SiteRanger™ Internet-based Site Monitoring System Comprehensive Broadband/ Enterprise site monitoring device for Headend’s, Hub Sites. 24 relay isolated input channels Smart transducers for power system monitoring Analog measurements such as temperature, generator fuel levels, AC and DC power systemvoltage, current and power 1. Wall mount NEMA4X/12 housing 2. Internal Circuit board with integrated electronic components. Internal webserver with TCP/IP, SNMP, Telnet 3. 24 contact closure input channels - active low inputs 12/24VDC. Accepts contact closures from UPS and DC systems, Generators, HVAC units, Fire Suppression, access control and other site devices 4. 24 channels, internal relay form-c dry contact closures. Provides electrical isolation to web server module 5. LED indicators for contact input on/off status, power supply status, reverse polarity, fuse fail alarm 6. Three master relays for use as major, minor, critical alarms or as user selectable alarm groups. Any of the 24 input alarms can be user programmed in groups to actuate the three master relays. Provides very flexible alarm mapping for local audible / visual site indicators 7. Set-screw terminal blocks for reliable compression crimp connections. Alarm channel input connections to support web server, front LCD annunciator panel and monitoring system. DC power and alarm input connections 8. Compliant with Comcast and Charter typical VOIP telemetry alarm requirements for site monitoring. SNMP trap output via internet connections, email, remote internet login webserver. Pending support for Spectrum enterprise management software for Regional/National NOC visibility 9. Universal +12/24VDC input. Surge protected, fuse protected, reverse polarity protected.Includes 12V battery back-up 10. Integrated annunciator LCD panel including digital site status, webserver configuration, ethernet port for communications to network infrastructure 11. Available smart transducer system options include AC monitor module for Generator ATS or UPS power parameter monitoring, DC module for -48VDC power system voltage, current, distribution monitoring, Environmental module for HVAC alarm status, high/low temperature, condensate drain alarms. Generator status module for generator alarms, fuel level. Smart transducers are powered from main control unit via the SiteRanger LAN for reliability and uninterrupted monitoring General Specifications Model # Configuration P/N 016-900-10 SiteRanger control module: 24 Contact inputs, Smart Part # 016-900-10 Description Wall mount non metallic housing. Accepts 24 contact Doc# 048–600–00/Nov.01.05 transducer interface, internal power supply-battery back-up, LCD interface panel,Wall mount housing P/N 016-905-10 ACM AC power module Monitors single or three phase AC voltage, current, power parameters Use for ATS site power monitoring, UPS output monitoring 016-905-10 016-906-10 016-907-10 016-908-10 P/N 016-910-10 DCM DC power module Monitors -48VDC rectifier and battery system status Measures DC voltage, current, distribution circuit breaker trip, battery status, accepts alarm contact outputs from DC power system 016-910-10 016-911-10 016-912-10 P/N 016-915-10 EVM Environmental module Monitors HVAC alarm contact outputs, temperature, condensate drain alarm, multiple temperature sensor inputs for zone temperature monitoring 016-915-10 016-916-10 P/N 016-92010 016-920-10 016-921-10 016-922-10 GSM Generator status module Monitors Generator contact closures, fuel level, starting battery voltage P/N 016-925-10 FSM Generator fuel status module Monitors Generator fuel level (Diesel or propane) 016-930-10 016-931-10 016-932-10 016-933-10 inputs, interfaces with CSI smart transducer SiteRanger LAN Ethernet 10/100 Base T jack with LED indicators. 120VAC input, internal power supply with battery back-up LCD front panel Non-metallic housing with terminal block connections for AC voltage sense, current transformer input sense, ATS position sensing (generator/commercial power), 5 alarm contact inputs SiteRanger LAN port. Specify 1,2 or 3 phase, 120V, 240V, 208V, 480V versions Current transformers available for 100, 200, 400 and 600A systems Non-metallic housing with terminal block connections for DC voltage sense, DC power system contact closure inputs, distribution alarm contact inputs, SiteRanger LAN port Specify input configuration, current monitoring kit, battery temperature probe kit Non-metallic housing with terminal block connections for 8 HVAC system alarm contact inputs. 4 Temperature sensor inputs, SiteRanger LAN port Specify number of temperature sensors required (up to 4) Non-metallic housing with terminal block connections for generator output AC voltage sense, 8 alarm contact inputs SiteRanger LAN port Specify 1, 2 or 3 phase Monitors Generator fuel level Specify diesel tank level sensor, propane tank transducer head (various versions depending upon tank vendor) Doc# 048–600–00/Nov.01.05 Common Specifications for All Models Dimensions: 13.5" W x 16.5" T x 7.5 D Weight: 15 lbs Wall mount with mounting flanges on top and bottom of enclosure NEMA 4X, 12 compliant. UL/CSA listed enclosure Structural foam thermoplastic enclosure and gasketed hinged cover w/LCD control panel Unit includes wiring diagra /instruction manual,software, spare fuses Electrical Specifications Input: 120VAC power supply with +12VDC nominal battery system 24 input terminal connections for alarm contacts, internal 12VDC source for alarm contact circuit power 3 master alarm form-C output connections with user 27 LED channel active indicators. LED's for input power OK, reverse polarity and input fuse fail Ethernet port with LED indicators, SiteRanger LAN ports for remote modules Digital LCD Control Panel Annunciator Specifications Color coded LED indicators for alarm conditions 2 line x 20 Character LCD alphanumeric text display with alarm status information Audible alarm with silence switch User programmable alarm mapping User programmable text for custom alarm conditions Ethernet 10/100 Base T RJ45 jack for laptop system programming and network connection Uses category 5 LAN cable and connectors for serial interface with PoE to remote SiteRanger transducer modules NFPA110 compliant Order Information Shipping box packaging for UPS/FedEx shipment. Typical configuration includes bill of materials / parts kit as per customer site survey order form. CSI Provides customer site surveys at no charge to provide customer proposals for the correct SiteRanger component and installation configurations. Doc# 048–600–00/Nov.01.05