Energy Auditing Techniques for Small Commercial Facilities 8 7 6 5 4 3 2 1 0 9/20 9/22 9/24 9/26 9/28 9/30 10/2 10/4 Sean Harleman, kW Engineering HVAC Systems Learning Objectives • • • • • Recognize common system types and controls Understand economizers and outside air Gather useful nameplate data Provide recommendations for replacements Do some simple energy savings calculations Energy Auditing Techniques Energy Auditor Role and Activities Basic • Inspect HVAC equipment • Record nameplate information • Review equipment operating schedules and controls • Develop a list of energy efficiency measures (EEMs) • Present EEMs, savings, incentives, and costs to the client Advanced • Above items plus: • Log existing power use (status, amps, or kW) • Log economizer operation (OAT, MAT, etc.) Energy Auditing Techniques HVAC Fundamentals • Heating – Offset heat that is lost to the environment – Temper ventilation air • Ventilating – Provide fresh air to building occupants • Air Conditioning (or Cooling) – – – – Offset heat that gained from the environment Offset heat generated internally Control interior moisture (Relative Humidity) Temper ventilation air Energy Auditing Techniques Why is HVAC Important? CA Commercial Sector Electricity Use California Commercial End Use Survey, Itron, CEC-400-2006-005. Energy Auditing Techniques Primary Purposes of HVAC 1. Comfort for occupants (ASHRAE 55) – Temperature – Humidity – Air movement 2. Fresh air (ASHRAE 62.1 & T24) – We need about 15 cfm per person (occupancy) – Remove dust, pollutants, contaminants & “bio-effluents” Energy Auditing Techniques Heat Sources, Sinks & Paths • Envelope – Solar – Conduction • Ventilation Air – Required for IAQ • Internal Loads – – – – Lighting Computers Equipment People Energy Auditing Techniques What is a HVAC Zone? • A discreet physical area that is conditioned by an HVAC system • Heat enters/leaves a zone through Conduction, Convection and Radiation • Borders on zones are not always clear, obvious, or tangible • Distinct zones in HVAC system marked by separate thermostats Return Air Exhaust Air Outside Air Energy Auditing Techniques COLD HOT Single Zone HVAC System Return Air Exhaust Air Outside Air COLD HOT T Energy Auditing Techniques Primary Cooling Technologies • Mechanical Cooling – Unitary equipment uses a direct expansion (DX) cooling coil • accounts for ≈ 67% of all commercial and ≈ 90% of all small commercial • this will be our focus today – Chilled water systems used in large buildings en.wikipedia.org Energy Auditing Techniques Unitary HVAC Equipment • Unitary refers to equipment where components are matched and rated together. These components include a compressor, condenser, evaporator and fan. • Unitary equipment has two main classes: Packaged and Split-System – Packaged equipment houses all components in the same enclosure – Split-Systems have the compressor & condenser in one enclosure and the evaporator and fan in another, connected by refrigeration tubing • Units can be cooling only or cooling with heating • All units circulate air, most provide ventilation Energy Auditing Techniques Unitary Equipment Identification • Packaged Unit – All components contained in one location – Ventilation is introduced through the unit – Heating is supplied by a gas furnace, heat pump, electric resistance or a hot water coil http://www.carrier.com Energy Auditing Techniques Packaged Unit Components Economizer EA OA Cooling Coils SA Filter Condenser Fan and Coils Heating Supply Fan Coils RA Controls T Thermostat Compressor Packaged Unit Energy Auditing Techniques Building Packaged With Horizontal Discharge http://www.carrier.com Energy Auditing Techniques Packaged With Vertical Discharge http://www.carrier.com http://www.carrier.com Energy Auditing Techniques Unitary Equipment Identification • Split-System – Compressor Component Only – No Ventilation provided by unit – Only heating is heat pump http://air-condition-units.com Energy Auditing Techniques Split-System www.carrier.com Energy Auditing Techniques Split-System Examples www.geo4va.vt.edu/A3/A3.htm Energy Auditing Techniques Split-System Examples www.amvair.com/typesofac.html www.letricharddoit.com/products.htm Energy Auditing Techniques Unclear on the concept Energy Auditing Techniques Primary Cooling Technologies • Mechanical cooling (e.g. DX) energy use can be reduced through the use of economizers and evaporative cooling • HVAC equipment is sized for design day loads, but operates the majority of the time under part load (~30-50% average is typical) Energy Auditing Techniques Economizers • The economizer cycle refers to using controls and dampers to make use of outside air for “free” cooling when it makes sense • Controls used to bring in outside air instead of return air • An “economizer” is generally not a single piece of equipment, although people may refer to it as such Return Air Exhaust Air Outside Air Energy Auditing Techniques COLD HOT Economizer Offsetting All Cooling Return Air 10,000 CFM, 75 deg F Exhaust Air 8,000 CFM 2,000 CFM Cooling Heating Coil Coil Outside Air 8,000 CFM, 50 deg F Discharge Air 10,000 CFM, 55 deg F Mixed Air 10,000 CFM, 55 deg F Energy Auditing Techniques Reduced Mechanical Cooling Return Air 10,000 CFM, 75 deg F Exhaust Air 10,000 CFM 0 CFM Cooling Heating Coil Coil Outside Air 10,000 CFM, 60 deg F Discharge Air 10,000 CFM, 55 deg F Mixed Air 10,000 CFM, 60 deg F Energy Auditing Techniques Air Side Economizer • Easy to show it’s not working, harder to show that it is working • Spot checks not conclusive; must trend data over time – Is the economizer bringing in 100% outside air when appropriate? – Is the system always providing minimum ventilation air? Energy Auditing Techniques Economizer Expected Performance Expected Economizer Operation 80 Minimum outside air 75 Outside Air Temperature 65 Return Air Temperature 60 55 Mixed Air Temperature Supply Air Temperature 100% Outside air 50 45 40 Mixed return and outside air 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Temperature 70 Noon Midnight Time Energy Auditing Techniques Economizer Expected Performance • Data taken from a study in Southern California Average Compressor Loading 100% 90% 80% Desert • Building type is Small Office • Percent Loaded is calculated as Compressor Run Hours / by Total Cooling Hours Percent Loaded 70% 60% Inland Valley 50% 40% Inland 30% Coastal 20% 10% 0% Energy Auditing Techniques Climate Economizer No Economizer Economizers: Implementation • Assess economizer operation by observing damper positions for various ambient conditions • Use temperature data loggers to better estimate economizer performance • Consider add-on economizer kits for existing units with failed economizers • Check for adequate relief for outside air Energy Auditing Techniques Evaporative Cooling • Cools air via evaporation of water • Direct evaporative coolers draw air through evaporative media lowering the temperature and increasing humidity • Indirect evaporative coolers use a heat exchanger to reduce the air temperature without increasing humidity; less effective Energy Auditing Techniques www.muntersamerica.com/ Direct Evaporative Cooling www.wikipedia.com This image has been (or is hereby) released into the public domain by its creator, Buster2058. This applies worldwide. Energy Auditing Techniques Evaporative Cooling: Implementation • Best when high percentage of outside air is required • Supply air temperature limited by ambient conditions • Direct evaporative cooling is best suited for areas where high humidity won’t cause problems • Indirect evaporative cooling can be used when humidity needs to be controlled or mechanical cooling will also be used Direct Evaporative Cooler www.muntersamerica.com/ Energy Auditing Techniques Primary Heating Technologies • Gas Furnaces are the most common source for heat in small commercial applications – Range of efficiencies available – Forced & Induced draft • Electric Heat Pumps provide both heating and cooling – Air source – Water Source – Ground Coupled highperformancehvac.com • Electric Resistance Heat Strips can be convenient if natural gas is limited or combustion exhaust is an issue, but Heat pumps are more energy efficient • Hot water or Steam coils can also be used, but are generally found in larger systems or systems with many zones Energy Auditing Techniques Air Source Heat Pump Utilizes same vapor compression refrigeration cycle, only now the condenser can be used to add heat to the space Energy Auditing Techniques Air Source Heat Pump oee.nrcan.gc.ca/publications/infosource/pub/h. .. Energy Auditing Techniques Air Source Heat Pump oee.nrcan.gc.ca/publications/infosource/pub/h. .. Energy Auditing Techniques Air Source Heat Pump • Use air as heat sink • Therefore: Efficiency depends on air temperatures (minimum outside operating temperature is ~ 17 °F) • Typically smaller systems / single zone • Best applicability: mild climates • SEERs range from 8 to 16 • Title 20 Sets minimum standards by size • Also: www.fmcs.coop/.../electrical_heat/air_source.htm – Water Source – Ground Coupled Energy Auditing Techniques Field Identification of HVAC Zones • Ask facility staff/engineer • Review as-built mechanical drawings • Inventory the number of thermostats and HVAC units • Observe placement of units to thermostats • Last resort: go after hours and observe response to changed setpoints Energy Auditing Techniques Unitary HVAC Nameplate • • • • Brand/Model # Age Voltage/Amperage/kW Other information: – – – – – – Rated efficiency Heating/cooling capacity Air flow rate Liquid flow rate Pressure rise Refrigerant Energy Auditing Techniques It’s not always easy to get the size Energy Auditing Techniques It’s not always easy to get the size Energy Auditing Techniques Reinforcement Activity • HVAC system exercise… Energy Auditing Techniques Energy Efficiency Opportunities • Retrofits – High Efficiency Units – Evaporative Cooling • Controls – Scheduling / reduce operating hours – Programmable thermostats – Economizer operation – Demand control ventilation • Operations – Reduce cooling loads – Keep units maintained Energy Auditing Techniques www.carrier.com High Efficiency Replacements • Package unit replacement isn’t generally cost effective on energy savings alone • So where are the opportunities? – Older units – Early retirement – New additions • How do we promote it? – Comfort – Reliability – Reduced O&M Costs www.trane.com Energy Auditing Techniques What to specify: Unitary AC and HP • For larger units, use Consortium for Energy Efficiency (CEE) guidelines (www.cee1.org) • Specify Tier 1 or 2 Efficiency level www.trane.com Energy Auditing Techniques What to specify: Unitary AC © 2009 Consortium for Energy Efficiency, Inc. All rights reserved. www.cee1.org Energy Auditing Techniques What to specify: Heat pumps © 2009 Consortium for Energy Efficiency, Inc. All rights reserved. www.cee1.org Energy Auditing Techniques Unitary HVAC: Calculations • Average Demand – kW = (Cooling CapacitykBtu/h) / (SEER) • Annual Energy Use – kWh/yr = (kW) * (hours per year) Energy Auditing Techniques Evaporative Pre-cooling • Lower head pressure by precooling condenser air by direct evaporation • New units use microprocessor controls to minimize excess water • Water off for outside air temps less than 70°F • Evaporative pre-cooling is available as add-on kit to fit many unitary systems Energy Auditing Techniques Evaporative Pre-cooler Details Energy Auditing Techniques Evaporative Pre-cooler Details Energy Auditing Techniques Evaporative Pre-Cooling Dining Unit 1 Evaporative Condenser Performance 85 Temperature exiting media (F) 80 75 70 65 60 55 55 60 65 70 75 80 Temperature entering media (F) Energy Auditing Techniques 85 90 95 100 Evaporative Pre-cooler Energy Auditing Techniques Control Measures • On/off • Setbacks • Demand Control Ventilation Energy Auditing Techniques The Opportunity: Controls General Concepts • Controls are generally the most cost effective of EEMs • Whatever doesn’t have controls probably needs it • Controls reduce opportunity for human “enhancements” • Limit hours of operation • Use to maximize system efficiencies Energy Auditing Techniques Scheduling • Mechanical Time Clocks http://www.moonlightinglls.com/ Energy Auditing Techniques Commissioning is key Even with simple equipment Energy Auditing Techniques Setbacks and Programmable Thermostats • Install Programmable Thermostats on all units • Scroll through settings during audit www.white-rodgers.com Energy Auditing Techniques Where there’s a will… Energy Auditing Techniques Setback Thermostats / Scheduling • Pitfalls – Need to be set correctly, not in “hold” mode – Persistence: document with a system manual how things are intended to work • Savings – Range widely depending on occupancy and use. Typical is 5% to 50%. – Demand savings are minimal • Non-Energy Benefits – Reduced wear on equipment Energy Auditing Techniques www.white-rodgers.com Web-enabled Thermostats • Web-based now available • About $170 to $300 each • Include ability to monitor remotely www.proliphixstore.com Energy Auditing Techniques For Classroom Control • Occupancy-based HVAC controls e.g. Bard CS2000 Energy Monitor • “Learns” occupancy patterns • No programming required • Can control lighting too • Outside air off when unoccupied www.proliphixstore.com www.doersales.com Energy Auditing Techniques Demand Control Ventilation (DCV) • Primary purpose of HVAC is to provide adequate ventilation • Basic method has been to provide sufficient ventilation for design conditions at all times • DCV provides sufficient ventilation based on actual occupancy, rather than worst case • Requires continuous monitoring of CO2 as proxy for occupancy Energy Auditing Techniques DCV: CO2 and Ventilation Rates Energy Auditing Techniques DCV: Implementation • All major controls companies support • Best practice is to measure outside air and indoor air CO2 concentrations • If only indoor concentrations monitored, typical outside CO2 concentration is 400 ppm • Controls typically set to introduce OA when indoor concentration is about 500 ppm higher than outside (T-24 requires 600 or better) • DCV should be overridden when system in economizer mode • Commission to ensure ventilation rates are not compromised • Select equipment that automates building purge for overnight buildup of contaminants Return Air Exhaust Air Outside Air Energy Auditing Techniques COLD HOT Load Shifting for Small Commercial • “Ice Bear” makes ice at night for use the next day • Thermal Energy Storage • Capacity = 5 tons • Storage = 30 tonhrs • Primary savings are in cost of energy due to load shifting • Peak kW cost savings • May have small energy savings too, depending… Energy Auditing Techniques www.ice-energy.com Ice Bear Installations www.ice-energy.com Energy Auditing Techniques Ice Bear Performance www.ice-energy.com Energy Auditing Techniques Operations and Maintenance • • • • Commissioning: check set points, schedules and resets Check for controls overrides (e.g. bypassed time-clocks) Filter changes for IAQ Check fixed damper and minimum damper positions • Adjust/tighten/replace belts • Lubricate rotary equipment Energy Auditing Techniques Operations and Maintenance (cont.) • • • • • Clean condenser coils Clean evaporator coils Insulate suction lines Check refrigerant charge Check thermostat/sensor calibration • Insulate/seal ductwork Energy Auditing Techniques O&M horrors from HVACfun.com Energy Auditing Techniques www.energy.ca.gov/pier PIER Buildings Program Design Guide: Big Savings on Small HVAC Systems Small HVAC: Frequent Issues Energy Auditing Techniques Reinforcement Activity • HVAC calculation system exercise… Energy Auditing Techniques Key Points to Remember • Economizers fail frequently and make a big difference in CA climates • HVAC units are sized for design-day conditions, but typically operate at 40-50% load • Calculating unitary HVAC annual energy use: Energy (kWh/yr ) = [Capacity (kBtu/h) *hours (hr)] / SEER • Evaporative pre-cooling can yield big savings in dry climates • Record the entire model number from HVAC units • DCV provides savings for building with variable occupancies Energy Auditing Techniques References and Resources • PG&E http://www.pge.com/mybusiness/ • Database for Energy Efficiency Resources http://www.deeresources.com • CEC Guide to Preparing Feasibility Studies for Energy Efficiency Projects www.energy.ca.gov/efficiency • Consortium for Energy Efficiency(guidelines for specifying EERs & rough costs/savings) www.cee1.org • Energy Design Resources www.energydesignresources.com • Washington State University (calculators & other resources) www.energyexperts.org Energy Auditing Techniques Course Tracker Please take a moment to fill out your Course Tracker excel sheet. Energy Auditing Techniques What is that? 1. Split - condenser 2. Packaged unit 3. Exhaust fan 4. Split - evaporator A. C. Exhaust fan Split - evaporator B. Packaged Unit D. Split - condenser Energy Auditing Techniques Model number: DPS-007-AHCY3 1. Cooling capacity: 7.5 tons 3. Line voltage: 230 2. EER: High? Need more info 4. Heating type: None Energy Auditing Techniques Appendix Energy Auditing Techniques VFD’s for Fans • Many systems use variable flow air distribution • Fan power laws dictate that power is roughly proportional to the flow rate cubed • VFD quality/reliability have improved greatly over time • VFD costs have dropped significantly with wider adoption • Now required by code for many applications in new construction Energy Auditing Techniques www.abb.com Why Fans with VFD’s Save Energy VFD 100% Power 80% 60% 40% 20% 0% 0% 20% 40% 60% 80% 100% Flow This relationships between fan energy and fan flow are taken from the California Energy Commission Guide to Preparing Feasibility Studies and the 1998 Nonresidential ACM Approval Manual. Note that a typical system curve, DOE2 default, is assumed and these relationships are not applicable to all systems. Energy Auditing Techniques A Note on IPLV • IPLV is being replaced by IEER – Integrated Energy Efficiency Ratio (IEER) – IEER Used for unitary equipment ≥ 65 kBtu/h – AHRI is dropping use of IPLV because it did not accurately represent efficiencies for units with multistage compressors – AHRI Standard 340/360 2007 defines IEER as "a single number figure of merit expressing cooling partload EER…” – Incorporated by addendum into ASHRAE 90.1 2007 – Not yet adopted by CEE, but soon Energy Auditing Techniques A Note on IPLV • Source: http://www.cee1.org/com/hecac/Prog_Guidance_IEER.pdf Energy Auditing Techniques DCV Savings www.energy.ca.gov/pier PIER Buildings Program Design Guide: Commercial Buildings Breathe Right with Demand-Controlled Ventilation Energy Auditing Techniques DCV Savings Case studies show real energy savings with payback periods of 2 years or less www.energy.ca.gov/pier PIER Buildings Program Design Guide: Commercial Buildings Breathe Right with Demand-Controlled Ventilation Energy Auditing Techniques Water-source Heat Pumps • • • • • • • • • AKA “California Heat Pump” system Uses water loop as heat sink Requires supplemental heat rejection/supply Cooling mode: rejects heat water loop Heating mode: absorbs heat from water loop Efficiency depends water loop temperatures Typically mid-sized commercial systems / multiple zone Best applicability: mild climates Title 20 Sets minimum standards by size McQuay Water Source Heat Pump Design Manual, C:330-1 Energy Auditing Techniques McQuay Water Source Heat Pump Design Manual, C:330-1 Water-source Heat Pump Configuration Energy Auditing Techniques Equipment Efficiencies • Efficiency: Ratios developed to represent equipment ability to transfer or generate heat relative to the input energy required by that equipment • COP - Coefficient of Performance (unit less) What you get divided by what you pay for (in same units) • EER - Energy Efficiency Ratio (BTU/Watt-hrs) Fully loaded unit output / electrical input • SEER - Seasonal Energy Efficiency Ratio (BTU/Watt-hrs) Average output over a range of conditions / Electrical input • IPLV - Integrated Part Load Value (units vary) Weighted average at four part load conditions • HSPF - Heating Seasonal Performance Factor (BTU/Watt-hrs) Similar to SEER (same units) but for Heat Pump heating • AFUE - Annual Fuel Utilization Efficiency (%) Efficiency of gas furnaces and small boilers measured as the useful energy output divided by the input Energy Auditing Techniques Equipment Efficiencies Equipment Type Single Point Efficiency Multi-Point or "Seasonal" Efficiency Chiller Packaged AC Furnace Boiler Heat Pump kW/Ton COP / EER Thermal Efficiency Combustion Efficiency COP / EER IPLV SEER / IPLV AFUE AFUE (<300kBTUh) HSPF Energy Auditing Techniques Units • Energy – Btu = Raises the temperature of 1 pound of water 1 degree Fahrenheit under standard conditions – Watt-Hour = 3.413 Btu – kilowatt-hr = 1000 Watt-hours = 1 kWh – 100,000 Btu = 100 kBTU = 1 therm • Rates (units of energy per time) – Watt = 3.413 Btu/h (Btu’s per hour) – kilowatt = 1000 Watts = 1 kW Energy Auditing Techniques Handy Equations • Motor Draw – kWh = (hp)(0.746 kW/hp)(%Loaded)(hours)/Efficiency – kWh = (FLA)(Volts)(PF)(%Loaded)(hours)(Phase^½) • Conduction – Btu/h = (U-Value)(Area in sq ft)(Toutside-Tinside) – Surface heat gain/loss due to Convection & Radiation • Ventilation / Infiltration – Btu/h = (1.085)(CFM)(Toutside-Tinside) • Radiation – Btu/h = Assess qualitatively Energy Auditing Techniques More Handy Equations • Efficiency Conversions – kW/ton = 12 / EER – COP = EER / 3.412 – COP = 3.516 / (kW/ton) • Heat Transfer in Water – Capacity (kBTUh) = GPM * ΔT / 2 • Power from hp – Power (kW) = 0.746 * Power (hp) • Pump power – – – – Water Power (hp) = (ft of head) * (GPM) / 3960 Pump Power = Water Power / [Pump eff * Motor eff] Fan power Fan Power (hp) = (cfm)*(SP) / [6354*ήfan* ήmotor] Energy Auditing Techniques Estimating Savings – Billing Data • Estimate amount of bill dedicated to air conditioning • Estimate the average efficiency of the existing equipment - SEER • Select new efficiency based on available equipment • Estimate savings as: SEERExist NewBill OldBill SEERproposed SEERExist or Savings OldBill 1 SEERproposed Energy Auditing Techniques Estimating Savings • Simplified Full Load Hour Calculation • Bin Simulation • SPC Software – PGE.COM/SPC – Order CD Single Zone Simulation (Constant Volume) Supply Air Flow rate (CFM) Fan kW 3 Supply Air Average Space Temp (F) Avg RAT (F) 72 Bin Midpoint 10.00 OSA LO (F) 0 107.5 102.5 97.5 92.5 87.5 82.5 77.5 72.5 67.5 62.5 57.5 52.5 47.5 42.5 37.5 32.5 27.5 22.5 4 10 38 74 114 163 219 263 318 436 558 483 330 226 105 38 8 1 TOTAL 3,388 450 Balance Temp (F) 60 Hours/yr COOLING HEATING VENTILATION 3,000 74 EER Cooling Minimum Minimum OSA OSA % OSA 15% Minimum Supply Air Flow 100% N 32 Efficiency Heating 15% 15% 15% 15% 15% 15% 15% 15% 15% 15% 15% 15% 15% 15% 15% 15% 15% 15% 79 78 78 77 76 75 75 74 73 72 72 71 70 69 69 68 67 66 3,846 kWh 366 Therms 10,163 kWh Energy Auditing Techniques 55 Design Htg Design Clg Temp Temp (F) (F) Econ MAT (F) Design SAT SAT (F) 55 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 80% Heating (kBtu/yr) 102 OSA LO (F) 120 Cooling (kBtu/yr) 0 0 0 0 0 0 0 0 0 0 1,807 6,264 7,478 7,310 4,082 1,836 469 49 278 759 2,576 4,338 5,546 6,353 7,093 5,976 4,125 1,412 0 0 0 0 0 0 0 0 29,295 38,456 Est Min SAT (F) 55 Estimated Max Zone Load 100% Example Calculation: The Problem • • • • • Existing 5 ton air conditioner is on 24/7 Site is Sunnyvale, CA EER is 10.0 Furnace is 80% efficient Office environment with fan in “on” position (i.e. not “auto”) • Propose to schedule M-F, 7 AM to 6 PM Energy Auditing Techniques Here’s the nameplate Energy Auditing Techniques Example Calculation: Scheduling RTUs • • Energy Savings from scheduling RTUs off consist primarily of two parts: 1. Reduced fan energy savings 2. Reduced ventilation loads No simple way to take credit for transient effects Energy Auditing Techniques Example Calculation: Part 1 Fan Savings • Fan draw: – 208V * (1 phase)^½ * 5.7A * (0.9 PF) = 1.07 kW • Hours reduced: – Was 24*365 = 8760 hrs/yr – Now 11 hrs per day * 365 days * 5/7 ≈ 2868 hrs/yr – Savings: 5892 hrs/yr • Savings = 1.07 kW * 5892 hrs = 6304 kWh • Assuming $0.15/kWh → $945.60 Energy Auditing Techniques Example Calc: Part 2 Ventilation Savings • Use Sunnyvale bin weather data • Ventilation load Btu/h = (1.085)(CFM)(Toutside-Tinside) • If positive, then cooling load • If negative, then heating load • Multiply by hours in bin • Divide by equipment efficiency Energy Auditing Techniques Example bin method calc: Calculating decrease in ventilation loads Min OA Outside Air Temp 97 92 87 82 77 72 67 62 57 52 47 42 37 32 27 Total 5 tons 400 cfm/ton 2,000 cfm 15% hrs 1 6 18 75 172 278 437 671 1,076 1,229 976 562 262 116 13 5,892 Room T 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 Ventilation Ventilation Ventilation Ventilation Cooling Cooling Heating Heating Load Load Load Load (kBtu/h) (kBtu) (kBtu/h) (kBtu) 8.0 7.0 5.0 3.0 2.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 8 42 90 225 344 0 0 0 0 0 0 0 0 0 0 709 0.0 0.0 0.0 0.0 0.0 0.0 2.0 3.0 5.0 7.0 8.0 10.0 11.0 13.0 15.0 0 0 0 0 0 0 874 2,013 5,380 8,603 7,808 5,620 2,882 1,508 195 34,883 Energy Auditing Techniques Cooling EER $ $ 709 10.0 71 0.15 10.64 kBtu kBtu/kW kWh /kWh Heating Efficiency 34,883 80% 43,604 436 $ 1.00 $ 436 kBtu kBtu therms /therm Savings Summary Energy Auditing Techniques