ECE 476 POWER SYSTEM ANALYSIS Lecture 3 Three Phase, Power System Operation Professor Tom Overbye Department of Electrical and Computer Engineering Reading and Homework • • For lecture 3 please be reading Chapters 1 and 2 For lectures 4 through 6 please be reading Chapter 4 – • we will not be covering sections 4.7, 4.11, and 4.12 in detail though you should still at least skim those sections. HW 1 is 2.9, 22, 28, 32, 48; due Thursday 9/8 • For Problem 2.32 you need to use the PowerWorld Software. You can download the software and cases at the below link; get version 15. http://www.powerworld.com/gloversarma.asp 1 Three Phase Transmission Line 2 Per Phase Analysis Per phase analysis allows analysis of balanced 3 systems with the same effort as for a single phase system Balanced 3 Theorem: For a balanced 3 system with – – All loads and sources Y connected No mutual Inductance between phases 3 Per Phase Analysis, cont’d Then – – – All neutrals are at the same potential All phases are COMPLETELY decoupled All system values are the same sequence as sources. The sequence order we’ve been using (phase b lags phase a and phase c lags phase a) is known as “positive” sequence; later in the course we’ll discuss negative and zero sequence systems. 4 Per Phase Analysis Procedure To do per phase analysis 1. Convert all load/sources to equivalent Y’s 2. Solve phase “a” independent of the other phases 3. Total system power S = 3 Va Ia* 4. If desired, phase “b” and “c” values can be determined by inspection (i.e., ±120° degree phase shifts) 5. If necessary, go back to original circuit to determine line-line values or internal values. 5 Per Phase Example Assume a 3, Y-connected generator with Van = 10 volts supplies a -connected load with Z = -j through a transmission line with impedance of j0.1 per phase. The load is also connected to a -connected generator with Va”b” = 10 through a second transmission line which also has an impedance of j0.1 per phase. Find 1. The load voltage Va’b’ 2. The total power supplied by each generator, SY and S 6 Per Phase Example, cont’d First convert the delta load and source to equivalent Y values and draw just the "a" phase circuit 7 Per Phase Example, cont’d To solve the circuit, write the KCL equation at a' (Va' 10)(10 j ) Va' (3 j ) (Va' 1 j 3 8 Per Phase Example, cont’d To solve the circuit, write the KCL equation at a' (Va' 10)(10 j ) Va' (3 j ) (Va' 1 j 3 10 (10 j 60) Va' (10 j 3 j 10 j ) 3 Va' 0.9 volts Vb' 0.9 volts Vc' 0.9 volts ' Vab 1.56 volts 9 Per Phase Example, cont’d * ' Va Va Sygen 3Va I a* 3Va 5.1 j 3.5 VA j 0.1 " " Va Sgen 3Va ' * Va 5.1 j 4.7 VA j 0.1 10 Example 2.14 11 Example 2.21 12 Example 2.29 13 Example 2.44 14 Development of Line Models Goals of this section are 1) develop a simple model for transmission lines 2) gain an intuitive feel for how the geometry of the transmission line affects the model parameters 15 Primary Methods for Power Transfer 1) 2) 3) 4) 5) The most common methods for transfer of electric power are Overhead ac Underground ac Overhead dc Underground dc other 16 Magnetics Review Ampere’s circuital law: F H dl I e F = mmf = magnetomtive force (amp-turns) H = magnetic field intensity (amp-turns/meter) dl = Vector differential path length (meters) = Line integral about closed path (dl is tangent to path) Ie = Algebraic sum of current linked by 17 Line Integrals Line integrals are a generalization of traditional integration Integration along the x-axis Integration along a general path, which may be closed Ampere’s law is most useful in cases of symmetry, such as with an infinitely long line 18 Magnetic Flux Density Magnetic fields are usually measured in terms of flux density B = flux density (Tesla [T] or Gauss [G]) (1T = 10,000G) For a linear a linear magnetic material B = H where is the called the permeability = 0 r 0 = permeability of freespace = 4 10-7 H m r = relative permeability 1 for air 19 Magnetic Flux Total flux passing through a surface A is = A B da da = vector with direction normal to the surface If flux density B is uniform and perpendicular to an area A then = BA 20 Magnetic Fields from Single Wire Assume we have an infinitely long wire with current of 1000A. How much magnetic flux passes through a 1 meter square, located between 4 and 5 meters from the wire? Direction of H is given by the “Right-hand” Rule Easiest way to solve the problem is to take advantage of symmetry. For an integration path we’ll choose a circle with a radius of x. 21 Single Line Example, cont’d 2 xH I H B 0 H I 2 x 0 I A 0 H dA 4 dx 2 x 5 I 5 0 ln 2 4 5 2 10 I ln 4 7 4.46 105 Wb For reference, the earth’s 2 104 2 B T Gauss magnetic field is about x x 0.6 Gauss (Central US) 22 Flux linkages and Faraday’s law Flux linkages are defined from Faraday's law d V = where V = voltage, = flux linkages dt The flux linkages tell how much flux is linking an N turn coil: = N i i=1 If all flux links every coil then N 23 Inductance For a linear magnetic system, that is one where B =H we can define the inductance, L, to be the constant relating the current and the flux linkage =Li where L has units of Henrys (H) 24 Inductance Example Calculate the inductance of an N turn coil wound tightly on a torodial iron core that has a radius of R and a cross-sectional area of A. Assume 1) all flux is within the coil 2) all flux links each turn 25 Inductance Example, cont’d Ie H dl NI H 2 R (path length is 2 R) NI H 2 R AB B H r 0 H N LI NI NAB NA r 0 2 R N 2 A r 0 H L 2 R 26 Inductance of a Single Wire To development models of transmission lines, we first need to determine the inductance of a single, infinitely long wire. To do this we need to determine the wire’s total flux linkage, including 1. flux linkages outside of the wire 2. flux linkages within the wire We’ll assume that the current density within the wire is uniform and that the wire has a radius of r. 27 Flux Linkages outside of the wire We'll think of the wire as a single loop closed at infinity. Therefore = since N = 1. The flux linking the wire out to a distance of R from the wire center is A B da length R r 0 I 2 x dx 28 Flux Linkages outside, cont’d A B da length R r 0 I dx 2 x Since length = we'll deal with per unit length values, assumed to be per meter. R r 0 I dx 0 R I ln 2 r 2 x Note, this quantity still goes to infinity as R meter 29 Flux linkages inside of wire Current inside conductor tends to travel on the outside of the conductor due to the skin effect. The pentration of the current into the conductor is approximated using the skin depth = 1 where f is the frequency in Hz f and is the conductivity in mhos/meter. 0.066 m For copper skin depth 0.33 inch at 60HZ. f For derivation we'll assume a uniform current density. 30 Flux linkages inside, cont’d Wire cross section Current enclosed within distance x2 x of center Ie 2 I r Ie Ix Hx 2 x 2 r 2 x r Flux only links part of current inside Ix x 2 dx 2 2 0 2 2 r r r r 0 0 r Ix3 dx I 4 8 r 31 Line Total Flux & Inductance 0 R 0 r Total (per meter) I ln I 2 r 8 0 R r Total (per meter) I ln 2 r 4 0 R r L(per meter) ln 2 r 4 Note, this value still goes to infinity as we integrate R out to infinity 32 Inductance Simplification Inductance expression can be simplified using two exponential identities: a ln(ab)=ln a + ln b ln ln a ln b a ln(e a ) b r 0 R r 0 4 L ln ln R ln r ln e 2 r 4 2 r 4 0 R 0 L ln ln R ln re 2 2 r ' Where r' re r 4 0.78r for r 1 33 Two Conductor Line Inductance Key problem with the previous derivation is we assumed no return path for the current. Now consider the case of two wires, each carrying the same current I, but in opposite directions; assume the wires are separated by distance R. To determine the R inductance of each conductor we integrate as before. However Creates counter- Creates a now we get some clockwise field clockwise fieldfield cancellation 34 Two Conductor Case, cont’d R R Rp Direction of integration Key Point: As we integrate for the left line, at distance 2R from the left line the net flux linked due to the Right line is zero! Use superposition to get total flux linkage. For distance Rp, greater than 2R, from left line left 0 Rp 0 Rp R I ln I ln 2 r ' 2 R Left Current Right Current 35 Two Conductor Inductance Simplifying (with equal and opposite currents) left Lleft 0 Rp Rp R I ln ln 2 r ' R 0 I ln Rp ln r ' ln( Rp R ) ln R 2 0 R Rp I ln ln 2 r ' Rp R 0 R I ln as Rp 2 r ' 0 R ln H/m 2 r ' 36