gd(j¢0.5/max)| ¢|d0| = |ymax| CONTROLLABILITY Example: Distillation column Response to 20% increase in feed rate (disturbance) with no control -3 16 x 10 Data for “column A” Product purities: xD = 0.99 § 0.002, xB =0.01 § 0.005 (mole fraction light component) Small reboiler holdup, MB/F = 0.5 min 14 12 xB(t) 10 8 6 ymax=0.005 4 xD(t) 2 0 -2 0 1 2 3 4 5 6 7 8 9 10 time [min] Max. delay in feedback loop, max = 3/2 = 1.5 min time to exceed bound = ymax/k’d |d| = 3 min Controllability: Must close a loop with time constant (c) faster than 1.5 min to avoid that bottom composition xB exceeds max. deviation If this is not possible: May add tank (feed tank?, larger reboiler volume?) to smooth disturbances CONTROLLABILITY Example: Distillation column Increase reboiler holdup to MB/F = 10 min Original holdup -3 16 x 10 -3 16 14 Larger holdup 14 xB(t) 12 10 12 10 8 8 6 6 4 4 2 2 0 0 -2 x 10 0 1 2 3 3 min 4 5 6 7 8 9 10 -2 xB(t) 0 1 2 3 4 5 6 5.8 min 7 8 9 10 time [min] With increased holdup: Max. delay in feedback loop: = 2.9 min CONTROLLABILITY Distillation example: Frequency domain analysis Frequency-dependent gains |Gd(j)| Column A with small reboiler holdup. LV-configuration 1 10 Effect of F on xB zF on xB 0 10 max -1 10 -3 10 -2 10 10 -1 0 10 1 10 Frequency where |Gd(j)| for feed disturbance crosses 0.5 (max): d = 0.3 min-1 ) Need response time c · max = 0.5/ d = 1.7 min Agrees with previous result (1.5 min) CONTROLLABILITY Other factors limiting controllability Input limitations (saturation or “slow valve”): Can sometimes limit achievable speed of response Unstable process (including levels): Need feedback control for stabilization ) Makes sure inputs do not saturate in stabilizing loops