10.7 MEASURES TO MINIMIZE DAMAGES DUE TO FIRE INCIDENTS OF POWER TRANSFORMER Power transformers, being an important and costly equipment of grid system network must be given priority attention for their safe and reliable operation. During normal and abnormal service of a power transformer, the chances of its damage or failure (silent failure or damage with fire out-breakage as it contains bulk quantity of inflammable oil) cannot be eliminated due to its construction design and operation characteristics. As per the local and the worldwide experiences of transformer engineering, the possible causes of transformer failure are summarized as under for awareness of the all concerned. Sr. Causes of No. Failure 1 Environment related 2 System related 3 4 5 6 7 Description & Analysis of Causes Hurricane, Earthquake, Lightning, Magnetic Storms, Site conditions, etc. Over-voltages, Switching operations, Fast front transients, Ferro resonance, Load rejection, Back-feeding, Shortcircuits, etc. Operation related Load duty, Overloading, Switching operations, Out-of-phase synchronization, etc. Design related Electrical stresses, Mechanical forces, Transient voltage distribution, Magnetizing flux, Leakage flux, Circulating currents, Lead disposition, Cooling arrangements, etc. Manufacturing Drying, Processing, Jointing, Connections, Assembly, etc. related Materials related Bushings, OLTC, Core steel, Non-magnetic steel, Conductors, Insulation, Insulating oil, etc Maintenance OLTC, Insulating oil, Oil preservation system, Paintwork, related Water contamination, Particle contamination, etc. Note. Transformers handling experience reveals that the most possible location and component parts of the transformer subjected to failure or damage are magnetic core, windings, leads, OLTC, bushings and tank. 1 10.8 CRITERIA OF RE-SWITCHING OF THE TRANSFORMERS AFTER THEIR OUTAGE During routine functioning of the power system, the transformers are expected to be disconnected forcedly from the system due to several abnormal conditions within the transformer or in the connected network. The criteria to re-switch the transformer in this situation are given below: - Cases allowing re-switching of the transformer without testing after its outage; a. Due to operation of over current relays with simultaneous operation of over current relay of the associated feeders. b. Due to overloading which resulted from excessive winding temperature (take care of excessive winding temperature in routine). c. Due to air accumulated in the Buchholz relay (non-combustible gases) Note. In any case as above, visual inspection of the transformer and the surrounding equipment and area to look for any abnormality must be carried out before reswitching. On the operation of any other protection relays, perform the prescribed tests to look for the cause. - Cases not allowing in re-switching of the transformer without routine and detailed diagnostic testing after its outage; a. Due to operation of differential protection relays (HV, LV, Tertiary windings). b. Due to operation of Buchholz relays with combustible gases accumulation. c. Due to operation of pressure relief devices, with or without gushing out of oil from the transformer. Note. In any case as above, visual inspection of the transformer and the surrounding equipment and area to look for any abnormality must be carried out in addition to the prescribed testing and before re-switching. Recommended routine and diagnostic tests - Windings continuity check - Insulation Resistance Test (Megger Test) 2 - T.T.R Test Oil DES Test Checking of Buchholz relay and OLTC protective relay Winding Resistance Test Short Circuit Test Open Circuit Test C&DF Test of windings and bushings DGA (Dissolved Gasses-in-oil Analysis) of oil OLTC operation - Fire detection and fire extinguishing arrangements The following fire detection and fire extinguishing techniques/arrangements are recommended for an effective fire control for electrical installations: - Fire detection and water spray system for external fire hazards. - Nitrogen gas injection explosion and fire prevention system for internal fire hazards - Measures to be taken to minimize the extent of damages if the fire out-breaks The following measures are to be taken to minimize the extent of damages to the transformer itself and the surrounding equipment in case of fire out-breakage in the transformer: - De-energize and isolate the affected transformer from the external system (HV & LV sides). - De-energize and isolate the surrounding transformers and the other equipment from the external system. - Inform fire brigade unit/Rescue service of the local area and start fire fighting with the local resources and continue efforts till the arrival of fire brigade units. - Clear the surrounding area of the affected transformer from the fire supporting items i.e. oil, wood, etc. Note. Provision of fire protection walls/partitioning walls between the transformers and oil catchments/sump below the transformers is the effective measures to control spreading of fire. 3 11. GENERAL APPLICATIONS 11.1 DEVICE FUNCTION NUMBERING Definition and Function Device Device Name Definition and Function Number Master Element is the initiating device, such as a control switch, 1 voltage relay, float switch, etc., which serves either directly, or through such permissive devices as protective and time-delay relays to place an equipment in or out of operation. Time-delay Starting, or Closing, Relay is a device, which 2 functions to give a desired amount of time delay before or after any point or operation in a switching sequence or protective relay system, except as specifically provided by device functions 62 and 79 described later. Checking or Interlocking Relay is a device which operates in 3 response to the position of a number of other devices, or to a number of predetermined conditions in an equipment to allow an operating sequence to proceed, to stop, or to provide a check of the position of these devices or of these conditions for any purpose. Master Contactor is a device, generally controlled by device No.1 or 4 equivalent, and the necessary permissive and protective devices, which serves to make and break the necessary control circuits to place an equipment into operation under the desired conditions and to take it out of operation under other or abnormal conditions. Stopping Device functions to place and hold an equipment out of 5 operation. Starting Circuit Breaker is a device whose principal function is to 6 connect a machine to its source of starting voltage. Anode Circuit Breaker is one used in the anode circuits of a power 7 rectifier for the primary purpose of interrupting the rectifier circuit if an arc back should occur. Control Power Disconnecting Device is a disconnecting device-such 8 as a knife switch, circuit breaker or pullout fuse block-used for the purpose of connecting and disconnecting, respectively, the source of control power to and from the control bus or equipment. Note: Control power is considered to include auxiliary power 4 9 10 11 12 13 14 15 16 17 18 19 20 21 which supplies such apparatus as small motors and heaters. Reversing Device is used for the purpose of reversing a machine field or for performing any other reversing functions. Unit Sequence Switch is used to change the sequence in which units may be placed in and out of service in multiple-unit equipments. Reserved for future application. Over-Speed Device is usually a direct-connected speed switch which functions on machine over speed. Synchronous-Speed Device, such as a centrifugal-speed switch, a slipfrequency relay, a voltage relay, an undercurrent relay or any type of device, operates at approximately synchronous speed of a machine. Under-Speed Device functions when the speed of a machine falls below a predetermined value. Speed or Frequency, Matching Device functions to match and hold the speed or the frequency of a machine or of a system equal to, or approximately equal to, that of another machine, source or system. Reserved for future application. Shunting, or Discharge, Switch serves to open or to close a shunting circuit around any piece of apparatus (except a resistor), such as a machine field, a machine armature, a capacitor or a reactor. Note: This excludes devices which perform such shunting operations as may be necessary in the process of starting a machine by devices 6 or 42, or their equivalent, and also excludes device 73 function which serves for the switching of resistors. Accelerating or Decelerating Device is used to close or to cause the closing of circuits which are used to increase or to decrease the speed of a machine. Starting-to-Running Transition Contactor is a device which operates to initiate or cause the automatic transfer of a machine from the starting to the running power connection. Electrically Operated Valve is a solenoid- or motor-operated valve which is used in a vacuum, air, gas, oil, water, or similar, lines. Note: The function of the valve may be indicated by the insertion of descriptive words such as "Brake" or "Pressure Reducing" in the function name, such as "Electrically Operated Broke Valve". Distance Relay is a device which functions when the circuit admittance, impedance or reactance increases or decreases beyond predetermined limits. 5 22 23 24 25 26 27 28 29 30 31 32 33 Equalizer Circuit Breaker is a breaker which serves to control or to make and break the equalizer or the current-balancing connections for a machine field, or for regulating equipment, in a multiple-unit installation. Temperature Control Device functions to raise or to lower the temperature of a machine or other apparatus, or of any medium, when its temperature falls below, or rises above, a predetermined value. Note: An example is a thermostat which switches on a space heater in a switchgear assembly when the temperature falls to a desired value as distinguished from a device which is used to provide automatic temperature regulation between close limits and would be designated as 90T. Reserved for future application. Synchronizing, or Synchronism-check, device operates when two a-c circuits are within the desired limits of frequency, phase angle or voltage, to permit or to cause the paralleling of these two circuits. Apparatus Thermal Device functions when the temperature of the shunt field or Under-voltage Relay is a device which functions on a given value of under voltage. Reserved for future application. Isolating Contactor is used expressly for disconnecting one circuit from another for the purposes of emergency operation, maintenance, or test. Annunciator Relay is a non automatically reset device which gives a number of separate visual indications upon the functioning of protective devices, and which may also be arranged to perform a lockout function. Separate Excitation Device connects a circuit such as the shunt field of a synchronous converter to a source of separate excitation during the Starting sequence; or one which energizes the excitation and ignition circuits of a power rectifier. Directional Power Relay is one when function on a desired value of power flow in a given direction, or upon reverse power resulting from arc back in the anode or cathode circuits of a power rectifier. Position Switch makes or breaks contact when the main device or piece of apparatus, which has no device function number, reaches a given position. apparatus, which has no device function number, 6 34 35 36 37 38 39 40 41 42 43 44 45 46 47 reaches a given position. Motor-Operated Sequence Switch is a multi-contact switch which fixes the operating sequence of the major devices during starting and stopping, or during other sequential switching operations. Brush-Operating, or Slip-Ring Short-Circuiting, Device is used for raising, lowering, or shifting the brushes of a machine, or for shortcircuiting its slip rings, or for engaging or disengaging the contacts of a mechanical rectifier. Polarity device operates or permits the operation of another device on a predetermined polarity only. Under-current or Under-power Relay is a device which functions when the current or power flow decreases below a predetermined value. Bearing Protective Device is one which functions on excessive bearing temperature, or on other abnormal mechanical conditions, such as undue wear, which may eventually result in excessive bearing temperature. Reserved for future application. Field Relay is a device that functions on a given or abnormally low value or failure of machine field current, or on an excessive value of the reactive component of armature current in an AC machine indicating abnormally low field excitation. Field Circuit Breaker is a device which functions to apply, or to remove, the field excitation of a machine. Running Circuit Breaker is a device whose principal function is to connect a machine to its source of running voltage after having been brought up to the desired speed on the starting connection. Manual Transfer or Selector Device transfers the control circuits so as to modify the plan of operation of the switching equipment or of some of the devices. Unit Sequence Starting Relay is a device which functions to start the next available unit in a multiple-unit equipment on the failure or on the non-availability of the normally preceding unit. Reserved for future application. Reverse-Phase, or Phase-Balance, Current Relay is a device which functions when the poly-phase currents are of reverse-phase sequence, or when the poly-phase currents are unbalanced or contain negative phasesequence components above a given amount, Phase-Sequence Voltage Relay is a device which functions upon a 7 1-9 48 49 50 51 52 53 54 55 56 57 58 59 predetermined value of poly-phase voltage in the desired phase sequence. Incomplete Sequence Relay is a device which returns the equipment to the normal, or off, position and locks it out if the normal starting, operating or stopping sequence is not properly completed within a predetermined time. Machine, or Transformer, Thermal Relay is a device which functions when the temperature of an a-c machine armature, or of the armature or other load carrying winding or element of a d-c machine, or converter or power rectifier or power transformer (including a power rectifier transformer) exceeds a predetermined value. Instantaneous Over-current or Rate-of-Rise Relay is a device which functions instantaneously on an excessive value of current, or on an excessive rate of current rise, thus indicating a fault in the apparatus or circuit being protected. AC Time Over-current Relay is a device with either a definite or inverse time characteristic which functions when the current in an a-c circuit exceeds a predetermined value. AC Circuit Breaker is a device which is used to close and interrupt an a-c power circuit under normal conditions or to interrupt this circuit under fault or emergency conditions. Exciter or D-C Generator Relay is a device which forces the d-c machine field excitation to build up during starting or which functions when the machine voltage has built up to a given value. High-Speed D-C Circuit Breaker is a circuit breaker which starts to reduce the current in the main circuit in 0.01 second or less, after the occurrence of the DC over-current or the excessive rate of current rise. Power Factor Relay is a device which operates when the power factor in an AC circuit becomes above or below a predetermined value. Field Application Relay is a device which automatically controls the application of the field excitation to an a-c motor at some predetermined point in the slip cycle. Short-Circuiting or Grounding Device is a power or stored energy operated device which functions to short-circuit or to ground a circuit in response to automatic or manual means. Power Rectifier Misfire Relay is a device which functions if one or more of the power rectifier anodes fail to fire. Overvoltage Relay is a device which functions on a given value of 8 60 61 62 63 64 65 66 67 68 69 overvoltage. Voltage Balance Relay is a device which operates on a given difference in voltage between two circuits. Current Balance Relay is a device which operates on a given difference in current input or output of two circuits. Time-Delay Stopping, or Opening, Relay is a time-delay device which serves in conjunction with the device which initiates the shutdown, -stopping, or opening operation in an automatic sequence. Liquid or Gas Pressure, Level, or Flow Relay is a device which operates on given values of liquid or gas pressure, flow or level, or on a given rate of change of these values. Buchholz relay, etc. Ground Protective Relay is a device which functions on failure of the insulation of a machine, transformer or of other apparatus to ground, or on flashover of a d-c machine to ground. Note: This function is assigned only to a relay which detects the flow of current from the frame of a machine or enclosing case or structure of a piece of apparatus to ground, or detects a ground on a normally ungrounded winding or circuit. It is not applied to a device connected in the secondary circuit or secondary neutral of a current transformer, or current transformers, connected in the power circuit of a normally grounded system. Governor is the equipment which controls the gate or valve opening of a prime mover. Notching, or Jogging, Device functions to allow only a specified number of operations of a given device, or equipment, or a specified number of successive operations within a given time of each other. It also functions to energize a circuit periodically,, or which is used to permit intermittent acceleration or jogging of a machine at low speeds for mechanical positioning. AC Directional Over-current Relay is a device which functions on a desired value of AC over-current flowing in a predetermined direction. Blocking Relay is a device which initiates a pilot signal for blocking of tripping on external faults in a transmission line or in other apparatus under predetermined conditions, or co-operates with other devices to block tripping or to block reclosing on an out-of-step condition or on power swings. Permissive Control Device is generally a two-position, manually operated switch which in one position permits the closing of a circuit 9 70 71 72 73 74 75 76 77 78 79 80 81 82 83 breaker, or the placing of an equipment into operation, and in the other position prevents the circuit breaker or the equipment from being operated. Electrically Operated Rheostat is a rheostat which is used to vary the resistance of a circuit in response to some means of electrical control. Reserved for future application. DC Circuit Breaker is used to close and interrupt a d-c power circuit under normal conditions or to interrupt this circuit under fault or emergency conditions. Load-Resistor Contactor is used to shunt or insert a step of load limiting, shifting, or indicating resistance in a power circuit, or to switch a space heater in circuit, or to switch a light, or regenerative, load resistor of a power rectifier or other machine in and out of circuit. Alarm Relay is a device other than an annunciator, as covered under device No. 30, which is used to operate, or to operate in connection with, a visual or audible alarm. Position Changing Mechanism is the mechanism which is used for moving a removable circuit breaker unit to and from the connected, disconnected, and test positions. DC Over-current Relay is a device which functions when the current in a d-c circuit exceeds a given value. Pulse Transmitter is used to generate and transmit pulses over a telemetering or pilot-wire circuit to the remote indicating or receiving device. Phase Angle Measuring, or Out-of-Step Protective Relay is a device which functions at a predetermined phase angle between two voltages or between two currents or between voltage and current. AC Reclosing Relay is a device which controls the automatic reclosing and' locking out of an a-c circuit interrupter. Reserved for future application. Frequency Relay is a device which functions on a predetermined value of frequency-either under or over or on normal system frequency-or rate of change of frequency. DC Reclosing Relay is a device which controls the automatic closing and reclosing of a d-c circuit interrupter, generally in response to load circuit conditions. Automatic Selective Control, or Transfer, Relay is a device which operates to elect automatically between certain sources or conditions in an equipment or performs a transfer operation automatically. 10 84 85 86 87 88 89 90 91 92 93 94 Operating Mechanism is the complete electrical mechanism or servomechanism, including the operating motor, solenoids, position switches, etc., for a tap changer, induction regulator or any piece of apparatus which has no device function number Carrier, or Pilot-Wire, Receiver Relay is a device which is operated or restrained by a signal used in connection with carrier-current or d-c pilot-wire fault directional relaying. Locking-out Relay is an electrically operated hand or electrically reset device which functions to shut down and hold an equipment out of service on the occurrence of abnormal conditions. Differential Protective Relay is a protective device which functions on a percentage of-phase angle or other quantitative difference of two currents or of some other electrical quantities. Auxiliary Motor, or Motor Generator is one used for operating auxiliary equipment such as pumps, blowers, exciters, rotating magnetic amplifiers, etc. line switch is used as a disconnecting or isolating switch in an a-c or d-c power circuit, when this device is electrically operated or has electrical accessories, such as an auxiliary switch, magnetic lock, etc. Regulating Device functions to regulate a quantity, , or quantities, such as voltage, current, power, speed, frequency, temperature, and load, at a certain value or between certain limits for machines, tie lines or other apparatus. Voltage Directional Relay is a device which operates when the voltage across an open circuit breaker or contactor exceeds a given value in a given direction. Voltage and Power Directional Relay is a device which permits or causes the connection of two circuits when the voltage difference between them exceeds a given value in a predetermined direction and causes these two circuits to be disconnected from each other when t h e p o w e r t h e m exceeds a given value in the opposite direction. Field Changing Contactor functions to increase or decrease in one step the value of field excitation on a machine. Tripping, or Trip-Free, Relay is a device which functions to trip a circuit breaker, contactor, or equipment, or to permit immediate tripping by other devices; or to prevent immediate reclosure of a circuit interrupter, in case it should open automatically even though its closing circuit is maintained closed. 11 95 96 97 98 99 Note Used only for specific applications on individual installations where none of the assigned numbered functions from 1 to 94 is suitable. Used only for specific applications on individual installations where none of the assigned numbered functions from 1 to 94 is suitable. Used only for specific applications on individual installations where none of the assigned numbered functions from 1 to 94 is suitable. Used only for specific applications on individual installations where none of the assigned numbered functions from 1 to 94 is suitable. Used only for specific applications on individual installations where none of the assigned numbered functions from 1 to 94 is suitable. Note: A similar series of numbers, starting with 201 instead of 1, shall be used for those device functions in a machine, feeder or other equipment when these are controlled directly from the supervisory system. Typical examples of such device functions are 201, 205, and 294. 12 11.2 TRANSFORMER’S IMPORTANT DEFINITIONS Power transformer A static piece of apparatus with two or more windings which, by electromagnetic induction, transforms a system of alternating voltage and current into another system of voltage and current usually of different values and at the same frequency for the purpose of transmitting electrical power. Auto-transformer A transformer in which at least two windings have a common part. Note. Where there is a need to express that a transformer is not auto-connected, use is made of terms such as separate winding transformer, or double-wound transformer. Booster transformer A transformer of which one winding is intended to be connected in series with a circuit in order to alter its voltage and/or shift its phase. The other winding is an energizing winding. Oil-immersed type transformer A transformer of which the magnetic circuit and windings are immersed in oil. Note. For the purpose of this part any insulating liquid, mineral oil or other product, is regarded as oil. Dry-type transformer A transformer of which the magnetic circuit and windings are not immersed in an insulating liquid. Oil preservation system The system in an oil-immersed transformer by which the thermal expansion of the oil is accommodated. Contact between the oil and external air may sometimes be diminished or prevented. Terminal A conducting element intended for connecting a winding to external conductors. Line terminal A terminal intended for connection to a line conductor of a network. Neutral terminal a) For three-phase transformers and three-phase banks of single-phase transformers: The terminal or terminals connected to the common point (the neutral point) of a starconnected or zigzag connected winding. b) For single-phase transformers: The terminal intended for connection to a neutral point of a network. Neutral point The point of a symmetrical system of voltages which is normally at zero potential. Corresponding terminals 13 Terminals of different windings of a transformer, marked with the same letter or corresponding symbol. Winding The assembly of turns forming an electrical circuit associated with one of the voltages assigned to the transformer. Note. For a three-phase transformer, the 'winding' is the combination of the phase windings (see phase winding). Tapped winding A winding in which the effective number of turns can be changed in steps. Phase winding The assembly of turns forming one phase of a three-phase winding. Note. The term 'phase winding' should not be used for identifying the assembly of all coils on a specific leg. High-voltage winding The winding having the highest rated voltage. Low-voltage winding The winding having the lowest rated voltage. Note. For a booster transformer, the winding having the lower rated voltage may be that having the higher insulation level. Intermediate-voltage winding A winding of a multi-winding transformer having a rated voltage intermediate between the highest and lowest winding rated voltages. Auxiliary winding A winding intended only for a small load compared with the rated power of the transformer. Stabilizing winding A supplementary delta-connected winding provided in a star-star-connected or starzigzag-connected transformer to decrease its zero-sequence impedance (see also tertiary winding). Note. A winding is referred to as a stabilizing winding only if it is not intended for three-phase connection to an external circuit. Common winding The common part of the windings of an auto-transformer. Primary winding The winding which receives active power from the supply source in service is referred to as a primary winding. Secondary winding The winding which delivers active power to a load is referred to as a secondary winding. 14 Note. These terms have no significance as to which of the windings has the higher rated voltage and should not be used except in the context of direction of active power flow. Tertiary winding A further winding in the transformer, usually with lower value of rated power than the secondary winding, is then often referred to as tertiary winding (see also stabilizing winding). Series winding The part of the winding of an auto-transformer or the winding of a booster transformer which is intended to be connected in series with a circuit. Energizing winding The winding of a booster transformer which is intended to supply power to the series winding. Rating Those numerical values assigned to the quantities which define the operation of the transformer in the conditions specified and on which the manufacturer's guarantees and the tests are based. Rated quantities Quantities (voltage, current, etc.), the numerical values of which define the rating. Note 1. For transformers having tappings, rated quantities are related to the principal tapping, unless otherwise specified. Corresponding quantities with analogous meaning, related to other specific tappings, are called tapping quantities. Note 2. Voltages and currents are always expressed by their r.m.s. values, unless otherwise specified. Rated voltage of a winding (Ur) The voltage assigned to be applied, or developed at no-load, between the terminals of an untapped winding, or of a tapped winding connected on the principal tapping. For a three-phase winding it is the voltage between line terminals. Note.1. The rated voltages of all windings appear simultaneously at no-load when the voltage applied to one of them has its rated value. Note.2. For single-phase transformers intended to be connected in star to form a threephase bank, the rated voltage is indicated as phase-to-phase voltage, divided by √3 for example Ur = 500/√3 kV. Note.3. For the series winding of a three-phase booster transformer which is designed as an open winding the rated voltage is indicated as if the winding were connected in star, for example Ur =23/√3 kV. Rated voltage ratio The ratio of the rated voltage of a winding to the rated voltage of another winding associated with a lower or equal rated voltage. Rated frequency (fr) 15 The frequency at which the transformer is designed to operate. Rated power (Sr) A conventional value of apparent power assigned to a winding which, together with the rated voltage of the winding, determines its rated current. Note.1. Both windings of a two-winding transformer have the same rated power which by definition is the rated power of the whole transformer. Note.2. For a multi-winding transformer, half the arithmetic sum of the rated power values of all windings (separate windings, not auto-connected) gives a rough estimate of its physical size as compared with a two-winding transformer. Rated current (Ir) The current flowing through a line terminal of a winding which is derived from rated power Sr and rated voltage Ur for the winding. Tapping In a transformer having a tapped winding, a specific connection of that winding, representing a definite effective number of turns in the tapped winding and, consequently, a definite turns ratio between this winding and any other winding with fixed number of turns. Note. One of the tapping is the principal tapping, and other tapping are described in relation to the principal tapping by their respective tapping factors. Tapping factor (corresponding to a given tapping) The ratio: Ud Ud (tapping factor) or x100 (% tapping factor) Ur Ur where Ur is the rated voltage of the winding ; Ud is the voltage which would be developed at no-load at the terminals of the winding, at the tapping concerned, by applying rated voltage to an untapped winding. Note. This definition is not appropriate in relation to a series winding of a booster transformer, and in that case the percentage notation would be referred to the voltage of the energizing winding or of the winding of an associated system transformer. Principal tapping The tapping to which the rated quantities are related. Plus tapping A tapping whose tapping factor is higher than 1. Minus tapping A tapping whose tapping factor is lower than 1. 16 Tapping step The difference between the tapping factors, expressed as a percentage, of two adjacent tapping. Tapping duty The numerical values assigned to the quantities, analogous to rated quantities, which refer to tapping other than the principal tapping. On load tap changer (OLTC) A device for changing the tapping connections of a winding suitable for operation whilst the transformer is energized or on load. Generally it consists of a diverter switch with a transition impedance and a tap selector which can be with or without a change-over selector, the whole being operated by the driving mechanism. In some form of on load tap changers, the functions of diverter switch and the tap selector are combined on a selector switch. Tap selector A device designed to carry, but not to make or break, current, used in conjunction with a diverter switch, to select tapping connections. Diverter switch A switching device used in conjunction with a tap selector to carry, make and break currents in circuits which have already been selected. Note. Diverter switches of spring-operated type include an independent means of storing energy for their operation. Selector switch A switching device capable of making, carrying and breaking currents, combining the duties of a tap selector and a diverter switch. Change-over selector A device designed to carry, but not to make or break, current, used in conjunction with a tap selector or selector switch to enable its contacts, and the connected tappings, to be used more than once when moving from one extreme position to another. Coarse change-over selector A change-over selector connecting the tapped winding to either the coarse winding or the main winding. Reversing change-over selector A change-over selector connecting one or other end of the tapped winding to the main winding. Transition impedance A resister or reactor consisting of one or more units, bridging the tappings in use and tapping next to be used, for the purpose of transferring load from one tapping to the other without interruption or appreciable change in the load current, at the same time limiting the circulating current for the period that both tappings are used. Driving mechanism 17 The means by which the drive of the on load tap changer is actuated. NOTE. The mechanism may include an independent means of storing energy to control the operation. Set of contacts A pair of individual fixed and moving contacts or a combination of such pairs operating substantially simultaneously. Main contacts (diverter switch and selector switch) A set of through-current carrying contacts which has no transition impedance between the transformer winding and the contacts and does not switch any current. Main switching contacts (diverter switch and selector switch) A set of contacts which has no transition impedance between the transformer winding and the contacts and makes and breaks current. Transition contacts A set of contacts which is connected in series with a transition impedance and makes and breaks current. NOTE. In the case of reactor transition on load tap changers, this set of contacts is used, in many instances, to carry the through-current in the full tap position. Circulating current The part of the current which flows through the transition impedance at the time when two tapping are bridged during a tap change operation and which due to the voltage difference between the tapping. Switched current The prospective current to be broken during switching operation by each set of main switching or transition contacts incorporated in the diverter switch or selector switch. Recovery voltage The power-frequency voltage which appears across each set of main switching pr transition contacts of the diverter switch or selector switch after these contacts have broken the switched current. Tap-change operation A complete sequence of events from the initiation to the completion of the transition of the through-current from one tap of the winding to an adjacent one. Cycle of operation The movement of tap-changer from one end of its range to the other and the return to its original position. Insulation level The withstand values of the impulse and the power-frequency test voltages to earth and where appropriate between the phases, and between those parts where insulation is required. Rated through-current (IU) 18 The current flowing through the tap-changer towards the external circuit, which the apparatus is capable of transferring from one tapping to the other at the relevant rated step voltage and which can be carried continuously while meeting the requirements of this standard. Note. See relationship between a rated through-current and the step voltage. Maximum rated through-current (Ium) The rated through-current for which both the temperature rise of the contacts and the service test apply. Rated step voltage (Ui) For each value of rated through-current, the highest permissible voltage between terminals which are intended to be connected to successive tappings of a transformer. Note. If a rated step voltage is given in connection with a rated through-current, it is called "relevant rated step voltage". Maximum rated step voltage (Uim) The highest value of rated step voltage for which the tap-changer is designed. Rated frequency The frequency of the alternating current for which the tap changer is designed. Number of inherent tapping positions The highest number of tapping positions for half a cycle of operation for which a tapchanger can be used according to its design. Number of service tap-positions The number of tapping positions for half a cycle of operation for which a tap-changer is used in a transformer. NOTE. 1 These terms are generally given as the ± values of the relevant numbers, e.g. ±11 positions; they are in principle valid also for the motor-drive mechanism. When using the term "number of tapping positions" in connection with a transformer, this always refers to the number of service tapping positions of the tap-changer. Type test A test made on a tap-changer or the components of a tap-changer, or a range of tapchangers or components all based on the same design, to prove compliance with the standard. NOTE. A range of tap-changers is a number of tap-changers based on the same design and having the same characteristics, with the exception of the insulation levels to earth and possibly between phases, the number of steps and the value of the transition impedances. Routine tests A test made on each completed tap-changer, the design of which has been verified by type test, to establish that the tap-changer is without manufacturing defects. Motor-drive mechanism A driving mechanism which incorporates an electric motor and control circuit. 19 Step-by-step control Electrical and mechanical devices stopping the motor-drive mechanism after completion of a tap-change, independently of the operating sequence of the control switch. Tap position indicator An electrical and/or mechanical device for indicating the tap position of the tapchanger. Tap-change in progress indication A device indicating that the motor-drive mechanism is running. Limit switches Electro-mechanical devices preventing the operation of the tap-changer beyond either end position, but allowing operation in the opposite direction. Mechanical end stop A device which physically prevents operation of the tap-changer beyond either end position, but allows operation in the opposite direction. Parallel control device Electrical control devices to move, in the case of parallel operation of several transformers with tappings, all tap-changers to the required position and to avoid divergence of the respective motor-drive mechanisms. Note. Such devices would be necessary also in the case single-phase transformers forming a three-phase bank when each single-phase tap-changer is fitted with its own motor-drive mechanism. Emergency tripping device An electrical and / or mechanical device for stopping the motor-drive mechanism at any time in such a way that a special action must be performed before the next tap changer operation can be started. Over current blocking device An electrical device preventing or interrupting operation of the motor-drive mechanism for the period in which an over current exceeding a preset value is flowing in the transformer winding. Note. Where diverter switches are actuated by spring energy system, interruption of the operation of the motor-drive mechanism will not prevent operation of the diverter switch if the spring release has been actuated. Restarting device A mechanical and/or electrical device restarting the motor-drive mechanism after an interruption of the supply voltage and thus completing a tap-change operation already initiated. Operation counter A device indicating the number of tap-changing accomplished. 20 Manual operation of motor-drive mechanism: Operation of the tap-changer manually by a mechanical device, blocking at the same time operation by the electric motor. Motor-drive cubical A cubical housing the motor-drive mechanism. No-load loss The active power absorbed when rated voltage (tapping voltage) at rated frequency is applied to the terminals of one of the windings, the other winding or windings being open-circuited. No-load current The r.m.s. value of the current flowing through a line terminal of a winding when rated voltage (tapping voltage) is applied at rated frequency, the other winding or windings being open-circuited. Note.1. For a three-phase transformer, the value is the arithmetic mean of the values of current in the three phases. Note.2. The no-load current of a winding is often expressed as a percentage of the rated current of that winding. For a multi-winding transformer this percentage is referred to the winding with the highest rated power. Load loss The absorbed active power at rated frequency and reference temperature, associated with a pair of windings when rated current (tapping current) is flowing through the line terminals of one of the windings, and the terminals of the other winding are shortcircuited. Further windings, if existing, are open-circuited. Note.1. For a two-winding transformer there is only one winding combination and one value of load loss. For a multi-winding transformer there are several values of load loss corresponding to the different two-winding combinations (see clause 6 of IEC 60606). A combined load loss figure for the complete transformer is referred to a specified winding load combination. In general, it is usually not accessible for direct measurement in testing. Note.2. When the windings of the pair have different rated power values the load loss is referred to rated current in the winding with the lower rated power and the reference power should be mentioned. Note.3. See general requirements of routine, type and special tests—any ambient temperature between 10 ºC and 40 ºC and with cooling water (if required) at any temperature not exceeding 25 ºC---reference correction temperature is 75 ºC for oilimmersed transformers. Total losses The sum of the no-load loss and the load loss. Note. The power consumption of the auxiliary plant is not included in the total losses and is stated separately. 21 Short-circuit impedance of a pair of windings The equivalent series impedance Z = R + jX, in ohms, at rated frequency and reference temperature, across the terminals of one winding of a pair, when the terminals of the other winding are short-circuited and further windings, if existing, are open-circuited. For a three-phase transformer the impedance is expressed as phase impedance (equivalent star connection). In a transformer having a tapped winding, the short-circuit impedance is referred to a particular tapping. Unless otherwise specified the principal tapping applies. The relative value is also equal to the ratio between the applied voltage during a shortcircuit measurement which causes the relevant rated current (or tapping current) to flow, and rated voltage (or tapping voltage). This applied voltage is referred to as the short-circuit voltage of the pair of windings. It is normally expressed as a percentage. Voltage drop or rise for a specified load condition The arithmetic difference between the no-load voltage of a winding and the voltage developed at the terminals of the same winding at a specified load and power factor, the voltage supplied to (one of) the other winding(s) being equal to: – its rated value if the transformer is connected on the principal tapping (the no-load voltage of the former winding is then equal to its rated value); – the tapping voltage if the transformer is connected on another tapping. This difference is generally expressed as a percentage of the no-load voltage of the former winding. Note. For multi-winding transformers, the voltage drop or rise depends not only on the load and power factor of the winding itself, but also on the load and power factor of the other windings (see IEC 60606). Zero-sequence impedance (of a three-phase winding) The impedance, expressed in ohms per phase at rated frequency, between the line terminals of a three-phase star-connected or zigzag-connected winding, connected together, and its neutral terminal. Note.1. The zero-sequence impedance may have several values because it depends on how the terminals of the other winding or windings are connected and loaded. Note.2. The zero-sequence impedance may be dependent on the value of the current and the temperature, particularly in transformers without any delta-connected winding. Note.3. The zero-sequence impedance may also be expressed as a relative value in the same way as the (positive sequence) short-circuit impedance. Temperature rise The difference between the temperature of the part under consideration and the temperature of the external cooling medium. 22 Highest voltage for equipment Um applicable to a transformer winding The highest r.m.s. phase-to-phase voltage in a three-phase system for which a transformer winding is designed in respect of its insulation. Rated insulation level A set of standard withstand voltages which characterize the dielectric strength of the insulation. Standard insulation level A rated insulation level, the standard withstand voltages of which are associated to Um ( tables 2 and 3 of IEC 60071-1). Uniform insulation of a transformer winding The insulation of a transformer winding when all its ends connected to terminals have the same rated insulation level. Non-uniform insulation of a transformer winding The insulation of a transformer winding when it has a neutral terminal end for direct or indirect connection to earth, and is designed with a lower insulation level than assigned for the line terminal. Star connection (Y-connection) The winding connection so arranged that each of the phase windings of a three-phase transformer, or of each of the windings for the same rated voltage of single-phase transformers associated in a three-phase bank, is connected to a common point (the neutral point) and the other end to its appropriate line terminal. Delta connection (D-connection) The winding connection so arranged that the phase windings of a three-phase transformer, or the windings for the same rated voltage of single-phase transformers associated in a three-phase bank, are connected in series to form a closed circuit. Open-delta connection The winding connection in which the phase windings of a three-phase transformer, or the windings for the same rated voltage of single-phase transformers associated in a three-phase bank, are connected in series without closing one corner of the delta. Zigzag connection (Z-connection) The winding connection in which one end of each phase winding of a three-phase transformer is connected to a common point (neutral point), and each phase winding consists of two parts in which phase-displaced voltages are induced. Note. These two parts normally have the same number of turns. Open windings Phase windings of a three-phase transformer which are not interconnected within the transformer. Phase displacement of a three-phase winding 23 The angular difference between the phasors representing the voltages between the neutral point (real or imaginary) and the corresponding terminals of two windings, a positive-sequence voltage system being applied to the high-voltage terminals, following each other in alphabetical sequence if they are lettered, or in numerical sequence if they are numbered. The phasors are assumed to rotate in a counterclockwise sense. Note. The high-voltage winding phasor is taken as reference, and the displacement for any other winding is conventionally expressed by the 'clock notation', that is, the hour indicated by the winding phasor when the H.V winding phasor is at 12 o'clock (rising numbers indicate increasing phase lag). Connection symbol A conventional notation indicating the connections of the high-voltage, intermediatevoltage (if any), and low-voltage windings and their relative phase displacement(s) expressed as a combination of letters and clock-hour figure(s). Routine test A test to which each individual transformer is subjected. Type test A test made on a transformer which is representative of other transformers, to demonstrate that these transformers comply with specified requirements not covered by routine tests. Note. A transformer is considered to be representative of others if it is fully identical in rating and construction, but the type test may also be considered valid if it is made on a transformer which has minor deviations of rating or other characteristics. These deviations should be subject to agreement between the manufacturer and the purchaser. Special test A test other than a type test or a routine test, agreed by the manufacturer and the purchaser. Monthly average temperature Half the sum of the average of the daily maxima and the average of the daily minima during a particular month – over many years. Yearly average temperature One-twelfth of the sum of the monthly average temperatures. Bushing Bushing is a device that enables one or several conductors to pass through a partition such as a wall or a tank, and insulates the conductors from it. The means of attachment (flange or fixing device) to the partition forms part of the bushing. Note. 1 The conductor may form an integral part of the bushing or be drawn into the central tube of the bushing. Note. 2 The bushing may be of the types as mentioned below. 24 Liquid-filled bushing Bushing in which the space between the inside surface of the insulating envelop and the solid major insulation is filled with oil. Compound-filled bushing Bushing in which the space between the inside surface of the insulating envelop and the solid major insulation is filled with an insulating compound. Liquid-insulated bushing Bushing in which the major insulation consists of oil or another insulating liquid. Gas-filled bushing Bushing in which the space between the inside surface of the insulating envelope and the solid major insulation is filled with gas (other than ambient air) at atmospheric pressure or higher. Note. This definition includes bushings which are intended to form an integral part of gas-insulated equipment, the gas of the equipment being in communication with that of the bushing. Gas-insulated bushing Bushing in which the major insulation consists of gas (other than ambient air) at atmospheric pressure or higher. Note. 1 This definition includes bushings which are intended to form an integral part of gas-insulated equipment, the gas of the equipment being in communication with that of the bushing. Note. 2 A bushing which contains solid insulating materials other than the envelope containing the gas (e.g. support for conducting layers or insulating cylinder), is a combined insulation bushing. Gas-impregnated bushing Bushing in which the major insulation of a core wound from paper or plastic film (GIF) and subsequently treated and impregnated with gas (other than ambient air) at atmospheric pressure or higher, the space the core and the insulating envelope being filled with the same gas. Oil-impregnated paper bushing (OIP) Bushing in which the major insulation of a core wound from paper and subsequently treated and impregnated with an insulating liquid, generally transformer oil. Note. The core is contained in an insulating envelope, the space between the core and insulating envelope being filled with the same insulating liquid as that used for impregnation. Resin-bonded paper bushing (RBP) Bushing in which the major insulation of a core wound from resin-coated paper. Note. 1 During the winding process, each paper layer is bonded to the previous layer by its resin coating and the bonding achieved by curing the resin. 25 Note. 2 A resin-bonded paper bushing can be provided with an insulating envelope, in which case the intervening space can be filled with an insulating liquid or another insulating medium. Note. 3 A rubber compound covering may be applied directly on to the bushing major insulation. Resin-impregnated paper bushing (RIP) Bushing in which the major insulation of a core wound from untreated paper and subsequently treated and impregnated with a curable resin. Note. 1 A resin-impregnated paper bushing can be provided with an insulating envelope, in which case the intervening space can be filled with an insulating liquid or another insulating medium. Note. 2 A rubber compound covering may be applied directly on to the bushing major insulation. Ceramic, glass or analogous inorganic material bushing: Bushing in which the major insulation consists of a ceramic, glass or analogous inorganic material. Note. A rubber compound covering may be applied directly on to the bushing major insulation. Cast or moulded resin-insulated bushing Bushing in which the major insulation consists of a cast or moulded organic material with or without an inorganic filter. Note. A rubber compound covering may be applied directly on to the bushing major insulation. Combined insulation bushing Bushing in which the major insulation consists of a combination of at least two different insulating materials. Capacitance graded bushing Bushing, in which a desired voltage grading is obtained by an arrangement of conducting or semi-conducting layers incorporated into the insulating material. Indoor bushing Bushing, both ends of which are intended to be in ambient air at atmospheric pressure, but not exposed to outdoor atmospheric conditions. Outdoor bushing Bushing, both ends of which are intended to be in ambient air at atmospheric pressure and exposed to outdoor atmospheric conditions. Outdoor-indoor bushing Bushing, both ends of which are intended to be in ambient air at atmospheric pressure. Note. One end is intended to be exposed to outdoor atmospheric conditions, and the other end not to be exposed to outdoor atmospheric conditions. Indoor-immersed bushing 26 Bushing, one end of which is intended to be in ambient air but not exposed to outdoor atmospheric conditions and the other end to be immersed in an insulating medium other than ambient air (e.g. oil or gas). Note. This definition includes bushings operating in air at temperatures above ambient, such as occur with air-insulated ducting. Outdoor-immersed bushing Bushing, one end of which is intended to be in ambient air and exposed to outdoor atmospheric conditions and the other end to be immersed in an insulating medium other than ambient air (e.g. oil or gas). Completely immersed bushing Bushing, both ends of which are intended to be immersed in an insulating medium other than ambient air (e.g. oil or gas). Bushing for separable connector (plug-in-type bushing) Bushing, one end of which is immersed in an insulating medium and the other end designed to receive a separable insulated cable connector, without which the bushing cannot function. Highest voltage for equipment (Um) Highest r.m.s. value of phase-to-phase voltage for which the equipment is designed in respect of its insulation as well as other characteristics which relates to this voltage in the relevant equipment standard. Rated phase-to-earth voltage Maximum r.m.s. value of the voltage which the bushing withstands continuously between the conductor and the earthed flange or other fixing device, under the specified operating conditions. Rated current (I r) Maximum r.m.s. value of current which the bushing can carry continuously under the specified operating conditions, with exceeding the specified temperature rise limits. Rated thermal short-time current (I th) R.M.S. value of a symmetrical current which the bushing withstands thermally for the rated duration (t th) immediately following continuous operation at rated current with the maximum temperatures of ambient air and immersion media. Rated dynamic current (I d) Peak value of a current which the bushing withstands mechanically. Temperature rise Difference between the measured temperature of the hottest spot of the metal parts of the bushing which are in contact with insulating material and the ambient air temperature. Rated frequency (Fr) Frequency at which the bushing is designed to operate. 27 Minimum operating pressure of gas for insulation Minimum pressure, referenced to 20oC, assigned by the bushing supplier, at which the rated insulation level applies. Maximum internal operating gas pressure Pressure, when the bushing is in operation, carrying rated current at the specified highest temperatures. Maximum external operating gas pressure Maximum pressure of the gaseous insulating medium in which the bushing is partially or completely immersed when in operation. Design pressure (of the enclosure) Pressure used to determine the thickness of the enclosure. Leakage rate of gas-filled, gas-insulated, gas-impregnated and gas-immersed bushings Quantity of dry gas at a given temperature that flows through a leak per unit of time and for a known difference of pressure across the leak. Note. The basic SI unit for leak rate is "Pascal cubic meter per second (Pa x m3/s)". The derived units "Pa x cm3/s and bar x cm3"are used commonly, as they better conform with the orders of magnitude used in common industrial practice. It should be remembered that; 1Pa x m3/s = 106 Pa x cm3/s = 10 bar x cm3/s. Insulating envelope Hollow insulator which is open from end to end, with or without sheds. Note. An insulating envelope may consist of one insulator unit or two or more permanently assembled insulator units. Creepage distance Shortest distance along the surface of an insulator between two conductive parts. Note. 1 The surface of cement or of any other non-insulating jointing material is not considered as forming part of the creepage distance. Note. 2 If high-resistance coating is applied to parts of the insulating part of an insulator, such parts are considered to be effective insulating surfaces and the distance over them is included in the creepage distance. Arcing distance Shortest distance in air external to the insulator between metallic parts which normally have the operating voltage between them. Note. The term "dry arcing distance" or "taut string distance" are also used. Test tap / measuring tap / tan δ tap Connection, accessible from outside the bushing, insulated the flange or other fixing device, made to one of the outer conducting layers of a capacitance graded bushing in order to allow measurement of dissipation factor, capacitance and partial discharge whilst the flange of the bushing is earthed. Note. 1 This connection should be earthed directly when it is not used. 28 Note. 2 When the test tap is used for condition monitoring, in service, care should be taken to avoid an open circuit. Voltage tap / potential tap / capacitance tap Connection, accessible from outside the bushing, insulated the flange or other fixing device, made to one of the outer conducting layers of a capacitance graded bushing in order to provide a voltage source whilst the bushing is in operation. Note. 1 This connection should be earthed directly when it is not used. Note. 2 This tap can also be used for the measurement of dissipation factor, capacitance and partial discharge. Rated voltage of the voltage tap Maximum voltage at which the tap is designed to supply the associated equipment with the rated load connected thereto, when the rated phase-to-earth voltage is applied to the bushing at the rated frequency. Composite bushing Bushing with an insulating envelope consisting of a resin impregnated fibre tube with or without a rubber compound covering. Main capacitance (C1) of bushing Capacitance between the high-voltage conductor and the test tap or the voltage of a capacitance-graded bushing. Tap capacitance (C2) of bushing Capacitance between the test tap or the voltage tap and the mounting flange of a capacitance-graded bushing. Capacitance (C) of bushing Capacitance between the high-voltage conductor and the mounting flange of a bushing without a voltage tap or test tap. 29 11.3 CIRCUIT BREAKER’ IMPORTANT DEFINITIONS, OPERATING TIME AND CHARACTERISTIC QUANTITIES Circuit breaker class E1 The circuit breaker with basic electrical endurance not falling into the category of class E2 is referred as class E1. Circuit breaker class E2 The circuit breaker designed so as not to require maintenance of the interrupting parts of the main circuit during its expected operating life, and only minimum maintenance of its other parts (circuit breaker with extended electrical endurance) Note. 1 The minimum maintenance may include lubrication, replenishment of gas and cleaning of external surfaces, where applicable. Note. 2 This definition is restricted to distribution circuit-breakers having a rated voltage above 1 kV, and up to and including 52 kV. See annex G for rationale behind introduction of class E2. Circuit breaker class C1 The circuit breaker with low probability of re-strike during capacitive current breaking as demonstrated by specific type tests Circuit breaker class C2 The circuit breaker with very low probability of re-strike during capacitive current breaking as demonstrated by specific type tests Circuit breaker class M1 The circuit breaker with normal mechanical endurance (mechanically type tested for 2000 operations) not falling into the category of class M2. Circuit breaker class M2 The frequently operated circuit-breaker for special service requirements and designed so as to require only limited maintenance as demonstrated by specific type tests (circuit-breaker with extended mechanical endurance, mechanically type tested for 10000 operations). Note. Combination of the different classes of circuit-breakers with regard to electrical endurance, mechanical endurance and the re-strike probability during capacitive current breaking is possible. For the designation of these circuit-breakers the notation of the different classes are combined following an alphabetical order, for example C1M2. Circuit breaker class S1 The circuit breaker intended to be used in a cable system. Circuit breaker class S2 The circuit breaker intended to be used in a line-system or in a cable system with direct connection (without cable) to overhead lines. 30 Opening time Opening time of a circuit-breaker defined according to the tripping method as stated below and with any time delay device forming an integral part of the circuit-breaker adjusted to its minimum setting: a) For a circuit-breaker tripped by any form of auxiliary power (DC trip), the opening time is the interval of time between the instant of energizing the opening release, the circuit-breaker being in the closed position, and the instant when the arcing contacts have separated in all poles; b) For a self-tripping circuit-breaker (AC trip), the opening time is the interval of time between the instant at which, the circuit-breaker being in the closed position, the current in the main circuit reaches the operating value of the over-current release and the instant when the arcing contacts have separated in all poles. Note. 1 The opening time may vary with the breaking current. Note. 2 For circuit-breakers with more than one interrupting unit per pole, the instant when the arcing contacts have separated in all poles is determined as the instant of contact separation in the first unit of the last pole. Note. 3 The opening time includes the operating time of any auxiliary equipment necessary to open the circuit breaker and forming an integral part of the circuitbreaker. Arcing time (of a multi-pole switching device) The interval of time between the instant of the first initiation of an arc and the instant of final arc extinction in all poles Break time The interval of time between the beginning of the opening time of a mechanical switching device and the end of the arcing time Closing time The interval of time between energizing the closing circuit, the circuit-breaker being in the open position, and the instant when the contacts touch in all poles Note. The closing time includes the operating time of any auxiliary equipment necessary to close the circuit breaker and forming an integral part of the circuitbreaker. Make time The interval of time between energizing the closing circuit, the circuit-breaker being in the open position, and the instant when the current begins to flow in the first pole Note. 1 The make time includes the operating time of any auxiliary equipment necessary to close the circuit breaker and forming an integral part of the circuitbreaker. Note. 2 The make time may vary, e.g. due to the variation of the pre-arcing time. 31 Pre-arcing time The interval of time between the initiation of current flow in the first pole during a closing operation and the instant when the contacts touch in all poles for three-phase conditions and the instant when the contacts touch in the arcing pole for single-phase conditions Note. 1 The pre-arcing time depends on the instantaneous value of the applied voltage during a specific closing operation and therefore may vary considerably. Note. 2 This definition for pre-arcing time for a circuit-breaker should not be confused with the definition for pre-arcing time for a fuse. Open-close time (during auto-reclosing) The interval of time between the instant when the arcing contacts have separated in all poles and the instant when the contacts touch in the first pole during a reclosing cycle Dead time (during auto-reclosing) The interval of time between final arc extinction in all poles in the opening operation and the first re-establishment of current in any pole in the subsequent closing operation Note. The dead time may vary, e.g. due to the variation of the pre-arcing time. Reclosing time The interval of time between the beginning of the opening time and the instant when the contacts touch in all poles during a reclosing cycle Re-make time (during reclosing) The interval of time between the beginning of the opening time and the first reestablishment of current in any pole in the subsequent closing operation Note. The re-make time may vary, e.g. due to the variation of the pre-arcing time. Close-open time The interval of time between the instant when the contacts touch in the first pole during a closing operation and the instant when the arcing contacts have separated in all poles during the subsequent opening operation Note. Unless otherwise stated, it is assumed that the opening release incorporated in the circuit-breaker is energized at the instant when the contacts touch in the first pole during closing. This represents the minimum close-open time. Make-break time The interval of time between the initiation of current flow in the first pole during a closing operation and the end of the arcing time during the subsequent opening operation Note. 1. Unless otherwise stated, it is assumed that the opening release of the circuitbreaker is energized one half-cycle after current begins to flow in the main circuit during making. It should be noted that the use of relays with shorter operating time may subject the circuit-breaker to asymmetrical currents that are in excess of the specified one. 32 Note. 2 The make-break time may vary due to the variation of the pre-arcing time. Pre-insertion time The interval of time during a closing operation in any one pole between the instant of contact touch in the closing resistor element and the instant of contact touch in the main breaking unit of that pole Note. For circuit-breakers having series connected breaking units, the pre-insertion time is defined as the interval of time between the instant of the last contact touch in any closing resistor element and the instant of the last contact touch in any main breaking unit. Minimum trip duration The minimum time the auxiliary power is applied to the opening release to ensure complete opening of the circuit-breaker Minimum close duration The minimum time the auxiliary power is applied to the closing device to ensure complete closing of the circuit breaker Normal current The current which the main circuit of a circuit-breaker is capable of carrying continuously under specified conditions of use and behaviour Peak factor (of the line transient voltage) The ratio between the maximum excursion and the initial value of the line transient voltage to earth of a phase of an overhead line after the breaking of a short-line fault current Note. The initial value of the transient voltage corresponds to the instant of arc extinction in the pole considered. First-pole-to-clear factor (in a three-phase system) When interrupting any symmetrical three-phase current the first-pole-to-clear factor is the ratio of the power frequency voltage across the interrupting pole before current interruption in the other poles, to the power frequency voltage occurring across the pole or the poles after interruption in all three poles Amplitude factor The ratio between the maximum excursion of the transient recovery voltage to the crest value of the power frequency recovery voltage Main circuit All conductive parts of the switchgear constituting wires to be opened and closed. Control circuit A circuit that controls energy for operation of the switchgear in response to signals from outside the GCB. Operating circuit A circuit used to operate the switchgear. 33 Auxiliary circuit Generic terms for all circuits except for the main circuit, operation circuit, and control circuit of the switchgear. Ambient air temperature The temperature of the air surrounding the switchgear as measured under certain conditions. Switch Mechanical switch capable of opening and closing wires under normal conditions and under specified overload running conditions, of flowing currents, or of flowing currents in a short-circuit or in a specified abnormal circuit state for a specified period. Terminal A conductive part designed to connect the GCB electrically to external circuits. Earth Terminal A terminal designed to ground part of the switchgear when connected to the ground in a specified manner. Contact The conductive portion of the switchgear designed to constitute a conductive part by getting into contact when closed, and move relatively to open and close the circuit involved. Fixed contact A contact mounted in the fixed region of a conductive part constituting a circuit. Moving contact A contact mounted in the movable region of a conductive part constituting a circuit. Main contact Contact provided in the main conductive part to supply current to the main circuit when the circuit is closed Arcing contact Contact provided to prevent arcing to the main contact by inducing an arc by opening or closing a-contact A contact in an auxiliary switch designed to close when the main contact of the switchgear closes and opens when the main contact opens. b-contact A contact in an auxiliary switch designed to close when the main contact of the switchgear opens and open when the main contact closes. Conductive part The current-conductive portion of the GCB. Main conductive part The conductive portion where the main circuit current flows. 34 Arc-control device Device that contains the arc contacts, and restrains the arc in the container to promote arc extinguishing. Control device Equipment that receives instructions or signals from outside the switchgear, selects from among them, and controls the energy level for running the switchgear. Control switch A mechanical switch that controls the operation of the switchgear. Pilot switch A control switch that gets activated automatically when a specified operating condition is reached. Pressure switch A detection switch that gets activated when the gas or liquid pressure reaches a specified level. Push-button switch A switch that interlocks with the operation of the switchgear and produces displays. Auxiliary switch Switch used for interlock indication by linking with the switching equipment. Change-over switch A control switch that switches between two or more circuits. Contactor A mechanical switch that always returns to a state before operation when a feed of operation energy is turned off and which is operated by means other than manual and frequently opens and closes wires in normal state including overloads. Control The action of energizing, de-energizing, or locking a solenoid valve, coil, or other equipment designed to activate the switchgear operator according to the purpose of operation. Control voltage Voltage applied to a terminal of the controller. Operation The action of moving a movable contact of the switchgear from one position to the one next to it. Operating voltage Voltage added to a terminal of the solenoid valve, motor, or other equipment on the operator. Closing operation The action of closing an open contact. Opening operation The action of opening a closed contact. 35 Manual operation An operation conducted by manual means alone without using any other source of motive power. Seal-in feature It is desirable to have the control circuit ensure that the circuit breaker will fully close each time that closing operation is initiated. If the circuit breaker is closed by a simple switch, the operator could be open the switch to cut off the closing power before the circuit breaker was fully closed and latched. In this event, the circuit breaker will fall open. In most circuit breakers a relay with one set of contacts used to seal-in itself is used to ensure a complete closing stroke once initiated. Trip free When contact of a contact or an arc between contacts has caused the main circuit to be active, the tripper can operate to trip the circuit breaker even if the closing command is being effective. Alternatively, even if a command for the closing device to conduct closing is still given after completion of tripping, the closing operation is conducted when the current closing command has been cancelled and another closing command has been given. When closing a circuit breaker, the closing coil (for example, the solenoid in solenoidoperated circuit breaker) is energized and the plunger operates through the linkage to close the circuit breaker contacts. At the end of the closing stroke, appreciable time is required to de-energize the solenoid coil. In the event that the circuit breaker has been closed on a faulted circuit, it must be reopened as quickly as possible. If a circuit breaker can trip automatically upon receiving a trip signal before closing operation is complete, it is said to be “trip free”. Various arrangements are provided to obtain trip-free action. Solenoid-operated circuit breakers are sometimes provided with collapsible linkage. Pneumatically-operated circuit breaker may be equipped two latches, one of which is unlatched during a normal trip operation and the other is only unlatched for trip signal while the circuit breaker is closing. Other circuit breakers use a large dump valve to quickly exhaust the air under the closing piston. Many motor-operated circuit breakers obtain a fast trip-free action by use of a relay energized from the trip circuit to open the closing circuit. These methods would be known as mechanically trip free, pneumatically trip free and electrically trip free respectively. Anti-pumping Preventing re-closing as long as the closing command is continuously effective upon completion of tripping. When a circuit breaker is closed and a trip-free operation results, the close and trip stroke will be completed in a very short time. For a modern pneumatically –operated high voltage circuit breaker, the complete operation will take less than one-half of one second, thus, it is quite likely that the operator will still have the control switch in the 36 closed position. Means must therefore be provided to prevent the circuit breaker from closing a second time, even though the operator is still holding the control switch in the closed position. This is usually accomplished by the use of a sealed-in relay (antipumping relay) which can only be released by opening the closing control switch. When this feature is incorporated in the control circuit, the circuit breaker is said to be “pump free” or “anti-pumping”. Following a trip-free operation of the circuit breaker, the operator must open the control switch before a second attempt to close the circuit breaker can be made. Anti-slam When a circuit breaker is in the closed position, energizing the closing coil could cause the solenoid plunger to move. Since the circuit breaker is in closed position, there is a very little to retard this movement and the plunger will “slam” at the end of its stroke. The control circuit should prevent slamming of the mechanism when the circuit breaker is in the closed position. Trip/release Control operation for opening the circuit of the switching equipment upon receiving the command from an external device. Operating current Minimum current for operating the tripper. Interlock Regulating the operation of the switching equipment by relating to the location or operation of other device. Breaking current Current which flows through each pole during opening operation of the switching equipment and is indicated by a value at a moment of arcing. Standard operating sequence Operating sequence used as a standard for defining the closing performance and opening performance of the circuit breaker and switch. O - 0.3s - CO - 3min - CO / CO - 15s - CO 37 11.4 PROPERTIES OF OIL, THEIR SIGNIFICANCE AND TEST METHODS ( Mineral insulating oils These oils are obtained by refining the naturally available crude petroleum. They are mixtures of many compounds known as hydrocarbons in different proportions which depend on the source of crude petroleum. Hydrocarbons can be divided into three classes, naphthenes, paraffins and aromatics. Naphthenes and paraffins are saturated hydrocarbons and are chemically stable. They differ from one another by their molecular structure and their physical and chemical properties. Aromatics are not saturated and as a result they are less stable and more chemically active. The generally used classifications of naphthenic and paraffinic do not imply that these oils contain naphthenes or paraffins exclusively but refer to the dominant characteristic of one of these classes in a mixture of naphthenic, paraffinic and aromatic hydrocarbons. The proportions vary according to the source of the crude petroleum and the refining process. The sources of naphthenic crude are becoming rare therefore the tendency to manufacture insulating oils from paraffinic crude petroleum is increasing. This does not cause any particular problem except from the point of view of the freezing point, and it may become necessary to use special additives. Mineral insulating oils are used universally but with necessary fire protection arrangements depending upon the installation conditions of the electrical equipment. Mineral insulating oils of different manufacturers are mutually mixable/ miscibility in any proportion, but it is not possible to restore used oil to a renewed condition by mixing. The use of oxidation inhibitors to retard ageing is recommended in exceptional cases such as in very large transformers subjected to severe operating conditions. Synthetic insulating oils Insulating oils other than the mineral insulating oils are known as synthetic insulating oils. The most common synthetic insulating oils derived from silicones are used only as special applications such as in power capacitors, etc. DEFINITIONS Transformer oil The mineral insulating oil for transformers and similar electrical equipment where normal oxidation resistance is required is termed as transformer oil. Low temperature switchgear oil The mineral insulating oil for oil-filled switchgear for outdoor application in very cold climatic conditions is termed as low temperature switchgear oil. 38 Additive A suitable chemical substance which is deliberately added to mineral insulating oil in order to improve certain characteristics is termed as an additive. Note. Examples include antioxidants, pour point depressants, electrostatic charging tendency depressants such as benzotriazole (BTA), anti-foam agents, refining process improvers, etc. Antioxidant additive An additive incorporated in an insulating oil to improve oxidation stability is termed as an antioxidant additive. Note. A large number of antioxidant additives are available. For this standard, these are limited to those identified in IEC 60666. Uninhibited oil The mineral insulating oil, containing no antioxidant additives, but which may contain other additives is termed as uninhabited oil. Trace inhibited oil The mineral insulating oil containing up to 0.08 % antioxidant additive together with other additives as included in the category of antioxidant additives. Inhibited oil The mineral insulating oil containing a minimum of 0.08 % and a maximum of 0.40 % antioxidant additive together with other additives as included in the category of antioxidant additives. Note. In certain countries the inhibited mineral insulating oil is defined as the mineral insulating oil containing at least 0.15% by mass, but not more than 0.40% by mass of 2.6-di-tert-butyle-paracresole (DBPC) or 2.6-di-turt-butyle-phenol (DBP). Unused mineral insulating oil The mineral insulating oil as delivered by the supplier is termed as unused mineral insulating oil. Note. Such oil has not been used in, nor been in contact with electrical equipment or other equipment not required for manufacture, storage or transport. The manufacturer and supplier of unused oil will have taken all reasonable precautions to ensure that there is no contamination with polychlorinated biphenyls or terphenyls (PCB, PCT), used, reclaimed or dechlorinated oil or other contaminants. Reclaimed oil The mineral insulating oil used in electrical equipment which has been subjected to chemical and/or physical processing to eliminate soluble and insoluble contaminants Note. A blend of unused and reclaimed oil in any proportion is regarded as being reclaimed. Viscosity Viscosity influences heat transfer and therefore the temperature rise of the equipment. The lower the viscosity, the easier the oil circulates leading to improved heat transfer. 39 At low temperatures the resulting higher viscosity of oil is a critical factor for the cold start of transformers with ON cooling (no circulation and therefore possible overheating at the hot spots) and negatively influences the speed of moving parts, such as in power circuit breakers, switchgear, on-load tap changer mechanisms, pumps and regulators. The viscosity at the lowest cold start energizing temperature (LCSET) shall not exceed 1800 mm2/s (respectively 2500 mm2/s at -40°C). This lowest cold start energizing temperature (LCSET) for transformer oils is defined in this standard as being –30 °C. Other LCSET (see Table 1) can be agreed between supplier and purchaser. Low temperature switchgear oil should have a lower viscosity at LCSET: max. 400 mm2/s. The standard LCSET of low temperature switchgear oil is defined with -40 °C but other LCSET may be agreed between supplier and purchaser. Table 1- Maximum viscosity and pour point of transformer oil at lowest cold start energizing temperature (LCEST) LCEST °C Maximum Viscosity mm2/s Maximum Pour Point °C 0 1800 -10 -20 1800 -30 -30 1800 -40 -40 2500 -50 Note.1 For more details concerning ON cooling (natural oil circulation without pump). Note.2 There is no lower viscosity limit set in this IEC 60296, but under certain conditions oil with a viscosity less than 7 mm2/s /40°C can be considered to be a potential hazard. Viscosity shall be measured according to ISO 3104, viscosity at very low temperature according to IEC 61868 Pour point Pour point of mineral insulating oil is the lowest temperature at which the oil will just flow. It is recommended that the pour point should be minimum 10 K below the lowest cold start energizing temperature (LCSET). If a pour point depressant additive is used, this should be mentioned by the supplier to the user. Pour point shall be measured in accordance with ISO 3016. Water content A low water content of mineral insulating oil is necessary to achieve adequate electrical strength and low dissipation losses. To avoid separation of free water, unused insulating oil should have a limited water content. Before filling the electrical equipment, the oil should be treated to meet the requirements of IEC 60422. Where requested by the purchaser, the supplier of oil shall demonstrate that after treatment to 40 remove solid particles, humidity and dissolved air by a vacuum procedure (see note), the oil shall have a high dielectric strength of minimum 70 kV break-down Voltage. Water content shall be measured in accordance with IEC 60814. Note. This laboratory treatment referred to consists of filtration of the oil at 60 °C by vacuum (pressure below 2.5 kPa) through a sintered glass filter (porosity 4). Breakdown voltage Breakdown voltage of transformer oil indicates its ability to resist electrical stress in electrical equipment. Breakdown voltage shall be measured in accordance with IEC 60156. Dielectric dissipation factor (DDF) DDF is a measure for dielectric losses caused by the oil. Increased DDF can indicate contamination of the oil by moisture, particles or soluble polar contaminants or poor refining quality. DDF shall be measured in accordance with IEC 60247 or IEC 61620 at 90 °C. In case of dispute, IEC 60247 at 90 °C should be used. Note. By agreement between parties, DDF may be measured at temperatures other than 90 °C. In such cases the temperature of measurement should be stated in the report. Appearance A visual inspection of insulating oil (oil sample in transmitted light under a thickness of approximately 10 cm and at ambient temperature) indicates the presence of visible contaminants, free water or suspended matter. Acidity Unused mineral insulating oil should be neutral and free from any acidic compound. Acidity should be measured following IEC 62021-1. Interfacial tension (IFT) Low IFT sometimes indicates the presence of undesirable contaminants. IFT shall be measured in accordance with ISO 6295. Sulfur content Different organo-sulfur compounds are present in transformer oils, dependent on the crude oil origin and the degree and type of refining. Refining treats sulfur and aromatic hydrocarbons. As some sulfur compounds have an affinity to metals, they may act as copper passivators or they may promote corrosion. Sulfur content should be measured following BS 2000 Part 373 or ISO 14596. Corrosive sulfur Some sulfur compounds, e.g. mercaptans, are very corrosive to metal surfaces, i.e. steel, copper and silver (switchgear contacts) and shall not be present in new oil. Corrosive sulfur should be measured following DIN 51353. Antioxidant additive content Antioxidant additive (inhibitor) slows down the oxidation of oil and therefore the formation of oil sludge and acidity. It is important to know whether and in what 41 proportion antioxidant additive has been added in order to monitor additive depletion during service. 2.6-di-tert-butylp-cresol (DBPC) is the most commonly used antioxidant, but others are also used. Detection and measurement of defined antioxidant additives shall be determined in accordance with IEC 60666. The type and quantity of each antioxidant additive present in the oil shall be stated in the quality certificate. If co-stabilizers are used during the refining process, their presence shall be agreed between the supplier and the purchaser. Oxidation stability Oxidation of oil gives rise to acidity and sludge formation and can be minimized as a result of high oxidation stability leading to longer service life time by minimizing sludge deposition, electrical losses, metal corrosion, electrical faults and maximizing insulation life. Oxidation stability is measured in accordance with method C of IEC 61125. There is an option for stricter limits for special applications. In some countries more stringent limits and/or additional requirements and tests may be requested. Gassing Gassing tendency of mineral insulating oil, i.e. the gas absorbing property of an oil under electrical stress, is only necessary and important for special transformers like HV (high voltage) transformers and is a measure of the rate of absorption or evolution of hydrogen into oil under prescribed laboratory conditions. Gas absorption properties are related to oil aromaticity which is subject to indirect control by the oil's oxidation requirements. Gassing tendency is measured using method A of IEC 60628. Gassing tendency is a specific requirement. Electrostatic charging tendency (ECT) ECT of oil is an important property for certain designs of HV and EHV transformers which have oil pumping rates that can give rise to the build-up of electrostatic charge. This charge can result in energy discharge causing transformer failure. A method to measure ECT is proposed by CIGRE SC12. ECT is a specific requirement. Flash point The safe operation of electrical equipment requires an adequately high flash point that is measured in accordance with ISO 2719 (Pensky-Martens closed cup procedure). Density Density of oil shall be low enough to avoid, in cold climates, that ice resulting from the freezing of free water is floating on the oil surface and possibly leading to fault conditions developing in flashover of conductors. Density shall be measured in accordance with ISO 3675 (reference method) but ISO 12185 as well is accepted. Polycyclic aromatics (PCA) Some PCAs are classified to be carcinogens and therefore need to be controlled to an acceptable level in mineral insulating oil. PCAs are defined so as to be detectable by extraction with DMSO (Dimethylsulfoxide) under the conditions of BS 2000 Part 346. 42 Polychlorinated biphenyls (PCB) Unused mineral insulating oil shall be free from PCB. The reference method is IEC 61619. The detection limit for a single peak is 0,1 mg/kg. Note. The total limits are given by national regulations. Furfural and related compounds (2-FAL) 2-FAL and related compounds in unused mineral insulating oils can result either from improper re-distillation after solvent extraction during refining or from contamination with used oil. Unused insulating oils should have a low level of 2-FAL and related compounds and measurement should be done according to IEC 61198. Furfural Concentration in Transformer Oil as an Indicator of Paper Aging The concentration of the chemical furfural in transformer oil is well known to be an indicator of the extent to which the paper insulation of the winding has deteriorated. The two major insulating materials used in transformers are mineral insulating oil and paper. Transformer insulation is subjected to electrical and thermal stresses during service. Life of the transformer is mainly decided by the condition of the insulation because the operation, loading and reliability of the transformer is dependent on the state of the insulation. The windings of oil-filled transformers use paper insulation and if this becomes weak the consequence of a fault current may be severe, the inevitably high forces on the windings may result in mechanical failure of the insulation and consequent inter-turn short circuits. The reduction in strength of paper as it deteriorates is thus of considerable importance. An important by-product of the degradation of paper is 2furfuraldehyde of ‘furfural’ whose presence can as an indicator of the progress of deterioration. Insulating paper degrades with time at rates which depends on factors like temperature, amount of air and moisture present. If the cellulose paper is heated above 100 °C, it begins to degrade more rapidly and the useful service life of the transformer is reduced as a result. Laboratory experiments and studies show a direct relationship between the degree of polymerization (DP) value and the amount of furanic concentration in the oil. The studies reveal the lower DP values indicate increased furfural content when paper samples were subjected to heating over a long period. Some reports suggest the end of life of the cellulose insulation would be reached when total furan content reaches 10 PPM for a corresponding DP value of 15-200. It has been observed that the products of degradation of cellulose material in transformer appear in the oil in the form of furanic compounds commonly referred to as forans; 2-Furfural, 2-Fururalalcohal, 5-Hydroxymethyl-2-furfural, 2-Acetylfuran, Methyl-2-furfural. 43 11.5 TREATMENT OF OIL (DEHYDRATION/RECONDITIONING, REGENERATION/RECLAIMING, RE-FINING) Treatment of transformer oil on site by continuous circulation through the oil filtration and dehydration plant without completely emptying the transformer tank is in general, satisfactory for routine maintenance. However where the presence of sludge is known, it may be necessary to remove the oil completely for filtration, so that the transformer itself may be inspected and cleaned. As sludge tends to harden when exposed to atmosphere, it is recommended that the cleaning be carried as soon as possible after the removal of oil and of the core and windings from the tank. Filtration of the oil for removal of sludge must be carried out in the cold, since, although sludge tends to dissolve in hot oil, it comes out of the solution when the oil is cooled. Water, too, is much more soluble in hot oil than in cold, but this contaminant can be rapidly and virtually completely removed by vacuum treatment of the hot oil, and the most sophisticated modern oil treatment plants employ high-vacuum equipment in combination with fine filtration. These plants are capable of removing almost completely, the dissolved air and water from transformer oil, particles of free solids such as fiber, as well as any free water. During a typical servicing period these types of oil treatment plants will reduce in a single pass, the dissolved air content of oil from 11% to less than 1% by volume and dissolved moisture from 30ppm to less than 5ppm. Simultaneously, the DES can be increased from under 30kV to over 70kV. The most prominent factors causing oil deterioration are the presence of air and the effect of temperature. The complete exclusion of air may be achieved by the use of sealed transformer tanks having suitable oil expansion arrangements, or by providing nitrogen or other inert gas cushions in the tank. However, a major exclusion of air is obtained by the use of oil conservators, particularly in the case of large transformers. Reconditioning This is a process which eliminates, by physical means only, solid particles from the oil and decreases water content to an acceptable level. The physical means that are used for removing water and solids from oil include several types of filtration, centrifuging and vacuum dehydration techniques. If vacuum -treatment is not employed it is advisable to limit the temperature to 60 °C. If vacuum is employed, a higher temperature may be advantageous. However, at the vacuum used, the initial boiling point of that oil should not be exceeded, to avoid undue loss of lighter fractions. If this information is not available, it is recommended 44 that the oil should not be vacuum treated at temperatures over 70 °C. If it is desired to reduce sludge or free water, cold treatment may be appropriate. Filters deal efficiently with solid impurities, but are generally capable of removing only small quantities of water such as may be found in oil from equipment housed in buildings. Where relatively large quantities of water are present, most of it can, and shall, be drained away before filtration of the oil. Centrifugal separators are, in general satisfactory for removing free water from oil and can in any case deal also with any finely divided solid impurities. If oil is purified hot its viscosity is reduced and the throughput with certain types of purifier is greater. On the other hand, sludge and free water are more soluble in hot oil than in cold; sludge and free water are, therefore, more effectively removed by cold treatment. Dissolved and suspended water is effectively removed by hot vacuum treatment. If the oil contains solid matter, it is advisable to pass it through some kind of filter before processing it under vacuum. Note. - Processing inhibited mineral oil under vacuum and at elevated temperatures may cause partial loss of oxidation inhibitors; the common inhibitors, 2.6-di-tert-butylparacresol and 2.6-ditert - butyl - phenol are more volatile than mineral insulating oil. The selectivity for removal of water and air in preference to loss of inhibitor and oil is improved by use of a low processing temperature. Conditions that have been found satisfactory for most inhibited mineral oil processing are: Temperature °C 40 50 60 70 80 Pressure pa 5 10 20 40 100 Filters in Reconditioning equipment These are generally based on the principle of forcing oil under pressure through absorbing material such as paper or other filter media. Filters of this type are preferentially used in removing contaminants in suspension. (The filter medium should be capable of removing particles larger than a nominal 10 rim.) These devices do not de-gas the oil. The water-removing ability of a filter is dependent upon the dryness and quantity of the filter medium. When filtering oil containing water, the water content of the filter medium rapidly comes into equilibrium with the water content of the oil. A 45 continuous indication of the water content of the outgoing oil is useful to monitor the efficiency of the process. Care should be taken that paper filters are of the correct grade to ensure that no fibers are shed by them. Centrifuges In general, a centrifuge can handle a much greater concentration of contaminants than can a conventional filter but cannot remove some of the solid contaminants as completely as a filter. Consequently, the centrifuge is generally found in use for rough bulk cleaning where large amounts of contaminated oil are to be handled. Frequently the output of the centrifuge is put through a filter for the final clean-up. Vacuum dehydrators The vacuum dehydrator is an efficient means of reducing the gas and water content of a mineral insulating oil to very low values. There are two types of vacuum dehydrator; both function at elevated temperature. In one method the treatment is accomplished by spraying the oil into a vacuum chamber; in the other, the oil flows in thin layers over a series of baffles inside a vacuum chamber. In both types the objective is to expose maximum surface and minimum thickness of oil to the vacuum. In addition to removing water, vacuum dehydration will degas the oil and remove the more volatile acids. Application to electrical equipment Direct purification The oil is passed through a purifier and then stored in suitable clean containers. When the electrical equipment is to be refilled the oil is passed through the purifier again and then directly into the equipment. This method should be used for switchgear. It is suitable, too, for the smaller transformer, but care is needed to ensure that the core, the windings, the interior of the tank and other oil-containing compartments are thoroughly cleaned. The oil-containing compartments of all equipment should also be well cleaned, by means of oil from the purifier. Purification by circulation The oil is circulated through the purifier, being taken from the bottom of the tank of the electrical equipment and re-delivered to the top. The return delivery should be made smoothly and horizontally at or near the top oil level to avoid, as far as possible, mixing cleaned oil with oil which has not yet passed through the purifier. The circulation method is particularly useful for removing suspended contaminants, but all adhering contaminants will not necessarily be removed. 46 Experience has shown that it is generally necessary to pass the total volume of oil through the purifier not less than three times, and equipment of appropriate capacity should be chosen with this in mind. The final number of cycles will depend on the degree of contamination, and it is essential that the process be continued until a sample taken from the bottom of the electrical equipment, after the oil has been allowed to settle for a few hours, passes the breakdown voltage test. The circulation should be performed with the electrical equipment disconnected from the power source, and this is essential when using a purifier which aerates the oil. In all cases, and especially when aeration has occurred, the oil should be allowed to stand for some time in accordance with the manufacturer's instructions before the equipment is re-energized. Another technique is sometimes used for transformers, in which oil is continuously circulated during normal service through an adsorbent, such as molecular sieve, thus keeping both oil and windings dry and removing many oil oxidation products; this is a specialized method not further considered in this guide. Reclaiming This is a process which eliminates soluble and insoluble contaminants from the oil by chemical and adsorption means in addition to mechanical means, in order to restore properties as close as possible to the original values. Reclaiming is a process often performed by an oil refiner but, since in some countries reclaiming is performed by the user on site. This is a process which eliminates, by chemical and adsorbent means, the acidic and colloidal contaminants and products of oil deterioration from the oil, to obtain oil with many characteristics similar to those of a new product. Safety; Hygiene and environmental precautions The oils with which this code of practice is concerned are mineral hydrocarbon (petroleum) oils. Although no special risks are involved in the handling and use of mineral insulating oils, attention is drawn to the need for personal hygiene (washing of skin and clothing which has come into contact with oil) by those working with these products. When mineral oil has to be disposed of, certain precautions are necessary to avoid risk of environmental pollution, and legal requirements may apply. Normally, if the precautions and regulations applicable to the handling and disposal of industrial and other lubricants (e. g. automobile crank-case draining) are applied to mineral insulating oils, no problems should arise. 47 12. Revision Table for SOP (M) Revised Number SOP(M)-TSG001/R0 SOP(M)-TSG001/R1 Contents of Reason for the Date revision revision revision New issue Aug. 2008 Revision Up-gradation May. 2013 of Person in in-charge Mirza Muhammad Akram Mirza Muhammad Akram 48 13. REFERENCES The following books/literatures have been consulted for preparation of this booklet of SOPs: 1. ONTARIO HYDRO/CIDA CANADA Training manuals 2. WAPDA Specifications 3. ABB Switchgear manuals 5. IEC Standards/Specifications 6. JICA/AKC TOT Training manuals 7. Instruction Manuals of grid system equipment in NTDC/DISCOs/WAPDA 49 Mailing Address of TSG Chief Engineer (TSG) NTDC TSG Training Center, 220kV Grid Station, NKLP, Feroze Pur Road Lahore. Telephone: 042 35821418 Fax: 042 35821498 50