048–600–00_SiteRanger_Internet-basedSiteMonitoringSystem_v4

advertisement
SiteRanger™ Internet-based Site
Monitoring System
Comprehensive Broadband/ Enterprise site monitoring device for Headend’s, Hub Sites.
 24 relay isolated input channels
 Smart transducers for power system monitoring
 Analog measurements such as temperature, generator fuel levels, AC and DC power
systemvoltage, current and power
1. Wall mount NEMA4X/12 housing
2. Internal Circuit board with integrated electronic components. Internal webserver with TCP/IP,
SNMP, Telnet
3. 24 contact closure input channels - active low inputs 12/24VDC. Accepts contact closures from
UPS and DC systems, Generators, HVAC units, Fire Suppression, access control and other site
devices
4. 24 channels, internal relay form-c dry contact closures. Provides electrical isolation to web
server module
5. LED indicators for contact input on/off status, power supply status, reverse polarity, fuse fail
alarm
6. Three master relays for use as major, minor, critical alarms or as user selectable alarm groups.
Any of the 24 input alarms can be user programmed in groups to actuate the three master
relays. Provides very flexible alarm mapping for local audible / visual site indicators
7. Set-screw terminal blocks for reliable compression crimp connections. Alarm channel input
connections to support web server, front LCD annunciator panel and monitoring system. DC
power and alarm input connections
8. Compliant with Comcast and Charter typical VOIP telemetry alarm requirements for site
monitoring. SNMP trap output via internet connections, email, remote internet login webserver.
Pending support for Spectrum enterprise management software for Regional/National NOC
visibility
9. Universal +12/24VDC input. Surge protected, fuse protected, reverse polarity protected.Includes
12V battery back-up
10. Integrated annunciator LCD panel including digital site status, webserver configuration, ethernet
port for communications to network infrastructure
11. Available smart transducer system options include AC monitor module for Generator ATS or UPS
power parameter monitoring, DC module for -48VDC power system voltage, current,
distribution monitoring, Environmental module for HVAC alarm status, high/low temperature,
condensate drain alarms. Generator status module for generator alarms, fuel level. Smart
transducers are powered from main control unit via the SiteRanger LAN for reliability and
uninterrupted monitoring
General Specifications
Model #
Configuration
P/N 016-900-10 SiteRanger control module:
24 Contact inputs, Smart
Part #
016-900-10
Description
 Wall mount non metallic
housing. Accepts 24 contact
Doc# 048–600–00/Nov.01.05
transducer interface, internal
power supply-battery back-up,
LCD interface panel,Wall mount
housing
P/N 016-905-10 ACM AC power module
Monitors single or three phase
AC voltage, current, power
parameters
Use for ATS site power
monitoring, UPS output
monitoring

016-905-10
016-906-10
016-907-10
016-908-10




P/N 016-910-10 DCM DC power module
Monitors -48VDC rectifier and
battery system status
Measures DC voltage, current,
distribution circuit breaker trip,
battery status, accepts alarm
contact outputs from DC power
system
016-910-10
016-911-10
016-912-10
P/N 016-915-10 EVM Environmental module
Monitors HVAC alarm contact
outputs, temperature,
condensate drain alarm, multiple
temperature sensor inputs for
zone temperature monitoring
016-915-10
016-916-10
P/N 016-92010
016-920-10
016-921-10
016-922-10
GSM Generator status module
Monitors Generator contact
closures, fuel level, starting
battery voltage
P/N 016-925-10 FSM Generator fuel status
module
Monitors Generator fuel level
(Diesel or propane)




016-930-10
016-931-10
016-932-10
016-933-10





inputs, interfaces with CSI smart
transducer SiteRanger LAN
Ethernet 10/100 Base T jack with
LED indicators. 120VAC input,
internal power supply with
battery back-up
LCD front panel
Non-metallic housing with
terminal block connections for
AC voltage sense, current
transformer input sense, ATS
position sensing
(generator/commercial power),
5 alarm contact inputs
SiteRanger LAN port. Specify 1,2
or 3 phase, 120V, 240V, 208V,
480V versions
Current transformers available
for 100, 200, 400 and 600A
systems
Non-metallic housing with
terminal block connections for
DC voltage sense, DC power
system contact closure inputs,
distribution alarm contact
inputs, SiteRanger LAN port
Specify input configuration,
current monitoring kit, battery
temperature probe kit
Non-metallic housing with
terminal block connections for 8
HVAC system alarm contact
inputs. 4 Temperature sensor
inputs, SiteRanger LAN port
Specify number of temperature
sensors required (up to 4)
Non-metallic housing with
terminal block connections for
generator output AC voltage
sense, 8 alarm contact inputs
SiteRanger LAN port
Specify 1, 2 or 3 phase
Monitors Generator fuel level
Specify diesel tank level sensor,
propane tank transducer head
(various versions depending
upon tank vendor)
Doc# 048–600–00/Nov.01.05
Common Specifications for All Models
Dimensions: 13.5" W x 16.5" T x 7.5 D
Weight: 15 lbs
Wall mount with mounting flanges on top and bottom of enclosure
NEMA 4X, 12 compliant. UL/CSA listed enclosure
Structural foam
thermoplastic enclosure and gasketed hinged cover w/LCD control panel
Unit includes wiring diagra /instruction manual,software, spare fuses
Electrical Specifications
 Input: 120VAC power supply with +12VDC nominal battery system
 24 input terminal connections for alarm contacts, internal 12VDC source for alarm contact
circuit power
 3 master alarm form-C output connections with user
 27 LED channel active indicators. LED's for input power OK, reverse polarity and input fuse fail
 Ethernet port with LED indicators, SiteRanger LAN ports for remote modules
Digital LCD Control Panel Annunciator Specifications
 Color coded LED indicators for alarm conditions
 2 line x 20 Character LCD alphanumeric text display with alarm status information
 Audible alarm with silence switch
 User programmable alarm mapping
 User programmable text for custom alarm conditions
 Ethernet 10/100 Base T RJ45 jack for laptop system programming and network connection
 Uses category 5 LAN cable and connectors for serial interface with PoE to remote SiteRanger
transducer modules
 NFPA110 compliant
Order Information
Shipping box packaging for UPS/FedEx shipment. Typical configuration includes bill of materials / parts
kit as per customer site survey order form.
CSI Provides customer site surveys at no charge to provide customer proposals for the correct
SiteRanger component and installation configurations.
Doc# 048–600–00/Nov.01.05