Copyright 2001 AIA MASTERSPEC - OUTLINE 12/01 SECTION 15562 - INDIRECT-FIRED H&V UNITS 1.1 SUMMARY A. 1.2 Factory-assembled, prewired, self-contained, indirect-fired, [gas] [oil] furnace H&V units[ with an evaporative cooling package,] installed [outside] [inside] the building. WARRANTY A. 1.3 Materials and Workmanship: [Five] [10] <Insert number> years for heat exchangers. COMPONENTS A. Cabinet: [Single] [Double]-wall galvanized-steel panels.[ Cabinet shall be fully weatherized for outside installation.] 1. 2. 3. 4. B. Access Panels: [Lift-out] [Piano hinged with cam-lock fasteners]. Internal Insulation: [Complete unit] [Furnace and fan sections only], [1 inch (25 mm)] [2 inches (50 mm)] thick. Discharge: [Horizontal] [Vertical] pattern. Roof Curb: [16 inches (400 mm)] <Insert dimension> high. Supply-Air Fan: Centrifugal type, with heavy-duty[, self-aligning, permanently lubricated ball bearings] [, pillow-block bearings rated for L50 or 200,000 hours with external grease fittings]. 1. 2. Motor: [Open dripproof] [Totally enclosed], single-speed motor. Mounting: In fan casing with [restrained,] [elastomeric] [spring] isolators. C. Outdoor-air hood. D. Air Filters: [1-inch- (25-mm-)] [2-inch- (50-mm-)] thick, [cleanable] [disposable-panel] type. E. Dampers: Outdoor air[ and return air]. F. Indirect-Fired Gas Furnace: 1. Burners: [Aluminized steel with stainless-steel inserts] [Stainless steel]. a. b. c. d. e. 2. 3. Gas Control Valve: [Single stage] [Two stage] [Modulating]. Fuel: [Natural] [Propane] gas. Minimum Thermal Efficiency: 80 percent. Ignition: Electronically controlled electric spark with flame sensor. High-Altitude [Model] [Kit]: For Project elevation above sea level. Venting: [Gravity] [Power]. Combustion-air intake. INDIRECT-FIRED H&V UNITS 15562 - 1 Copyright 2001 AIA 4. 5. 12/01 Heat Exchanger: [Aluminized] [Stainless] steel. Safety Controls: a. b. c. d. e. f. g. h. i. G. MASTERSPEC - OUTLINE Vent Flow Verification: [Differential pressure switch to verify open vent] [Flame rollout switch]. Control transformer. High Limit: Thermal switch or fuse to stop burner. Gas Train: Gas valve assembly containing pilot solenoid valve, [hydraulic] [electronic]-modulating temperature control valve, pilot filter, pressure regulator, pilot shutoff, and manual shutoff all in one body. Purge-period timer. Gas Manifold: Safety switches and controls to comply with ANSI standards [and] [FMG] [IRI]. Airflow proving switch. Automatic-reset, high-limit control device. Safety lockout switch. Indirect-Fired Oil Furnace: 1. 2. Heat Exchanger: Welded, [stainless ]steel. Oil Burner: Flame-retention, pressure-atomizing, forced-draft, gun type with integrated fuel pump and electronic-spark ignition. a. b. c. 3. Fuel: No. [2] <Insert number> fuel oil. Minimum Thermal Efficiency: [80] [81] <Insert number> percent. Ignition: Electronically controlled electric spark with flame sensor. Safety Controls: a. b. c. d. e. Factory piped and wired to electrical junction box mounted on unit. Oil-pressure switch. Control transformer. Cad-cell safety system. Manual reset flame safety. H. Evaporative Cooling Package: [Single] [Double]-wall cabinet[, fully weatherized for outside installation], [6-inch- (150-mm-)] [8-inch- (200-mm-)] [12-inch- (300-mm-)] thick [cellulose] [glass-fiber] media, and with a water-[circulation] [saver] system. I. Control Panel: [Surface-mounted] [Recessed, with trim ring,] remote panel. 1. 2. 3. 4. 5. 6. 7. 8. 9. [On-off] [On-off-auto] fan switch. [Summer-winter-off] [Heat-vent-cool] switch.[ Automatic changeover.] Supply-fan operation indicating light. Heating operation indicating light. Thermostat. Damper position potentiometer. Cooling operation indicating light. Dirty-filter indicating light operated by unit-mounted differential pressure switch. Safety-lockout indicating light. INDIRECT-FIRED H&V UNITS 15562 - 2 Copyright 2001 AIA MASTERSPEC - OUTLINE 12/01 J. Refer to Division 15 Section "HVAC Instrumentation and Controls" for control equipment and sequence of operation. K. Control Devices: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Remote thermostat. Remote setback thermostat. Static-pressure transmitter. Fire-protection thermostats. Timers: [Seven-day, programming-switch timer] [Solid-state, programmable time control]. Ionization-type smoke detectors. Fan Control: Interlocked with exhaust fan(s). Fan Control: Timer with [fan-discharge thermostat for units with evaporative cooling package, and] smoke detectors in supply[ and return] air. Damper Control: [Outdoor-air damper control, 100 percent outdoor-air units] [Mixed outdoor- and return-air damper control]. Temperature Control: [Factory-mounted sensor in blower outlet] [Wall-mounting, field-wired sensor] [Timer] [Two or four steps of control using one or two furnace sections in series] [20 to 100 percent modulation of the firing rate. 10 to 100 percent with dual furnace units]. Evaporative Cooling Control: [Water-circulation system with sump pump, automatic fill control, and drain control] [Water-saver system with remote thermostat to control water-supply valve and timer to activate thermostat]. DDC stand-alone control module for link between unit controls and DDC system. END OF SECTION 15562 INDIRECT-FIRED H&V UNITS 15562 - 3