Division - Name - Date - Language
Introduction
Why RTRC or TFRC?
Limitations of Conventional Solutions
The RTRC and TFRC Solution
Applications
Benefits
Product Characteristics
2
Schneider Electric is the world’s largest LV capacitor manufacturer by market share
Power Quality Correction Group (PQc) located in
Toronto, Canada has marketing, sales, application engineering, design and technical support responsibility for North America
Low Voltage Equipment is manufactured at the
Waterman facility
Medium Voltage Equipment is assembled at
Square D facility outside of Cincinnati
Division - Name - Date - Language 3
Fixed Capacitors
Standard Automatic Capacitor Banks
Anti-Resonant Automatic Capacitor Banks
Filtered Automatic Capacitor Banks
Real Time Reactive Compensation Systems
Transient Free Reactive Compensation
Systems
MV Metal Enclosed Systems
MV Real Time & Transient Free Systems
Division - Name - Date - Language 4
On-site measurement
Computer Network
Simulations
Analysis of Problem
Report
Specifications
Custom Engineered
Equipment
Commissioning
Verification of
Performance
Training
Commission
Specify & Propose
After Sale Servicing
Measure
Solution
Cycle
Analyze & Report
Simulate
Division - Name - Date - Language 5
Division - Name - Date - Language
Ratio of Active (Real) Power to Total
(Apparent) Power (kW/kVA)
A measure of efficiency
Depends on the phase angle between voltage and current waveforms
6
Division - Name - Date - Language
Reactive
Power develops the magnetic field required by machines to perform useful work
7
Before After In this example, demand was reduced to 8 250 kVA from 10 000 kVA.
The power factor was improved from 80% to 97%
Division - Name - Date - Language 8
Apparent Power
2500 KVA
1
2
Real Power
1500 KW
1700 KVA
Reactive Power
2000 kVAR
Uncompensated
Reactive Power
800 kVAR
Compensated cos
cos
1
= .60
2
= .882
Any capacitor based system reduces apparent power (KVA) and load current
Potential savings in capital investment
Alternately, additional load can be added to the network without the risk of overload
Division - Name - Date - Language 9
Division - Name - Date - Language
Current Limiting Reactors in multi-step MV standard systems limit capacitor inrush currents
Air or Iron Core reactors in MV
Anti-Resonant and Filtered systems detune the system to prevent resonance and remove up to 50% of the 5th harmonic
1
0
Division - Name - Date - Language 1
1
The installation of standard capacitors can magnify harmonic currents on the network
Division - Name - Date - Language 1
2
Resonant Point likely to amplify dominant harmonic (typically 5th)
Magnification of Harmonic Current when Standard
Capacitors are Added to the Network
Division - Name - Date - Language 1
3
Resonant Point where no Harmonic Content present ( 3.7th typical)
5th Harmonic on Network is reduced
(4.4 Tuning)
Effect on Harmonic Current when Anti-Resonant Capacitor
Bank is Applied
Division - Name - Date - Language 1
4
To compensate reactive power required by rapid and frequent load variations
• motivation:
– increased productivity
– elimination of voltage flicker and sags
– increased system capacity and energy efficiency
Division - Name - Date - Language 1
5
Compensates reactive energy of stable loads only
Unable to cope with rapid and frequent load variations
Limited Speed - Why?
To reduce wear of vacuum switches
To allow capacitors to discharge before reconnection
Conventional Controller speed limitation
Division - Name - Date - Language 1
6
L1 L2 L3
HRC Fuses
Vacuum
Contactors
Optional
De-tuned
Inductor
Vacuum (or
SF6)contactors or breakers are used to connect a capacitor group.
Division - Name - Date - Language 1
7
Division - Name - Date - Language
One cycle (17 ms) or less response to load fluctuations
Transient Free Connection of
Capacitors
Minimal wear of electronic switching elements
1
8
Division - Name - Date - Language
3-4 second response to load fluctuations
Transient Free Connection of
Capacitors
Minimal wear of electronic switching elements
1
9
L1 L2 L3
Fuses
SCR-Diode
De-tuned
Inductor
Division - Name - Date - Language 2
0
ion ect nn Co th moo - S RC RT
Current inrush with vacuum switching can be 15 - 20 times steady state current
Resultant voltage transient can effect sensitive electronics
RTRC and TFRC systems generate no network voltage transient
Division - Name - Date - Language 2
1
Load Current
V
System Voltage
A
Acquisition Time 17 ms
RTRC Bank Current
B
Division - Name - Date - Language 2
2
Any variation in reactive power is compensated within one cycle (16.7 ms) using transient free switching of capacitor stages resulting in:
• increased productivity
• elimination of voltage flicker & sags
• increased system capacity & energy efficiency
Division - Name - Date - Language 2
3
Unstable Loads (rapid changes):
• Injection molding machines
• Elevators
• Presses
• Rock Crushers
• Wood Chippers
• Mining Conveyors
• Induction Heat Treating
• DC Hoisting
Motor Starting
• compensation of inrush current for many motors
• allows normal starting torque
Spot Welding (typically at low voltage)
extremely fast changes - less than one second (typically at low voltage)
• Re-enforced Mesh for concrete
• Automotive industry
Division - Name - Date - Language 2
4
• Gas Pumping Station in Colorado
• 25 KV Line to 2.5
MVA Transformer step down to 2.4 KV
• Three FVNR Motors
(500 HP, 700 HP, 700
HP)
• Motor start causing unacceptable voltage drop on 25 KV line (16-
18%)
Division - Name - Date - Language 2
5
• Solution was a 3.6
MVAR, 2.4 KV Real
Time System
• Three equal steps of
1.2 MVAR each
• Utilized air cooled
SCR/Diode modules
• Installed outdoors
• Goal to obtain less than 5% voltage drop on the 25 KV line
Division - Name - Date - Language 2
6
500 HP & 700 HP
Running
Starting 2nd 700 HP
Motor
Division - Name - Date - Language 2
7
Objective to limit voltage drop to less than 5% on the
25 KV line has been met
• initial voltage drop is only 4.2% on the 2.4 KV line
• secondary voltage drop of 7.3% at 2.4 KV line (as stages turn off)
– modifications to the control will improve this further
Motors previously took 4-6 seconds to come up to speed
• with RTRC, motors are up to speed in less than 2 seconds
Division - Name - Date - Language 2
8
Sensitive Networks
Hospitals
Data Processing Centers
Microelectronics Fab Facilities
Pharmaceutical Facilities
Airports
Research laboratories
Other Industrial and commercial facilities with high concentrations of sensitive electronic loads
Division - Name - Date - Language 2
9
Zs = |Zs| +90
0
V
L
V
I
TOTAL I
C
I
LOAD V
V
With V
S
~ RTRC
CAP
LOAD
With Without
• Voltage sag is reduced as a result of reactive compensation during the load fluctuation.
• The voltage sag during is affected more by the power factor than by current amplitude reduction.
Division - Name - Date - Language 3
0
Energy saving due to reduction of losses and harmonics:
Losses in cables:
• Copper losses - I 2 R.
• Skin effect losses due to reduction of harmonics.
Losses in transformers:
• Copper losses - I 2 R.
• Skin effect losses due to reduction of harmonics.
• Iron losses due to reduction of harmonics.
Total estimated saving: 3 - 5%
Division - Name - Date - Language 3
1
RTRC Advantages
Flicker Reduction
Compliance with flicker standards
Network Stabilization and reduced equipment outages
Voltage Regulation Improvement
Reduced duty on tap changers
Improved Network Utilization
Reduced Transformer loading
Current reduction on Bus Bars, Breakers and Cables
Energy Saving, Power Factor Correction &
Harmonic Reduction
Division - Name - Date - Language 3
2
The RTRC will eliminate:
failed motor starts due to voltage sags
undervoltage tripping of sensitive loads
lighting flicker and HID lighting shutdown
overloaded distribution equipment
capacitor switching transients
Division - Name - Date - Language 3
3
ADVANTAGES
• Increases network capacity
• Minimizes voltage sags
• Minimizes voltage flicker
• Reduces load current
• Avoids wear of vacuum contactors & capacitors
• Transient free switching in sensitive networks
• Avoids use of reduced voltage starters
• Saves energy and improves
Power Factor
DISADVANTAGES
• Costly solution compared to standard capacitor systems (but often the only viable solution)
• Physical space requirements
Division - Name - Date - Language 3
4
Metal Enclosed Systems up to
15 kV
Three-Bushing, delta capacitor units available up to 5 kV. Twobushing capacitors connected in
Delta for higher voltages
Type 1 indoor or Type 3R outdoor enclosure types.
Division - Name - Date - Language 3
5
Transient Free Reactive Compensation
Systems
MT6000 Series
Power Factor Correction of networks with sensitive electronic loads
Real Time Reactive Compensation Systems
MV9000 Series
Power Factor Correction of highly cyclical loads
Division - Name - Date - Language 3
6
MT6000 & MV9000 are typically Antiresonant or filtered but may also be standard with current limiting reactors only
Filtered used for Power Factor Correction of networks with more than 50% Non-Linear
Loads
Anti-resonant and filtered systems are manufactured with higher than nominal voltage capacitor elements to ensure long term system stability.
Division - Name - Date - Language 3
7
Status Indicators
Readings Display
Function Keys Description
Function Keys
Division - Name - Date - Language
3
8
Unbalance and Overload protection via phase current sensing standard for either wye or delta capacitor steps
Optional unbalance protection by neutral current sensing on wye connected capacitor steps
Optional Neutral to Ground Potential transformer for unbalance protection for wye connected banks
Division - Name - Date - Language 3
9
Division - Name - Date - Language
Merlin Gerin PROPIVAR or
Cooper (McGraw Edison)
External Fusing Standard
4
0
Division - Name - Date - Language
Available as
Three Phase,
Three-Bushing
Delta Connected, up to 5 kV or
Single Phase,
Two-Bushing for voltages higher than 5 kV
4
1
Division - Name - Date - Language
Environmentally safe biodegradable non PCB dielectric liquid
Good Heat Dissipation and Low dielectric losses result in long element life
4
2
Division - Name - Date - Language
High Overvoltage and
Overcurrent withstand:
• 10% Overvoltage for 12 hours a day
• 30% Continuous Overcurrent
Highly resistant to transient overvoltages and partial discharge levels
4
3
Division - Name - Date - Language
Suitable for harmonic filtering applications and networks with poor voltage regulation
4
4
Division - Name - Date - Language
Single Phase, Two-Bushing for
Wye or Delta connection
125% Continuous rms
Overvoltage withstand and 135% peak overvoltage capability
Wide operating temperature range:
• 40 to 131ºF (-40 to 55ºC)
Environmentally acceptable dielectric fluid
4
5
Division - Name - Date - Language
Standard unit power rating from
50 to 400 kVAR single phase from 2.4kV
4
6
Division - Name - Date - Language
To protect capacitors, fuses are rated as closely as possible to the capacitor steady state current
Blown fuse indication directly on the fuse (pop-up indicators)
Visible via viewing windows in enclosure
4
7
Three
Phase
Reactor
Capacitors
Current
Transformers for unbalance detection
Vacuum
Contactor
Division - Name - Date - Language 4
8
Switching two phases with
Delta connected capacitors
Air or Liquid Cooled Stick
Stacks of anti-polar SCR/Diodes with failsafe cooling systems
• temperature, air flow, pressure monitoring
Multiple modules connected in series for higher voltages
Liquid Cooled Stick Stack
Division - Name - Date - Language 4
9
Division - Name - Date - Language
Direct Drive Operator
Fused for short circuit protection or Unfused available
Load Break to max
2400 kVAR @ 5 kV or
15 kV
5
0
Division - Name - Date - Language
Necessary to Detune network to prevent resonance when large harmonic producing loads are present
Reactors Filter dominant harmonic (usually the 5th)
5
1
Division - Name - Date - Language
Single or Three phase laminated low hysteresis reactors with precision air gap
All copper windings, mounted on insulated bushings up to 95 kV
BIL
Current Limiting Reactors in standard systems are Air or Iron
Core
5
2
Division - Name - Date - Language
Modular Style Design either indoor NEMA 1 or outdoor NEMA
3R (others available)
All Silver-Flashed Copper Bus
• Better fault withstand ratings
(50kA IC standard)
5
3
Division - Name - Date - Language
Removable Panels over bolted steel frame
• Rigid construction while allowing ease of servicing
Standard ASA49 Gray paint finish. Other finishes available upon request.
5
4
Division - Name - Date - Language
Key interlocks standard
• Electrical interlocks standard
Tamper resistant interlocked ground switch for each capacitor stage
Viewing windows to ensure ground switch and main switch operation
5
5
Division - Name - Date - Language
Control Cabinet mounted rear or side of main (remote mounting optional)
Optional thermostatically controlled, ball bearing fans
Welded lifting eyes
Three point door latch
5
6
Schneider Electric
Power Quality Correction Group
255 Orenda Road
Bramalea, Ontario, L6T 1E6 www.reactivar.com
Tel.: (905) 459-8805
Fax: (905) 454-3603
Division - Name - Date - Language
Division - Na me - Da te - Lan gua ge
Schneider Electric Can ada Inc.
19 Waterman Avenue
Toronto, Ontario, M4B 1Y2 www.schneider-electric.ca
Tel.: (416) 752-8020
Fax: (416) 752-6230
© 2001 Schneider Electric Can ada, All Rights Reserved June, 2001 5
7
20