Copyright 2000 AIA MASTERSPEC - OUTLINE 12/00 SECTION 13915 - FIRE-SUPPRESSION PIPING 1.1 SUMMARY A. Fire-suppression piping inside the building: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 1.2 Automatic wet-type, Class [I] [II] [III] standpipe systems. Automatic dry-type, Class [I] [II] [III] standpipe systems. Semiautomatic dry-type, Class [I] [II] [III] standpipe systems. Manual wet-type, Class I standpipe systems. Manual dry-type, Class I standpipe systems. Wet-pipe sprinkler systems. Dry-pipe sprinkler systems. Preaction sprinkler systems. Deluge sprinkler systems. Combined dry-pipe and preaction sprinkler systems. SYSTEM PERFORMANCE REQUIREMENTS A. Standard Piping System Component Working Pressure: Listed for at least 175 psig ((1200 kPa)). B. High-Pressure Piping System Component Working Pressure: Listed for [250 psig ((1725 kPa)) minimum] [300 psig ((2070 kPa))]. C. Fire-Suppression Standpipe System Design: 1. Minimum Residual Pressure at Each Hose-Connection Outlet: a. b. 2. Maximum Residual Pressure at Required Flow At Each Hose-Connection Outlet: a. b. D. NPS 1-1/2 ((DN 40)) Hose Connections: [65 psig ((450 kPa))] <Insert other>. NPS 2-1/2 ((DN 65)) Hose Connections: [100 psig ((690 kPa))] <Insert other>. NPS 1-1/2 ((DN 40)) Hose Connections: [100 psig ((690 kPa))] <Insert other>. NPS 2-1/2 ((DN 65)) Hose Connections: [175 psig ((1200 kPa))] <Insert other>. Sprinkler Occupancy Hazard Classifications: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Automobile Parking Areas: [Ordinary Hazard, Group 1] <Insert other>. Building Service Areas: [Ordinary Hazard, Group 1] <Insert other>. Churches: [Light Hazard] <Insert other>. Electrical Equipment Rooms: [Ordinary Hazard, Group 1] <Insert other>. Dry-Cleaners: [Ordinary Hazard, Group 2] <Insert other>. General Storage Areas: [Ordinary Hazard, Group 1] <Insert other>. Laundries: [Ordinary Hazard, Group 1] <Insert other>. Libraries, Except Stack Areas: [Light Hazard] <Insert other>. Library Stack Areas: [Ordinary Hazard, Group 2] <Insert other>. Machine Shops: [Ordinary Hazard, Group 2] <Insert other>. FIRE-SUPPRESSION PIPING 13915 - 1 Copyright 2000 AIA 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. E. 2. 3. 4. 5. 6. Mechanical Equipment Rooms: [Ordinary Hazard, Group 1] <Insert other>. Office and Public Areas: [Light Hazard] <Insert other>. Plastics Processing Areas: [Extra Hazard, Group 2] <Insert other>. Printing Plants: [Extra Hazard, Group 1] <Insert other>. Repair Garages: [Ordinary Hazard, Group 2] <Insert other>. Residential Living Areas: [Light Hazard] <Insert other>. Restaurant Service Areas: [Ordinary Hazard, Group 1] <Insert other>. Solvent Cleaning Areas: [Extra Hazard, Group 2] <Insert other>. Upholstering Plants: [Extra Hazard, Group 1] <Insert other>. <Insert area: Insert hazard and group.> Light-Hazard Occupancy: [0.10 gpm over 1500-sq. ft. ((6.3 mL/s over 139-sq. m))] <Insert other> area. Ordinary-Hazard, Group 1 Occupancy: [0.15 gpm over 1500-sq. ft. ((9.5 mL/s over 139-sq. m))] <Insert other> area. Ordinary-Hazard, Group 2 Occupancy: [0.20 gpm over 1500-sq. ft. ((12.6 mL/s over 139-sq. m))] <Insert other> area. Extra-Hazard, Group 1 Occupancy: [0.30 gpm over 2500-sq. ft. ((18.9 mL/s over 232sq. m))] <Insert other> area. Extra-Hazard, Group 2 Occupancy: [0.40 gpm over 2500-sq. ft. ((25.2 mL/s over 232sq. m))] <Insert other> area. Special Occupancy Hazard: As determined by authorities having jurisdiction. Minimum Density for Deluge-Sprinkler Piping Design: 1. 2. 3. 4. 5. Ordinary-Hazard, Group 1 Occupancy: [0.15 gpm ((9.5 mL/s))] <Insert other> entire area. Ordinary-Hazard, Group 2 Occupancy: [0.20 gpm ((12.6 mL/s))] <Insert other> entire area. Extra-Hazard, Group 1 Occupancy: [0.30 gpm ((18.9 mL/s))] <Insert other> entire area. Extra-Hazard, Group 2 Occupancy: [0.40 gpm ((25.2 mL/s))] <Insert other> entire area. Special Occupancy Hazard: As determined by authorities having jurisdiction. G. Maximum Protection Area per Sprinkler: Per UL listing H. Maximum Protection Area per Sprinkler: 1. 2. 3. 4. 5. I. 12/00 Minimum Density for Automatic Sprinkler Piping Design: 1. F. MASTERSPEC - OUTLINE over over over over Office Spaces: [120 sq. ft. ((11.1 sq. m))] [225 sq. ft. ((20.9 sq. m))] <Insert other>. Storage Areas: [130 sq. ft. ((12.1 sq. m))] <Insert other>. Mechanical Equipment Rooms: [130 sq. ft. ((12.1 sq. m))] <Insert other>. Electrical Equipment Rooms: [130 sq. ft. ((12.1 sq. m))] <Insert other>. Other Areas: According to NFPA 13 recommendations, unless otherwise indicated. Total Combined Hose-Stream Demand Requirement: NFPA 13, unless otherwise indicated. 1. Light-Hazard Occupancies: [100 gpm ((6.3 L/s)) for 30 minutes] <Insert other>. FIRE-SUPPRESSION PIPING 13915 - 2 Copyright 2000 AIA 2. 3. 4. J. 1.3 MASTERSPEC - OUTLINE 12/00 Ordinary-Hazard Occupancies: [250 gpm ((15.75 L/s)) for 60 to 90 minutes] <Insert other>. Extra-Hazard Occupancies: [500 gpm ((31.5 L/s)) for 90 to 120 minutes] <Insert other>. <Insert other occupancy or storage class or group: Insert requirements.> Seismic Performance: NFPA 13 and [ASCE 7, "Minimum Design Loads for Buildings and Other Structures": Section 9, "Earthquake Loads."] <Insert applicable code requirement.> QUALITY ASSURANCE A. 1.4 Quality Standard: [NFPA 13] [NFPA 13R] [NFPA 14] [NFPA 24] [NFPA 230]. COMPONENTS A. Corrosion-protective encasement for piping. B. Sprinkler Specialty Fittings: UL listed or FMG approved. C. Listed Fire-Protection Valves: UL listed or FMG approved. D. Specialty Valves: 1. Sprinkler system control valves, UL listed or FMG approved. a. b. c. 2. 3. Alarm check valves. Dry-pipe valves. Deluge valves. Pressure-regulating valves. Automatic drain valves. E. Manual Control Stations: Hydraulic operation, UL listed or FMG approved. F. Control Panels: 1. 2. Type: Single-area, two-area, or single-area cross-zoned type. Manual Control Station Operation: [Electric] [Hydraulic]. G. Excess-Pressure Pumps: UL listed, positive-displacement, gear type. H. Sprinklers: UL listed or FMG approved. I. Hose Connections: [Nonadjustable] [Pressure-regulating] valve operation. J. Hose Stations: 1. 2. Valve Operation: [Nonadjustable] [Pressure-regulating] type. Fire Hose: Lined hose with couplings, gaskets, and nozzle. FIRE-SUPPRESSION PIPING 13915 - 3 Copyright 2000 AIA 3. 4. 5. 6. 7. 8. 9. MASTERSPEC - OUTLINE 12/00 Mounting: [Freestanding] [Cabinet mounted]. Type: [NPS 2-1/2 (DN 65) hose valve with hose rack] [NPS 1-1/2 (DN 40) hose valve with hose rack] [NPS 2-1/2 and NPS 1-1/2 (DN 65 and DN 40) hose valves with hose rack] [NPS 1-1/2 (DN 40) hose valve with hose reel] for NPS 1-1/2 (DN 40) hose. Hose Rack Finish: [Red enamel] [Polished chrome-plated]. Valve and Trim Finish: [Rough brass] [Rough chrome-plated] [Polished chromeplated]. Fire Hose Length: [50 feet (15 m)] [75 feet (23 m)] [100 feet (30 m)]. Nozzle: [Brass] [Polished brass] [Rough-chrome-plated brass] [Polished-chromeplated brass] [Polycarbonate plastic], adjustable from shutoff to [fog spray or straight stream] [full fog; for use on electrical fires]. Nozzle: [Brass] [Polished brass] [Rough-chrome-plated brass] [Polished-chromeplated brass] [Polycarbonate plastic], plain, for nonadjustable water stream. K. Roof Hose Cabinets: FMG-approved, low-profile type with NPS 1-1/2 (DN 40) valve and hose. L. Monitors: Stationary, single-waterway type for 750-gpm (47.3-L/s) water stream. M. Wall-Type Fire Hydrants: 1. 2. N. Fire Department Connections: 1. 2. 3. 4. O. 1.5 Flush, Wall Type: [One] [Two] [Three] [Four] <Insert other> inlet(s). Exposed, Projecting Wall Type: Two inlets. Exposed, freestanding type. Finish: [Polished chrome-plated] [Rough chrome-plated] [Polished brass]. Alarm Devices: 1. 2. 3. 4. 5. P. Type: [Flush] [Exposed, projecting]. Finish: [Polished chrome-plated] [Rough chrome-plated] [Polished brass]. Alarm: [Water-motor] [Electrically] operated. Water-flow indicator. Pressure switch. Valve supervisory switch. Indicator-post supervisory switch. Pressure Gages: UL listed, dial type. INSTALLATION A. Fire-Hydrant Flow Test: By [Owner] [Contractor]. B. Piping between Fire Department Connections and Check Valves: Galvanized, standard-weight steel pipe with [threaded] [grooved] joints. C. Underground, below Building, Service-Entrance Piping Application: Ductile-iron pipe with [push-on] [mechanical] [grooved-end] joints[ and corrosion-protective encasement]. FIRE-SUPPRESSION PIPING 13915 - 4 Copyright 2000 AIA MASTERSPEC - OUTLINE 12/00 D. Underground, below Building, Service-Entrance Piping Application: Soft copper tube with [Type K (Type A)] [Type L (Type B)] with brazed joints[ and corrosion-protective encasement]. E. Standard-Pressure, Wet-Type Standpipe Application: 1. 2. 3. 4. 5. 6. 7. F. High-Pressure, Wet-Type Standpipe Application: 1. 2. 3. 4. G. Galvanized, standard-weight steel pipe with [threaded] [grooved] joints. Galvanized, Schedule 30 steel pipe with grooved joints. Hard copper tube, [Type K (Type A) with roll-grooved] [Type L (Type B) with rollgrooved] [Type K (Type A) with brazed] [Type L (Type B) with brazed] joints. High-Pressure, Dry-Type Standpipe Application: 1. 2. I. Standard-weight [black] [black or galvanized-] [galvanized-] steel pipe with [threaded] [grooved] joints. Standard-weight black steel pipe with welded joints. Schedule 30 [black] [black or galvanized-] [galvanized-] steel pipe with [threaded] [grooved] joints. Schedule 30 black steel pipe with welded joints. Standard-Pressure, Dry-Type Standpipe Application: 1. 2. 3. H. Standard-weight [black] [black or galvanized-] [galvanized-] steel pipe with [threaded] [grooved] joints. Standard-weight black steel pipe with welded joints. Schedule 30 [black] [black or galvanized-] [galvanized-] steel pipe with [threaded] [grooved] joints. Schedule 30 black steel pipe with welded joints. Threadable, thinwall steel piping with [welded] [grooved] joints. Schedule 10 steel pipe with [grooved] [welded] joints. Copper tube, [Type K (Type A) with roll-grooved] [Type L (Type B) with rollgrooved] [Type K (Type A) with brazed] [Type L (Type B) with brazed] joints. Galvanized, standard-weight steel pipe with [threaded] [grooved] joints. Galvanized, Schedule 30 steel pipe with grooved joints. Standard-Pressure, Wet-Pipe Sprinkler System Application: 1. 2. 3. 4. 5. Sprinkler-Piping Fitting Option: Specialty sprinkler fittings, [NPS 2 ((DN 50))] [NPS 21/2 ((DN 65))] [NPS 3 ((DN 80))] and smaller, including mechanical-T and -cross fittings, may be used downstream from sprinkler zone valves. Copper-Tube Fitting Option: Copper, mechanically formed tee branches NPS 2 ((DN 50)) and smaller, with brazed joints, may be used downstream from sprinkler zone valves. Standard-weight [black] [black or galvanized-] [galvanized-] steel pipe with [threaded] [twist-locked] [grooved] joints. Standard-weight black steel pipe with welded joints. Schedule 30 [black] [black or galvanized-] [galvanized-] steel pipe with [threaded] [twist-locked] [grooved] joints. FIRE-SUPPRESSION PIPING 13915 - 5 Copyright 2000 AIA 6. 7. 8. 9. 10. 11. 12. 13. J. 2. 3. 4. 5. 6. 7. 8. 9. 2. 3. 4. 5. Standard-weight [black] [black or galvanized-] [galvanized-] steel pipe with [threaded] [grooved] joints. Standard-weight black steel pipe with welded joints. Schedule 30 [black] [black or galvanized-] [galvanized-] steel pipe with [threaded] [grooved] joints. Schedule 30 black steel pipe with welded joints. Threadable, thinwall steel piping with welded joints. Schedule 10 steel pipe with welded joints. Nonstandard OD, thinwall steel pipe with [grooved] [welded] joints. Hybrid steel pipe with [welded] [grooved] joints. Schedule 5 steel pipe with pressure-sealed joints. Sprinkler-Piping Fitting Option: Specialty sprinkler fittings, [NPS 2 ((DN 50))] [NPS 21/2 ((DN 65))] [NPS 3 ((DN 80))] and smaller, including mechanical-T and -cross fittings, may be used downstream from sprinkler zone valves. Standard-weight galvanized steel pipe with [threaded] [twist-locked] [grooved] joints. Standard-weight black steel pipe with welded joints. Schedule 30 galvanized steel pipe with [threaded] [twist-locked] [grooved] joints. Schedule 30 black steel pipe with welded joints. High-Pressure, Dry-Pipe Sprinkler System Application: 1. 2. M. Schedule 30 black steel pipe with welded joints. Threadable, thinwall steel piping with [threaded] [twist-locked] [welded] [grooved] joints. Schedule 10 steel pipe with [twist-locked] [welded] [grooved] joints. Nonstandard OD, thinwall steel pipe with [grooved] [welded] joints. Hybrid steel pipe with [welded] [grooved] joints. Schedule 5 steel pipe with pressure-sealed joints. Hard copper tube, [Type K (Type A)] [Type L (Type B)] with brazed joints. CPVC pipe with solvent-cemented joints. Standard-Pressure, Dry-Pipe, Sprinkler System Application: 1. L. 12/00 High-Pressure, Wet-Pipe Sprinkler System Application: 1. K. MASTERSPEC - OUTLINE Standard-weight galvanized-steel pipe with [threaded] [twist-locked] [grooved] joints. Schedule 30 [black] [black or galvanized-] [galvanized-] steel pipe with [threaded] [twist-locked] [grooved] joints. Sprinkler Applications: 1. 2. 3. 4. Rooms without Ceilings: [Upright sprinklers] <Insert other>. Rooms with Suspended Ceilings: [Pendent sprinklers] [Recessed sprinklers] [Flush sprinklers] [Concealed sprinklers] [Pendent, recessed, flush, and concealed sprinklers, as indicated]. Wall Mounting: Sidewall sprinklers. Spaces Subject to Freezing: [Upright sprinklers] [Pendent, dry sprinklers] [Sidewall, dry sprinklers] [Upright, pendent, dry sprinklers; and sidewall, dry sprinklers as indicated] <Insert other>. FIRE-SUPPRESSION PIPING 13915 - 6 Copyright 2000 AIA 5. 6. MASTERSPEC - OUTLINE 12/00 Deluge-Sprinkler Systems: [Upright] [Upright and pendent] [Pendent], open sprinklers. Special Applications: [Extended-coverage, flow-control, and quick-response sprinklers where indicated] <Insert other>. END OF SECTION 13915 FIRE-SUPPRESSION PIPING 13915 - 7