SECTION 25 50 00
INTEGRATED AUTOMATION FACILITY CONTROLS
Equipment Specified in this section:
CONTROL PROCESSOR: Crestron AV3
Table of Contents
PART 1 GENERAL.................................................................................................................... 3
1.1 SECTION INCLUDES ................................................................................................................3
A. Control Processor ..................................................................................................................3
B. Related Requirements............................................................................................................3
PART 2 PRODUCTS ................................................................................................................. 4
2.1 CONTROL PROCESSOR ............................................................................................................4
A. Manufacturers .......................................................................................................................4
B. Basis of Design Product: ........................................................................................................4
C. Minimum Characteristics: .......................................................................................................4
D. External Ports .......................................................................................................................5
E. Memory Expansion Card Slot ..................................................................................................7
F. Control Port Expansion Card Slot Option..................................................................................8
G. BACnet Protocol Implementation: ...........................................................................................8
H. Mounting ..............................................................................................................................9
I. Front Panel Controls ...............................................................................................................9
J. Front Panel Indicators .............................................................................................................9
PART 3
EXECUTION ................................................................................................................ 9
END OF SECTION 25 50 00 ........................................................................................................ 9
Integrated Automation Facility Controls
2
25 50 00
SECTION 25 50 00
INTEGRATED AUTOMATION FACILITY CONTROLS
Specifier: The Specifier/Design Professional is responsible for the accuracy of all project specifications,
including system application and coordination with related sections. This guide specification is provided
as a convenience and requires editing to match actual project requirements. CRESTRON ELECTRONICS,
INC. SHALL NOT BE LIABLE FOR ANY DAMAGES ARISING OUT OF THE USE OF ANY OF ITS GUIDE
SPECIFICATIONS. For Crestron design assistance and design review please contact Sales Support Services Department at 800.237.2041 or techsales@crestron.com.
PART 1
1.1
GENERAL
SECTION INCLUDES
A.
Control Processor
1.
Central control processor for automation and control systems. Control processor is
capable of integrated system control including native intersystem communication
with equipment and processors by same manufacturer as well as scheduling and
management servers. Control processor shall be the central connecting point for
equipment and devices under control in a specified system. As the central
element of communication for system devices under control, and all devices and
sensors providing status, and feedback, the control processor integrates multiple
disparate devices and systems without requiring multiple third party protocol
adaptors, translators, or gateways. The control processor is also capable of sharing
status, state, and feedback information from other connected devices.
Specifier: Related requirements paragraph is optional. If retaining, edit and coordinate list of sections
below to correspond to Project requirements.
B.
Related Requirements
1.
Section 12 24 13 — Roller Window Shades
2.
Section 23 09 23 — Direct Digital Control System for HVAC
3.
Section 25 08 00 — Commissioning of Integrated Automation
4.
Section 25 10 00 — Integrated Automation Network Equipment
5.
Section 25 11 13 — Integrated Automation Network Servers
6.
Section 25 13 13 — Integrated Automation Control and Monitoring Network
Supervisory Control
7.
Section 25 13 16 — Integrated Automation Control and Monitoring Network
Integration Panels
8.
Section 25 13 19 — Integrated Automation Control and Monitoring Network
Interoperability
9.
Section 25 15 16 — Integrated Automation Software for Control and Monitoring
Networks
10.
Section 26 09 43.13 — Digital-Network Lighting Controls
11.
Section 26 05 00 — Common Work Results for Electrical
12.
Section 26 09 23 — Lighting Control Devices
Integrated Automation Facility Controls
3
25 50 00
PART 2
2.1
13.
Section 26 09 36 — Modular Dimming Controls
14.
Section 26 09 43 — Network Lighting Controls
15.
Section 27 15 00 — Communications Horizontal Cabling
16.
Section 27 41 00 — Audio-Video Systems
PRODUCTS
CONTROL PROCESSOR
A.
Manufacturers
1.
B.
Basis of Design Product:
1.
C.
Basis-of-Design Manufacturer: Subject to compliance with requirements, provide
products of Crestron Electronics, Inc., Rockleigh, NJ 07647, Phone 800-2372041, Fax: 201-767-1903, www.crestron.com [or comparable products from a
single manufacturer approved by Architect prior to bidding], with the following
components and characteristics.
Crestron AV3
Minimum Characteristics:
1.
Operating System:
a.
Modular architecture supports multiple simultaneous running programs.
1)
2.
b.
Real-time, preemptive multithreaded/multitasking kernel.
c.
Vector floating point coprocessor.
d.
Utilize a real time, event driven, multi-tasking, multi-threaded operating
system.
Communication:
a.
3.
Number of simultaneously running user programs: 10
Control Processor shall support direct communication with the following
devices:
1)
Connected Ethernet devices.
2)
Devices connected to built-in control ports.
3)
Proprietary control network devices.
4)
BACnet IP devices.
5)
Control processors of same type.
Native BACnet/IP
Specifier:
A free license for 50 BACnet objects is available for the AV3. The AV3 processor may be upgraded to
support a maximum of 2000 BACnet IP objects.
a.
4.
Number of BACnet objects supported: 2000
File Structure:
a.
Transaction-safe extended FAT32 file system
Integrated Automation Facility Controls
4
25 50 00
5.
Memory:
a.
RAM:
1)
b.
c.
Flash:
1)
Built-In: 4 GB
2)
USB or MMC slot: up to 32 GB
External Storage
1)
6.
1 GB
Supports up to 1 TB.
Network:
a.
Two built-in 10/100/1000BaseT Ethernet ports.
1)
Primary LAN port:
a)
2)
Subnet port
a)
D.
Isolated WAN connection
The control processor shall automatically discover and assign
IP addresses to compatible devices.
b.
Built-In Web Server: IIS v.6.0
c.
SNMP remote management.
d.
Active Directory support.
e.
IPv6 ready.
f.
TCP/IP Communications
g.
DHCP and DNS Support
h.
Native Email Client
i.
Remote Diagnostics
j.
Remote Program Loading and Administration
k.
SSL security plug in
l.
Support user assigned or dynamic IP address.
External Ports
The control system shall be equipped with the following external connection ports:
1.
Infrared Output Port
a.
Number of built-in ports: 8
b.
Connector: 2-pin 3.5mm detachable terminal blocks.
c.
Signal:
1)
One-way infrared: up to 1.2 MHz
2)
One-way serial output: TTL/RS-232 (0-5 Volts)
a)
2.
Baud rate: 9600 to 115,200 baud
Serial Communication Port - Type 1
Integrated Automation Facility Controls
5
25 50 00
a.
Number of built-in ports: 2
b.
Connector: 5-pin 3.5mm detachable terminal blocks.
c.
Signal:
1)
Bidirectional RS-232
a)
b)
2)
Bidirectional RS-422 or RS-485
a)
b)
c)
3.
a.
Number of built-in ports: 4
b.
Connector: 3-pin 3.5mm detachable terminal blocks.
c.
Signal:
Bidirectional RS-232
a)
b)
Baud rate: up to 115,000 baud
Software handshaking.
Input Output Port
a.
Number of built-in ports: 8
b.
One 9-pin 3.5mm detachable terminal block.
c.
Individual programmable 2Kohm pull-up resistor.
d.
Individually configurable to one of three modes.
e.
Digital Input Mode
1)
Digital contact closure inputs
2)
Rating:
a)
b)
c)
d)
3)
f.
Rated for 0-24 Volts DC, referenced to GND.
Rating:
a)
g.
0-24 VDC
Impedance: 20Kohm
Logic threshold High: >3.125V
Logic threshold Low: < 1.875V
Digital Output Mode
1)
250 mA sync from maximum 24 VDC
Analog Input Mode
1)
Rating:
a)
b)
c)
5.
Baud rate: 1200 to 115,000 baud
Hardware handshaking: CTS, RTS, or RTS/CTS
Software handshaking: off or XON
Serial Communication Port - Type 2
1)
4.
Baud rate: 1200 to 115,000 baud
Software handshaking: off or XON
0-10 VDC
Protection: 24 VDC maximum
Impedance: 21Kohm
Relay Port
Integrated Automation Facility Controls
6
25 50 00
a.
Number of built-in ports: 8
b.
Two 8-pin 3.5mm detachable terminal blocks.
1)
Normally open, isolated relays.
2)
Rating:
a)
3)
6.
b.
Number of built-in ports: 2
1)
Port 1: Primary LAN
2)
Port 2: Control Subnet
Two 8-wire RJ45 with 2 LED indicators.
1)
10/100/1000BaseT Ethernet port.
2)
Connection speed LED indicator.
3)
Ethernet activity LED indicator.
Communication Network
a.
Number of built-in ports: 1
b.
Four 4-pin 3.5mm detachable terminal block.
1)
8.
MOV arc suppression across contacts.
Ethernet
a.
7.
Master net communications port.
USB Type 1
a.
Programming and configuration interface.
1)
Number of built-in ports: 1
2)
Connector:
a)
9.
USB Type-B female USB 2.0
USB Type 2
a.
Memory storage device port.
b.
Number of built-in ports: 1
c.
Connector:
1)
E.
1 Amp, 30 Volts AC/DC.
USB Type-A female USB 2.0
Memory Expansion Card Slot
1.
Number of built-in slots: 1
2.
Slot Type:
a.
3.
MMC
Slot Capacity
a.
32 GB maximum
Integrated Automation Facility Controls
7
25 50 00
Specifier:
Additional control expansion slots may be added to the AV3 using the optional accessory Control Card
Expansion Cage (CAGE3).
F.
G.
Control Port Expansion Card Slot Option
1.
Capable of adding card cage for expansion cards.
2.
Number of card slots in optional card cage: 3
BACnet Protocol Implementation:
1.
BACnet Standardized Device Profile:
a.
2.
3.
4.
5.
Application Specific Controller (B-ASC)
BACnet Interoperability Building Blocks Supported:
a.
Data Sharing-ReadProperty-A (DS-RP-A)
b.
Data Sharing-ReadProperty-B (DS-RP-B)
c.
Data Sharing - ReadProperty Multiple - A (DS-RPM-A)
d.
Data Sharing - ReadProperty Multiple - B (DS-RPM-B)
e.
Data Sharing-WriteProperty-A (DS-WP-A)
f.
Data Sharing-WriteProperty-B (DS-WP-B)
g.
Data Sharing – COV – A (DS-COV-A)
h.
Data Sharing – COV – B (DS-COV-B)
i.
Device Management-Dynamic Device Binding-A (DM-DDB-A)
j.
Device Management-Dynamic Device Binding-B (DM-DDB-B)
k.
Device Management-Dynamic Object Binding-B (DM-DOB-B)
l.
Device Management-DeviceCommunicationControl-B (DM-DCC-B)
Standard Object Types Supported:
a.
Device Object
b.
Analog Input Object
c.
Analog Value Object
d.
Binary Input Object
e.
Binary Value Object
f.
Multi-State Input
g.
Multi-State Value
Data Link Layer Options:
a.
BACnet IP
b.
BACnet IP, Foreign Device
Network Options:
a.
BACnet/IP Broadcast Management Device (BBMD)
1)
Supports registration by foreign devices.
Integrated Automation Facility Controls
8
25 50 00
6.
Character Set Supported:
a.
H.
I.
J.
ANSI X3.4
Mounting
1.
Standard 19 inch rack mount, 2 rack units high.
2.
Rack mounting ears shall be removable for free standing applications.
Front Panel Controls
1.
Hardware reset button.
2.
Software reset button.
3.
Communication network fault indicator reset button.
Front Panel Indicators
1.
Power
2.
Control Network Communication.
3.
Control Processor Error.
4.
Communication network fault indicator.
5.
Expansion port card 1-3 status indicator.
Specifier: This indicator is only functional when the optional CAGE3 (expansion card cage) is installed.
The CAGE3 allows installation of up to 3 expansion cards.
PART 3
EXECUTION
Not Used
END OF SECTION 25 50 00