General Duty Safety Switch Type VBII, 60 Amp, 240 Volts, Type 3R (Outdoor) Standards and Ratings • UL Listed under file #E4776 • Meets UL98 for switches and UL 50 for enclosures • Meets NEMA Standard KS-1 for enclosed switches • Meets NEC wire bending space requirements • Rated 10,000 AIC as standard or 100,000 AIC when protected by Class R fuses rated 60 amp max • Suitable for use as service entrance equipment Features • Quick-make and break switching action • Double break visible blade design • Highly visible ON/OFF indication • Rugged installer friendly enclosure design • Modular design allows quick and easy replacement of parts • Single cover interlock General Information Catalog Number Description Shipping Weight (lbs.) GNF322R 3 Pole, 3 Wire, Non-Fusible 13 Horsepower Ratings 1 60A GD NFTY3R ENCLOSURE Catalog Number GNF322R 1 Phase, 3 Wire, 240V AC Std Max — 10 3 Phase, 3 Wire, 240V AC Std Max — 15 Accessories Catalog Number Description HG61234 HN612 HS075 HS100 HS125 Equipment Ground Lug Kit Neutral Kit 0.75” Type “HS” Outdoor Hub 1.00” Type “HS” Outdoor Hub 1.25” Type “HS” Outdoor Hub Replacement Parts Catalog Number HNB612 GH223 HM6123 HL612 Description Non-Fusible Replacement Base Replacement Handle/Handle Guard Replacement Mechanism Replacement Lugs (3 lugs per kit) Mechanical Lug Wire Ranges (60/75°C, Cu/Al) Description Wire Range Line, Load Neutral Ground #12-3 AWG (Al) or #14-3 AWG (Cu) #14-4 AWG 1 Dual horsepower ratings: Std - applies when non-time delay fuses are installed. Max - applies when time-delay fuses are installed. Product Specification Sheet GD60.3 Answers for industry. 250V DC 10 Product Specification Sheet #GD60.3 Dimension Drawing (page 2 of 2) 3.32 [ 84 ] PROVISION FOR TYPE "HS" HUB .64 [ 16 ] 8.61 [ 219 ] 1.32 [ 34 ] 7.91 [ 201 ] 12.31 [ 313 ] 1.50 [ 38 ] 1.71 [ 43 ] 1.50 [ 38 ] 4.34 [ 110 ] .95 [ 24 ] 1.60 [ 41 ] .28 [ 7] .27 DIA [ 7] .25 DIA GROUND KNOCKOUT B (3) .91 [ 23 ] 1.80 [ 46 ] 6.77 [ 172 ] 1.04 [ 26 ] 8.71 [ 221 ] 1.51 [ 38 ] 11.11 [ 282 ] 1.60 [ 41 ] A (2) .91 [ 23 ] LEFT SIDE 5.05 [ 128 ] .90 [ 23 ] 6.52 [ 166 ] .68 [ 17 ] B 5.71 [ 145 ] 1.19 [ 30 ] 1.35 [ 34 ] OF BOX .27 DIA (3) [ 7] 1.46 [ 37 ] 7.45 [ 189 ] SEE DETAIL C 1.80 [ 46 ] .65 [ 16 ] DETAIL C .75 [ 19 ] .25 [ 6] 6.64 [ 169 ] Dimensions shown in inches and millimeters ( ). Dimension shown accurate to + ¹⁄₈ inch. Siemens Industry, Inc. Building Technologies Division 5400 Triangle Parkway Norcross, GA 30092 1-800-964-4114 KNOCKOUT CODE A (Concentric) CONDUIT SIZE .75 1.00 B (Tangential) .50 .75 1.00 Non-Fused LINE SIDE WIRE BEND LOAD SIDE WIRE BEND 3.02 (77) 4.11 (104) Enclosure: Galvanized Steel .054 Thick (17 Gauge) Finish: ANSI Grey #61 Paint KNOCKOUT CONDUIT NOTES: CODE SIZEwithout prior notice Siemens is a registered trademark of Siemens AG. Product names Subject to change mentioned may be trademarks or registered trademarks of their All rights reserved .75 ,1 MATERIAL: GA LVANIZED STEEL,.054 THICK APrinted in USA copanies. Specifications subject to change without notice. [19] [25] FINISH:ANSI GRA Y #61respective PAINT © 2009 Siemens Industry, Inc. .5 ,.75 1, www.usa.siemens.com/switches B [13] [19] [25] 60A GD NFTY3R ENCLOSURE