Florida Reliability Coordinating Council Relay Class John White System Protection Manager Ray Dawson System Protection Technician Introduction • The reasons for protection • Safety of the public and employees. • Reliability of power supply to the customers. • Prevent damage to equipment. • What kind of equipment is protected: generators, transformers, transmission lines, breakers and distribution lines. 1 Types of faults • Three phase, three phase to ground, phase to phase, phase to phase to ground and single phase to ground. • Three phase faults have the highest fault current. • Single phase faults have the lowest fault current. • The fault current is determined by the impedance of the fault path. • Fault paths closer to the source will have less impedance. • Faults caused by trees will have higher impedance. Equipment used • • • • • • • • CT current transformer PT potential transformer Transducers Time overcurrent relay/51 Instantaneous Over current relay/50 Undervoltage relay/27 Recloser relay/79 Under frequency relay/81 2 CT current transformer • The secondary winding has a standard • • rating of 5 amp. It’s indicated as 400/200/5 the 400 and 200 are the primary current which gives us an 80 to 1 and 40 to 1 ratio respectably. It is important that CTs be accurate at fault levels which may be 10 times normal load current. Standard classifications of CTs allow 10% error for current flow up to 20 times rated value. They are marked “Class C ###“. The higher the number the higher current that can flow though the CT and still be 10% accurate. Never open a live CT circuit without first shorting the secondary side. Without the secondary side shorted very high voltage will be seen on the secondary circuit. Potential Transformers PT’s • The secondary voltage is usually 69V for relaying and 120V for metering. • There is no problem with error readings as during a fault the voltage will drop. • At above 115KV coupling capacitors are used. This is called CCVT. They are connected in series causing a voltage drop across each cap. • PT’s should never be shorted. 3 Transducers • Measure voltages and currents and converts them to a 0 to 1 milliamp dc output. • A scaling is used in SCADA (supervisory control and data acquisition) to convert the milliamp signal to a numerical number. Time Over current relay/51 • Operate on the electromagnetic induction principle. The protective relay is essentially a small AC motor. Using shaded pole produce two fluxes that are at different phase angles. • When current is passed through the electromagnet coil,a magnetic field is produced, which applies a torque to the disc. When the magnetic field becomes strong enough to overcome friction in the damping magnet, bearing and tension in the spiral spring, the disc rotates to move the moving contact. Eventually the moving and fixed contacts close, completing the trip coil circuit to the breaker. 4 Time Over current relay/51 • The disc rotates at a speed directly proportional to the amount of flux induced into it by the electromagnet. • The time dial provides adjustment for how long it takes the moving contact and stationary contact to make contact. With a higher number on the time dial, this increases traveling distance and contact time. • The spiral spring is use to set minimum pickup, resets the disc in normal conditions or after a trip and provides a temporary path for the DC trip current. The spiral spring is not designed to carry the trip current for very long. A seal-in bypass is used. 5 Time Over current relay/51 • The seal in coil is in series with the contacts on the spiral spring. The seal in coil contacts are in parallel with the spiral spring contacts. The seal in contacts shunt the current away from the spiral spring contacts. • The seal in coil also has a flag that drops to indicate which relay had the overcurrent condition. 6 Instantaneous Over current relays/50 • Instantaneous relays have no time delay. With a high level fault the instantaneous unit will operate before time overcurrent relay. • It’s a simple clapper relay with a core screw on top to adjust the pickup range. • The contacts are two moving contact on a bridge and two stationary contacts. The contacts are directly across the trip circuit for the breaker. Undervoltage relays/27 • The construction of a undervoltage relay is very similar to an overcurrent relay. The main different is the operating coil. An overcurrent relay’s operating coil is wound with a few turns of heavy wire. A voltage relay’s operating coil is wound with many turns of fine wire. • The disc rotates in the counterclockwise direction. • The contact closing torque for an undervoltage relay is provided by the tension in the spiral spring. • A time delay is the same as for an over current relay. 7 DEVICES USED AT OUC • • • • • • • • • • • • • • • • • • 21 Distance relay 25 Synchronizing-check device 27 Undervoltage relay 43 Manual transfer or selector device 50 Instantaneous overcurrent relay 51 Time overcurrent relay 52 AC circuit breaker 57 Grounding device 59 Overvoltage relay 63 Gas pressure relay 64 Ground protective relay 67 AC directional overcurrent relay 69 Permissive control device 74 Alarm relay 79 Reclosing relay 81 Frequency relay 86 Locking-out relay 87 Differential protective relay The right man for the job Mr. Bill Douglas 8 OUC SYSTEM OUC Protective Relay Statistics • • • • • • • 60 Transmission Lines 4000 Protective Relays 36 Substations 14 Generators 400 Breakers 200 Transformers 200 Feeder Breakers 9 OUC Protective Relay main schemes • • • • • • Protects Transmission Lines Protects Distribution Lines Protects Transformers Protects Generators Protects Busses Protects Reactors 10 Stanton Substation 11 S**t Happens 12 13 FAULT CHARACTERISTICS Test Question # 11 TYPES of FAULTS : •Single Phase to Ground •Two Phase to Ground •Three Phase to Ground •Phase to Phase •Phase to Phase to Phase Impedance Diagram FAULT Voltage= 22800 volts Load Z (one leg)= 70 ohms I= 300 amps Test Question # 12: 22800 volts / 3 ohms of fault impedance= 7600 amps. 14 Ground current possibly damages generator before 50 G relay operates. Ground Fault Current circulates from the load to the generator stator unimpeded. 15 Resistance, Reactance, Impedance Resistance-(R) The opposition to the flow of current in an electrical circuit. Reactance-(X) Impedance- (Z)Combination of Resistance and A measure of opposition to a sinusoidal current made up of Capacitance and inductance Reactance that opposes flow of current. Test Question # 13 Test Question #14: Reactor/Resistor limits fault current to about 10 amps preventing damage to stator. 16 •Utility standard of Delta Wye configuration for GSU transformer prevents fault current from circulating through stator. •GSU boosts voltage for ease of transmission- 20kV to 230kV. Voltages and Currents are 120 degrees between phases. During fault Voltage A-n collapses and Current A-n increases dramatically. 17 Disturbance recording VA • Part of System Protections responsibilities is to analyze fault data acquired from the microprocessor based protective relays such as the examples shown. VB VC IA IB IC R1 Trip Brkr 757 R2 Trip Brkr 759 R3 SCADA RS1 Op R6 757 RI N/A R7 759 RI N/A R9 757 BF Init File: J:\System Protection\Faults and oscillographys\SECA 6,20,03\SECA,6,20,03. Generator Protection OUC uses high speed generator schemes that isolates the fault in the Generator in approximately 2 cycles clearance (.033 seconds). Generator Relay Generator GSU Transformer 150,000 volt Breaker 507 To OUC system 509 150,000 volt Breaker FAULT 18 GENERATOR PROTECTION Test Question # 15 TYPES of Generator Faults : •Stator Fault •Motoring by loss of Prime Mover •Rotor Ground •Excitation Failure •Over-voltage/ Over-excitation •Turbine Trip •87G- Generator Differential •87T- GSU Transformer Differential •87ST- Reserve Auxiliary Differential. 19 Test Question #16: VAR= Volt Ampere Reactive •40- Loss of Field Relay •81- Under frequency Relay •59-Under Voltage Relay. With loss of field condition, Generator cannot produce VARS, lowering terminal voltage and overheating of the stator. •46- Negative Sequence Relay 20 •59G- Generator Ground Relay •27G- Third harmonic supervision Relay Test Question # 17: Third Harmonic is at 180 HZ TRANSFORMER PROTECTION Test Question # 18 Types of Transformer Faults : •Winding to Winding Fault •Winding to Ground Fault •Core Movement •Bushing Failure •Arrestor Failure •Through Fault 21 Transformer Protection • Relay Set 1 and 2 are high speed current differential schemes isolates the faulted transformer. Approximately 2 cycle clearance (33 milliseconds) • KBCH digital Current Differential relays for RS1. • T60 GE microprocessor Current Differential for RS2 • Also uses Backup Overcurrent Protection in RS2 Differential relay 507 SWGR 10 XFMR 509 FAULT Transformer Damage Curve Test Question # 19: Transformer damaged in 50 seconds at 20,000 Amps 22 Transformer Differential Relay General Electric T60 UR Differential relay Primary Current Flow Normal Operation 23 Fault Current Flow Fault Condition Transformer Protection • OUC uses a high speed current differential scheme that isolates faulted substation transformers in approximately 2 cycles clearance (.033 seconds) Differential relay 150,000 volt Breaker switchgear To customers 13,000 volt Breaker 507 10 509 FAULT transformer 150,000 volt Breaker 24 Test Question #20: 51 G Ground Relay located in ground leg of the low side of the transformer Test Question # 21: 87T – Transformer Differential Relay 63 – Sudden Pressure Relay 51- Over-current Back Up Relay low side 50/51 - Over-current Back Up Relay high side 25 TRANSMISSION LINE PROTECTION Test Question # 22 Types of Transmission Line Faults : •Single Phase to Ground •Two Phase to Ground •Three Phase to Ground •Phase to Phase •Phase to Phase to Phase •Arrestor Failure •Through Fault 26 Transmission Line Protection • Relay Set 1 is high speed current differential schemes isolates the faulted segment of a transmission line. Approximately 2 cycle clearance (33 milliseconds) • L90 digital Current Differential relays used by OUC. • Also uses Direct Transfer Trip for Breaker Failure Fiber communication L90 L90 501 507 FAULT 503 509 Transmission Line Protection • OUC uses high speed current differential schemes that isolates the faulted segment of a transmission line in approximately 2 cycles clearance (.033 seconds). •The relays communicate over the OUC fiber Optic Network Protective Relay 501 Fiber communication Transmission Breaker Protective Relay Transmission Breaker 507 Transmission Breaker 509 Transmission Line 503 Transmission Breaker FAULT 27 Transmission Line Protection • Relay Set 2 is high speed directional impedance relay that isolates the faulted segment of a transmission line using Permissive Overeach Transfer Trip Test Question # 23: Zone 1 set at 95% of transmission line Zone 2 set at 125% of transmission line T1 T1 P442 Zone 1 95 % of line 501 503 P442 507 Zone 2 125 % of line FAULT 509 Directional distance relay Remote Substation Substation Length of Line = 10. 7 miles Line Impedance – Positive sequence - .20 + j 1.11 Zero sequence - 1.97 + j 3.55 28 Under Load Conditions no Trip outside of zone. During fault, impedance moves into trip zone For short transmission lines we use Reactance Relays that operate at 90 degrees between voltage and current. 29 Line Current Differential Relay General Electric L90 UR Relay Line Current Differential Relay 30 Fault Line Current Differential Relay Trip Conditions 31 Description of Substation Automation INTERNET OUC CUSTOMER CORPORATE NETWORK OUC INTRANET Firewall CORPORATE USER PERSHING OPERATIONS CONTROL CENTER REMOTE (EMERGENCY) CONTROL ROOM Firewall ENERGY MANAGEMENT SYSTEM TRANSMISSION SYSTEM WIDE AREA NETWORK BACKUP ENERGY MANAGEMENT SYSTEM (ALL SUBSTATIONS) MODEM LINE SUBSTATION FUTURE SYSTEMS RELAYS SUBSTATION AUTOMATION SYSTEM MODEM LINE PROGRAMMABLE LOGIC CONTROLLERS REMOTE TERMINAL UNITS Comparison of Electro-Mechanical to Microprocessor-Based Protective Relays 32 Advantages of Electromechanical •Lower Cost Test Question # 24: •Easier to Test Disadvantages of Electromechanical •Need three individual relays •Maintain more often •Moving Parts •Usually performs only one protective function •Slower operating than Micro-Processor Based Advantages of Micro-Processor Based •Performs hundreds of protective functions •Only one relay needed for all phases •Faster operating than Electromechanical •Self-Monitoring Test Question # 25: •Takes up less space •Longer maintenance cycle Disadvantages Micro-Processor Based •Higher Cost •Complex training for testing 33 How a Micro-Processor Based Relay works. Test Question # 26: It takes an analog signal from PT’s and CT’s and converts it into digital data for analysis. How a Micro-Processor Based Relay works. Analog data under Sine Wave is converted to digital data and analyzed by the processor 34 How a Micro-Processor Based Relay works. The microprocessor in the relay analyzes millions of bits of data per second and determines if the amplitude is sufficient to trip. All in 18 milliseconds or less. Converted into Digital samples Analog data Customer Feeder Protection • OUC uses a high speed microprocessor feeder relay that isolates faulted customer feeder in approximately 3 cycles clearance (.050 seconds) Main relay Feeder relay 150,000 volt Breaker 13,000 volt Breaker 13,000 volt Breaker 11 501 10 503 switchgear FAULT transformer 150,000 volt Breaker 35