Winnipeg Information Bulletin 2006-001-E 2006 CANADIAN ELECTRICAL CODE CHANGES, POWERPOINT PRESENTATION See the subsequent pages to view Ken Oertel’s PowerPoint presentation from the electrical code seminar at the Fort Rouge Leisure Centre on March 22, 2006. March 22, 2006 Issued by: Ken Oertel, Chief Electrical Inspector Development & Inspections Division, Planning Property & Development Department 65 Garry Street • Winnipeg • Manitoba R3C 4K4 koertel@winnipeg.ca Page 1 of 1 2006 Canadian Electrical Code Changes Ken Oertel, Chief Electrical Inspector Mike Anderson, Plan Examination Engineer Shirley Jenken, Plan Examiner CET John Barnes, Chief Housing Inspector Lloyd Mah, Housing Inspector 1 Today's Seminar Highlights of Changes in the 2006 CEC. The delta symbol or triangle signifies a change to the rule. There are now no references to the imperial system of measurements. 2 General Arrangement of Rules Subdivision of rules. 2002 CE Code Rules are subdivided in the manner illustrated by Rules 8202 and 8-206 and the subdivisions are identified as follows: 00-000…………………….Rule (1) ……………………Subrule (a) ……………….Paragraph (i) ………… Subparagraph (A) ………………Clause 3 General Arrangement of Rules Subdivision of Rules - 2006 CE Code Rules are subdivided in the same manner but are now identified as follows: 00-000………………………..Rule (1) ……………………….Subrule (a) ……………………… Item (i) ………………………. Item (A) ……………………….Item 4 Section 0 (Amended) Accredited Field Evaluation Agency A Change has been made in the City of Winnipeg amendments. This change recognizes agencies that are accredited by the Standards Council of Canada as field evaluation agencies that perform assessments on electrical equipment. 5 2-006 Annual Electrical Permit Amendment to allow annual electrical permits to holders of an “A” or “B” contractors licence. The permit is for minor work such as changing light fixture ballasts,wiring motors, or making changes to a product assembly line. It is specific to one site. (Palliser, Casino, Home Depot etc.) Separate electrical permits are required for capital works or renovations. 6 2-006 (continued) The contractor is responsible for maintaining a record of work done and the inspector will attend the building, either as called or on a quarterly basis, to inspect all work that has been done, and to ensure the appropriate fees are being applied. 7 2-102(3) Rebuilt Equipment Except as provided in Subrule (4) the requirements of Part 2 of the CEC that apply to new electrical equipment shall also apply to rebuilt and rewound equipment. Rebuilt or refurbished molded case circuit breakers or molded case switches shall not be considered approved. 8 2-128 Flame Spread Requirements for Totally Enclosed Non-metallic Raceways The National Building Code of Canada allows totally enclosed nonmetallic raceways not exceeding 175 mm in outside diameter, or equivalent cross-sectional area, to be used in noncombustible buildings, as long as the raceway has a flame spread rating of FT4. This is an increase from 120 mm. There is no change in size limit when penetrating fire separations as per NBC 3.1.9.3.(2) 9 2-128 Flame Spread Requirements for Totally Enclosed Non-metallic Raceways 10 2-130 Sunlight Resistance Requirements Insulation on electrical conductors and cables and nonmetallic raceways can deteriorate when exposed to direct rays of sunlight creating a shock and fire hazard. This rule requires that all products exposed to the rays of the sun be approved and marked for exposure to the direct rays of sunlight to ensure their designed performance. Marking will be the letters “SR”. Nexans cable is marked “OUTDOOR”. 11 2-306 Shock and Flash Protection The City of Winnipeg, Property and Development Department has deleted this rule in the amendments to the code. This rule was deleted because it was not enforceable. We do anticipate that this rule will be amended again to reinstate it at a later date. 12 2-306 Shock and Flash Protection 13 4-008(3) Sheath Currents in Singleconductor Metal-sheathed Cables. This common (manufacturer’s recommended) installation practice for single conductor MI cables has now been included as a new Subrule (3) in this Rule. 14 4-028 Identification of Insulated Neutral Conductors up to and Including No. 2AWG There are now no conditions in Subrule (1) as to when the insulated neutral conductor must be identified by a white or natural grey covering, i.e. part of a low-voltage consumer’s service up to 200A. It must be white or natural grey or three continuous white stripes because it is readily available. Conductors with a continuous white covering are not sunlight resistant as required by Rule 2-130. When the insulation on a neutral conductor is exposed to sunlight the type with three continuous white stripes is allowed to be used. 15 8-304 Maximum Number of Outlets Per Circuit This rule is the old rule 12-3000. There are no changes to the rule other than its location in the book. 16 10-204(4) Grounding Connections for Alternating-current Systems There has been a change to allow the size of the grounded conductor, if paralleled, to be smaller than no.1/0. 17 10-406(6) Non-electrical Equipment In areas where there are raised floors, such as computer rooms, the floor assembly, if of conductive material and with wiring under the floor, shall be bonded. The conductor shall be no smaller than No.6 AWG.copper and installed in a manner that the flooring panels or materials form an effective equipotential plane. There is an Appendix B note that gives an explanation of the intent. 18 10-700 Grounding Electrodes Item 10-700(2)(a) for manufactured rod grounding electrodes is amended in the City of Winnipeg By-law. Manufactured grounding electrodes shall be: 2 copper-clad rod electrodes. 15.8mm in diameter. Spaced no less than 3m apart. Bonded together sized to Table 17 Driven to full length of the rod. The two local amendments are that the rods must be copper clad and 15.8 mm in diameter. The remainder of the rule remains the same. 19 10-700 (continued) In-situ (in place) grounding electrodes. In-situ grounding electrodes are parts of a building’s infrastructure which fulfill the same function as manufactured grounding electrodes. Examples of in-situ grounding electrodes are: Underground metal water piping systems Metal water well casing 20 10-702 Spacing and Interconnection of Grounding Electrodes Multiple electrodes. Separated at least 2m from each other. Bonded with No.6 AWG copper. 21 10-806(4) Installation of System Grounding Conductors Magnetic materials enclosing grounding conductors must be bonded at both ends. Minimum No.6 will be required to avoid mechanical injury. 22 10-806(4) Installation of System Grounding Conductors (continued) 23 10-812 Grounding Conductor Size for AC Systems Table 17 used to determine size. Reference to Table 18 has been removed and Table 18 has also been removed. Table 17, maximum size now #2/0. Examples: 200 A residential service using #2/0 conductors (200 amp), No.6 AWG acceptable for grounding. 200 A commercial service using #3/0 conductors (210 amp), No. 3 AWG required for grounding. 24 10-814 (1) Bonding Conductor Size Table 16, heading of left hand column. Subrule (3), if paralled can be smaller than 1/0. 25 12-516(2)(c) Protection for Cable in Concealed Installations The requirement to support the cable so that it was isolated from metal studs when running parallel to the stud has been removed. 26 12-1500 and 12-1502 Electrical nonmetallic tubing Underground use in accordance to 12-012. If subject to damage must be protected. 27 14-114 Application of Supplementary Protectors Supplementary protectors are not suitable for the protection of branch circuit conductors. A circuit breaker: automatically protects a branch circuit from both overload and short circuit currents. protects wiring and itself. requires manual on/off contacts. A supplementary protector: automatically provides some overcurrent protection, but may not protect completely against short circuits. provides some protection for wiring, but may not protect itself. does not require manual/off contacts. 28 29 14-114 Application of Supplementary Protectors (continued) 30 22-700 Sewage Lift and Treatment Plants Rules 22-700 to 22-710 for sewage lift and treatment plants were in the City of Winnipeg amendments for many years and have now been incorporated into the CEC, word for word. 31 24-106(3) Receptacles in Basic Care Areas Appendix B now makes reference for the requirement of a GFCI as Section 26 requirements are now brought in here. Paragraph (c) has been deleted. Rule 26-700(11) now makes reference to the GFCI requirements for all receptacles within 1.5 m of sinks. 32 24-116 Receptacles Subject to Standing Fluids on the Floor or Drenching of Work Area. GFCI required or, Supplied from an isolated system. 33 26-000 Reserved for Future Use The original Rule 26-000 has now been moved to 26-142. No change other than that. 34 26-242(2) Outdoor Transformer Installations The intent and requirements have not changed.The wording has been rearranged so that it is clearer. 35 26-700(8) Receptacles (General) Where existing ungrounded outlets are to be replaced with a grounding type receptacle, all buildings are now included in the requirements. 36 26-700(11) Receptacles (General) All 15A and 20A receptacles within 1.5m of sinks now have to be GFCI protected. Includes all sinks in residential, commercial, and industrial applications. This would include kitchen sinks, slop sinks, laundry sinks, sinks that may be installed in labs, etc. 37 38 26-710(h) Receptacles for residential occupancies (General) Receptacle for cord connected hydromassage tub to be installed not less than 300mm from floor. 39 26-712(d)(iii), (iv), (v) Receptacles for Dwelling Units Reference to 20 A T-slot receptacles is now here, 26-726 has been removed. Each permanent island counter 600mm or longer and 300mm or more wide requires a receptacle. Each peninsula 600mm or longer and 300mm or more wide requires a receptacle. 40 41 26-714 Receptacles for Single Dwellings This rule is amended by adding Item (c ). At least one receptacle shall be provided for each driveway. 42 26-720(f) Branch Circuits for Residential Occupancies The ampere rating of the branch circuit wiring for 20A Tslot receptacles shall be not less than 20A. This is relocated from old rule 26-726 43 26-722(b) Branch Circuits for Dwelling Units The requirement was that adjacent receptacles shall not be connected to the same circuit. This has been removed. This was the old 26-722(b)(iii). 44 45 26-724 Branch circuits for single dwellings This rule is amended by adding Item (c) – At least one branch circuit shall be provided solely for receptacle(s) for the driveway in accordance with 26-714(c). 46 26-956(1)(d) Submersible Pumps Installed in Lakes, Rivers, and Streams Ground fault protection is now required for submersible pumps, not a GFCI protected circuit. GFCI protects people. Ground fault protection protects equipment. 47 30-308(4) Circuit Connections The rule requires that a disconnecting means integral with the fluorescent luminaire be supplied on circuits exceeding 150 volts to ground. (I.e.: 347 V) This rule is deleted by the City of Winnipeg by-law. It is anticipated to be reintroduced in about one year. 48 30-320(3) Lighting Equipment in Damp Locations or Near Grounded Metal Switches shall be located at least 1m from a bathtub or shower. If not practicable, it may be located no less than 500mm from the tub or shower and be GFCI protected. 49 32-200 Fire Pumps (Conductors) Conductors can be other than copper. Appendix B reference to requirement of 1 hour fire protection. 50 62-300(4) Electric Surface Heating Ground fault protection is required for all electric heating cable sets and heating panel sets. 51 72-110(4) Connection Facilities for Recreational Vehicles and Mobile Homes. 15A and 20A 2-pole receptacles shall be protected by ground fault circuit interrupters. 52 76-016 Temporary Wiring GFCI protection is required for 15A and 20A receptacles installed on construction or demolition projects. 53