Incident Energy Study Christian Brothers University MAESC CONFERENCE - 2005 Jermichael Beaver, Bruce Luong, David Temple, and John Ventura Background Everyday electricians across North America are injured as a result of arc explosions. Many of these injuries could have been prevented with proper training and adequate protective clothing. To reduce the likelihood of an arc explosion, Buckman Labs has decided to have the amount of incident energy exposure calculated to ensure that they are within safety standard regulations. What is Arc Flash? An arc flash is basically a short circuit current through the air. Temperatures >5000o F At least 5-10 people are injured every day e.g. facial burns, brain damage, hearing loss. Arc Flash Test – 20kA on a 480V bus 1. 2. 3. 4. Objectives: Determine incident energy levels present at 20 service panels within Buckman Laboratories. Establish the rating of protective clothing worn at the plant Propose a corrective design if necessary Calculation Guides NFPA (National Fire and Protection Agency) 70-E ASTM (American Society of Testing and Materials) F-1506 IEEE (Institute of Electronic and Electrical Engineers) 1584 OSHA (Occupational Safety and Health Association) 29CFR1910.269 Oberon Selected Method Type IEEE 1584 (A guide to incident Arc Flash Calculations) – most extensive and comprehensive set of equations regarding arc-flash Based on lab testing on wide range of system conditions Plan of Attack Gather site specifications Determine short circuit currents at the panel locations Obtain circuit breaker parameters e.g. opening times, arc gap Collect data concerning worker distance from panel. Site Specifications Transformers Conductors Circuit Breakers Bus Voltages Transformers Main transformer – Y-Y 2000KVA, 23KV/480V, Z=5.8% 16 sub-transformers - D-Y, 480V/208V, Z = 5% Conductors 3-phase 4-wire system two to six conductors per phase Copper conductors used through out the plant Wire sizes: 300,000 cm to 600,000 cm Circuit Breakers Manufacturer – SquareD Breaker name – Px-2500 Opening time – 5 cycles Arc gap – 2 inches Bus Voltages Main Bus 480VLL Lighting Panels 208VLL Sample Schematics 23KV/480V 2000 KVA Fault #1 Isc=41.4 KA Z = 5.8% Electric Panel 600 / 3 Load 1 2600 / 3 600 / 3 Load 2 700 / 3 30KVA Isc=1.67 KA 480V/208V Load 3 Fault #2 Determine 3-phase short circuit currents Per unit analysis used in calculations ISC = short circuit current Isc = 41.455 KA at main panel Sample Calculations Cont. Calculate short circuit current on secondary side of transformer Per unit analysis used to determine the short circuit current on the secondary transformer. Calculate Incident Energy Eqn (1): l g ( I ) K . 6 6 2 l g ( I ) . 0 9 6 6 V . 0 0 0 5 2 6 G . 5 5 8 8 V ( l g I ) . 0 0 3 0 4 G ( l g I ) a b f b f b f Where; lg is the log10 Ia is the arcing current (kA) K is –0.097 for box configurations Ibf is the bolted fault current for three-phase faults (kA) V is the bus voltage (kV) G is the gap between conductors (mm) Calories/cm^2=35.616 Incident Energy Calculations Cont. Eqn (2): l g I a . 0 9 7 . 6 6 2 l g ( 4 1 . 4 5 ) ( . 0 9 6 6 4 8 0 ) ( . 0 0 0 5 2 6 2 5 ) ( . 5 5 8 8 4 8 0 ) ( l g 4 1 . 4 5 ) . 0 0 3 0 4 ( l g 4 1 . 4 5 ) lgIa1.3425 Ia = 22.08 kA Eqn (3): lg En = K1 + K2 + 1.081 lg Ia + .0011G where, En is the incident energy (J/cm2) normalized for time and distance K1 is –0.555 for box configurations K2 is –0.113 for grounded systems G is the gap between conductors (mm) lg En = -.555 + -.113 + 1.081 * lg(22.08) + (.0011)(25) En = 6.49 J. Incident Energy Calculations Cont. The normalized energy must now be converted to J/cm2. t 610 x Eqn(4) : E 4.184C f En .2 D x where, E is the incident energy (J/cm2) Cf is the calculation factor (1.5 voltages at or below 1kV) En is the normalized energy t is the arcing time in seconds D is the distance from the possible arc point to the person (mm) x is the distance exponent (1.641 for voltages between .208 and 1 kV) Incident Energy Calculations Cont 1.641 .04 610 12.96 J Eqn(5) : E (4.184)(1.5)(6.49) 2 1.641 cm . 2 460 E = 12.96 J/cm2 Converting to cal/cm2 we have E = 3.095 cal/cm2 Arc Flash Suits Fault to Fault Calculations ra xa L (1) : Zwire n 5280 2 2 VLL (2) : ILN Zwire Ztrans Vreal (3) : Z sec trans 2 a Ireal L = distance from transformer in feet ra = Resistance/mile xa= Inductance/mile n = # of conductors/phase VLL = Line-Line Voltage Zwire = wire impedance Zsectrans = transformer impedance ILN = Fault Current Fault to Fault Calculations Z sec 11.57 m .1006 2 .432 2 360' (1) : Zwire 3 5280' Zwire 10.08m Ztot 10.08m Z sec Ztot 10.08m 11.57 m Ztot 21.652m 480V ( 2) : ILN 21.652m ILN 22.17 KA Current Progress Calculate short circuit currents at all 20 panels. Calculate corresponding energy levels. Determine protective rating of clothing. QUESTIONS ? Possible Design Solution: Modify electrical components of the facility i.e. decreasing bus voltage and decreasing arc duration. Sample Calculations Cont. Calculate short circuit current on primary side of transformer Per unit analysis used V 23KV ; Sbase 2MVA; Zp.u .058 base Vreal 23KV; Sreal 2MVA Vreal 23KV Vp.u . 1p.u. Vbase 23KV Sample Calculations Cont-2 Vp.u . 1 Ip.u . 17.24 p.u . Zp.u . .058 Sbase 2 MVA Ibase 50.2 A Vbase 3 23KV 3 Ireal Ibase Ip.u. 17.24 50.2 A 865.52 A Is.c 865.52 A Short Circuit Current of Secondary Sbase 2MVA Ibase 2.406 kA Vbase sec 3 480 3 Ireal Ip.u. Ibase 17.24 2.406kA 41.45kA Sbase 2 MVA Ibase 2.406 kA Vbase sec 3 480 3 Ireal Ip.u . Ibase 17.24 2.406kA 41.45kA Vbase 23kV Zbase 458.167 Ibase 50.2 A Zreal Zp.u. Zbase 458.16 .058 26.57 26.57 26.57 Z sec .01158 2 2 a 47.9