Table of Contents Executive Summary 2 Introduction Background Experimental Apparatus and Procedures Safety Assumptions Calculation Flowcharts Theory 5 5 7 10 10 11 15 Discussion Experimental Objectives Trend Analysis Error Analysis 23 23 23 27 Results 29 Conclusions 36 Recommendations 38 Bibliography 39 Appendix A Operating Instructions 40 40 Appendix B Table of Nomenclature 42 42 Appendix C Jacketed Tank Calculations Graphs Sample Calculations Concentric Tube Parallel Flow Calculations Sample Calculations Concentric Tube Counter Flow Calculations Sample Calculations 44 44 44 45 46 48 48 49 52 52 53 Appendix D Raw Data 56 56 1 Executive Summary Buff Facilities Optimization Group has contracted with Team Excellence to determine the advantages and disadvantages of two types of heat exchangers. Specifically, Buff Facilities Optimization Group has asked Team Excellence to determine the amount of time required to process 50 liters of water from 20oC to 35oC in each unit. When performing the heat exchanger analysis, we obtained measurements from two types of equipment which include: A jacketed stir-tank A concentric tube in parallel and counter flow All measurements obtained throughout these experiments, allowed us to determine the overall heat transfer coefficients, effectiveness and amount of time required to heat 50 liters of water from 20oC to 35oC by each apparatus. We were then able to recommend which heat exchanger would perform best for the clients’ desired use. Through our analysis of a jacketed stir-tank and a concentric tube heat exchanger Team Excellence has concluded that the concentric tube will perform best for our clients’ specified needs. We determined made this determination by evaluating the effectiveness, overall heat transfer coefficient both theoretically and experimentally and most importantly the time required to heat 50 liters of water from 20 degrees Celsius to 30 degrees Celsius. The concentric tube heat exchanger proved to perform best throughout the experiment and all evaluation procedures. Also, we determined that in the case of limited area available for the heat exchanger itself, the concentric tube takes up a considerably less amount of space than does the jacketed stir-tank heat exchanger. 2 Through our analysis, Team Excellence has determined that the jacketed stir-tank is a very inefficient apparatus. The jacketed tank has a considerable amount of heat loss out of the top of the tank resulting in an increase in the overall heat transfer coefficient, UA, and a decrease in the effectiveness. This apparatus also takes a considerable amount of time to heat 50 liters of water from 20 degrees Celsius to 35 degrees Celsius, on the order of 180 to 205 minutes. The complete results for the jacketed stir-tank are as follows: Table I: Jacketed Stir Tank Results Run 1 Run 2 Uexp A(W/K) Uth A(W/K) ε t (s) t (min) 72.32 114.41 174.52 240.71 0.0370 0.0431 12268.00 10811.02 204.47 180.18 The large values of the theoretical and experimental overall heat transfer coefficient lead to a rather large decrease in the effectiveness of the system. The effectiveness for run 1 is about 0.037 and for run 2 the effectiveness is about 0.043. The effectiveness is a measure of how well the system operates and should lie between 0.10 and 0.30, where 0.03 to 0.04 is basically unacceptable. In contrast to the jacketed tank, the concentric tube heat exchange preformed very well throughout all evaluations and experimental procedures. We ran the concentric tube in both parallel flow and counter flow. The effectiveness of the concentric tube for both types of flow was between 0.11 and 0.22, which is considerably higher than the jacketed tank with an effectiveness of 0.03 to 0.04. The concentric tube has minimal heat loss resulting in a significant decrease in the amount of time required to heat 50 liters of water from 20 degrees Celsius to 35 degrees Celsius when compared to the jacketed tank. The jacketed tank took about 180 to 205 minutes to heat the water, while the concentric tube 3 on average took about 30 minutes, independent of the type of flow used. The complete results are as follows: Table II: Concentric Tube in Parallel Flow Results Run 1 Run 2 Run 3 UAexp (W/K) 46.03 40.39 50.34 ε 0.2056 0.1761 0.2197 UAther (W/K) 49.23 44.00 56.70 t (s) 1983.23 2313.60 1832.47 t (min) 33.05 38.56 30.54 t (s) 1767.25 2116.03 1763.65 t (min) 29.45 35.27 29.39 Table III: Concentric Tube in Counter Flow Results Run 1 Run 2 Run 3 UAexp (W/K) 47.25 41.91 49.05 ε 0.1062 0.1826 0.2156 UAther (W/K) 53.36 34.84 36.68 By evaluating tables I, II and III we clearly see the best arrangement for our clients would be to use the concentric tube in counter flow using run 3. Run 3 of our experiment for the concentric tube in counter flow had a cold water flow rate of 2.68 L/min and a hot water flow rate of 4.21 L/min. The effectiveness for this procedure was 21.56%, which is within expected range and a considerably good value. The amount of time required to heat 50 liters of water from 20 degrees Celsius to 35 degrees Celsius is about 29.4 minutes, which is about 6 to 7 times less than that of the jacketed tank. 4 Introduction Background Buff Facilities Optimization Group has contracted with Team Excellence to determine the overall heat transfer coefficients, effectiveness and the advantages and disadvantages of two types liquid-liquid of heat exchangers. Specifically, Buff Facilities Optimization Group has asked Team Excellence to determine the amount of time required to process 50 liters of water from 20oC to 35oC in each unit. The analysis of heat exchangers involves many aspects of heat and mass transfer. Convection caused by internal and external flow, conduction, radiation, condensation and evaporation are all important concepts to consider. Industrially, heat exchangers are widely used to increase the conversion of reactants to products by increasing or decreasing the reactor temperature. The first apparatus evaluated by Team Excellence was a jacketed tank heat exchanger. This apparatus consists of a water reservoir and stir propeller surrounded by a tube of hot flowing fluid. The path of heat transfer for a jacketed tank is from the tube to the bath and also from the fluid motion caused by stirring the water bath. In this system we have convection through the tube. The second apparatus evaluated by Team Excellence was a concentric tube heat exchanger in parallel and counter flow. A concentric tube is a tube within a tube or a double pipe. In this system, hot and cold fluids move in the same (parallel flow) or opposite (counter flow) directions. In our case, the hot fluid runs through the outer tube while the cold fluid runs through the inner tube keeping in mind that this can run 5 opposite. The heat transfer of a concentric tube is between hot and cold fluids throughout the tube and consists of convection. To determine the amount of time required to heat the water from 20oC to 35oC we first determined the overall heat transfer coefficient, UA. The overall heat transfer coefficient was determined by use of inlet and outlet temperatures and flow rates for both hot and cold fluids. The temperatures of all fluids throughout this experiment were measured by thermocouples at all inlet and outlet areas. Using the centerline temperatures we were then able to determine the heat capacity, viscosity, thermal conductivity and Prandtl number for each fluid. These values, assumed to be constant, are then used to find the experimental and theoretical overall heat transfer coefficients and the effectiveness of each system. After determining the overall heat transfer coefficient we were then able to determine the effectiveness and time required to heat water from 20 degrees Celsius to 35 degrees Celsius by each system. By comparing these values we were then able to give our recommendation of which heat exchanger would work best for our clients’ desired use. 6 Experimental Apparatuses and Procedures When performing the heat exchanger analysis, we obtained measurements from two types of equipment. These measurements allowed us to determine the amount of time required to heat 50 liters of water from 20oC to 35oC by each apparatus. We also determined the advantages and disadvantages of each heat exchanger as well as the effectiveness and overall heat transfer coefficients. The two types of equipment involved in our analysis were a jacketed tank and a concentric tube in both parallel and counter flow. Operating instructions for both apparatuses can be found in Appendix A. The jacketed tank experiment consisted of a water reservoir and stir propeller surrounded by a tube of hot flowing fluid, as seen in Figure 1 on page 8. There are thermocouples at the inlet and outlet areas of the tube and a thermocouple in the bath itself. Also, there is a control box that measures the flow rate of hot water through the tube. The computer records measurements of temperature and the fluid flow rate through the tube. The propeller speed remains constant during each experiment and is measured by a hand-held tachometer. The concentric tube was the second heat exchanger that we evaluated. The concentric tube consists of a tube within a tube connected to the flow rate control box that is connected to both hot and cold water sources, as seen in Figure 2 on page 9. The inlet and outlet temperatures, for both hot and cold flow, are measured by thermocouples and recorded by the LabView program. The fluid flow rates remain constant throughout each experiment, but are varied for each separate experiment. These flow rates are measured and recorded by LabView. 7 HOT WATER RESERVOIR HOSE COLD WATER PUMP CONTROL BOX Valves Hot Water Flowmeter LabView Cold Water Flowmeter Drain Thermocouples 20” 12” HEAT EXCHANGER HOT WATER OUT TOP VIEW COLD WATER OUT HOT WATER IN COLD WATER IN Figure 1: Jacketed Stir Tank Heat Exchanger 8 HOT WATER RESERVOIR HOSE COLD WATER PUMP LabView CONTROL BOX Valve s Hot Water Flowmeter Cold Water Flowmeter Drain COLD WATER OUT ¾” Copper Pipe, ½” Copper Pipe 20” 12” 16” HOT WATER OUT 12” HOT WATER IN Thermocouples COLD WATER IN Figure 2: Concentric Tube Heat Exchanger 9 Safety There are a couple of obvious safety concerns involved with this lab. First and most importantly, this experiment involves water and electricity, which are a dangerous combination. It is important to keep the area as dry as possible and report any leaking equipment immediately. Also, in regards to the flow meter, which has a temperature limit of 50 degrees C and a flow rate limit of 10 L/minute. Deviations above these limits could lead to the burning out of electrical equipment, but more importantly mixing of water and electricity. Assumptions To calculate values associated with this experiment, the following assumptions were made: Jacketed Tank Negligible kinetic and potential energies Constant fluid properties Negligible tube to wall thermal resistance and fowling factors Fully developed flow conditions Concentric Tube Negligible heat loss to the surroundings Negligible kinetic and potential energies Constant fluid properties Negligible tube to wall thermal resistance and fowling factors Fully developed flow conditions 10 Calculation Flowcharts Jacketed Tank All calculations completed throughout the analysis of the jacketed tank are as follows: Experimental Overall Heat Transfer Coefficient Determination mh = mass flow rate of hot fluid mc = mass flow rate of cold fluid Di = diameter of tank (jacketed) Do = diameter of helical tubes (jacketed) Di = inner diameter of annulus (concentric) Do = outer diameter of outer tube (concentric) Do,i = inner diameter of outer tube (concentric) = viscosity Re = Reynolds number Nu= Nusselt Number Pr = Prandtl Number hi = heat transfer coefficient for inner fluid ho = heat transfer coefficient for outer fluid k = thermal conductivity Cp = heat capacity = density U = overall heat transfer coeff. q = heat transfer rate = efficiency Tm = (Tc,i + Tc,o)/2 Tmf = mean temperature of cold fluid final Tm,i = mean temperature of cold fluid initially Tci = temperature of cooling water in Tco = temperature of cooling water out Thi = temperature of hot water in Tho = temperature of hot water out T∞ = temperature of water in tank Nr= stir speed of propeller Lp = length of propeller t = time Ai = area of heat transfer inside Ao = area of heat transfer outside Energy Balance: . mc C p dT UA(Tm T ) dt Let θ = Tmf -T∞ θi = Tm,i - T∞ d θ = dT Integrating: Ln θ / θi = 1/(UA/mc *Cp) *t Measure Tco, Tci, T Plot ln θ / θi vs time Slope =1/ (-UA/ mc /Cp) Calculate U: U =1/ ( -slope* mc *Cp/A) Compare the calculated U values to theoretical U obtained using the following literature correlations 11 Jacketed Tank Calculation Flow Chart Continued Theoretical Overall Heat Transfer Coefficient L2 p N r hi * 0.54 * Di kf 2 3 cp * k 13 ho kf Do * b w 1 1 1 1 UA hi Ai ho Ao Effectiveness of Jacketed Tank Cmin = mc*Cpc qactual = mccp,c(Tc,o-Tc,i) qmax = Cmin(T∞-Tc,i) qactual/qmax 12 4 mc Re D * .23 * Re .8 * Pr 3 * ( Theoretical U can be calculated: Calculate effectiveness: . 0.14 b .14 ) w Concentric Tube All calculations completed throughout the analysis of the concentric tube are as follows: Experimental Overall Heat Transfer Coefficient Tlm q mc c p ,c (Tc ,o Tc , I ) (Th ,o Tc ,o ) (Th,i Tc ,i ) ln(( Th,o Tc ,o ) /(Th,i Tc ,i )) Experimental U can be calculated: q UATlm Theoretical Overall Heat Transfer Coefficient Re 4m h Di Nui .023 Re hi Nu i 4 5 Hydraulic diameter D h Do Do , i Pr 0.4 Re o k Di 4m c Dh Nuo .023 Re 4 5 ho Nu o Theoretical U can be calculated: 1 1 1 UA hi Ai ho Ao 13 Pr 0.4 k Dh Concentric Tube Calculation Flow Chart Continued Effectiveness of Concentric Tube Cmin = mc*Cpc or Cmin = mh*Cph qactual = mccp,c(Tc,o-Tc,i) qmax = Cmin(Th,i-Tc,i) Calculate effectiveness: qactual/qmax 14 Theory When performing the heat exchanger analysis, we obtained measurements from two types of equipment. These measurements allowed us to determine the advantages and disadvantages of each heat exchanger as well as the effectiveness and overall heat transfer coefficients. Most importantly were are able to use the above findings to determine the amount of time required to heat 50 liters of water from 20oC to 35oC by each apparatus. The two types of equipment involved in our analysis were a jacketed tank and a concentric tube in both parallel and counter flow. An overall heat transfer coefficient is needed in order to determine the effectiveness of each unit. The overall heat transfer coefficient is a quantity of the rate at which heat is transferred and is calculated differently for each heat exchanger. Given energy balances and appropriate correlations, a theoretical overall heat transfer coefficient, found in literature, can be compared to an experimentally measured overall heat transfer coefficient yielding the effectiveness of the system. The overall heat transfer coefficient, UA, is dependent upon the different modes of heat transfer. These three modes consist of conduction, convection and radiation. For the two apparatuses that we analyze we can ignore the effects of conduction and radiation. Instead, we will concentrate on two different forms of convection: convection due to internal flow convection due to external flow A general correlation for the overall heat transfer coefficient, UA, is as follows: R" f ,i ln( Do / Di ) R" f ,o 1 1 1 UA hi Ai 2kL Ao h0 Ao Ai 15 eq. (1) [1] eq. (1) relates the inverse of the overall heat transfer coefficient, UA, to the heat transfer of the individual heat transfer modes as a sum of the resistances. The first term in equation (1) represents the inverse of the convection coefficient due to internal tubular flow, hi, multiplied by the internal tube’s surface area, Ai. The second term represents the fouling factor inside of the tube, R”f,i. The fouling factor is a measures the buildup of a film or other deposits that could affect the heat transfer rate. The third term in equation (1) measures the effect of conduction through the tube. Di and Do are the inner and outer tube diameters, L is the length of the tube and k is the thermal conductivity of the tube. The fourth term in equation (1) is a measurement of the fouling factor outside of the tube, R”f,o, divided by the outside surface area of the tube, Ao. The last term is the inverse of the convection coefficient due to condensation, ho, multiplied by the outside surface area of the tube, Ao. Measuring, calculating or using literature values for all of the above quantities will result in determining a theoretical value for the overall heat transfer coefficient, UA. Jacketed Tank Convection in a heat exchanger is due to heat transfer occurring between two fluids in motion at different temperatures separated by a bounding surface layer. In order to calculate the theoretical value of the internal convection coefficient, hi, the following correlation is needed. A convection coefficient, hi, correlation for internal flow is as follows: hi kf Di * .54 * ( L2p N r 2 )3 *( Cp k 16 1 )3 *( b .14 ) w eq. (2) [2] eq. (2) takes into account both the thermal conductivity of the fluid, kf, the length of the propeller, Lp, the stir speed of the propeller, Nr, the density of the fluid, , the heat capacity of the fluid, Cp, and the viscosity, , of the fluid. The next value to calculate is that of the convection coefficient due to external flow, ho; which can be calculated using the following correlation: ho kf .8 D0 1 3 * .23 * Re * Pr * ( b .14 ) w eq. (3) [2] eq. (3) contains the Reynold’s number, Re, that relates the tube diameter to the flow rate. The Reynold’s number, Re, can be calculated by the following equation for a jacketed tank: . 4 mc Re D eq. (4) [1] . where m c in eq. (4) is the mass flow rate of the water. Equation (3) also contains the Prandtl number, Pr, which is a dimensionless ratio of the kinematic viscosity of the fluid and the fluid’s thermal diffusivity. Pr eq. (5) [1] Once equations (4) and (5) are calculated, a value for ho can then be generated. We will now consider the fouling factor, R”f, terms in equation (1). A common value for the fouling factor for water is 0.0001 m2K/W, which we can divide by the premeasured outer area of the tube. The fouling factor inside of the tube, R" f ,i , is unknown. Once equations (2), (3), (4), and (5) have been calculated, a theoretical overall heat transfer coefficient, UA, can be obtained by use of equation (1). 17 An experimental overall heat transfer coefficient, UAexp, is to be determined next, which will require an energy balance around the fluids being cooled and heated. For the jacketed tank: . mc C p dT UA(Tm T ) eq. (6) [1] dt where Tm in equation (6) is the mean temperature of the cold fluid and T is the temperature of the water in the tank. Since the temperature distribution is dependent on the time, integration is necessary. To simplify terms, let: Tm, f T i Tm,i T d dT Substitution and integration leads to: mc * C p ) * t eq. (7) i UA Ln( The plot of ln( ) versus time will give a slope equal to mc*Cp / (-UA). With this value i of the slope in hand, we are then able to solve for the experimental overall heat transfer coefficient, UA. Having obtained both the theoretical and experimental overall heat transfer coefficients, the effectiveness can now be calculated using the following correlation: q actual UAexp q max UAtheor eq.(8) [1] qactual is the heat transfer rate through the system and is found using: . qactual mc C p,c (Tc,o Tc,i ) eq. (9) [2] 18 qmax is the maximum heat transfer rate possible through the system and can be obtained using: . qmax mc C p,c (T Tc,i ) eq. (10) [2] Values obtained from equations (9) and (10) are inserted into equation (8). The resulting value of the effectiveness, , will quantify the quality of experimental data and the apparatus itself. Lastly, the time taken to drain the tank needs to be calculated. The time can be obtained from a relationship involving the volumetric flow rate and the volume. This equation takes the form: t V eq. (11) o [1] This time correlation will be used to determine the amount of time required to heat 50 liters of water from 20 degrees Celsius to 35 degrees Celsius. Therefore, the volume, V, will be 50 liters. The volumetric flow rate, vo, is determined by use of the following correlation: o qc eq. (12) C pc c T [1] where Cpc is the heat capacity of the fluid, c is the density of the fluid and T is the temperature difference 15 degrees Celsius of the fluid. Substitution of these known values into equation (11) will give the requested draining time. 19 Concentric Tube The theoretical overall heat transfer coefficient for the concentric tube is also calculated using equation (1). The differences are in the method for calculating the convection coefficients, hi and ho. The internal convection coefficient, hi, can be calculated using an internal flow equation: 4 5 Nu .023 * Re * Pr .4 eq. (13) [2] This correlation contains both the Reynolds number, Re, and the Prandtl number, Pr, which can be found using equations (4) and (5) respectively. Once the Nusselt number, Nu, is known, we can find the internal tube flow convection coefficient, hi using the following correlation: hi Nu * k D eq. (14) [2] The outer tube flow convection coefficient, ho, can also be obtained using equations (13) and (14). The difference lies in the calculation of the Reynolds number. The procedure for calculating the Reynolds number still follows equation (2), except this time the diameter is different. For this correlation we need the hydraulic diameter, Dh, which is the difference between the tube’s outer diameter and inner diameter. After calculating the hydraulic diameter, the remaining calculations are straightforward. The fouling factors, Rf”, and the effects of conduction are calculated in the same manner as for the jacketed tank. With all of this information, it is now possible to obtain a value for the theoretical overall heat transfer coefficient, UA. The experimental overall heat transfer coefficient can be found by performing an energy balance: 20 q UATlm eq. (15) [2] q is the heat transfer rate through the concentric tube and can be found by performing the following energy balance: . q mc * C p,c (Tc,o Tc,i ) eq. (16) [2] . Equation (16) contains the mass flow rate of the cold fluid, m c , the heat capacity of the cold fluid, Cp,c, and the temperature difference, final minus initial, (Tc,o-Tc,i). The last value needed in order to calculate the experimental overall heat transfer coefficient, UAexp, is the log mean temperature difference, Tlm . The log mean temperature is defined numerically as: Tlm (Th ,o Tc ,o ) (Th ,i Tc ,i ) ln(( Th ,o Tc ,o ) /(Th ,i Tc ,i ) eq. (17) [2] It is now possible to calculate the experimental overall heat transfer coefficient, UA, using equation (15). This value is then compared the theoretical value obtained earlier to determine the effectiveness,, by the following equation: q actual UAexp q max UAtheor eq. (18) [2] where qactual in equation (18) is determined from equation (9) and qmax can be calculated using equation (10). When calculating qmax, a value of Cmin is necessary. The value of Cmin is either: . C min mc * C p ,c or . C min mh * C p ,h 21 Cmin along with the values calculated from equations (9) and (10) are then used to determine the effectiveness,, of the system found in equation (18). Again, the time taken to drain the tank needs to be calculated. The time can be obtained from a relationship involving the volumetric flow rate and the volume. This equation takes the form: t V eq. (11) o [1] The volume is already a known quantity of 50 liters given by the clients. The volumetric flow rate can be found from the following correlation: o qc eq. (12) C pc c T [1] where Cpc is the heat capacity of the fluid, c is the density of the fluid and T is the temperature difference of 15 degrees Celsius. Substitution of these known values into equation (12) will determine the amount of time required to heat 50 liters of water from 20 degrees Celsius to 35 degrees Celsius or any other specified rates. 22 Discussion Experimental Objectives The objective throughout this experiment is to analyze two types of heat exchangers to determine the experimental and theoretical overall heat transfer coefficient and effectiveness of each heat exchanger. Also, determine which heat exchanger can heat 50 liters water from 20 degrees Celsius to 35 degrees Celsius in the shortest amount of time. These findings will help us to determine which heat exchanger will perform best for the clients’ specified use. Trend Analysis A few trends were evident in our analysis of the heat exchangers. The jacketed tank heat exchanger seemed to have more heat transfer as the stir speed increased. This trend, shown in Figure 3 below, was the expected result, because as the stir speed increases the convection coefficient of the water bath increases, which results in an increase in the heat transfer rate. Experimental UA and Effectiveness versus Stir Speed for Jacketed Tank 140 Ex per 120 im ent 100 al UA (W/ 80 K) 60 0.05 0.045 0.04 Eff 0.035 ect ive 0.03 ne 0.025 ss 0.02 0.015 40 0.01 20 0.005 0 0 100 120 140 160 180 200 Stir Speed (rpm) Figure 3: Experimental UA and effectiveness versus the stir speed. 23 Effectiveness Exp UA Another trend for the jacketed tank was that the time required to heat 50 liters of water by 15 degrees Celsius increased with a decrease in stir speed, which directly corresponds to the heat transfer rate, as seen in Figure 4 below. This decrease was the expected result that the time would decrease with an increase in the heat transfer rate. Time versus Stir Speed for the Jacketed Tank 210 205 t (min) 200 195 190 185 180 175 100 120 140 160 180 200 Stir Speed (rpm) Figure 4: Jacketed tank plot of time versus stir speed. The results for the concentric tube heat exchanger exhibited trends that were similar for the counter flow and the parallel flow cases. The trends followed a polynomial curvature, indicating that either a maximum or a minimum occurred corresponding to changes in flow rate. The heat transfer rate increased when the flow rate difference increased from a minimum of 0 kg/s to a maximum of 0.025 kg/s and then proceeds to decrease. These observations can be seen in Figure 5 for parallel flow and Figure 6 for counter flow below: 24 60 0.3 50 0.25 40 0.2 30 0.15 20 0.1 10 0.05 0 0 0.01 0.02 0.03 0.04 Effectiveness Exp UA Effectiveness and Experimental UA versus Difference between Cold and Hot Water Flow Rates for Parallel Flow Effectiveness Exp UA 0 0.05 Difference (kg/s) Figure 5: Effectiveness and experimental UA versus difference between cold and hot water flow rates for parallel flow. 60 0.3 50 0.25 40 0.2 30 0.15 20 0.1 10 0.05 0 0 0.01 0.02 0.03 0.04 Effectiveness Exp UA Effectiveness and Experimental UA versus Difference between Cold and Hot Water Flow Rates for Counter Flow Exp UA Effectiveness 0 0.05 Difference (kg/s) Figure 6: Effectiveness and experimental UA versus the difference between the cold and hot water flow rates for counter flow. As seen in Figures 5 and 6 above, the effectiveness and overall heat transfer coefficients exhibit maximum values of 0.217 and 48.74 W/K, respectively, at a flow rate difference of 0.025 kg/s. Starting at a flow rate difference of 0, the heating time also exhibits a polynomial trend as seen in Figure 7 for parallel flow and Figure 8 for counter flow below. 25 Time versus the Difference between the Cold and Hot Water Flow Rates for Paralell Flow 45 40 35 t (min) 30 25 20 15 10 5 0 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 Difference (kg/s) Figure 7: Time versus the difference between the cold and hot water flow rates for parallel flow. Time versus Difference between the Cold and Hot Water Flow Rates for Counter Flow 45 40 35 t (min) 30 25 20 15 10 5 0 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 Difference (kg/s) Figure 8: Time versus the difference between the hot and cold water flow rates for counter flow. As seen in Figures 7 and 8 above the time is a maximum at flow rate difference of 0 it then decreased to a minimal until reaching a difference of 0.025 kg/s and then increases as it reaches a difference of 0.045 kg/s. This trend was the expected result of increasing the heat transfer rate, which should decrease the amount of time needed to heat a cold water stream from 20 degrees C to 35 degrees C. 26 Error Analysis In this experiment, the main source of error was from our assumption that each heat exchanger was adiabatic. This assumption was more accurate for the concentric tube heat exchanger than for the jacketed stir-tank heat exchanger. The adiabatic assumption was more accurate for the concentric tube because the theoretical values for the overall heat transfer coefficient, UA, were closer to the experimental values than when comparing the same the values for the jacketed stir-tank. However, not one of our experiments had exactly the same experimental overall heat transfer coefficient, UA, as the theoretical overall heat transfer coefficient, UA. This situation demonstrates that neither heat exchanger was completely adiabatic. Heat loss was evident from the experimental overall heat transfer coefficient, UA, being smaller than the theoretical overall heat transfer coefficient, UA, which means that there was other heat transfer occurring rather than just convection from the hot water to the cold water in the heat exchanger. Also, the jacketed stir-tank was less adiabatic than the concentric tube heat exchanger because the jacketed tank had a significant amount of heat loss through the top of the tank. The only barrier between the top of the tank and the ambient air was a piece of aluminum foil. Although, the foil helped decrease the amount heat loss, it is not a great insulator because it conducts heat quite rapidly. Therefore, heat was lost by conduction through the aluminum out of the top of the tank combined with convection from the air. The concentric tube heat exchanger had some heat loss, but less than the jacketed stir-tank. The heat was probably lost by conduction through the copper walls of the 27 concentric tube heat exchanger. In contrast to the jacketed stir-tank, there was more metal in between the air and the water inside the concentric tube heat exchanger. This increase in metal thickness insulated the heat exchanger more efficiently. Also, copper conducts heat less heat than aluminum foil resulting in less heat transfer. One other factor in the favor of the adiabatic assumption for the concentric tube heat exchanger was that the hot water ran through the outer annulus and the cold water ran through the inner of the annulus. This situation allowed for maximum heat transfer between the cold and hot water. If the hot and cold were switched, then the heat from the hot water would have a longer distance to conduct through the copper to the outside air, which would decrease heat loss. Overall, neither heat exchanger was totally adiabatic, but the concentric tube had less heat loss than the jacketed stir-tank. In order for the adiabatic assumption to be valid, each heat exchanger would have to be insulated very well and vacuum tight to avoid convection from air. This task would be quite expensive and time consuming. Another easier way to analyze the heat exchangers is to account for the heat loss. The heat loss can be accounted for by measuring the temperature of the air and the temperature of the surface of the heat exchanger being exposed to the air. These observations would allow for an overall energy balance to be performed and calculate the more accurate theoretical overall heat transfer coefficient, UA. 28 Results Jacketed Tank The first step in the analysis of the jacketed tank heat exchanger was to evaluate the experimental overall heat transfer coefficient, UA, and effectiveness as a function of the stir speed of the stir propeller in the tank, as shown in Figure 3 below. Experimental UA and Effectiveness versus Stir Speed for Jacketed Tank 140 0.05 0.045 0.04 100 0.035 0.03 80 0.025 60 0.02 0.015 40 Effectiveness Experimental UA (W/K) 120 Effectiveness Exp UA 0.01 20 0 100 0.005 0 120 140 160 180 200 Stir Speed (rpm) Figure 3: Experimental UA and effectiveness versus the stir speed. Figure 3 demonstrates that the stir speed directly affects the overall heat transfer coefficient and the effectiveness of the jacketed tank. As shown in Figure 3, decreasing the stir speed caused the effectiveness of the heat exchanger to decrease, meaning that the heat transfer between the cold and hot fluid also decreased. Also, Figure 3 demonstrates that the overall heat transfer coefficient, UA, increased with an increase stir speed, which corresponds to an increase the heat transfer between the cold and hot fluid. This situation makes sense physically, since the increase in stir speed should increase the convection inside the stir tank, hence increasing the overall heat transfer. Considering these findings, 29 we thought that the time to heat 50 liters of water by 15 degrees Celsius would decrease with an increase in stir speed, as Figure 4 below shows this assumption is true. Time versus Stir Speed for the Jacketed Tank 210 205 t (min) 200 195 190 185 180 175 100 120 140 160 180 200 Stir Speed (rpm) Figure 4: Jacketed tank plot of time versus stir speed. Figure 4 shows that the time needed to heat 50 liters of water from 20 degrees Celsius to 30 degrees Celsius actually decreased with the stir speed, and thus decreased with the heat transfer rate. This result makes sense because an increase in heat transfer should heat up the water faster. However, evaluating the heat loss out of the top of the tank, stirring the tank more should cause less heat loss to the surroundings resulting in a higher UA value. The preceding situation causes faster stir speeds to heat the water faster. The jacketed stir tank definitely takes a large amount of time to heat 50 liters of water than the concentric tube. According to our calculations, the time required for heating the water by 15 degrees Celsius is about 180 to 205 minutes. The theoretical overall heat transfer coefficient, UA, was calculated for each stir speed of the jacketed tank and the results are given in Table IV. 30 Table IV: Jacketed Stir Tank Results Run Speed Theoretical UA(W/K) 1 115 rpm 174.52 2 192 rpm 240.71 Uncertainties +/-1 rpm +/-.05 Experimental UA (W/K) 72.32 114.41 +/-.05 Table I shows that the experimental overall heat transfer coefficient, UA, was marginally less than the theoretical overall heat transfer coefficient, UA. This situation was more than likely due to the assumption that the apparatus operated adiabatically. While minimizing heat loss from the top of the tank with aluminum foil, we were unable to completely prevent heat loss. Therefore, our adiabatic operation assumption is flawed. Concentric Tube The parallel flow concentric tube heat exchanger analysis begins by evaluating the experimental overall heat transfer coefficient, UA, and effectiveness as they relate to the difference between the cold water and hot water flow rates, as shown in Figure 5. 60 0.3 50 0.25 40 0.2 30 0.15 20 0.1 10 0.05 0 0 0.01 0.02 0.03 0.04 Effectiveness Exp UA Effectiveness and Experimental UA versus Difference between Cold and Hot Water Flow Rates for Parallel Flow Effectiveness Exp UA 0 0.05 Difference (kg/s) Figure 5: Effectiveness and experimental UA versus difference between cold and hot water flow rates for parallel flow. 31 Figure 5 shows that the experimental overall heat transfer coefficients, UA, and effectiveness increase as the difference between the hot and cold water flow rates increase. This increase occurs until UA and the effectiveness reach a maximum value at a flow rate difference of about 0.025 kg/s, they then begin to decrease. The time to heat 50 liters of water by 15 degrees Celsius was also calculated for this condition and is depicted in Figure 7 below. Time versus the Difference between the Cold and Hot Water Flow Rates for Paralell Flow 45 40 35 t (min) 30 25 20 15 10 5 0 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 Difference (kg/s) Figure 7: Time versus the difference between the cold and hot water flow rates for parallel flow. Figure 7 shows that the time to heat the 50 liters of water decreases as the heat transfer rate and effectiveness increase. By evaluation of Figures 5 and 7, the optimum difference between the hot and cold flow rates for parallel flow is to about 0.025 kg/s. According to our calculations, the time required for heating the water by 15 degrees Celsius in the parallel flow concentric tube is about 30 minutes. The theoretical overall heat transfer coefficient, UA, was calculated for the parallel flow concentric tube heat exchanger, and the results are in the following Table V. 32 Table V: Concentric Tube Parallel Flow Results Run Difference (kg/s) Theoretical UA (W/K) 1 2 3 Uncert. Experimental UA (W/K) 49.23 44.00 56.7 +/-.05 0.046 0.0003 0.0254 +/-.005 46.03 40.39 50.34 +/-.05 The theoretical overall heat transfer coefficients, UA, for the parallel flow were only slightly larger than the experimentally determined values. This suggests that there was minimal heat loss from this heat exchanger to the surrounding. Therefore, our assumption of adiabatic operation holds true. The concentric tube heat exchanger was also evaluated for counter flow operation. The effectiveness and experimental overall heat transfer coefficient, UA, versus the difference between the flow rates is shown in Figure 6. 60 0.3 50 0.25 40 0.2 30 0.15 20 0.1 10 0.05 0 0 0.01 0.02 0.03 0.04 Effectiveness Exp UA Effectiveness and Experimental UA versus Difference between Cold and Hot Water Flow Rates for Counter Flow Exp UA Effectiveness 0 0.05 Difference (kg/s) Figure 6: Effectiveness and experimental UA versus the difference between the cold and hot water flow rates for counter flow. Figure 6 has a similar trend to Figure 5. As the difference between the cold and hot water flow rates increased the overall heat transfer coefficient, UA, and effectiveness increased to a certain maximum point, again around 0.025 kg/s. Therefore, the heat transfer rate for 33 the concentric tube is independent of the type of flow. The difference in flow rates of the concentric tube should be about 0.025 kg/s to achieve optimal heat transfer. The time to heat 50 liters of water was calculated for the counter flow case and is illustrated in Figure 8 below. Time versus Difference between the Cold and Hot Water Flow Rates for Counter Flow 45 40 35 t (min) 30 25 20 15 10 5 0 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 Difference (kg/s) Figure 8: Time versus the difference between the hot and cold water flow rates for counter flow. Figure 8 demonstrates that the time to heat the 50 liters of water is a minimum at a flow rate difference of 0.025 kg/s. Also, Figure 8 shows that the time started to slightly increase with an increase in flow rate difference. The time to heat the water was again much less than the jacketed stir tank, taking around 28 minutes as opposed to 180 to 205 minutes. The theoretical UA values were calculated for the counter flow case and are summarized in Table VI. Table VI: Concentric Tube Counter Flow Results Run Difference (kg/s) Theoretical UA (W/K) 1 52.98 0.0438 2 34.56 0.0006 3 36.36 0.0245 Uncert. +/-.05 +/-.005 34 Experimental UA (W/K) 46.97 41.66 48.74 +/-.05 Table VI shows that the theoretical overall heat transfer coefficient, UA, values were slightly larger than the experimental UA values. This situation shows that the adiabatic assumption is not completely accurate. 35 Conclusions The concentric tube heat exchanger heated the water in a shorter amount of time than the jacketed stir-tank. This situation makes sense because the jacketed stir-tank is a batch process. A batch process has a large amount of fluid volume on the inside of the tank compared to a much smaller amount of volume of hot fluid flowing through the tubes surrounding the tank. This tank has much less surface area of heat transfer than the concentric tube. The concentric tube has more surface area of heat transfer because the hot fluid is flowing constantly over the cold fluid. A similar amount of volume flows through the outer and inner annulus of the concentric tube, allowing for much greater heat transfer. For these reasons the experimental and theoretical overall heat transfer coefficient, UA, for the jacketed-stir tank is much larger than that of the concentric tube. By evaluating complete results listed in tables I, II and III below, with a heating time of about 29.4 minutes we clearly see the best arrangement for our clients would be to use the concentric tube in counter flow Run 3. Run 3 of our experiment on the concentric tube in counter flow had a cold water flow rate of 2.68 L/min and a hot water flow rate of 4.21 L/min. The effectiveness for this procedure was 21.56%, which is within expected range and a considerably good value. Table I: Jacketed Stir Tank Results Run 1 Run 2 Uexp A(W/K) Uth A(W/K) ε t (s) t (min) 72.32 114.41 174.52 240.71 0.0370 0.0431 12268.00 10811.02 204.47 180.18 t (s) 1983.23 2313.60 1832.47 t (min) 33.05 38.56 30.54 Table II: Concentric Tube in Parallel Flow Results Run 1 Run 2 Run 3 UAexp (W/K) 46.03 40.39 50.34 UAther (W/K) 49.23 44.00 56.70 36 ε 0.2056 0.1761 0.2197 Table III: Concentric Tube in Counter Flow Results Run 1 Run 2 Run 3 UAexp (W/K) 47.25 41.91 49.05 UAther (W/K) 53.36 34.84 36.68 37 ε 0.1062 0.1826 0.2156 t (s) 1767.25 2116.03 1763.65 t (min) 29.45 35.27 29.39 Recommendations Overall, we have two different recommendations for the use of the heat exchangers based on the clients’ needs. If the clients desire to run the apparatus continuously or for long periods of time, the concentric tube heat exchanger would be their best option. The concentric tube is the best choice for this situation because it does not require any downtime for setup or shut down; the opposite is true for the jacketed stirtank. Likewise, if the clients wish to heat large amounts of water at any one time quickly, then their best option would be a concentric tube heat exchanger because of its ability to heat large amounts of water quickly. One other concern for the clients to consider is how much space they have available for the heat exchanger. Concentric tube heat exchangers are generally smaller than jacketed stir-tanks and are therefore the best option when dealing with a limited amount of space. The best arrangement for our clients would be to use the concentric tube in counter flow use run 3. Run 3 of our experiment on the concentric tube in counter flow had a cold water flow rate of 2.68 L/min and a hot water flow rate of 4.21 L/min., which corresponds to a flow rate difference of 0.025 kg/s. The effectiveness for this procedure was 21.56%. The time required to heat water from 20 degrees Celsius to 35 degrees Celsius is 29.4 minutes using the above arrangement. 38 Bibliography 1. Chemical Engineers’ Handbook Perry, Robert; Chilton, Cecil H. McGraw-Hill Book Company New York, 5th edition 1973 Section 11 2. Fundamentals of Heat and Mass Transfer Incropera, Frank P.; DeWitt, David P. John Wiley & Sons, Inc. New York, 5th edition 2002 Chapter 11 39 Appendix A Operating Instructions: Modular Heat Exchanger Set Up for Jacketed Tank 1) Verify all drains are closed and then fill the water reservoir on the main cart of the heat exchanger with a mixture of hot and cold water from the sink. 2) Set the main cart for the heat exchanger next to the spigot and drain. Verify all valves are closed and all switches are off. 3) Make the following electrical connections: plug the thermocouple control box into the large extension cord hanging by the vertical I-beam, verify all connections, plug the military connecter into the labview. 4) Turn the unit on. 5) Set the hot water setpoint using the “up” and “down” arrows on the “heater control”. 6) Open the bypass valve and turn on the pump and both heaters. Allow water to circulate until the desired temperature is met. Set up for Concentric Tube Heat Exchanger 1) Attach thermocouples directly to the heat exchanger entrance and exit. 2) Place one flowmeter downstream of the heat exchanger on the hot stream and one upstream of the exchanger on the cold side. 3) Connect a hose to the “cold water in” port on the right side. 4) Connect the “cold water out” port to the inlet of the cold flowmeter. 5) Connect the exit of the flowmeter to a thermocouple fitting and then to the cold water inlet in the heat exchanger. 6) Connect the cold water exit of the heat exchanger directly to the second thermocouple fitting. 7) Connect this fitting to the clear tubing labeled “drain” and return to floor drain. 8) Connect the “hot water out” port to a thermocouple fitting and connect the fitting directly to the hot water inlet on the heat exchanger. 9) Connect a second thermocouple fitting to the hot water exit of the heat exchanger and then to the inlet of the “hot” flowmeter. 10) Plug flowmeter cables into the back of the control box. 11) Open LabView. 12) Enter thermocouple channels and time intervals when we want data taken. Operation 1) Start the flow of water. 2) Turn on the cold water, close the bypass valve, and open the “cold water out” valve, the “hot water out” valve, and the “hot water return” valve. Use regulators to monitor flowrate, never exceeding 10 L/min. 3) Verify that the temperatures and flowrate data are visible. 40 4) If after a while the tank heaters cannot keep up with cooling capability of the exchanger, circulate the water in the tank until the temperature stabilizes. Clean Up 1) 2) 3) 4) Turn off all heaters, pumps and the main power switch. Disconnect all wires and tubing. Drain each side of the exchanger, the water reservoir, and each piece of tubing. Clean up any water on the floor. 41 Appendix B Nomenclature Description Symbol Units Value area of heat transfer inside m2 calculated area of heat transfer outside m2 calculated A (tubes) surface area of helical tubes m2 calculated A (tank) h (tank) surface area of jacketed tank height of the jacketed tank m2 m calculated measured Di inner diameter of the tubes m measured m m m m m m m kg/s kg/s measured measured measured calculated measured measured measured specified specified Ai Ao Do outer diameter of the tubes D (tank) diameter of jacketed tank Do (tubes) outer diameter of the helical tubes Dh hydraulic diameter of tubes L (tubes) length of the jacketed tank tubes L length of the concentric tubes Lp propeller length m (dot), c mass flow rate of cold fluid m (dot), h mass flow rate of hot fluid μ Re Nu Pr viscosity reynolds number nusselt number prandtl number hi convective heat transfer coefficient of inside W/m2K calculated convective heat transfer coefficient of outside W/m2K calculated k Cmin thermal conductivity minimum heat capacity rate W/m2K W/K looked up calculated Cp heat capacity J/kgK looked up density kg/m3 looked up U overall heat transfer coefficient W/m2K calculated qactual heat transfer rate from experiment W calculated qmax ε maximum heat transfer rate possible effectiveness Th (bar) centerline temperature of hot fluid K calculated Tc (bar) centerline temperature of cold fluid K calculated Tm mean temperature K calculated Tm,f final mean temperature of cold fluid K calculated Tm,i initial mean temperature of of cold fluid K calculated Tci temperature of cooling water in K specified Tco temperature of cooling water out K specified ho ρ N*s/m2 looked up dimensionless calculated dimensionless calculated dimensionless calculated 42 W calculated dimensionless calculated Symbol Nomenclature (cont) Description Units Value Thi temperature of hot water in K specified Tho T∞ temperature of hot water out temperature of water in tank K K specified specified Nr t stir speed of propeller time ΔTlm log mean temperature K calculated V (tank) volume of jacketed tank m3 measured V volumetric flow rate for concentric tube m3 /s calculated rpm measured seconds calculated 43 Appendix C Jacketed Tank Calculations Jacketed Tank Parameters h (tank) 0.2445 m D (tank) 0.2020 m A (tank) 0.1552 m2 Lp 0.0630 m Do (tubes) 0.0160 m L (tubes) 11.23 m A (tubes) 0.5645 m V(tank) = 6.231 L Temperature (oK) Stir Motor Run 1 Run 2 Flow (L/min) 4.12 4.17 Tc,o 284.09 283.04 Tc,i 283.20 282.04 T(inf) 307.22 305.21 Speed (rpm) 115 192 Run 1 Run 2 Tc (bar) 283.65 282.54 Cp,c (J/Kg K) 4191.2 4193.2 mu (N s/m2) 1.27E-03 1.32E-03 k (W/m K) 0.644 0.643 Pr 9.16 9.48 Run 1 Run 2 mdot,c (kg/s) 0.06873 0.06948 Time(s) 2116.015 2340 Slope -8.00E-07 -5.00E-07 Uexp A(W/K) 72.32 114.41 Run 1 Run 2 hi (W/m2/K) 1147.45 1595.27 ho (W/m2/K) 15628.13 15493.17 1/UA (K/W) 0.00573 0.00415 Uth A(W/K) 174.52 240.71 Run 1 Run 2 Cmin (W/K) 4.801 4.856 qactual (W) 4.270 4.848 qmax (W) 115.29 112.53 ε 0.03704 0.04308 V (L/s) Run 1 Run 2 0.004075645 0.004624912 t (s) 12268.00 10811.02 Uexp A(W/K) Uth A(W/K) ε t (s) t (min) 72.32 114.41 174.52 240.71 0.0370 0.0431 12268.00 10811.02 204.47 180.18 Run 1 Run 2 44 p (kg/m3) 1000 1000 Ln(Theta/Theta i) versus Time for 115 rpm 1 0.8 y = -8E-07x + 0.0012 0.6 Ln(Theta/Theta i) 0.4 0.2 0 0 500 1000 1500 2000 2500 -0.2 -0.4 -0.6 -0.8 -1 Time (s) Ln(Theta/Theta i) versus Time for 192 rpm 1.000000 0.800000 y = -5E-07x + 0.0008 0.600000 Ln (Theta/Theta i) 0.400000 0.200000 0.000000 0 500 1000 1500 -0.200000 -0.400000 -0.600000 -0.800000 -1.000000 Time (s) 45 2000 2500 46 47 Concentric Tube Parallel Flow Concentric Tube Parameters Ai 0.0264 m2 Ao 0.0425 m2 Di 0.0138 m Dh 0.0084 m Do 0.0222 m L 0.6100 m Temperature (K) Run 1 Run 2 Run 3 Flow 0 (L/min) 5.44 2.67 2.66 Flow 1 (L/min) 2.71 2.72 4.24 Tc,o 286.68 289.90 291.83 Th,o 316.83 318.81 320.79 Tc,i 282.50 282.59 282.56 Th,i 326.36 327.14 327.44 Run 1 Run 2 Run 3 Tc (bar) 284.59 286.25 287.20 Cp,c (J/Kg K) 4189.7 4187.8 4186.8 µ (N s/m2) 1.24E-03 1.19E-03 1.16E-03 k (W/m K) 0.589 0.592 0.594 Prc 8.93 8.5 8.26 ρc (Kg/m3) 1000 1000 1000 Run 1 Run 2 Run 3 Th (bar) 321.60 322.98 324.11 Cp,h (J/Kg K) 4180.6 4181.2 4181.6 µ (N s/m2) 5.61E-04 5.48E-04 5.37E-04 k (W/m K) 0.642 0.643 0.644 Prh 3.658 3.56 3.48 ρh (Kg/m3) 988.53 987.95 987.56 Run 1 Run 2 Run 3 m(dot),c (Kg/s) 0.0906 0.0445 0.0443 m(dot),h (Kg/s) 0.0446 0.0448 0.0697 qc (W) 1588.32 1361.51 1718.99 qh (W) 1778.93 1560.48 1939.71 qmean (W) 1683.62 1461.00 1829.35 Delta Tlm 36.58 36.17 36.34 Run 1 Run 2 Run 3 ReD,c 7343.1 7544.3 11979.5 NuD,c 47.8 48.4 69.4 hi,c (W/m2 K) 2225.3 2252.9 3236.8 ReD,h 11075.10 5664.75 5791.09 NuD,h 94.96 54.46 54.79 ho,h (W/m2 K) 6658.59 3837.80 3874.67 Cmin (J/s*K) 186.66 186.24 185.55 qmax (W) 8187.45 8297.30 8326.80 V (m3/s) 2.5211E-05 2.1611E-05 2.7286E-05 V (L/s) 0.02521 0.02161 0.02729 UAther (W/K) 49.23 44.00 56.70 ε 0.2056 0.1761 0.2197 t (s) 1983.23 2313.60 1832.47 t (min) 33.05 38.56 30.54 Uther (W/m2 K) Run 1 1842.50 Run 2 1650.57 Run 3 2130.48 Run 1 Run 2 Run 3 UAexp (W/K) 46.03 40.39 50.34 48 49 50 51 Concentric Tube Counter Flow Concentric Tube Parameters Ai 0.0264 m2 Ao 0.0425 m2 Di 0.0138 m Dh 0.0084 m Do 0.0222 m L 0.6100 m Temperature (K) Run 1 Run 2 Run 3 Flow 0 (L/min) 5.35 2.69 2.68 Flow 1 (L/min) 2.75 2.76 4.21 Tc,i 281.92 282.02 282.29 Th,o 317.35 318.53 320.81 Tc,o 286.69 289.94 291.83 Th,i 326.73 326.89 327.14 Run 1 Run 2 Run 3 Tc (bar) 284.30 285.98 287.06 Cp,c (J/Kg K) 4196.7 4188 4186.9 µ (N s/m2) 1.25E-03 1.20E-03 1.17E-03 k (W/m K) 0.589 0.592 0.593 Prc 9.013 8.57 8.3 ρc (Kg/m3) 1000 1000 1000 Run 1 Run 2 Run 3 Th (bar) 322.04 322.71 323.98 Cp,h (J/Kg K) 4180.8 4181 4181.6 µ (N s/m2) 5.5701E-04 5.5044E-04 5.3800E-04 k (W/m K) 0.642 0.643 0.644 Prh 3.63 3.58 3.49 ρh (Kg/m3) 988.34 988.04 987.56 Run 1 Run 2 Run 3 m(dot),c (Kg/s) 0.0891 0.0449 0.0447 m(dot),h (Kg/s) 0.0453 0.0455 0.0692 qc (W) 1782.44 1488.64 1786.07 qh (W) 1779.18 1589.95 1832.72 qmean (W) 1780.81 1539.29 1809.39 Delta Tlm 37.69 36.73 36.89 Run 1 Run 2 Run 3 ReD,c 6484.86 3400.73 3472.96 NuD,c 62.11 36.32 36.47 hi,c (W/m2 K) 2613.27 1535.93 1544.71 ReD,h 12957.58 13160.24 20485.33 NuD,h 66.03 66.57 94.13 ho,h (W/m2 K) 5298.63 5350.87 7577.50 Cmin (J/s*K) 374.06 187.92 187.07 qmax (W) 16761.75 8432.01 8390.72 V (m3/s) 2.82926E-05 2.36292E-05 2.83503E-05 V (L/s) 0.02829 0.02363 0.02835 UAther (W/K) 53.36 34.84 36.68 ε 0.1062 0.1826 0.2156 t (s) 1767.25 2116.03 1763.65 t (min) 29.45 35.27 29.39 Uther (W/m2 K) Run 1 1750.12 Run 2 1193.38 Run 3 1283.13 Run 1 Run 2 Run 3 UAexp (W/K) 47.25 41.91 49.05 52 53 54 55 Appendix D 56