University of Manitoba MECHANICAL GENERAL REQUIREMENTS Req # Section 15010 Page 1 PART 1 – GENERAL 1.1 GENERAL REQUIREMENTS .1 All drawings and all sections of the specifications apply to and form an integral part of this section. .2 Provide fully operational mechanical systems in complete accordance with applicable codes and bylaws. .3 Contract documents of this section are diagrammatic and approximate to scale. Do not scale from the drawings, for dimensions refer to architectural and structural drawings. The drawings and specifications establish scope for material and installation quality and are not detailed installation instructions. Follow Manufacturers’ recommendations for installation supplemented by contract documents, unless otherwise specified by the Consultant. Any discrepancies must be brought to the Consultant’s attention in writing prior to the close of tenders. .4 Connect to equipment specified in other sections and to equipment supplied and installed by other Contractors or by the University of Manitoba. .5 All Mechanical Work to be bid as a single complete sub-contract even though work of various mechanical trades has been further sub-divided into Sections as noted. 1.2 DEFINITIONS .1 Wherever the term University, U of M, or Owner is used in the Division 15 drawings and specifications it means: The University of Manitoba .2 .3 .4 .5 .6 .7 .8 .9 .10 .11 Wherever the term "Consultant" is used in the Division 15 drawings and specifications it means [Insert Consultant’s name, contact person, address, fax and phone no.]. This Sub-Contractor shall be wholly responsible to the "Contractor" for all work of this division. Wherever the term "install" (and tenses of "install") is used in the Division 15 drawings and specifications, it means install and connect complete. Wherever the term "supply" (and tenses of “supply”) is used in the Division 15 drawings and specifications, it means supply only. Wherever the term "provide" or “provision of” (or tenses thereof) is used in relationship to equipment, piping and other materials specified for the work of Division 15, it means "supply, install and connect". Wherever the terms “provide” or “provision of” are used in connection with services such as testing, balancing, start-up, preparation of drawings for any part of the work of Division 15, it means procure, prepare, supervise, take responsibility for, and pay for these services. Whenever "drawings” and “specifications" are referred to, it means "the contract documents". Wherever the term "typical" is used in Division 15 drawings and specifications, it means a representative characteristic that is standard for all installations whether individually noted or not throughout the documents. “Typical” applies to each individual or combined installation except where specifically noted or otherwise indicated that the application is non-typical. Wherever the terms "Authorities" or "Authorities having jurisdiction" are used in the Division 15 drawings and specifications it means any and all agencies that enforce the applicable laws, ordinances, rules, regulations or codes that apply at the place of the work. Refer to Division One. Wherever the term "work" is used in the Division 15 drawings and specifications it means all equipment, permits, materials, labour and services to provide a complete mechanical installation as described and detailed on the drawings and in the specifications. Wherever the term "performance" is used in the Division 15 drawings and specifications in relation to specified equipment, it means the specified capacity of that equipment as it applies to provide air, steam or water flow, heating and/or cooling within the specified conditions of operation including air, steam and water pressures, physical space limitations and noise levels. February 27, 2015 University of Manitoba MECHANICAL GENERAL REQUIREMENTS Req # Section 15010 Page 2 .12 .13 .14 The word "exposed" where used with regard to Division 15, means any work, which is not concealed in wall, shaft, or ceiling cavities or spaces. Work behind doors, in closets or cupboards or under counters is considered exposed. All references to water shall include condensate, glycol and other fluids that apply for this project. Wherever the term “acceptable” is used in the Division 15 drawings and specifications, it means acceptable to the Consultant and the University of Manitoba. 1.3 WORK INCLUDED .1 Sections of these mechanical specifications are not intended to delegate functions or to delegate work and supply to any specific trade. The work shall include all labour, materials, equipment, and tools required for a complete and working installation as described but not necessarily limited to items in the following sections: 15010 Mechanical General Requirements 15020 Acceptable Manufacturers 15030 Precast Utility System 15050 Basic Materials and Methods 15100 Duct Cleaning 15180 Insulation 15200 Chemical Treatment 15300 Site Services 15400 Plumbing 15500 Fire Protection 15700 Heating and Cooling 15725 Variable Speed Drives 15800 Air Distribution 15860 Sound and Vibration Isolation 15900 Controls – General Requirements 15910 Controls – Field Work 15920 Controls – Panels 15930 Controls – Drawings 15950 Controls – Sequence of Operations 15990 Testing and Balancing 1.4 CASH ALLOWANCES 1. Cash allowances are carried in Division One. 1.5 COMMISSIONING .1 Refer to Section 01810 Quality Commissioning for the details of the commissioning process. 1.6 CONTRACT DRAWINGS AND SPECIFICATIONS .1 Drawings and specifications are complementary each to the other, what is called for by one shall be binding as if called for by both. .2 Specification Sections are not provided to define trade work scope. Trade work scope is the responsibility of the Contractor responsible for this project and covering the entire scope of work included in this project is the responsibility of the Contractor. .3 Should any discrepancy appear between the drawings and specifications, which leave the Contractor in doubt as to the true intent and meaning of the plans, and specifications, the Contractor shall obtain a ruling from the Consultant in writing before submitting a tender. If this is not done it will be assumed that the most expensive alternative has been included in the tender price. For any ruling to become binding, the Consultant must issue the new direction in a published form. .4 Examine all contract documents, including all drawings, specifications and work of other trades to ensure that work is co-ordinated and satisfactorily carried out without changes to the building or contract value. .5 The drawings for mechanical work are performance drawings. They are generally diagrammatic and are not to scale unless detailed otherwise. They establish scope, material February 27, 2015 University of Manitoba Req # MECHANICAL GENERAL REQUIREMENTS Section 15010 Page 3 .6 .7 .8 .9 .10 .11 .12 .13 .14 .15 .16 .17 and installation quality and are not detailed installation instructions showing every offset, fitting, valve or every difficulty encountered during execution of work and will not be used as an excuse for deficiencies or omissions. In addition to all of the requirements in the contract documents, include recommended installation details and procedures for equipment as found in Manufacturers’ technical data. As work progresses and before installing piping, ductwork, fixtures or equipment interfering with interior treatment and use of building, contact Consultant for comment. If the Contractor fails to perform above checking and fails to inform Consultant of such interference, the Contractor to bear all subsequent expense to make good the installation. Install piping, ductwork, etc., generally in the locations and routes shown on the drawings, close to the building structure to minimize furring and interference with other services or free space. Remove piping, wiring, ductwork, etc. that is not properly installed and replace to the satisfaction of the Owner/Consultant at no cost to the Owner. Equipment, materials and work shall comply with the requirements of generally recognized agencies, including but not limited to CSA, ULC, CGA, NBFU, NFPA and the requirements of authorities having jurisdiction. Be completely responsible for the acceptable condition and operation of systems and equipment components forming part of the installation or associated with it. Promptly replace defective materials, parts and equipment and repair related damage. The drawings are intended to convey the scope of work and indicate general arrangement and approximate location of apparatus and fixtures, and indicate the general location and route to be followed by pipes and ducts. Where required installations are not shown on plans or are only shown diagrammatically, install in such a way as to conserve headroom and interfere as little as possible with free use or space through which they pass, while there adequate space is allowed for service, maintenance, repair, or replacement for all equipment. All serviceable items, such as valves, controls, bearings, filters and similar items, must be installed is such a manner as to be accessible for service, maintenance, repair and replacement without the removal of other material or equipment, and without the need for specialized equipment such as lifts, harnesses, or other safety items. All work to be installed to allow easy equipment isolation and servicing functions while all surrounding systems continue to operate. Refer to Architectural drawings for roof and other construction details. These shall relate to roof supports, piping penetrating roofs, etc. as indicated on mechanical detail sheets. Drawings and specifications to be considered as an integral part of contract documents and neither drawings nor specifications are to be used alone. Misinterpretation of requirements of plans or specifications shall not relieve Contractor of responsibility of properly completing work to approval of Consultant. Do not scale drawings. Obtain information involving accurate dimensions from dimensions shown on Architectural and Structural drawings, and by site measurement. Visit and inspect the site of the work to verify location and elevation of existing services which may affect the Tender and work of this Division (water, electrical, sanitary, voice and data cabling, ductwork etc.) before submission of tender and proceeding with work. Make all necessary changes or additions to runs to accommodate structural conditions (pipes or ducts around beams, columns etc.) without additional expense to the University of Manitoba. Locations of pipes, ducts and other equipment to be altered without charge to the University of Manitoba provided change is made before installation and does not necessitate additional materials and that all such changes are acceptable to the Consultant and are suitably recorded on record set of drawings. Confirm on the site the exact location and mounting elevation of outlets and fixtures as related to existing Mechanical & Electrical components as well as Architectural & Structural details. As work progresses and before installing piping, ductwork, wiring, fixtures and equipment interfering with interior treatment and use of building, consult Consultant for appropriate action before proceeding. This applies to all levels and proper grading of piping. If February 27, 2015 University of Manitoba Req # MECHANICAL GENERAL REQUIREMENTS Section 15010 Page 4 .18 .19 .20 .21 Contractor fails to perform above checking and fails to inform Consultant of such interference, Contractor to bear all subsequent expense to make good the installation. Spaces reserved for equipment noted as future or allowances made for future extension to buildings, to be left clear so that future connections can be made. Provide adequate clear space for Owner supplied equipment and connections for such equipment. Provide detailed layouts for checking and approval by Consultant before commencing work. Refer to Architectural drawings for roof construction details. These shall relate to roof supports, piping penetrating roofs, etc. as indicated on mechanical detail sheets. Alter, at no additional cost, the locations of materials and/or equipment as directed that do not necessitate additional material. Install ceiling mounted or exposed components (e.g. diffusers, sprinkler heads, grilles) in accordance with reflected ceiling drawings or floor plans. 1.7 COORDINATION DRAWINGS .1 Prepare interference and coordination drawings for all areas, wherever there is possible conflict and/or obstruction due to the positioning of mechanical equipment, piping, wiring, ductwork, or other work of this Division relative to other trades. .2 Prepare drawings in conjunction with other trades .3 Show all sleeves and openings for passage through structure, and all inserts, equipment bases, sumps, pits and supports, and relate these to suitable grid lines and elevation datum. .4 Submit drawings for acceptance by the Consultant. .5 Drawings shall be to a scale sufficient to show the necessary details. Submit to the Owner/Consultant for review and distribute drawings after review to trades concerned. .6 Prepare fully dimensioned detail drawings of shafts, duct spaces, pipe spaces and tunnels. Show holes and sleeves, and include information pertaining to access, clearances, tappings, drains and electrical connections. .7 Base information used to prepare drawings on certified shop drawings. .8 Prepare, and submit for review, scale drawings of equipment bases, anchors and their relationship to structure, inertia slabs, floor and roof curbs, which pertain to Division 15 work and which are not shown on Architectural or Structural Drawings. 1.8 CUTTING AND PATCHING .1 Cutting, coring, drilling, patching and repairs to existing surfaces required as a result of the removal and/or relocation of existing equipment and piping, and/or installation of new equipment and piping to be included by Division 15 - Mechanical in tender price. Division 15 to employ and pay appropriate sub-trade whose work is involved, for carrying out work described above. .2 The cutting of openings not requiring lintels or other structural support will be the responsibility of the trade requiring the opening, the opening size will be the minimum required, and that patching will be the responsibility of the trades normally engaged in working with the finishing materials required to restore the opening to the original or specified conditions. .3 Where openings require lintels or other structural support, or roofing work, such openings will be specified under other divisions of this specification. 1.9 EQUIPMENT PROTECTION AND CLEAN-UP .1 Protect equipment and materials in storage, on site, during and after installation until final acceptance. Leave factory covers in place and take special precautions to prevent entry of foreign material into working parts of piping and duct systems. .2 Protect equipment with polyethylene covers and crates. .3 Operate, drain and flush out bearings and refill with new charge of lubricant, before final acceptance. .4 Thoroughly clean piping, ducts and equipment of dirt, cuttings and other foreign substances. Disconnect, clean and reconnect whenever necessary for purpose of locating and removing obstructions. Repair work damaged in course of removing obstructions. February 27, 2015 University of Manitoba Req # MECHANICAL GENERAL REQUIREMENTS Section 15010 Page 5 .5 .6 .7 .8 .9 Vacuum clean and remove debris from the inside of air handling systems, fans, heat pumps, ducts, coils, terminal units, etc. Clean exposed surfaces of mechanical equipment, ductwork, piping, etc., and polish plated work. Comb all bent fins to proper configuration on all coils in ductwork, air handling units, fan coil units, heat pumps, entrance heaters, finned radiation elements, and other heating and cooling equipment. Protect bearings and shafts during installation. Grease shafts and sheaves to prevent corrosion. Supply and install extended nipples to outside of bearing enclosures for lubrication purposes. Remove tools, surplus, and waste material from the building site upon completion of work. Clean grease, dirt, and excess material from walls, floors, ceilings, surfaces, and fixtures for which this Contractor was responsible, and leave the premises suitable for immediate use. 1.10 EXAMINATION OF THE SITE AND DOCUMENTATION .1 Prior to submitting tender, carefully examine site conditions, adjacent buildings and local conditions at the site, which could affect the work of this Division. .2 Examine Structural, Architectural, Mechanical, Electrical, and all other contract documents to ensure work can be performed without changes to the building, or work, as shown on plans. No allowance will be made later for necessary changes, unless notification of interferences have been brought to Consultant’s attention, in writing, prior to closing of tenders. .3 Verify that materials and equipment can be delivered to the place of the work and that sufficient space and access is available to permit installation thereof in locations shown on the drawings. .4 Check locations and inverts of service lines leaving and entering building to ensure their proper function prior to commencing work. .5 Verify location and elevation of existing services (water, electrical, sanitary, storm sewers, equipment, natural gas, voice and data cabling, ductwork and piping), which may affect the tender and work of this Division. Repair any damage to existing underground services caused by neglect to determine and mark out the location of such services prior to excavation work commencing. .6 Refer also to room finish schedules to determine finished, partially finished and unfinished areas of the building. .7 Visit site to determine access route for bringing equipment into the building. 1.11 EXISTING EQUIPMENT .1 Carefully dismantle existing mechanical equipment to be removed or relocated. Temporarily disconnect, remove, and reinstall existing equipment, piping, ductwork, conduit, light fixtures, and similar items, which interfere with the new installation after completion of new work. Store equipment and materials on the premises as directed by the University of Manitoba. .2 All usable salvaged equipment and materials shall remain the property of the University of Manitoba unless specifically noted otherwise. Such material shall be removed from the building and be safely and neatly stored on the site for removal by the University of Manitoba. The Contractor shall remove all rejected salvage from the site and legally dispose of it off site. .3 Reuse existing equipment in new work after first repairing and reconditioning any defective items where noted. Safely cap and seal disconnected mechanical services within finished surfaces. .4 The drawings indicate most equipment to be removed and/or disconnected. Mechanical equipment not indicated on drawings as being removed or disconnected, but needing to be removed due to removal of existing walls is to be removed and services capped at no additional cost to the University of Manitoba. February 27, 2015 University of Manitoba Req # MECHANICAL GENERAL REQUIREMENTS Section 15010 Page 6 .5 .6 The abandonment of existing equipment and material in place is not acceptable. All redundant services are to be removed back to active mains, which shall then be capped at existing point of connection. All mechanical equipment conflicting with new equipment being installed shall be moved or disconnected, without damage, by Contractor and shall remain property of the University of Manitoba. Remove ducts and piping not required in revised systems and interfering with new installation. This material shall become property of Contractor. 1.12 EXISTING SERVICES .1 Location, routing and depth of sanitary sewers, water mains, natural gas, voice and data cabling, and other utilities shown on drawings are based on recorded information and are approximate only. Contractor and his site services Subtrades shall carry out following verification procedure prior to installing the site services: .1 Reconfirm information noted on contract drawings, by comparing with the University of Manitoba and the local Utility’s most current records. .2 Referring to same benchmarks used by Contractor; take invert readings at nearest manholes and check for discrepancies with contract drawings. .3 Dig test hole and expose service mains at point or points of connection. Follow same procedure as in .2 and, in addition, confirm that service main size is same or larger than shown on contract drawings. If service is smaller than indicated, immediately notify the Consultant and the University of Manitoba in writing. .4 Take grade level readings along route of services to be installed and confirm that services will be located below frost level under finished grade. .2 Prior to installation of piping, advise Consultant of any discrepancy found during above procedure. Revised drawings or instructions will be given to Contractor. Extra payment will be made for revisions to each service requiring more than two test holes; more than 3m (10 feet) of extra pipe length and more than 300mm (12”) of additional excavation. .3 Avoid damaging or displacing existing services where exact position is not known. Should any damage occur, advise Consultant in writing for remedial instructions. 1.13 EXPEDITING AND DELIVERIES .1 Continuously check and expedite delivery of equipment and materials. If necessary, inspect at the source of manufacture. .2 Ensure that materials and equipment are delivered to the site at the proper time and in such assemblies and sizes so as to enter into the building and to be moved into the spaces where they are to be located without difficulty. Perform any cutting and patching involved in getting assemblies into place. .3 Continuously check and expedite the flow of necessary information to and from all parties involved. .4 Immediately inform the Consultant of any difficulties in delivery of equipment or if any information is required. 1.14 GUARANTEES AND WARRANTIES .1 Guarantee satisfactory operation of all work, equipment, and material installed under this contract. Replace, at no expense to the University of Manitoba, all items, which fail or prove defective within a period of two (2) years after final acceptance of complete contract by the University of Manitoba. Make good all damage incurred as a result of failure or repair of mechanical work. .2 No certification given, payment made, partial or entire use of equipment by the University of Manitoba, shall be construed as acceptance of defective work or acceptance of improper materials. Make good at once, without cost to the University of Manitoba, all such defective work or materials and consequence resulting, within two year of final acceptance date. .3 This general guarantee shall not act as a waiver for any specified guarantee and/or warranty of greater length of time noted elsewhere in these documents. .4 Comply with requirements of Division One. Provide warranties on specified products, equipment and components as well as on the installation of these items. Include for all February 27, 2015 University of Manitoba Req # MECHANICAL GENERAL REQUIREMENTS Section 15010 Page 7 .5 .6 .7 .8 .9 costs for cutting and patching, removals and restoration materials and work and repairs to other equipment affected in performance of warranty work. Provide warranty certificates, wherever given or required, that are in excess of the normal warranty period showing the name of the firm giving the warranty, dated and acknowledged, on specific equipment and systems. Plumbing brass shall be warranted for period of five (5) years. Warranties for [chillers], [variable speed drives], [boilers] and [energy management and control systems (EMCS)] to start on the date of verification of acceptance issued in writing by the Consultant. The date of verification of acceptance is independent of Substantial Performance of the Work and may occur after certification of Substantial Performance. [Chillers] and [boilers] will be accepted after start-up, a minimum of six hours of logged operation and submission of written verification of acceptance by Manufacturer's Representative. [Refer to Section 15725 for requirements for acceptance of variable speed drives.] The Consultant must also witness a portion of any of these procedures. Acceptance of the EMCS - refer to Section 15900. 1.15 LIABILITIES .1 Install work in advance of concrete pouring or similar work. Provide and set pipe sleeves as required. .2 Install concealed pipes and ducts neatly, close to building structure so furring is minimum size. Pipes, ducts and equipment installed improperly, to be removed and replaced without cost to the University of Manitoba. .3 Protect and maintain work until building has been completed and accepted. Protect work against damage during installation. Cover with tarpaulins if necessary. Repair all damage to floor and wall surfaces resulting from carrying out of work, without expense to Owners. .4 During welding or soldering ensure structure is protected against fire, shield with firerated sheets and galvanized iron sheets. Mount portable fire extinguishers in welding or soldering areas. .5 Co-ordinate work with other sections to avoid conflict and to ensure proper installation of all equipment. Review all contract drawings. .6 On completion of work, remove tools, surplus, and waste material and leave work in clean, perfect, and usable condition. 1.16 MECHANICAL SUBTRADES .1 Submit, with the tender, the names of all Sub-Trades to be used on this project as well as the extent of work to be performed by each. .2 Request and receive Consultant’s approval in writing, of all Sub-Trades before placing Sub-Trade contract. .3 Substitution of listed Sub-trades after close of Tender will not be accepted. .4 Contractor to have minimum five years experience in field of mechanical contracting and to have successfully performed work of similar nature and approximate size to that indicated in specifications and on drawings. Sub-trades shall employ, on this project, foremen or supervisory personnel who have had similar experience to that required of Contractor. 1.17 MUNICIPAL AND UTILITY SERVICES .4 Co-ordinate, arrange, and pay for all municipal and utility relocation, termination, and connections as required and shown on the drawings, complete with all metering. Install all metering equipment in accordance with the University of Manitoba standards as well as all municipal or utility requirements. .5 Refer to Existing Conditions in this Section. 1.18 PATENTS February 27, 2015 University of Manitoba Req # MECHANICAL GENERAL REQUIREMENTS Section 15010 Page 8 .1 Pay all royalties and license fees, and defend all suits or claims for infringement of any patent rights, and save the University of Manitoba and Consultant harmless of loss or annoyance on account of suit, or claims of any kind for violation or infringement of any letters patent or patent rights, by this Sub-Contractor or anyone directly or indirectly employed by him or by reason of the use by him or them of any part, machine, manufacture or composition of matter on the work, in violation or infringement or such letters patent or rights. 1.19 PERFORMANCE OF WORK .1 Install work in advance of concrete pouring or similar work. Provide and set pipe sleeves as required. .2 Install concealed pipes and ducts neatly, close to building structure so furring is minimum size. Pipes, ducts and equipment installed improperly, to be removed and replaced without cost to the University of Manitoba. .3 Protect and maintain work until building has been completed and accepted. Protect work against damage during installation. Cover with tarpaulins if necessary. Repair all damage to floor and wall surfaces resulting from carrying out of work, without expense to the University of Manitoba. .4 During welding or soldering ensure structure is protected against fire, shield with firerated sheets and galvanized iron sheets. Mount portable fire extinguishers in welding or soldering areas. Conform to the University of Manitoba standard for “Hot Work Procedure”. .5 Co-ordinate work with other sections to avoid conflict and to ensure proper installation of all equipment. Review all contract drawings. .6 On completion of work, remove tools, surplus and waste material, and leave work in clean, perfect condition. .7 Protect and defend the University of Manitoba in full and free use of any device which may be applied as part of work, either in its construction or use after completion. 1.20 PERMITS, FEES AND INSPECTION .1 Apply for, obtain, and pay for all permits, licences, inspections, examinations and fees required for work of Division 15. Submit, if required by the Authorities, information such as heat loss calculations, and other data that may be obtained from the Consultant. Should the Authorities require the information on specific forms, fill in these forms by transcribing the information provided by the Consultant. .2 If the municipality is structured as a "single permit jurisdiction", the University of Manitoba will apply, pay for and obtain the municipal building permit. In this case, the Division 15 Sub-Contractor has no financial obligation for permit application except for permits not covered in the "single permit". .3 Arrange for inspection of all work by the Authorities having jurisdiction. On completion of the work, present to the Consultant the final unconditional certificate of acceptance of the inspecting Authorities. .4 In case of conflict, codes and regulations take precedence over the contract documents. In no instance reduce the standard or scope of work or intent established by the drawings and specifications by applying any of the codes referred to herein. Any discrepancies must be brought to the Consultant’s attention in writing. .5 Before starting any work submit the required number of copies of drawings and specifications to the Authorities for their approval and comments. Comply with any changes requested as part of the contract, but notify the Consultant immediately of such changes. Prepare and submit any additional drawings, details or information as may be required. 1.21 REGULATORY REQUIREMENTS .1 Comply with the most stringent requirements of all Municipal, Provincial and Federal Bylaws and Ordinances, the requirements of Utilities such as Manitoba Hydro, and all sections of this specification. February 27, 2015 University of Manitoba Req # MECHANICAL GENERAL REQUIREMENTS Section 15010 Page 9 .2 .3 .4 .5 .6 .7 The University of Manitoba has a number of Policies and Procedures that must be followed. Copies of these may be obtained from the Physical Plant Department. These include: .1 Lock Out Procedure .2 Hot Work Procedure .3 Guidelines for Working with Asbestos .4 Fire and Evacuation Procedure .5 ID Procedures .6 Environmental Health & Safety Issues .7 Controlled Products Standards Before any work is proceeded with, approved layouts to be filed with and to be approved by proper authorities. Provide necessary notices, obtain permits and pay all fees, in order that work specified may be carried out. Charges and alterations required by authorized inspector of any authority having jurisdiction, shall be carried out without charge or expense to the University of Manitoba. Pay all charges for service connections to municipal utility mains. Furnish certificates confirming work installed conforms to requirements of authorities having jurisdiction. Do not reduce quality of any part of the Work specified and/or shown on the Drawings by following regulatory requirements. In general and as applicable, perform all Work of Division 15 to comply with physical and chemical properties, characteristics and performance requirements of recognized associations and agencies as listed herein and in the following: .1 Natural Gas Systems: CAN1-B149.1, installation code for Natural Gas Burning Appliances and Equipment. .2 Propane Systems: CAN1-B149.2, installation code for Propane Burning Equipment. .3 Fuel Oil Systems: CSA Standard B139, installation code for Oil Burning Equipment. .4 High Pressure Steam and Compressed Air Systems over 103 kPa (15 psi): Requirements of the Department of Labour, CAN B 51, Pressure Vessel Act and CAN B31.1 Power Piping. .5 Sprinkler Systems: NFPA 13, Standards for the installation of Sprinkler Systems. .6 Standpipe and Hose Systems: NFPA 14, Standard for the Installation of Standpipe and Hose Systems. .7 Plumbing Systems: National and Provincial Codes and Municipal By-laws. .8 Medical Gas and Vacuum Systems: CSA Z305.1, Non Flammable Medical Gas Piping Systems. .9 Refrigerant Piping: CSA B52. .10 Fibreglass Drainage Piping: ASTM D2310 .11 Commercial Gas Hot Water Heaters Efficiency Standard: ANSI Z21.10.3, CSA 4.31998. ACCGH AMCA ADC ANSI ARI ASCII ASHRAEASME ASTM AWWA CGA CGSB CIRI CPC CSA CTI - American Conference of Governmental Industrial Hygienists Air Moving & Conditioning Association Air Diffusion Council American National Standards Institute Air Conditioning & Refrigeration Institute American Standard Communication Information Interchange American Society of Heating, Refrigerating and Air Conditioning Engineers American Society of Mechanical Engineers American Society for Testing and Materials American Water Works Association Canadian Gas Association Canadian General Standards Board Canadian Industrial Risk Insurers Canadian Plumbing Code Canadian Standards Association Cooling Tower Institute February 27, 2015 University of Manitoba MECHANICAL GENERAL REQUIREMENTS Req # Section 15010 Page 10 EIA FCC FM ISA IAO MTC NBCC NFPA MBC ULC - Electronic Industry Association Fire Commissioner of Canada Factory Mutual Instrument Society of America Insurers Advisory Organization Ministry of Transportation and Communication National Building Code of Canada National Fire Protection Association Manitoba Building Code Underwriter's Laboratories of Canada 1.22 RIGHTS RESERVED .1 Rights are reserved to furnish any additional detail drawings, which, in the judgement of the Consultant, may be necessary to clarify the work, and such drawings shall form a part of this contract. 1.23 SAFETY DEVICE TESTING .1 Make complete inspection of all safety devices such as: fire extinguishers, hose cabinets; freeze protection devices; fire dampers, smoke dampers, fire stops, and the like to ensure: .1 That all safety devices are complete in accordance with specifications and Manufacturer’s recommendations. .2 That all safety devices are connected and operating according to all local regulations. .2 Safety devices to be inspected shall include, but not be limited to: .1 Pressure relief valves .2 Low-water cut-offs .3 High or low water alarms .4 Sprinkler alarm valves .5 Fire hydrants .6 Fire extinguishers .7 Hose cabinets .8 Carbon monoxide detectors .9 Freeze protection devices .10 Fire dampers .11 Ceiling fire stops .12 Motorized fire/smoke dampers .3 On completion of inspections, supply the Consultant with letters and/or certificates, confirming that inspections have been completed. 1.24 SCHEDULING OF WORK .1 Refer to Division 1 – General Requirements. 1.25 SHOP DRAWINGS .1 Conform to requirements of Division One except as varied by this article. .2 Present a schedule to the Consultant of shop drawings 2 weeks after the award of Contract indicating drawings submission and equipment delivery dates. .3 Submit to the Consultant for review a minimum of one (1) hard copy set and one (1) electronic set (PDF) of detailed shop drawings . .4 Check shop drawings for conformity to plans and specifications prior to submission. .5 Submit shop drawings for all items specified in the sections of Division 15. For equipment, provide performance, physical and operating data as described in the Specifications and listed in equipment schedules. Provide performance curves for all pumps and fans. Include sound and vibration data for all equipment such as fans, VAV terminals and chillers. .6 All shop drawings shall be referenced by specification section and sub-section numbers. .7 Shop drawings shall include copies of applicable brochure or catalogue material clearly indicating Manufacturer and model. Ambiguous shop drawings will not be reviewed. February 27, 2015 University of Manitoba Req # Section 15010 Page 11 .8 .9 .10 .11 .12 .13 .14 .15 .16 .17 .18 .19 .20 .21 .22 1.26 MECHANICAL GENERAL REQUIREMENTS Clearly mark submittal to indicate all differences from the specified material. The Consultant will require all options and material indicated on the shop drawing to be provided and installed. Specifically note on the submittal specified features such as tank linings, pump seal materials, painting finish, etc. Include dimensional and technical data sufficient to determine if equipment meets requirements, including weights, loading points, electrical data and motor sizes. Identify the equipment by system name and number, e.g." S1, Second Floor, Air Supply Fan", "P1, Chilled Water Pump", etc. Provide dimensions and mounting details for all items of equipment, and weight and support point loads of equipment weighing in excess of 14 kg (30 lbs.). All dimensions, weights and performance characteristics are to be in both Metric and Imperial values. Drawings submitted not in conformance with the foregoing will be rejected. Where equipment is specified with control panels or electrical control components such as float switches, control valves, level controllers, relays and the like, provide wiring diagrams and component descriptions that are specific to the item. General data covering a wide range of similar devices or components is not acceptable. Installed materials and equipment shall meet specified requirements regardless of whether or not the shop drawings were reviewed by the Consultant. Each drawing to include name of project, equipment supplier and clause number equipment is specified under. Clearly show division of responsibility. No item, equipment or description of work shall be indicated to be supplied or work to be done “By Others” or “By Purchaser”. Any item, equipment or description of work shown on shop drawings shall form part of contract, unless specifically noted to contrary. Take full responsibility for securing and verifying field dimensions. In case where fabrication must proceed prior to field dimensions being available, check all shop drawings and approve for dimensions only. In this case guarantee that dimensions will be worked to and ensure that other sub-trades are aware of these dimensions and shall comply with them. Review by Owner and/or Consultant shall be mutually understood to refer to general design only. If errors in detailed dimensions or interference with work are noticed, attention of Contractor will be called to such errors of interferences, but Owner’s/Consultant’s review of drawings will not in any way relieve Contractor from responsibility for said errors or interferences, or from necessity of furnishing such work, and materials as may be required for completion of work as called for in contract documents. This review by the Owner and/or Consultant is for the sole purpose of ascertaining conformance with the design concept. This review shall not mean that the Owner/Consultant approved the detail design inherent in the shop drawings, responsibility for which to remain with the Contractor, and such review shall not relieve the Contractor of responsibility for errors or omissions in the shop drawings or responsibility for meeting all requirements of the contract documents. The Contractor is responsible for dimensions to be confirmed and correlated at the job site, for information that pertains solely to fabrication processes or to techniques of construction and installation and for co-ordination of the work of other interfacing Trades as well as compliance with codes and requirements of Authorities. Do not order equipment until the University of Manitoba and the Consultant have reviewed and returned the reviewed shop drawings. Keep one set of shop drawings on the site. SITE REVIEW .1 The Contractor's work will be reviewed periodically by the University of Manitoba, Consultant or their representatives, solely for the purpose of determining general quality of work. Guidance will be offered to Contractor in interpretation of plans and specifications as assistance to carry out work. February 27, 2015 University of Manitoba Req # MECHANICAL GENERAL REQUIREMENTS Section 15010 Page 12 .2 Reviews and directives given to Contractor, his agents, servants and employees does not relieve the Contractor, his agents, servants or employees of their responsibility to provide the work in all its parts in a safe and workmanlike manner, and in accordance with plans and specifications, nor impose upon the University of Manitoba, and/or Consultant or their representatives, any responsibility to supervise or oversee erection or installation of any work. 1.27 SPARE PARTS .1 Furnish the University of Manitoba with spare parts as follows: .1 One set of pump seals/packing for each pump. .2 One casing joint gasket for each size pump. .3 One head gasket for each heat exchanger. .4 One glass for each gauge glass installed. .5 One set of v-belts for each piece of machinery. .6 One set of filters for each filter bank installed. (i.e. one set for both pre-filter and high efficiency filters. .7 One spare cartridge for each thermostatic mixing valve. .2 Identify spare parts containers as to contents and replacement parts numbers. 1.28 STANDARDS .1 Provide new materials and equipment as specified of proven design and quality. Provide current models of specified equipment with published ratings certified by recognized testing and standards agencies. .2 Conform to the best modern practices of workmanship and installation methods and employ only skilled tradespeople working under the direction of fully qualified personnel. 1.29 STANDARD OF MATERIAL .1 All materials and equipment installed under this contract shall be new unless otherwise noted. .2 Materials and equipment specified and acceptable Manufacturers are named in this specification for the purpose of establishing the standard of materials and workmanship to which Contractor shall adhere. Tender price shall be based on the use of materials and equipment as specified. .3 Provide new material and equipment of first class quality, delivered, erected, connected, and finished in every detail, and supplied with the acceptance of the Consultant. Assume responsibility of ensuring that provided equipment performs as specified. .4 Materials of same general type to be of same manufacture (e.g. all air supply units shall be of same Manufacturer). Contractor to ensure that all sub-trades provide products of same Manufacturer. .5 If, in the preparation of the tender, this Sub-Contractor neglects to name the Manufacturer where accepted equals have been shown, it will be understood that the specified equipment will be provided. .6 Where a Manufacturer's name is mentioned, it is for the purpose of setting a standard of quality, performance, capacity, appearance and serviceability. Acceptable equals will be shown, where deemed necessary by the Consultant, and can be used in the preparation of the tender. Where no equals are indicated, provide the exact make specified. Requests for approval of equals must be submitted not less than seven days prior to closing date of the tender and submissions must bear proof of acceptance by the University of Manitoba if used in the tender. .7 Assume full responsibility for ensuring that, when providing accepted equals, all space, weight, connections, power and wiring requirements, etc. are considered and adjusted costs are included in the tender. Alternative equipment requiring greater than specified energy requirements or unduly limiting service space requirements will not be accepted. .8 Follow Manufacturer’s recommendations for safety, adequate access for inspection, maintenance and repairs of individual equipment installed. February 27, 2015 University of Manitoba Req # MECHANICAL GENERAL REQUIREMENTS Section 15010 Page 13 .9 .10 .11 .12 .13 .14 .8 .9 Permit equipment maintenance and disassembly with minimum disturbance to connecting piping and duct systems and without interference with building structure or other equipment. Provide accessible lubricating means for bearings, including permanent lubricated “Lifetime” bearings. Contractor may propose alternative for any specified item, which is considered equal to that specified. Submit prior to tender submissions, complete specifications for proposed equal for consideration by the Consultant. All alternate items submitted for consideration must not exceed available space limitations. All additional costs for mechanical, electrical, structural and architectural revisions required to incorporate materials substituted by Contractor shall be responsibility of Contractor. Equipment listed as “equal” in specifications or submitted as equal by the Contractor must meet all space requirements, specified capacities and must have equipment characteristics of specified equipment as interpreted by Consultant. Install equipment in strict accordance with Manufacturer’s published recommendations. Equipment and materials shown on drawings and not specified herein, or specified herein and not shown on drawings, shall be included in this contract as though both shown and specified. “Request for equals” must be submitted to the Consultant and the University of Manitoba simultaneously to enhance the review process. Include only that information which will assist in the determination of product “equal” or “alternate” status. Both the Consultant and the University of Manitoba must both provide acceptance of any product as equal before it is allowed to be used on this project. Product status will be listed in addendum prior to tender closing for information to all bidding contractors and suppliers. Cut off date for “Request for Equals” submissions is 10 working days before close of tender. NO SUBMISSIONS WILL BE ACCEPTED AFTER THIS DATE. 1.30 SUPERINTENDENCE .1 Maintain qualified job site personnel consisting of licensed tradesmen and registered apprentices with proven experience in erecting, supervising, testing and adjusting projects of comparable nature and complexity. .2 Supervision personnel and their qualifications are subject to the approval of the University of Manitoba and the Consultant. 1.31 TEMPORARY USE OF EQUIPMENT .1 Permanent systems and/or equipment not to be used during construction period, without the University of Manitoba and Consultant’s written permission. .2 Heating systems may be used for temporary heating within limitations outlined in this specification. .3 Equipment used during construction period to be thoroughly cleaned and overhauled. Replace worn or damaged parts so equipment is in perfect condition, to entire satisfaction of Consultant and the University of Manitoba. .4 Provide proper care, attention and maintenance for equipment while it is being used. If, in opinion of Consultant, sufficient care and maintenance is not being given to equipment and systems, Consultant reserves right to forbid further use of said equipment and systems. .5 Temporary use of equipment shall in no way relieve Contractor of providing twenty-four month guarantee on all equipment so used this guarantee period to commence as of date of final acceptance of building by the University of Manitoba as interpreted by Consultant. .6 All air filters shall have bi-monthly inspection. Filters shall be cleaned and/or replaced depending on filter type during period in which ventilation units are being used for temporary heat. Contractor to be responsible for and pay all costs for air filter cleaning service. Filters to operate between pressure drops noted in filter Manufacturer’s catalogue. .7 All return air grilles/openings shall be equipped with MERV 8 filters to keep return air system clean of dust and dirt if air handling equipment is being used before turnover to the Owner. February 27, 2015 University of Manitoba Req # MECHANICAL GENERAL REQUIREMENTS Section 15010 Page 14 1.32 TEMPORARY HEATING .1 Written permission must be obtained from Consultant and the University of Manitoba to use permanent heating system for temporary heat. Systems are to be operated in strict accordance with Consultant’s recommendations. 1.33 TEMPORARY SERVICES .1 Refer to Division One regarding temporary services, Contractor's shop, storage and other such facilities. .2 Do not use any of the permanent mechanical systems during construction except as may be specified in Division One, or unless specific written approval is obtained from the Consultant and the University of Manitoba. .3 The use of permanent facilities for temporary construction service will not affect, in any way, the commencement date of the warranty period. Refer to Division One. .4 Thoroughly clean and overhaul permanent equipment used during the construction period, replacing damaged work or parts. Exchange equipment or components not properly operating at the final inspection with new equipment or components. .5 Use of permanent systems shall not modify the terms of guarantee/warranty. .6 Operate systems under conditions that ensure no temporary or permanent damage. Operate systems with proper treatment. Operate fans at proper resistance with filters installed. Change filters at regular intervals and prior to final acceptance. Operate with proper safety devices and controls installed and fully operational. .7 Provide filter media on return and exhaust air outlets on air systems. Change filters at regular intervals and prior to final acceptance. Clean duct systems that have become dirty. .8 Replace mechanical seals in pumps used with new mechanical seals, regardless of the seal’s condition. Turn used seals over to the Owner. .9 Obtain approval from the Owner/Consultant for the thermal insulation, and automatic control equipment associated with temporary usage of the systems. The temporary heating system shall have the approval of the Manitoba Department of Labour. 1.34 TRIAL USAGE AND TESTS .1 The University of Manitoba has the privilege of trial usage of mechanical systems or parts thereof for the purpose of learning operational procedures. .2 The University of Manitoba reserves right to use any piece of mechanical equipment, device or material installed under this contract, for such reasonable lengths of time and at such times as the Consultant may require to make complete and thorough tests of same, before final completion and acceptance of any part of contract. It is agreed and understood, that no claim for damage will be made for any injury or breakage to any part or parts of the above due to aforementioned tests, whether caused by weakness or inaccuracy of parts, or by defective materials or workmanship of any kind whatsoever. Supply all labour and equipment for such tests. .3 Assist in trial usage over a length of time, as deemed reasonable by the Consultant, at no extra cost and do not waive any responsibility because of trial usage. .4 Trial usage shall not be construed as acceptance by the University of Manitoba or as Substantial Completion of the Work. .5 Provide and pay for all testing required on the system components where, in the opinion of the Consultant, Manufacturer's ratings or specified performance are not being achieved. 1.35 WELDING REGULATIONS .1 Do not weld when temperature of base metal is lower than -18°C (0°F) except with the consent of the Consultant. At temperatures below 0°C (32°F), surface of all areas within 75mm (3”) of point where weld is to be started is to be heated to a temperature that is at least warm to the hand before welding is commenced. At all temperatures below +4°C (40°F), operator and work is to be protected against direct effect of wind and snow. .2 Welding shall be performed by welder holding current welder’s certificate from Provincial Department of Labour. February 27, 2015 University of Manitoba MECHANICAL GENERAL REQUIREMENTS Section 15010 Req # Page 15 1.36 WORK IN EXISTING AREAS .1 Perform work in existing areas to best suit available space and not interfere with or obstruct use of existing facilities. .2 Cut, cap-off, modify and extend, as necessary or as shown in the Contract Documents or as directed by the Consultant, existing material or equipment to be reused or relocated to suit the Work. Use new materials to match existing systems that are modified or extended. .3 Where disruptions of existing mechanical services are required, co-ordinate shut down with the Consultant and the University of Manitoba, and do the work at a time and in a manner mutually acceptable. Carefully schedule disruptions to keep "down time" to a minimum. Submit a concise written schedule of each disruption at least 72 (seventy-two) hours in advance and obtain the University of Manitoba's written consent prior to implementation. 1.37 WORKMANSHIP .1 Employ trades people fully qualified under Federal, Provincial, and Municipal regulations pertaining to the licensing and qualifications of trades. .2 Only first class workmanship will be accepted, not only with regard to safety, efficiency, and durability but also as it applies to neatness of detail. Pipework and ductwork must be installed parallel, or at right angles, to building planes. Equipment must be accurately similar in true vertical adjustment. The entire work shall present a neat and clean appearance on completion. PART 2 - PRODUCTS NIL PART 3 – EXECUTION NIL END OF SECTION 15010 February 27, 2015