Preliminary Building Assessment Report STATE OF MONTANA LONG RANGE BUILDING PROGRAM MONTANA STATE UNIVERSITY-BILLINGS SCIENCE HALL SCIENCE HALL MONTANA STATE UNIVERSITY BILLINGS, MT Site Visit Date: September 19, 2008 Contact: Mr. O.E. “Eakle” Barfield Director of Facilities Services (406) 657-2309 State of Montana A&E Division Mechanical Engineer: Mark Hines State A&E Division 1520 East Sixth Avenue Provided By: CTA Architects Engineers 1143 Stoneridge Drive Bozeman, Montana 59718 Energy Engineer: Dan Stevenson, P.E. CTA Architects Engineers 1143 Stoneridge Drive Bozeman, MT 59718 (406) 556-7100 State of Montana Long Range Building Program Montana State University Abbreviated Energy Assessment Billings Campus, Science Hall Project Detail: This report is an abbreviated analysis of energy conservation projects identified with the Science Hall building located on the Billings, MT campus. These potential projects were identified as projects with a substantial energy conservation component. The same projects achieve improvements in facility maintainability and replacement of systems that are at or beyond the end of their usable life. The projects assessed include: 1. Steam heating system replacement 2. Chiller and cooling tower replacement 3. Multi-zone air handling unit replacement 4. DDC control upgrade. 5. Lighting upgrade The methods of analyzing the energy savings and costs associated with these energy conservation measures are preliminary in nature and require verification before project implementation. The compressed timeframe in which this analysis was produced may have an effect on the accuracy of cost and energy savings accuracy. The purpose of this analysis is strictly for identifying the magnitude of energy conservation potential and rough economic performance. HVAC and Controls: The existing HVAC system consists of a pair of duel deck multi-zone air handling units, one delivering 14,000 cfm supply air to the Northeast portion of the building and the other delivering 16,000 cfm to the Southwest portion of the building. Both multi-zone units installed as part of a 1976 addition are equipped with chilled water cooling and steam heating coils. These duel deck multi-zone units do not meet ASHRAE Standard 90.1-2004 because of the enormous amounts of energy wasted in the process of reheating and mixing of both cooled and heated air streams to provide temperature control. There are also approximately 11 steam fined tube radiation heaters installed as part of a 1976 addition and 21 original 1947 construction convector style steam heaters providing perimeter heat. Laboratory exhaust consists of about 16 individual laboratory exhaust fans on the roof serving 11 individual lab hoods and 4 general exhaust locations within the building. Heating energy is provided by a 1947 vintage, 2,800 MBH input fire tube steam boiler. Cooling energy is provided by a 100 ton water cooled reciprocating chiller in the basement mechanical room coupled with a cooling tower located outside adjacent the mechanical room. One of the four chiller compressors has become inoperable eliminating one of the two evaporator circuits in affect limiting overall capacity to 50 tons. The chiller and cooling tower have been in service for 30+ years and are beyond the end of their usable life. The Lecture Auditorium was renovated in 2007 at which time it was isolated from the rest of the building’s HVAC systems with a pair of 5 ton packaged rooftop units. The existing control system consists of pneumatic zone controls throughout the building. The only DDC controls are on the two new rooftop units serving the Lecture Auditorium. With exception to the Lecture Auditorium, none of the energy systems are controllable or viewable from the campus front end. State of Montana Long Range Building Program Montana State University Abbreviated Energy Assessment Billings Campus, Science Hall Lighting System: Lighting throughout the building consists of high output T12’s, 5% of which have already been upgraded to T-8’s. Energy Summary MSU ENERGY USE HISTORY - AVERAGE Science Hall Billings, MT Total Building Area: 34,040 sf ELECTRIC ENERGY Month Year kWh Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Totals 35988 38131 42683 42118 44431 45595 49874 40504 42687 40099 40025 38662 500795 EUI: Btu/sf= $/sf= STEAM Total Electric Cost (Bills) $2,159.25 $2,287.86 $2,560.98 $2,527.08 $2,665.86 $2,735.67 $2,992.44 $2,430.21 $2,561.22 $2,405.91 $2,401.50 $2,319.69 $30,047.67 198,495 Average Rates: $2.66 Fuel Type Percentage: Steam Dkt Cost TOTAL COST 771.5 743.5 663.0 458.5 175.5 39.1 7.7 6.3 107.9 544.0 730.0 801.0 5048.0 $9,258.00 $8,922.00 $7,956.00 $5,502.00 $2,106.00 $469.14 $92.58 $75.72 $1,294.20 $6,528.00 $8,760.00 $9,612.00 $60,575.64 $11,417.25 $11,209.86 $10,516.98 $8,029.08 $4,771.86 $3,204.81 $3,085.02 $2,505.93 $3,855.42 $8,933.91 $11,161.50 $11,931.69 $90,623.31 $0.0600 /kWh 25.3% electric $12.0000 74.7% /Dkt gas State of Montana Long Range Building Program Montana State University Abbreviated Energy Assessment Billings Campus, Science Hall H1 - Steam Heating System Replacement Replacement of the existing steam boiler and associated steam and condensate return piping systems with multiple, redundant, high efficiency boilers and associated heating hot water supply and return piping would increase efficiency and controlability. High efficiency hot water boilers typically operate at lower temperatures 80% of the year taking advantage of increased efficiencies up to 98% AFUE. A multiple boiler arrangement will closely match varying demand while offering freeze protection should any one of the multiple boilers fail. Estimated Cost for Steam Heating System Replacement: Demolition of existing steam boiler, Associated steam piping and trim Asbestoses pipe insulation abatement High efficiency heating hot water boiler (2@ $22,000) Heating Hot Water Pumps (2@ $4,000) Insulated supply and return piping system Subtotal Overhead and Markup @ 15% Contingency/Other @ 25% Small Project @ 10% Total Cost Estimated Annual Steam Consumption Energy Savings Estimated Annual Energy Savings Value (using current rates) Simple Payback $3,000 $5,000 $44,000 $8,000 $200,000 $260,000 $39,000 $65,000 $26,000 $390,000 744.6 DKT (15% of building total) $9,000 43.3 Years H2 - Chiller and Cooling Tower Replacement Replacement of the existing reciprocating chiller and associated cooling tower with a high efficiency screw chiller and cooling tower would increase chiller plan efficiencies. A screw chiller can modulate output to match demand to provide better efficiencies at low demand. Estimated Cost for Chiller and Cooling Tower Replacement: Demolition of existing chiller and Associated cooling tower High efficiency screw chiller Cooling tower Subtotal Overhead and Markup @ 15% Contingency/Other @ 25% Small Project @ 10% Total Cost Estimated Annual Electric Consumption Energy Savings Estimated Annual Energy Savings Value (using current rates) Simple Payback $5,000 $55,500 $20,000 $80,500 $12,075 $20,125 $8,050 $120,750 19,200 KWH (4% of building total) $1,152 148.4 Years State of Montana Long Range Building Program Montana State University Abbreviated Energy Assessment Billings Campus, Science Hall H3 - Multi-zone Air Handling Unit Replacement Replacement of the existing Multi-zone air handling units with VAV air handlers with heating hot water preheat and chilled water cooling coils. Install individual VAV boxes with hot water reheat adjacent to each air handler reusing existing supply ductwork at each zone. Medium pressure air handlers with VFD drives have the ability to reduce fan speeds to meet demand providing fan energy savings. Hot water reheat will provide tighter temperature control within each zone. Estimated Cost for Multi-zone Air Handling Unit Replacement with VAV Demolition of existing multi-zone units (2@ $2,000) Air handler with VFD drive (2@ $42,500) Pressure independent VAV boxes (25@ $1,000) Subtotal Overhead and Markup @ 15% Contingency/Other @ 25% Small Project @ 10% Total Cost Estimated Annual Electric Consumption Energy Savings Estimated Annual Steam Consumption Energy Savings Estimated Annual Energy Savings Value (using current rates) Simple Payback $4,000 $85,000 $25,000 $114,000 $17,100 $28,500 $11,400 $171,000 10,330 KWH (2% of building total) 314 DKT (6% of building total) $4,388 39 Years State of Montana Long Range Building Program Montana State University Abbreviated Energy Assessment Billings Campus, Science Hall H4 - DDC Control Upgrade Upgrade of the controls for the two airhandling units, chilled water plant control, and terminal units would allow substantial energy saving to be realized through implementation of control strategies. Some of these strategies include: 1. Implementation of unoccupied period setbacks and run time schedules. 2. Airflow volume measurement and pressure independent controls at vav terminals. 3. Hot deck temperature reset based on outside air temperature. Operation advantages of this project are also substantial. A building-wide DDC system will allow spaces to adapt to new uses and airflow/tempering energy to be optimized to the use through operator interface. Estimated Cost for DDC Upgrade: Network controller with web browser interface Chiller control and chilled water loop interface Boiler control and heating hot water interface Pump control (4@ $500) Airhandler control verification and upgrade Air terminal DDC controllers (25@ $1,000) Perimeter radiation valves (32 @ $150) Subtotal Overhead and Markup @ 15% Contingency/Other @ 25% Small Project @ 10% Total Cost Estimated Annual Electric Consumption Energy Savings Estimated Annual Steam Consumption Energy Savings Estimated Annual Energy Savings Value (using current rates) Simple Payback $10,000 $2,500 $2,500 $2,000 $50,000 $25,000 $4,800 $96,800 $14,520 $24,200 $9,680 $145,200 100,098 KWH (20% of building total) 905 DKT (18% of building total) $16,865 8.6 Years L1 - Lighting Upgrade Although not addressed in detail as part of this study, significant energy savings can be achieved by switching out the remaining 95% high output T12 fixtures to T8’s. Simple payback based on twelve hours run time per day would be roughly four to five years.