Electrical equipment and apparatus

advertisement
Assumption University
Thailand
EE4503
Electrical Systems Design
Electrical Equipment and
Apparatus
1
Assumption University
Thailand
Topics
• Introduction to Electrical Equipment and
Apparatus
• Medium Voltage Equipment
• Low Voltage Equipment
2
Assumption University
Thailand
Equipment
Degree of Protection Level: IP
• IPxy or IPxyz: IP follow by two or three digit
number
– x: level of protection against contact or solid
material getting into
– y: level of protection against liquid
– z: level of protection against impact
3
Assumption University
Thailand
Equipment
Degree of Protection Level: IP
http://www.apemswitches.be/1-26428-General-information.php
4
Assumption University
Thailand
Electrical Equipment and
Apparatus
• HV Equipment (High Voltage): more than
36kV
• MV Equipment (Medium Voltage): 1kV to
36kV
• LV Equipment (Low Voltage): less than 1kV
5
Assumption University
Thailand
Electrical Equipment and
Apparatus
MV Equipment
6
Assumption University
Thailand
MV Equipment
http://www.geelectrical.com/catalog/buylog/15_BL.pdf
7
Assumption University
Thailand
MV Equipment
Electrical Systems Design: ประสิทธิ์ พิทยพัฒน์
8
Assumption University
Thailand
MV Equipment
Lightning Arrester: LA
• Operation
– Normal: High Impedance so low Leakage Current
– Overvoltage: Impedance Drop so Lightning Current
goes to ground
• Type: Spark Gap Arrester & Arrester without Spark
Gap
• Rating: Voltage and Discharge Current
9
Assumption University
Thailand
MV Equipment
LA: Spark Gap Arrester
• Old type, less uses
• Components:
– Spark Gap
– Varistor
• SiC-Arrester
http://c03.apogee.net/contentplayer/?coursetype=foe&utilityid=northwestern&id=4486
10
Assumption University
Thailand
MV Equipment
LA: Arrester Without Spark Gap
• Components: Strong Non-linear Voltage
dependent e.g Zinc Oxide
– MO-Arrester
– ZnO-Arrester
http://zone4info.com/articles/401/constructive-design-of-mo-arresters
11
Assumption University
Thailand
MV Equipment
Disconnector or Disconnecting Switch (DS)
Use to disconnect the circuit
• Disconnect high voltage but low (or no)
current circuit
– If on-load disconnection, require Load Buster
• Create large isolating distance for safety
** For safety, interlocks with other devices
12
Assumption University
Thailand
MV Equipment
Disconnector or Disconnecting Switch (DS)
• Manual Operated, Motor Operated, or
Pneumatic Drive
• Rating: Rated Voltage, Rated Normal Current,
Short Circuit Current, BIL
13
Assumption University
Thailand
MV Equipment
Earthing Switches: ES
• Connect the metal parts to ground
– discharging extra charge that left in the circuit.
– for the safety when maintain the system.
• May interlock with other devices e.g. DS
• Rating: Rated Voltage, Short Circuit Current, BIL
14
Assumption University
Thailand
MV Equipment
High Voltage High Rupturing Capacity
Fuses: HV HRC Fuses
• Protect the electrical system from overcurrent or short-circuit.
• Compose of fuse string and material to
suppress arcs.
• Some have a “Striker Pin” to indicate the
disconnecting.
15
Assumption University
Thailand
MV Equipment
High Voltage High Rupturing Capacity
Fuses: HV HRC Fuses
• Rating: Maximum Operating Voltage Rating,
Continuous Current Rating, Short Circuit Current
Rating, Selectivity (cooperate more than one safety
devices together)
• Special Rating for using with motor: Starting
Current & Starting Time
16
Assumption University
Thailand
MV Equipment
Switch Disconnector or Load Break Switch:
SD
• Able to disconnect circuit at load current
• Contain Arc Suppression
• Create large isolating distance for safety
• Rating: BIL, Rated Voltage, Rated Operating Current,
Rated Breaking Current, Rated Short Circuit Making
Current
17
Assumption University
Thailand
MV Equipment
SD
• Arc Suppression
– Air
– Vacuum
– Gas (e.g. SF6)
• Operated by Spring
http://www.accessscience.com/search.aspx?rootID=792429
18
Assumption University
Thailand
MV Equipment
Instrument Transformer
• Voltage Transformer
• Current Transformer
http://4hv.org/print.php?plugin:forum.134619
19
Assumption University
Thailand
MV Equipment
Voltage Transformers
• Transform the high voltage to the
measurable voltage level
• Do not SHORT circuit the secondary coil
• Rating: Burden, Primary Voltage, Secondary Voltage,
Permissible Voltage Stress, Accuracy
– Measurement: Class 0.1 = 0.1%, Class 0.5 = 0.5%
– Protection: Class 3P = 3%, Class 6P = 6%
20
Assumption University
Thailand
MV Equipment
Current Transformers
• Transform the high current to the
measurable current level (usually 5A)
• Do not OPEN circuit the secondary coil
– Some have “OPEN-circuit” protection
• Rating: Burden, Primary Current, Secondary
Current, Short-circuit Current, Rated
Voltage, Accuracy Class
21
Assumption University
Thailand
MV Equipment
Current Transformers
• Sometime have two secondary core:
protection & measuring cores.
• Measuring Core: small saturation factor
– Accuracy: Class 0.1 = 0.1%, Class 0.5 = 0.5%
• Measuring Core: high saturation factor
– Accuracy: Class 5P = 5%, Class 10P = 10%
– Accuracy: Class 5P10 = 5% at 10 time rated current
22
Assumption University
Thailand
MV Equipment
Protective Relay
• Detect the event and signal circuit breaker.
• Usually need CT & VT
• Mechanism
– Electromechanical Relays
– Solid State Relays
– Digital Relays
23
Assumption University
Thailand
MV Equipment
Protective Relay
• Overcurrent Relay (50, 51)
• Distance Relay (21)
• Ground Fault Relay (50N,
51N)
• Differential Relay (87)
• Under Voltage Relay (27)
• Directional Overcurrent
Relay (67)
• Directional Ground Fault
Relay (67N)
• Directional Power Relay
(32)
24
Assumption University
Thailand
MV Equipment
MV Circuit Breaker: MVCB
• MVCB is able to break the circuit in the
normal load and in the short circuit
condition.
• MVCB take the order from specific relays
to trip.
25
Assumption University
Thailand
MV Equipment
MV Circuit Breaker: MVCB
• Need to suppress arcs:
– Vaccum
– SF6
• Rating: Voltage, BIL, Nominal Current,
Short Circuit Current
26
Assumption University
Thailand
MV Equipment
MV Contactors
• Switch that use for the situation where a lot
of open/close circuit happen: e.g. Motor
circuit
27
Assumption University
Thailand
MV Equipment
MV Switchgears
• Complete set of switching devices,
protection devices, measurement devices.
• Use at the incoming of the power system
and distribute out on the other side
28
Assumption University
Thailand
MV Equipment
MV Switchgears
• Enclosure
• Busbar
• Protection Devices
• Measurement Devices
http://www.daidongs.com/eng/high-voltage-switchgear.htm
29
Assumption University
Thailand
MV Equipment
MV Switchgears
• Cubicle
• Compartmented
• Metal - Clad
http://metechakir.blogspot.com/2012/05/metal-clad-switchgear-power-systems.html
30
Assumption University
Thailand
MV Equipment
Ring Main Unit: RMU
• Like Switchgear
• Like Selector Switch
http://www.t.optimumalelektrik.com/ring-main-unit-teknik-cizimleri.html
31
Assumption University
Thailand
MV Equipment
Transformer
• Bridge to Low Voltage system
• Categorized by insulator & heat ventilation
– Liquid-immersed Transformer
• Oil-type Transformer
• Less-Flammable Liquid-insulated Transformer
– Dry-Type Transformer
32
Assumption University
Thailand
MV Equipment
Transformer
• Usually contain over-heat protection
– Sensors: 3 levels (start ventilation, warning,
shutdown)
– Temperature-Relay
• Protective Enclosure (even dry type)
• Cast Resin Transformer: can overload by
30-40% using extra heat ventilation
33
Assumption University
Thailand
Electrical Equipment and
Apparatus
LV Equipment
34
Assumption University
Thailand
LV Equipment
Circuit Breaker
• switch and able to disconnect circuit when
there is overload or short-circuit
• Two main types:
– Molded Case Circuit Breaker (MCCB)
– Air Circuit Breaker (ACB)
• Rating: Continuous Current, Interrupting
Capacity
35
Assumption University
Thailand
LV Equipment
Circuit Breaker - MCCB
MCCB is made of strong polymer material.
• Miniature Circuit Breaker (MCB) used in
the consumer unit: 1, 2 or 3 poles for IC around
3kA to 10kA.
– Earth Leakage Circuit Breaker (ELCB) or
Residual Current Circuit Breaker: 10mA or 30mA
36
Assumption University
Thailand
LV Equipment
Circuit Breaker - MCCB
• Standard CB: usually around 100AF to 2,500AF
and the IC is around 18kA to 30kA
• High Interrupting Capacity Circuit Breaker:
Used when there is a chance of high short-circuit
current. IC is usually very high 25kA to 100kA.
• Current Limiting Circuit Breaker: Used for
very fast breaking and very high short-circuit current
37
Assumption University
Thailand
LV Equipment
Circuit Breaker - ACB
• Usually large circuit breakers
• Two types:
– Fixed Type
– Drawout
38
Assumption University
Thailand
LV Equipment
Circuit Breaker – ACB v.s. MCCB
• ACB’s components can be accessed
• MCB is required no maintenance
• ACB is suitable for large systems when the
short circuit current is high
http://www.everfarelec.com/index.php/product/Air%20Circuit%20Breaker.html
39
Assumption University
Thailand
LV Equipment
Circuit Breaker – Continuous Current
• The amount of current that can pass thru the
CB under the given ambient temperature
• Usually manufactures usually offer one
frame with many rating:
– Ampere Frame (AF): maximum rating for the
specified structure
– Ampere Trip (AT): selected rating for each CB
40
Assumption University
Thailand
LV Equipment
Circuit Breaker – Interrupting Capacity
• Interrupting Capacity (IC) or Breaking
Capacity is the maximum short-circuit
current that the CB is still functional.
• IC has to be tested under many parameters,
e.g. voltage, power factor, harmonics, etc.
41
Assumption University
Thailand
LV Equipment
Circuit Breaker – Tripping Unit
• The main function of the CB is to properly
trip the system
– Thermal – Magnetic
– Solid State Trip
42
Assumption University
Thailand
LV Equipment
Circuit Breaker – Thermal & Magnetic Trip
• Thermal (Bimetal) Device: Small Overload
about 125% of rated current & Long Time
Delay
• Electromagnetic Device: Large Overload
about 10 times of rated current &
Instantaneous Trip Time
43
Assumption University
Thailand
LV Equipment
Circuit Breaker – Thermal & Magnetic Trip
Electrical Systems Design: ประสิทธิ์ พิทยพัฒน์
44
Assumption University
Thailand
LV Equipment
Circuit Breaker – Thermal & Magnetic Trip
http://electrical-engineering-portal.com/how-circuit-breaker-trip-unit-works
45
Assumption University
Thailand
LV Equipment
Circuit Breaker – Thermal & Magnetic Trip
http://electrical-engineering-portal.com/how-circuit-breaker-trip-unit-works
46
Assumption University
Thailand
LV Equipment
Circuit Breaker – Thermal & Magnetic Trip
http://electrical-engineering-portal.com/how-circuit-breaker-trip-unit-works
47
Assumption University
Thailand
LV Equipment
Circuit Breaker – Solid State Trip
• Use electronics to decide the trip action
• High accuracy and reliability
• Can be configuration tripping pattern in
many ways
48
Assumption University
Thailand
LV Equipment
Low Voltage Fuses
• Breaking the circuit by melting the metal
when over current.
– D-fuse
– D0-fuse
– NH (HRC) fuse (usually in industries)
• Rating: Nominal Current, Nominal Voltage,
Short-circuit Current
49
Assumption University
Thailand
LV Equipment
Low Voltage Fuses – D & D0 Fuse
http://www.galco.com/techdoc/brsh/10d27r_dat.pdf
50
Assumption University
Thailand
LV Equipment
Low Voltage Fuses – HRC Fuse
• Many sizes
(dimensions)
• Rated current from
6A to 1,250A
• Short-circuit current
up to 100kA
http://www.hausmanngroup.de/ip/fuses.pdf
51
Assumption University
Thailand
LV Equipment
Panelboards
• The equipment that takes the main power in
and distributes power out to many feeder.
http://www.automatech.co.uk/products/moeller.asp?scid=18&gpcid=1&cid=4
52
Assumption University
Thailand
LV Equipment
Panelboards - components
• Enclosures to protect the inside components
• Busbars conducts the current to Branch CB
and also hold the CB
• Circuit Breakers
– Main CB
– Branch CB: Plug-in unit
53
Assumption University
Thailand
LV Equipment
Panelboards – consumer units
• IC is about 10kA
• Single phase
– 4, 6, 8, 12, 16 branches
– Main CB: AT=16, 20, 32, 45, 63, 70, 80, 110A
• Three phases
– 12, 18, 24, 30, 36, 42 branches
54
Assumption University
Thailand
LV Equipment
Panelboards – industrial units
• Three phases
– 12, 18, 24, 30, 36, 42 branches
• Usually being used as “Load Center”
– Main Lugs: is mainly for distributing load
– Main Circuit Breaker: complete with main
circuit breaker
55
Assumption University
Thailand
LV Equipment
Panelboards – industrial units
http://conceptorg.com/techlibrary/PowerTechnology/AC_Load_Centers.pdf
56
Assumption University
Thailand
LV Equipment
Measuring Instruments
• Ammeter (I, A)
• Voltmeter (V, V)
• Frequency Meter (F, Hz)
• Power Factor Meter (pf)
• Power Meter (kW)
• Energy Meter (kW-hr)
• Current Transformers
• Universal Measuring Device
57
Assumption University
Thailand
LV Equipment
Magnetic Contactors
• Switch controlled by electrical power
• Rating: Utilization Category
– AC1: general load p.f.>0.95
– AC2: slip-ring motor (2.5 x In)
– AC3: squirrel cage motor (5 to 7 x In) disconnect at load
– AC4: squirrel cage motor (5 to 7 x In) and disconnect at
the starting current
58
Assumption University
Thailand
LV Equipment
Magnetic Contactors - usage
• Commonly use in the motor starting circuit
– Direct-on-line Motor Starter (DOL)
– Start-Delta Motor Starter (Y)
– Auto Transformer Motor Starter
– Resistance Motor Starter
59
Assumption University
Thailand
LV Equipment
Switchboards
• Distribution panel that distribute the main
power unit (e.g. out of transformer) to the
branch circuit
• Standard: height around 2 to 2.2m
• Enclosure from steel sheet
– Protect against physical damage, thermal
damage and erosion
60
Assumption University
Thailand
LV Equipment
Switchboards
• Busbar attached inside the enclosure
• Circuit Breaker: Main CB & Feeder CB
• Measuremnet Instrument
• Protection device (Ground Fault Protection,
Lightning Arrestor)
• Follow standards (e.g. IEC60439)
61
Assumption University
Thailand
LV Equipment
Switchboards
• Rating: Rated Voltage, Rated Current,
Rated Short-Circuit Current
http://en.wikipedia.org/wiki/Electric_switchboard
62
Assumption University
Thailand
LV Equipment
Busways or Busduct
• Equipment that transmits power from one
place to the other
http://www.sengchai.com/busduct.html
63
Assumption University
Thailand
LV Equipment
Busway or Busduct
• Rating: Indoor or Outdoor usage, Voltage
Drop, Rated Current, Short-Circuit Rating
• Busway can be reduced as long as the
protection is still valid and the extension is
no longer than 15.2m (50 ft)
64
Assumption University
Thailand
Reference
• Electrical Systems Design: ประสิทธิ์ พิทยพัฒน์
65