SECTION 25 50 00 INTEGRATED AUTOMATION FACILITY CONTROLS Equipment Specified in this section: CONTROL PROCESSOR: Crestron AV3 Table of Contents PART 1 GENERAL.................................................................................................................... 3 1.1 SECTION INCLUDES ................................................................................................................3 A. Control Processor ..................................................................................................................3 B. Related Requirements............................................................................................................3 PART 2 PRODUCTS ................................................................................................................. 4 2.1 CONTROL PROCESSOR ............................................................................................................4 A. Manufacturers .......................................................................................................................4 B. Basis of Design Product: ........................................................................................................4 C. Minimum Characteristics: .......................................................................................................4 D. External Ports .......................................................................................................................5 E. Memory Expansion Card Slot ..................................................................................................7 F. Control Port Expansion Card Slot Option..................................................................................8 G. BACnet Protocol Implementation: ...........................................................................................8 H. Mounting ..............................................................................................................................9 I. Front Panel Controls ...............................................................................................................9 J. Front Panel Indicators .............................................................................................................9 PART 3 EXECUTION ................................................................................................................ 9 END OF SECTION 25 50 00 ........................................................................................................ 9 Integrated Automation Facility Controls 2 25 50 00 SECTION 25 50 00 INTEGRATED AUTOMATION FACILITY CONTROLS Specifier: The Specifier/Design Professional is responsible for the accuracy of all project specifications, including system application and coordination with related sections. This guide specification is provided as a convenience and requires editing to match actual project requirements. CRESTRON ELECTRONICS, INC. SHALL NOT BE LIABLE FOR ANY DAMAGES ARISING OUT OF THE USE OF ANY OF ITS GUIDE SPECIFICATIONS. For Crestron design assistance and design review please contact Sales Support Services Department at 800.237.2041 or techsales@crestron.com. PART 1 1.1 GENERAL SECTION INCLUDES A. Control Processor 1. Central control processor for automation and control systems. Control processor is capable of integrated system control including native intersystem communication with equipment and processors by same manufacturer as well as scheduling and management servers. Control processor shall be the central connecting point for equipment and devices under control in a specified system. As the central element of communication for system devices under control, and all devices and sensors providing status, and feedback, the control processor integrates multiple disparate devices and systems without requiring multiple third party protocol adaptors, translators, or gateways. The control processor is also capable of sharing status, state, and feedback information from other connected devices. Specifier: Related requirements paragraph is optional. If retaining, edit and coordinate list of sections below to correspond to Project requirements. B. Related Requirements 1. Section 12 24 13 — Roller Window Shades 2. Section 23 09 23 — Direct Digital Control System for HVAC 3. Section 25 08 00 — Commissioning of Integrated Automation 4. Section 25 10 00 — Integrated Automation Network Equipment 5. Section 25 11 13 — Integrated Automation Network Servers 6. Section 25 13 13 — Integrated Automation Control and Monitoring Network Supervisory Control 7. Section 25 13 16 — Integrated Automation Control and Monitoring Network Integration Panels 8. Section 25 13 19 — Integrated Automation Control and Monitoring Network Interoperability 9. Section 25 15 16 — Integrated Automation Software for Control and Monitoring Networks 10. Section 26 09 43.13 — Digital-Network Lighting Controls 11. Section 26 05 00 — Common Work Results for Electrical 12. Section 26 09 23 — Lighting Control Devices Integrated Automation Facility Controls 3 25 50 00 PART 2 2.1 13. Section 26 09 36 — Modular Dimming Controls 14. Section 26 09 43 — Network Lighting Controls 15. Section 27 15 00 — Communications Horizontal Cabling 16. Section 27 41 00 — Audio-Video Systems PRODUCTS CONTROL PROCESSOR A. Manufacturers 1. B. Basis of Design Product: 1. C. Basis-of-Design Manufacturer: Subject to compliance with requirements, provide products of Crestron Electronics, Inc., Rockleigh, NJ 07647, Phone 800-2372041, Fax: 201-767-1903, www.crestron.com [or comparable products from a single manufacturer approved by Architect prior to bidding], with the following components and characteristics. Crestron AV3 Minimum Characteristics: 1. Operating System: a. Modular architecture supports multiple simultaneous running programs. 1) 2. b. Real-time, preemptive multithreaded/multitasking kernel. c. Vector floating point coprocessor. d. Utilize a real time, event driven, multi-tasking, multi-threaded operating system. Communication: a. 3. Number of simultaneously running user programs: 10 Control Processor shall support direct communication with the following devices: 1) Connected Ethernet devices. 2) Devices connected to built-in control ports. 3) Proprietary control network devices. 4) BACnet IP devices. 5) Control processors of same type. Native BACnet/IP Specifier: A free license for 50 BACnet objects is available for the AV3. The AV3 processor may be upgraded to support a maximum of 2000 BACnet IP objects. a. 4. Number of BACnet objects supported: 2000 File Structure: a. Transaction-safe extended FAT32 file system Integrated Automation Facility Controls 4 25 50 00 5. Memory: a. RAM: 1) b. c. Flash: 1) Built-In: 4 GB 2) USB or MMC slot: up to 32 GB External Storage 1) 6. 1 GB Supports up to 1 TB. Network: a. Two built-in 10/100/1000BaseT Ethernet ports. 1) Primary LAN port: a) 2) Subnet port a) D. Isolated WAN connection The control processor shall automatically discover and assign IP addresses to compatible devices. b. Built-In Web Server: IIS v.6.0 c. SNMP remote management. d. Active Directory support. e. IPv6 ready. f. TCP/IP Communications g. DHCP and DNS Support h. Native Email Client i. Remote Diagnostics j. Remote Program Loading and Administration k. SSL security plug in l. Support user assigned or dynamic IP address. External Ports The control system shall be equipped with the following external connection ports: 1. Infrared Output Port a. Number of built-in ports: 8 b. Connector: 2-pin 3.5mm detachable terminal blocks. c. Signal: 1) One-way infrared: up to 1.2 MHz 2) One-way serial output: TTL/RS-232 (0-5 Volts) a) 2. Baud rate: 9600 to 115,200 baud Serial Communication Port - Type 1 Integrated Automation Facility Controls 5 25 50 00 a. Number of built-in ports: 2 b. Connector: 5-pin 3.5mm detachable terminal blocks. c. Signal: 1) Bidirectional RS-232 a) b) 2) Bidirectional RS-422 or RS-485 a) b) c) 3. a. Number of built-in ports: 4 b. Connector: 3-pin 3.5mm detachable terminal blocks. c. Signal: Bidirectional RS-232 a) b) Baud rate: up to 115,000 baud Software handshaking. Input Output Port a. Number of built-in ports: 8 b. One 9-pin 3.5mm detachable terminal block. c. Individual programmable 2Kohm pull-up resistor. d. Individually configurable to one of three modes. e. Digital Input Mode 1) Digital contact closure inputs 2) Rating: a) b) c) d) 3) f. Rated for 0-24 Volts DC, referenced to GND. Rating: a) g. 0-24 VDC Impedance: 20Kohm Logic threshold High: >3.125V Logic threshold Low: < 1.875V Digital Output Mode 1) 250 mA sync from maximum 24 VDC Analog Input Mode 1) Rating: a) b) c) 5. Baud rate: 1200 to 115,000 baud Hardware handshaking: CTS, RTS, or RTS/CTS Software handshaking: off or XON Serial Communication Port - Type 2 1) 4. Baud rate: 1200 to 115,000 baud Software handshaking: off or XON 0-10 VDC Protection: 24 VDC maximum Impedance: 21Kohm Relay Port Integrated Automation Facility Controls 6 25 50 00 a. Number of built-in ports: 8 b. Two 8-pin 3.5mm detachable terminal blocks. 1) Normally open, isolated relays. 2) Rating: a) 3) 6. b. Number of built-in ports: 2 1) Port 1: Primary LAN 2) Port 2: Control Subnet Two 8-wire RJ45 with 2 LED indicators. 1) 10/100/1000BaseT Ethernet port. 2) Connection speed LED indicator. 3) Ethernet activity LED indicator. Communication Network a. Number of built-in ports: 1 b. Four 4-pin 3.5mm detachable terminal block. 1) 8. MOV arc suppression across contacts. Ethernet a. 7. Master net communications port. USB Type 1 a. Programming and configuration interface. 1) Number of built-in ports: 1 2) Connector: a) 9. USB Type-B female USB 2.0 USB Type 2 a. Memory storage device port. b. Number of built-in ports: 1 c. Connector: 1) E. 1 Amp, 30 Volts AC/DC. USB Type-A female USB 2.0 Memory Expansion Card Slot 1. Number of built-in slots: 1 2. Slot Type: a. 3. MMC Slot Capacity a. 32 GB maximum Integrated Automation Facility Controls 7 25 50 00 Specifier: Additional control expansion slots may be added to the AV3 using the optional accessory Control Card Expansion Cage (CAGE3). F. G. Control Port Expansion Card Slot Option 1. Capable of adding card cage for expansion cards. 2. Number of card slots in optional card cage: 3 BACnet Protocol Implementation: 1. BACnet Standardized Device Profile: a. 2. 3. 4. 5. Application Specific Controller (B-ASC) BACnet Interoperability Building Blocks Supported: a. Data Sharing-ReadProperty-A (DS-RP-A) b. Data Sharing-ReadProperty-B (DS-RP-B) c. Data Sharing - ReadProperty Multiple - A (DS-RPM-A) d. Data Sharing - ReadProperty Multiple - B (DS-RPM-B) e. Data Sharing-WriteProperty-A (DS-WP-A) f. Data Sharing-WriteProperty-B (DS-WP-B) g. Data Sharing – COV – A (DS-COV-A) h. Data Sharing – COV – B (DS-COV-B) i. Device Management-Dynamic Device Binding-A (DM-DDB-A) j. Device Management-Dynamic Device Binding-B (DM-DDB-B) k. Device Management-Dynamic Object Binding-B (DM-DOB-B) l. Device Management-DeviceCommunicationControl-B (DM-DCC-B) Standard Object Types Supported: a. Device Object b. Analog Input Object c. Analog Value Object d. Binary Input Object e. Binary Value Object f. Multi-State Input g. Multi-State Value Data Link Layer Options: a. BACnet IP b. BACnet IP, Foreign Device Network Options: a. BACnet/IP Broadcast Management Device (BBMD) 1) Supports registration by foreign devices. Integrated Automation Facility Controls 8 25 50 00 6. Character Set Supported: a. H. I. J. ANSI X3.4 Mounting 1. Standard 19 inch rack mount, 2 rack units high. 2. Rack mounting ears shall be removable for free standing applications. Front Panel Controls 1. Hardware reset button. 2. Software reset button. 3. Communication network fault indicator reset button. Front Panel Indicators 1. Power 2. Control Network Communication. 3. Control Processor Error. 4. Communication network fault indicator. 5. Expansion port card 1-3 status indicator. Specifier: This indicator is only functional when the optional CAGE3 (expansion card cage) is installed. The CAGE3 allows installation of up to 3 expansion cards. PART 3 EXECUTION Not Used END OF SECTION 25 50 00 Integrated Automation Facility Controls 9 25 50 00