VARIABLE FLOW SYSTEMS INCORPORATING DIFFERENTIAL PRESSURE CONTROL VALVES (DPCVs) Andy Lucas - Crane BS&U Chris Parsloe - Parsloe Consulting Ltd Crane Co. was founded in 1855 by Richard Teller Crane, who made the following resolution: “I am resolved to conduct my business in the strictest honesty and fairness; to avoid all deception and trickery; to deal fairly with both customers and competitors; to be liberal and just towards employees; and to put my whole mind upon the business” Crane Limited was founded in Ipswich in 1919 Crane Building Services & Utilities was created 2009 including including Water, Air and Steam Safety Valves Automatic Air Eliminators Differential Pressure Control Valves (DPCVs) DPCVs hold pressure constant across a varying resistance (such as a 2 port valve). An impulse tube connects upstream of the variable resistance (A) to the top side of a flexible diaphragm. A separate capillary (or internal tube) connects from downstream of the variable resistance (B) to the underside of the diaphragm. As the overall pressure available A-C changes, the DPCV adjusts its position such that the pressure drop A-B remains constant. This means that the 2 port valve only needs to close against a fixed, pre-set pressure differential C B A Two Port Control Valves This is important because some 2 port control valves are limited in their ability to close against large pressure differentials. TRV IV An in-built temperature sensor closes the valve when satisfied The simplest form of 2 port control valve is the Thermostatic Radiator Valve (TRV). These valves sense the temperature in the room and gradually close when the required temperature is achieved. They usually rely on the expansion and contraction of a wax capsule inside the valve. TRVs are typically only capable of closing against around 30kPa pressure differential. Hence, left unprotected in a system with pump pressure greater 30kPa, they may struggle to close and can become noisy. 2 Port Control Valves Heating and cooling coil circuits use more sophisticated 2 port control valves that are operated by electrically powered actuators. This means that the valves can shut off against much larger pressure differentials (200-500kPa, depending on valve size). Room sensor However, simply because the valve can close against such a high pressure differential doesn’t mean it is a good idea to let it do so. Actuator Cavitation in 2 Port Control Valves The closure of valves against excessive pressures can still cause noise and, if the static pressure in the system is low enough, there is a risk of cavitation in the valve. Cavitation is the localised vaporisation of a liquid. When the absolute pressure approaches the vapour pressure of the liquid, dissolved air is released and small bubbles of vapour are formed. These bubbles form and then collapse rapidly releasing enormous amounts of energy which can cause damage to metal components such as valves. Percentage flow rate If good modulating control is required, then the control valve needs to achieve an equal percentage characteristic i.e. a characteristic that mirrors the heat transfer characteristic of the coil. This will ensure that closure of the valve will achieve a steady reduction in heating or cooling output from the coil enabling close control of internal temperature. Coil characteristic Valve characteristic Percentage open Valve Authority p1 % flow An equal percentage control valve can be specified, but it will only operate with an equal percentage characteristic if, when fully open, the pressure loss across it represents a significant proportion of the overall pressure loss in the circuit it controls. This relationship p1 / (p1 + p2) in the diagram below is referred to as “valve authority”. Ideally the authority should never be less than 0.3. The graphs below show the effect of varying valve authority on the valve’s characteristic. % open DPCVs to Protect Downstream 2 Port Control Valves In large systems it is usually impossible to select modulating 2 port control valves with an acceptable authority unless there is some form of differential pressure control that limits the pressure differential against which the 2 port valves have to close. The positioning of DPCVs on sub-branches serving downstream 2 port control valves is therefore essential to achieve good control, as well as to avoid noise or cavitation. A B C A DPCV holds pressure constant between points A and B regardless of changes in pressure between A and C. System Layout Branches to each level feed flow return circuits which are themselves broken down into a series of sub-circuits. Each sub-circuit has its own DPCV. The secondary pumps are variable speed. Terminal Branches End terminal units should be given constant flow (3 or 4 port valves) to ensure that: - there is flow through the pump at minimum load - water treatment chemicals are circulated to extremities - when control valves open, there is a ready supply of hot or cold water in the mains. 1 in 5 of the central control valves on each circuit should also be selected as a constant flow (3 or 4 port valves) with the aim of achieving approximately 80% reduction in flow at minimum load. Locations of DPCVs to Facilitate 2 Port Valve Selection The constant pressure, controlled by the DPCV must not exceed 1.5 times the pressure drop across the end terminal branch Dptb Branches should be limited to no more than 12 terminal units per DPCV controlled sub-branch. Dptb This will make it possible to select 2 port control valves with acceptable authorities (i.e. >0.3) 2 Port Valve Selection 2 port valves must be sized to achieve an authority of at least 0.3 i.e. p1 divided by p1 plus p2 must be greater than 0.3 where p1 plus p2 is equal to the total loss through the downstream index branch. p1 + p2 p1 p1 + p2 = total loss through downstream index branch Commissioning Features Around DPCVs A Companion Valve, FODRV, should be located upstream of the DPCV so that the DPCV can be adjusted until the required design flow rate is achieved. A Capillary tube connects each side of the controlled sub-circuit. Pressure test points should be located adjacent to each capillary tube connection so that the pressure controlled constant by the DPCV can be measured and recorded. Pump Speed Control Pressure Dp (kPa) Speed control based on constant pump pressure Speed control based on remote differential pressure sensors . . . Flow Rate Q (kg/s) 50% . Maximum load operating point The pump energy saving achieved is influenced by how pump speed is controlled. Integral pump controllers enable the pump to be controlled to maintain constant pressure or at an arbitrarily selected pressure proportional to the reduction in flow rate. The savings achieved using these methods are not as good as by using remote differential pressure sensors. Speed control based on proportion of flow rate Typical energy saving 30-40% Typical energy saving 80-90% 100% Typical energy saving 50-60% Pump Speed Control Could the index move to an upstream sub-branch? (Yes if the entire index branch closes down) If so an additional sensor is required here. Pump speed should be controlled to maintain the minimum specified pressure differentials at all sensors. P Differential pressure sensor across the DPCV controlled index sub-branch. The pump speed should be controlled to maintain the minimum specified pressure differential. PP Could the index move to the floor below? (Yes if the entire top floor closes down) If so, an additional differential pressure sensor should be installed here. Features Around Differential Pressure Sensors Differential pressure sensors should be located across the most remote DPCV controlled sub-branch with additional sensors on any upstream branches that might become the index under part load conditions. Pump speed should be controlled such that the minimum specified pressure differential at each sensor is maintained. Isolating valves should be incorporated in pipe connections so that the sensor can be isolated and removed if necessary. Tee off connections to the sensor must be at least five diameters downstream of bends or other restrictions. Pressure tappings should be included either side of the sensor, so that the sensor can be checked and recalibrated. P A by-pass with an isolating valve should be included to allow the differential pressure to be checked and zeroed. Centralised Valve Modules Pre-assembled centralised valve modules contain all of the valves required to feed a group of terminal units. Flexible multilayer pipe connects from the module to the terminals. Valve Module Centralised Valve Modules Commissioning sets on each return to enable flow balancing. A single DPCV ensures a constant pressure across the flow and return manifolds. An integral flushing by-pass in accordance with BSRIA guidance Drain cock for back flushing of terminals A Ball valve on each flow to enable isolation. A large bodied strainer provides protection to downstream valves. Centralised Valve Modules CommPac Flow Management Module