Selection and Application Guide Type VBII safety You Asked for It. Murray Listened. Contents Features 4 Genral Duty Plug Fuse Type 5 General Duty Switches Features 6 General Duty Types 7 Heavy Duty Switches Features 8-9 Heavy Duty Types 10-12 Accessories 13-14 Hub and Lug Data We asked contractors for everything they wanted in an enclosed safety switch.Their input helped create the toughest, most reliable, most hassle-free enclosed safety switch in the business - the Murray Type VBII Safety Switch. It’s a switch that’s right for any commercial, industrial or special use application. The Murray Safety Switch line offers a list of important features that gives contractors a competitive edge: • • • • • Highly visible, easy-to-grip red handle Visible blade construction Door that opens greater than 180º Quick-make, quick-break mechanism All copper current carrying parts on heavy duty switches (except wire grips) • Positive two- and three-point mounting 15 Ratings Heavy Duty Protector-Lock Type 16 Feature Comparison 17 Double Throw Switches 18-19 Detailed Dimension Drawings 20-33 Replacement Parts 34 Fuse Application & Selection 35 Fuse Application & Dimensions 36-37 Ratings & Test Requirements 38-39 Catalog Numbering System 2 40 • • • • • • • • • 30-1200 Amps 240 and 600 Volts AC 250 and 600 Volts DC 100 AlC for general duty switches 200 AlC for heavy duty switches Design E horsepower rated Suitable for use as service equipment Provisions for UL Class T, R, J, L, and H fuses 12X overload rating that exceeds industry standard of 10X One Tough Switch - Murray Type VBII Safety Switch closed in operation Murray now offers a complete line of enclosed switches featuring unique and innovative designs that are unparalleled in the industry. General and Heavy Duty Switches Feature a Double Break Design The Murray VBII double-break switching action breaks the arc in two places. This reduces heat generation and increases switching speed by doubling the breaking distance. The result is enhanced performance and increased longevity. We also provide the most visible blade design available today. Unlike conventional knife blade switches, the blades are selfaligning to ensure positive contact. In addition, they have no wear and friction point since the “electrical hinge” has been eliminated. The result is a very fast, positive and reliable switching action for even the most severe applications. One Tough Switch: More Rugged and Durable in Demanding Applications Our engineers tackled the problem of designing a switch that would stand up under the most demanding industrial conditions, such as steel mills and mining operations. These environments require a switch that must work reliably and safely in the midst of falling liquids, airborne fibers, dust, metal particles, coolants and other contaminants. Tested and Retested All Murray safety switches have been tested to meet all UL requirements and well beyond. These tests include those for general purpose enclosed switches and those designed for more specialized purposes where applicable. The result is a rugged, reliable design that will provide superior performance in a wide variety of applications. open 3 General and Heavy Duty Features Murray Type VBII Safety Switch Application General Duty Switches General Duty Switches are intended for applications where reliable performance and continuity of service are needed, but where duty requirements are not severe and usual service conditions prevail. (These switches are intended for use primarily with supply circuits rated 240V AC or less where the available fault current is less than 100,000A when used with Class R or T fuses or 10,000A max. when used with Class H fuses.) Application Heavy Duty Switches Heavy Duty Switches are intended for use in applications where: 1. Rugged construction, reliable performance, continuity of service and ease of maintenance are emphasized, or 2. Available fault currents higher than 10,000A are likely to be encountered, such as in manufacturing plants, mass production industries, and commercial, institutional and other large buildings served by network systems or transformers of higher capacities. 3. System voltage is 600V AC or DC Max. 4. A Type 12 or 4 / 4X enclosure is required. Short Circuit Withstand Ratings General Duty Switches Suitable for use on systems capable of delivering not more than 100,000 RMS symmetrical amperes of fault current when Class R fuses are installed. Also rated 100,000 AC max. In 200-600A ratings with Class J and T fuses. Short Circuit Withstand Ratings Heavy Duty Switches Suitable for use on systems capable of delivering not more than 200,000 RMS symmetrical amperes of fault current when Class J or R fuses are installed except the 800 and 1200A switches, which are suitable for use on circuits capable of delivering not more than 200,000 RMS symmetrical amperes of fault current when Class L fuses are installed. 100-1200A switches with Class T fuses and field adapter kit are also 200,000 RMS symmetrical rated. 4 Fuses General Duty Switches Fusible switches will accept the following UL class fuses: Class H Class K Class R - Class R fuse clip rejecter kits are required. Class T - 200-600A switches (200A switches require field adapter kit). Heavy Duty Switches Fusible switches will accept the following UL class fuses: Class H Class K Class R - Class R fuse clip rejecter kits are required. Class J - 240 and 600V switches. All switches are field convertible. Class L - 800 and 1200A switches only. Class T - 100-1200A switches (100 and 200A switches require an adapter kit). Cover Interlocks General Duty Switches Defeatable-cover interlocks on Type 1 switches and 60-600A Type 3R switches prevent the switch door from being opened when in the “ON” position. Heavy Duty Switches Defeatable dual cover interlocks are standard on all heavy duty switches. Prevents cover from being opened when switch is in the “ON” position and prevents switch from being turned “ON” when door is opened. Underwriters’ Laboratories, Inc. Listed by UL under file #E4776 per standard UL98 for enclosed switches and also suitable for use as service equipment. NEMA Specifications Meets NEMA standard KS-1-1990 for type GD and HD switches. General Duty Switches Plug Fuse and Special Application Types Features➃ • Compact size • Visible blade, double-break switching action • Quick-make, quick-break operating mechanism • Highly visible ON/OFF indicators • Padlock-off handle feature • Door padlock provision • Bondable neutral (where indicated) • Lugs suitable for copper or aluminum wire • 30A cartridge fuse switches rated 100,000 AC with Class R fuses Ampere Rating Catalog Number Indoor-Type 1 Ship. Wgt.*➀ Dwg. Fig. Catalog Number Outdoor-Type 3R Ship. Wgt.*➀ Dwg. Fig. — — — Horsepower Ratings➄ 1-Phase, 2-Wire Std. Max. 120/240 Volt Fusible (Plug Fuse Type) 10,000 AIC Max 1-Pole and Solid Neutral 30 120 Volt - 1-Phase, 2-Wire GP211N 31 1 2-Pole and Solid Neutral 30 1/2 2 120/240V - 1-Phase, 3-Wire GP321N 37 1 GP321NW 35 12 1 1/2 3 35 11➁ — 3 36 11➁ — 10 240 Volt Non-Fusible (Special Application) 2-Pole 240 Volt - 1- or 2-Pole - No Fuse 240 Volt - 1 Phase, 2 Wire 30 GU221 33 1 GU221AW➁ 60 — — — GU222AW➁ Steel AC Disconnects 1ø, Outdoor – Type 3R➁➂ Ampere Rating Disconnect Type Catalog No. Horse Power Rating Height Dimensions (Inches) Width Depth 30 60 60 60 Fused Pullout Fused Pullout Non-fused Pullout Non-automatic Switch PE230F PE260F PE260N PE260NAS 2 10 10 10 7 1/4 9 7 1/4 7 1/4 5 5 5 5 2 1/8 2 1/8 2 1/8 2 1/8 Height Dimensions (Inches) Width Depth 5 3/4 5 3/4 5 3 1/8 3 1/8 2 1/8 Plastic AC Disconnects 1ø, Outdoor – Type 3R➁ Ampere Rating Disconnect Type Catalog No. Horse Power Rating 30 60 60 Fused Pullout Fused Pullout Non-fused Pullout PE230FPL PE260FPL PE260NPL 3 10 10 * In pounds (lbs). ➀ Package of 10.➁ No hub provision with this switch. ➂ Steel AC disconnects with a 15A GFCI receptacle are also available. 8 8 7 1/4 ➃ Features apply to 30A General Duty and Plug Fuse Type Switches. ➄ Dual horsepower ratings: Std.- applies when non-time delay fuses are installed. Max.- applies when time delay fuses are installed. 5 General Duty Switches-Features (60-600A) 11 5 9 3 6 10 1 8 4 7 2 12 1. Cover interlock 2. Tangential knockouts through 600A for easy conduit lineup 3. Quick-make, quick-break operating mechanism that ensures positive operation 4. Provisions for T, R, J, H, and K class fuses (T & J 200-600A) 5. Generous wiring gutters that meet or exceed NEC wirebending space requirements 6. Visible blade, double-break switch action 7. Positive 2 or 3 point mounting 8. Highly visible red handle grip 9. Informative door labeling which includes replacement parts list 6 10. Handle and cover padlocking provisions 11. Side-hinged door that opens 180 degrees for easier wiring 12. A unique enclosure design that adds rigidity and strength. Its rolled edge prevents cuts and scrapes to conductors and to installer’s hands General Duty Switches Indoor - Type 1 System Ampere Rating Catalog Number Ship. Wgt.* Horsepower Ratings➀ 240 Volt AC Outdoor - Type 3R Dwg. Fig Catalog Number Ship. Wgt.* 1 4 6 7 9 9 9 9 GHN321NW GHN322NW GHN323NW GHN324NW GHN325NWH➂ GHN325NW GHN326NWH➂ GHN326NW 35 (10) 14 24 48 130 157 135 159 Dwg. Fig. 1-Phase, 2-Wire 2-Phase, 4-Wire 3-Phase, 3-Wire 250 Volt DC Std. Max. Std. Max. 11 14 16 17 19 19 19 19 1 1/2 3 7 1/2 15 — — — — 3 10 15 — — — — — — — — — — — — — — — — — — — — — 24 (5) 15 25 50 12 14 16 17 1 1/2 3 7 1/2 15 3 10 15 — — — — — — — — — 3 7 1/2 15 25 7 1/2 15 30 60 5 10 20 40 138 162 19 19 — — — — — — — — 50 50 125 125 141 165 19 19 — — — — — — — — 75 75 200 200 50 50 — — 24 (5) 13 24 47 12 — — — — — — — — — — — — — — — — 7 1/2 Std. Max. Std. 240 Volt Fusible 2-Pole, 2-Fuse and Solid Neutral➁ 30 GHN321N 35 (10) 60 GHN322N 14 100 GHN323N 23 200 GHN324N 47 400 GHN325NH➂ 128 400 GHN325N 153 600 GHN326NH➂ 133 600 GHN326N 159 240 Volt AC / 250 Volt DC 3-Pole, 3-Fuse and Solid Neutral 30 60 100 200 400 400 600 600 GHN421N GHN422N GHN423N GHN424N GHN425NH➂ GHN425N GHN426NH➂ GHN426N 3 7 1/2 15 25 50 50 75 75 7 1/2 15 30 60 125 125 200 200 5 10 20 40 50 50 — — 240 Volt AC / 250 Volt DC 24 (5) 15 25 49 2 4 6 7 136 158 9 9 138 161 9 9 GHN421NW GHN422NW GHN423NW GHN424NW GHN425NWH➂ GHN425NW GHN426NWH➂ GHN426NW 24 (5) 12 23 46 2 3 6 7 GUN321AW GUN322AW GUN323AW GUN324AW 240 Volt Non-Fusible 2-Pole or 3-Pole 30 60 100 200 240 Volt AC / 250 Volt DC GUN321 GUN322 GUN323 GUN324 13 16 17 15 30 60 — — — — 5 10 20 40 * In pounds (lbs). ➀ Dual horsepower ratings: Std.- applies when non-time delay fuses are installed. Max.- applies when time-delay fuses are installed. ➁ These switches are UL-listed for application on grounded B-phase systems. ➂ Height reduced switch (45.25 rather than 56 inches in height) for use with 500 MCM or smaller conductors. 7 Heavy Duty Switches Features 15 3 2 4 18 6 1. Quick-make, quick-break operating mechanism that ensures positive operation 2. Visible blade, double-break switching action 3. Arc chutes dissipate heat and prolong switch life 4. Highly visible red handle grip. Designed for hook stick operation 5. Defeatable dual cover interlock 6. Center punch provided for field drilling to allow ON padlocking 7. Handle can be padlocked in the OFF position with up to (3) padlocks with 5/16” hasps 8. Generous top, bottom, and side gutters that meet or exceed NEC wire-bending space requirements 9. Informative door labeling which includes replacement parts list 10. Tangential knockouts through 200A for easy conduit lineup 11. Side-hinged door that opens past 180 degrees for easier wiring 12. Unique enclosure design increases rigidity and prevents cuts and scrapes to conductors and installer’s hands 13. Spring reinforced fuse clips that assure reliable contact for cool operation 14. Door latch securely holds door closed and allows cover padlocking 7 15. Front removable mechanical lugs that are suitable for CU/AI 60 or 75º conductors 16. Lugs are field convertible to copper body and to a wide variety of compression connectors 17. Hinged clear line terminal shield with probe holes for inspecting or testing line side terminals 18. Large nameplate on Heavy Duty Switches provides highly visible ON/OFF indication 10 19. Drawn cover for increased rigidity and resistance to abuse 20. Top key hole and bottom mounting holes provide easy 2 or 3 point mounting 8 20 11 17 16 9 1 5 13 19 8 14 12 9 Heavy Duty Switches Horsepower Ratings➁ Indoor - Type 1 System Ampere Rating Catalog Number Outdoor - Type 3R Ship. Wgt.* Dwg. Fig. Catalog Number 12 18 23 47 129 153 134 155 360 362 4 5 6 7 9 9 9 9 10 10 HHN321NW HHN322NW HHN323NW HHN324NW HHN325NWH➀ HHN325NW HHN326NWH➀ HHN326NW — — 14 19 25 49 137 158 139 161 380 382 4 5 6 7 9 9 9 9 10 10 HHN421NW HHN422NW HHN423NW HHN424NW HHN425NWH➀ HHN425NW HHN426NWH➀ HHN426NW HLN427NW HLN428NW Ship. Wgt.* 240 Volt AC Dwg. Fig. 1-Phase, 2-Wire Std. Max. 2-Phase, 4-Wire Std. Max. 3 10 15 — — — — — — — — — — — — — — — — — — — — — — — — — — — 1 1/2 3 7 1/2 15 — — — — — — 3 10 15 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — 250 3-Phase, 3-Wire Std. Max. Volt DC 240 Volt Fusible 2-Pole, 2-Fuse and Solid Neutral➂ 30 60 100 200 400 400 600 600 800 1200 HHN321N HHN322N HHN323N HHN324N HHN325NH➀ HHN325N HHN326NH➀ HHN326N HLN327N HLN328N 3-Pole, 3-Fuse and Solid Neutral 30 60 100 200 400 400 600 600 800 1200 C 240 Volt AC / 250 Volt DC (Also used for 2-Pole, 2-Wire Applications) 13 19 24 48 131 157 135 159 362 364 14 15 16 17 19 19 19 19 — — 1 1/2 3 7 1/2 15 — — — — — — (Also used for 3-Pole, 3-Wire Applications) HHN421N HHN422N HHN423N HN424N HHN425NH➀ HHN425N HHN426NH➀ HHN426N HLN427N HLN428N 15 20 26 50 138 162 142 165 383 385 14 15 16 17 19 19 19 19 20 20 3 7 1/2 15 25 50 50 75 75 100 100 7 1/2 15 30 60 125 125 200 200 250 250 5 10 20 40 50 50 — — — — 240 Volt AC / 250 Volt DC 3 7 1/2 15 25 50 50 75 75 100 100 7 1/2 15 30 60 125 125 200 200 250 250 5 10 20 40 50 50 50 — — — 240 Volt Fusible (For 2-Pole Applications use outside poles of 3-Pole Switches) 3-Pole, 3-Fuse➃ Type 4 / 4X Stainless 30 60 HHN321AS HHN322AS 14 20 22 23 Type 12 Industrial — — — — 240 Volt AC / 250 Volt DC — — * In pounds (lbs). ➀ Height reduced switch (45.25 rather than 56 inches in height) for use with 500 MCM or smaller conductors.. ➁ Dual horsepower ratings: Std.- applies when non-time delay fuses are installed. Max.- applies when time-delay fuses are installed. ➂ These switches are UL-listed for application on grounded B-phase systems. ➃ Also used for 2-pole, 2-wire applications. 10 3 7 1/2 7 1/2 15 — 10 Heavy Duty Switches Horsepower Ratings ➂ Indoor - Type 1 System Ampere Rating Catalog Number Ship. Wgt.* Outdoor - Type 3R Dwg. Fig. Catalog Number Ship. Wgt.* 480 Volt AC Dwg. Fig. 1-Phase, 2-Wire Std. Max. 3-Phase, 3-Wire Std. Max. 600 Volt AC 250 600 1-Phase, 2-Wire 3-Phase, 3-Wire Volt Volt DC DC Std.Max. Std. Max. 600 Volt Fusible (Also used for 2-Pole, 2-Wire Applications) 3-Pole, 3-Fuse 30 60 100 200 400 400 600 600 800 1200 HHN361 HHN362 HHN363 HHN364 HHN365H➁ HHN365 HHN366H➁ HHN366 HLN367 HLN368 14 19 24 48 136 154 138 157 380 383 4 5 6 7 9 9 9 9 10 10 HHN361AW HHN362AW HHN363AW HHN364AW HHN365AWH➁ HHN365AW HHN366AWH➁ HHN366AW HLN367AW — 15 20 25 49 137 157 141 161 382 — 14 15 16 17 19 19 19 19 20 — 3 5 10 25 — — — — — — 7 1/2 20 30 50 — — — — — — 14 19 4 5 HHN461NW HHN462NW 15 20 14 15 3 5 7 1/2 20 5 15 25 50 100 100 150 150 200 200 15 30 60 125 250 250 400 400 500 500 5 15 15 30 — — — — — — — — 5 15 25 50 15 30 60 125 3 10 15 30 — — — — — — 10 25 40 50 — — — — — — 7 1/2 15 30 60 125 125 200 200 250 250 20 50 75 150 350 350 500 500 500 500 5 10 20 40 50 50 — — — — — 25 25 50 — — — — — — 20 50 5 10 — 25 480 Volt AC / 600 Volt AC / 250 Volt DC ➀ 3-Pole, 3-Fuse and Solid Neutral 30 60 480 Volt AC / 600 Volt AC / 250 Volt DC ➀ — — 3 10 10 25 7 1/2 15 600 Volt Fusible (For 2-Pole Applications use outside poles of 3-Pole Switches) 3-Pole, 3-Fuse Type 4 / 4X Stainless 30 60 100 200 HHN361AS HHN362AS HHN363AS HHN364AS 13 20 25 49 22 23 24 25 480 Volt AC / 600 Volt AC / 250 Volt DC ➀ Type 12 Industrial HHN361AJ HHN362AJ HHN363AJ HHN364AJ 14 20 25 49 22 23 24 25 — — — — — — — — 7 1/2 15 30 60 20 50 75 150 5 10 20 40 — 25 25 50 * In pounds (lbs). ➀ 60-200A 3-Pole switches are also rated 600V DC when 2 poles are connected in series. Consult factory for 30A, 600V DC switches. ➁ Height reduced switch (45.25 rather than 56 inches in height) for use with 500 MCM or smaller conductors. ➂ Dual horsepower ratings: Std.- applies when non-time delay fuses are installed. Max.- applies when time-delay fuses are installed. 11 Heavy Duty Switches Indoor - Type 1 System Ampere Rating Catalog Number Ship. Wgt. Outdoor - Type 3R Dwg. Fig. Catalog Number Ship. Wgt. Horsepower Ratings Dwg. Fig. 480 Volt 240 Volt 1-Phase 3-Phase 1-Phase 600 Volt 3-Phase 1-Phase 3-Phase 250V 600V DC DC 600 Volt Non-Fusible 3-Pole 480 Volt AC / 600 Volt AC / 250 Volt DC ➀ (Also used for 240 Volt AC and 2-Pole, 2-Wire Applications) 30 60 100 200 400 600 600 Volt Non-Fusible 3-Pole HUN361 HUN362 HUN363 HUN364 HUN365 HUN366 12 18 23 46 114 116 3 5 6 7 8 8 13 19 24 47 118 120 13 15 16 17 18 18 3 10 15 15 15 15 10 20 40 60 125 200 7 1/2 20 30 50 50 50 3 10 15 15 15 10 20 40 60 — 7 1/2 20 30 50 50 20 50 75 125 250 400 10 25 40 50 50 50 HUN361AS HUN362AS HUN363AS HUN364AS — 13 19 24 47 — 21 23 24 25 — 5 10 20 40 50 — — 25 25 50 — — 480 Volt AC / 600 Volt AC / 250 Volt DC ➀ Type 12 Industrial HUN361AJ HUN362AJ HUN363AJ HUN364AJ HUN365AJ 13 19 24 47 119 21 23 24 25 26 20 50 75 125 250 10 25 40 50 50 ➀ 60-200A 3-Pole switches are also rated 600V DC when 2 poles are connected in series. Consult factory for 30A, 600V DC switches. 12 30 60 100 150 350 500 (Also used for 240 Volt AC and 2-Pole, 2-Wire Applications) Type 4/4X Stainless 30 60 100 200 400 HUN361AW HUN362AW HUN363AW HUN364AW HUN365AW HUN366AW 30 60 100 150 350 5 10 20 40 50 — 25 25 50 — General and Heavy Duty Accessories Class J Fuse All 200-600A General Duty and 30-600A, 600V Heavy Duty Switches are field convertible to accept Class J fuses by moving the load base to a pre-drilled J fuse position. HN612M Neutral Kits Standard Neutral Kits can be field installed in General and Heavy Duty Switches. Neutral Kits HT63M Class T Fuse Adapter Kits All 200-600A, General Duty and 100-1200A Heavy Duty Switches are field convertible to accept Class T fuses. 400 & 600A switches are field convertible to accept Class T fuses by moving the load base to a pre-drilled T fuse position. Switch Ampere Rating Kit Catalog Number 30 GD W410190M 30 HD, 60 GD HN612M 60, 100 HD, 100 GD HN623M 200 HN64M 400 & 600 HN656M 800 & 1200 VBII HN678M Class T Fuse Adapter Kits ➀ Catalog Number Description HT23M 100A, 240V Kit HT63M 100A, 600V Kit HT24M 200A, 240V Kit HT64M 200A, 600V Kit HX327TF 800A, 240V Kit HX367TF 800A, 600V Kit HX328TF 1200A, 240V Kit ➀ One kit per pole required. 13 General and Heavy Duty Accessories HA261234M HA161234M Auxiliary Contacts Auxiliary Contacts are available only for Heavy Duty Switches. The auxiliary contacts are available in 1 normally open and 1 normally closed or 2 normally open and 2 normally closed configurations. All auxiliary contacts make after and break before main switch contacts. Auxiliary Contacts Switch Ampere Rating Aux. Switch Catalog Number Kit Ampere Rating 125V AC 250V AC 28V DC Max. Max. Max. Kit Horsepower Rating 125V AC 250V AC 28V DC Max. Max. Max. With 1 NO & 1 NC Isolated Contacts 30-200 HA161234M 10 10 – 1/2 3/4 – 400-1200 HA165678M 10 10 – 1/2 3/4 – With 2 NO & 2 NC Isolated Contacts 30-200 HA261234M 10 10 7 1/2 3/4 – 400-1200 HA265678M 10 10 7 1/2 3/4 – Equipment Ground Kits Equipment Ground Lug Kits are available for all General and Heavy Duty Switches. They are field installable in Type 1 and Type 3R Switches and are factory installed as standard in Type 4 / 4X and Type 12 Switches. Equipment Ground Kits Switch Ampere Rating Catalog Number Number of Terminals 30A GD GSGK60M 2 #14-8 AWG 60-200 GD HG61234M 2 #14-4 AWG 30-200 HD HG61234M 2 #14-4 AWG 400 & 600 HG656M 4 #14-2/0 AWG 800-1200 HG678M 8 #6 AWG-250 Kcmil Class R Fuse Clip Kits All 30-600A General Duty and Heavy Duty Switches are field convertible to accept Class R Fuse Clip Kits. The kits prevent the installation of Class H and K fuses (one kit required per switch). Wire Range Per Terminal (Cu/Al) Class R Fuse Clip Kits Catalog Number Description GSRK321M 30A, 240V Kit (GD only) HR21M 30A, 240V Kit (HD only) HR612M 30A, 600V Kit / 60A, 240V Kit HR62M 60A, 600V Kit HR63M 100A Kit HR64M 200A Kit HR612M HR656M 14 400A / 600A Kit General and Heavy Duty Hub and Lug Data / Protector - Lock ECHS200 Kirk-Key Interlocks Kirk-Key Interlocks can be factoryinstalled only on Type VII Heavy Duty and Double Throw Safety Switches. ECHV300 Interchangeable Hubs 30-200A Type 3R Switches are provided with a conduit hub provision and a removable hub plate on their top rainshed. Hubs Conduit Size (inches) Catalog Number Used On Type 3R ➀ 3/4 1 1 1/4 3/4 1 1 1/4 1 1/2 2 2 1/2 2 1/2 3 3 1/2 4 ECHA075 ECHA100 ECHA125 ECHS075 ECHS100 ECHS125 ECHS150 ECHS200 ECHS250 ECHV250 ECHV300 ECHV350 ECHV400 Compact and 30A GD Only Interlocks can be used to prevent the authorized operator from making an unauthorized operation. The interlock system is a simple method of applying key interlocks to safety switches so as to require operation in a predetermined sequence. Before consulting the factory, the following information is required: • User name and address • Key number from lock assemblies on any existing locks to be interlocked with • Complete locking scheme. Consult factory for delivery. 60-200A GD 30-200A HD 400-1200A Lugs 30-100A Switches are suitable for use with 60º or 75ºC wire. 100-1200A are suitable for use with 75ºC rated wire. Wire Ranges (Line, Load and Standard Neutral) Switch Ampere Rating Wire Range with Wire-Bending Space Per NEC Table 373-6 Lug Wire Range 30GD #14-8 AWG (Cu/Al)≠ 30HD #12-6 AWG (Al) or #14-6 AWG (Cu/Al) #14-2 AWG (Cu/Al) #14-3 AWG (Cu/Al) #14-2 AWG (Cu/Al) 60➂ #14-8 AWG (Cu/Al) 100 #14-1/0 AWG (Cu/Al) #14-1/0 AWG (Cu/Al) 200➃ #6 AWG-250 Kcmil (Cu/Al) #6 AWG-300 Kcmil (Cu/Al) 400➄ 1/0 AWG-750 Kcmil (Cu/Al) or (2) 1/0 AWG-250 Kcmil (Cu/Al) (1) 1/0 AWG-750 Kcmil (Cu/Al) or (2) 1/0 AWG-250 Kcmil (Cu/Al) 600➄ (2) 1/0 AWG-750 Kcmil (Cu/Al) or (4) 1/0 -250 Kcmil (Cu/Al) (2) 1/0 AWG-750 Kcmil (Cu/Al) or (4) 1/0 AWG-250 Kcmil (Cu/Al) 800 (3) 1/0 AWG-750 Kcmil (Cu/Al) or (6) 1/0 AWG-250 Kcmil (Cu/Al) (4) 1/0 AWG-750 Kcmil (Cu/Al) neutral (4) 1/0 AWG-750 Kcmil (Cu/Al) (3) 1/0 AWG-750 Kcmil (Cu/Al) Line and Load (4) 1/0 AWG-600 Kcmil (Cu/Al) neutral 1200 NOTE: 30 thru 200A, Type 3R Switches have removable hub plates on rainshed. 400A and larger Type 3R Switches have no provisions for mounting hubs. Drill or punch hole in the field to accommodate hub size desired. (4) 1/0 AWG-750 Kcmil (Cu/Al) Line and Load (4) 1/0 AWG-750 Kcmil (Cu/Al) neutral ➀ ➁ ➂ ➃ ➄ Hubs suitable for 3R Switches. Line lugs are UL approved and have wire-bending space for #14 - 6 conductors. 60A HD switches are also UL approved for #2 Cu/Al conductors. 200A HD switches have a wire range & wire bending space for (1) 6-300 Kcmil (Cu/Al). Max. wire size for height reduced 400&600A switches is 500 Kcmil (Cu/Al). 15 Heavy Duty Protector-Lock® / Interlocked Receptacle Switches Application Description ➀➁ Receptacle Safety Switches provide cord connection protection of heavy-duty portable equipment (welders, infrared ovens, batch feeders, portable conveyors, assembly line fixtures and tools, refrigerator trucks, etc.) under load or fault conditions. Type 12 receptacle Safety Switches are available with 3-phase, 4-wire grounded type Crouse-Hinds Arkite™ or Arrow-Hart® receptacle pre-wired and mounted with interlock linkage to the switch mechanism. Insertion or removal of the plug is prevented by the interlock linkage while the switch is in the “ON” position. Receptacle prevents operation of switch if incorrect plug is inserted. Protector-Lock Switches with Arrow-Hart®, Power Lock® Receptacles 600V AC Fusible, 3-Pole in Type 12 Industrial Enclosure ➂➃ Ampere Rating Catalog Number Shipping Weight Use Plug # Switch Recept. 30 30 HHN361KJ 17 AX103S, 20415S 60 30 HHN362KJ➁ 17 AX103S, 20415S 60 60 HHN362LJ 17 26415S with Crouse-Hinds® Receptacles 600VAC Fusible, 3-Pole in Type 12 Industrial Enclosure ➂➃ Ampere Rating Switch Recept. 60 60 Catalog Number HHN362CJ Shipping Weight Use Plug # 30 AP6485 600V AC Non-Fusible, 3-Pole in Type 12 Industrial Enclosure ➃ Ampere Rating 16 Switch Recept. 60 60 Note: Protector-Lock® is a registered trademark of Siemens Energy & Automation, Inc. Arrow-Hart®, Power Lock® and Crouse-Hinds® are registered trademarks of Cooper Industries, Inc. Catalog Number HUN362CJ ➀ ➁ ➂ ➃ Shipping Weight Use Plug # 29 APJ6485 Arkite™ is a registered trademark of the Crouse-Hinds Company. Not UL-listed. See page 14 for Class R Fuse Clip Kits. Also rated Type 3R/3S. Feature Comparison General Duty Heavy Duty Double Throw ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ Underwriters’ Laboratories Inc. Listed by UL under file #E4776 as enclosed switches and also suitable for use as service equipment except on 1200A switches on Y systems of more than 150V to ground. ✓ ✓ ✓ ✓ ✓➂ Meets UL98 standard for enclosed switches and enclosures Type 1 switches—general purpose enclosures (Type 1) Type 3R switches—rainproof enclosures (Type 3R) Type 4 / 4X switches—special purpose enclosures (Type 4/4X) Type 12 switches—special purpose enclosures (Type 12). ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ➅ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓➆ ✓ ✓ ✓➃ ✓ ✓ ✓ ✓ ✓ ✓➀ ✓➀ ✓ ✓ ✓ Groundable Neutrals General & Heavy Duty Switches Switches designed for use on systems requiring neutrals have groundable neutral blocks. Padlocks General & Heavy Duty Switches Padlockable cover latch and multiple padlock provisions on handle. ✓ ✓➆ ✓➄ ➀ ➁ ➂ ➃ ➄ ➅ ➆ ✓ Features / Ratings 30 thru 600 Amps 800 and 1200 Amps 240 Volts AC 600 Volts AC 250 Volts DC 600 Volts DC Double-break visible blade design (30-200A) Quick-make, quick-break switching action Highly visible ON/OFF handle indication Handle design for hook stick operation Padlockable cover latch Padlockable handle Single voidable cover interlock Dual voidable cover interlock Type 1 enclosure Type 3R enclosure Type 12 enclosure Type 4/4X enclosures Generous wiring gutters that meet UL and NEC wire-bending space requirements Lugs suitable for copper or aluminum at 60˚C or 75˚C CU/AL wire lugs that meet UL 486B requirements Suitable for field-convertible compression connectors All plated copper current carrying parts (except lugs) Spring reinforced Fuse Clips ➁ (except 30A general duty) Clear pivoting line terminal shield Replacement parts Provisions for UL Class T, R and H fuses Provisions for UL Class J and L fuses Aux. switch kit Type 4X with stainless steel interior parts Rolled flange enclosure design (30-200A) UL approved HP ratings for high efficiency motors 400 & 600A fusible, double-throw switches accept only Class J or T fuses. 30A general duty switches have fuse clips constructed of spring type copper. Not supplied on 30A outdoor & plug fuse switches. 30-200A Type VBII in stainless steel enclosures. 60-200A 200A general duty switches have aluminum neutral assemblies. 100-600A GD and 100-1200A HD switches will accept Class T fuses 17 Double Throw Switches Application Double Throw Safety Switches are supplied from the factory to provide a manual transfer means from normal to an alternate power source. They can also be used to connect a single source of power to either of two loads. They are commonly used in residential, commercial and light industrial applications when a means to switch to alternate power supply is needed and automatic transfer is not required. Description Double throw switches are suitable for use as service equipment,. All are UL listed. Switches are rated for use on sytems up to 10,000A when protected with Class H fuses or 200,000A when protected with Class R or Class T fuses➁. They can also be used to connect a single source of power to either of two loads. In this application it is necessary to field modify fusible switches so that the fuses are on the load side of the switching mechanism. A cover interlock is provided on all ampere ratings. The operating handle may be padlocked in the OFF position. System Amps ① Type 1 ¨Type 3R① Catalog Number Catalog Number System Amps 240 VAC - 250 VDC/3-Pole Fusible ON OFF ON Fuse Type H R Std Yes (kit) Std Yes (kit) Std Yes (kit) HDHN321 HDHN322 HDHN323 HDHN324 HDHN325 HDHN321AW HDHN322AW HDHN323AW — — ① Type 3R① Catalog Number — — — — — — — — — — (3-pole shown) System Amps NonFusible 30 60 100 200 400 Fuse Capabilities of Fusible Switches Amp Rating 30 & 60A, 240V 30 & 60A, 600V 100 & 200A 30 60 100 200 400 Type 1 Catalog Number 240 VAC - 250 VDC/2-Pole HDUN221 HDUN222 HDUN223 HDUN224 HDUN225 — — — HDUN224AW HDUN225AW 240 VAC - 250 VDC/3-Pole HDUN321 HDUN322 HDUN323 HDUN324 HDUN325 — — HDUN323AW HDUN324AW — — — — — — — — — — — — — ON OFF T J No No No Yes➂ Yes (kit) Yes➂ ON (3-pole shown) Amps 30 60 100 200 400 600 600 VAC/3-Pole HDUN361 HDUN362 HDUN363 HDUN364 HDUN365 — HDUN361AW HDUN362AW HDUN363AW HDUN364AW HDUN365AW HDUN366AW ➀ Use ECHS type hubs for 30-200A switches (400&600A switches do not have hub provisions). ➁ Non-fusible double throw switches are rated 10,000 AIC when protected by a circuit breaker or Class H fuses & 200,000 AIC when protected by Class R, J or T fuses. ➂ Move load bases. 18 Double Throw Switches Horsepower Ratings, Lug Data and Accessories Accessories Catalog Number Description Neutral Kits Ground lug, Class R fuse clip & aux. switch kits 30A 60&100A 200A 400&600A HNC612M HN263M HNC264M HN678M 30-600A Use kits on page 14 Maximum Horsepower Ratings Fused (with Time Delay Fuses) 1-Phase AC Ampere Lug Data 240V 240V 30 3 7 1/2 5 60 10 15 10 100 15 30 20 200 15 60 40 400 — 125 50 No. of Cables Per Terminal Cu and /or Al 30 60 100 200 1 pc. 1 pc. 1 pc. 1 pc. Cu or Al Cu or Al Cu or Al Cu or Al #14 to #6 AWG #14 to #2 AWG #12 to #1/0 AWG #6 AWG to 250 Kcmil 400 2 pcs. or Cu or Al #1/0 AWG to 250 Kcmil Ampere 1 pc. Cu or Al 250 to 750 Kcmil 2 pcs. Cu or Al 250 to 500 Kcmil 30 60 100 200 400-600 Wire Range 250V Rating Switch Ampere Range 600 3-Phase AC DC Maximum Horsepower Ratings Non-Fused 1-Phase AC Rating 3-Phase AC 250V 240V 480V 600V 240V 480V 600V DC 5 10 15 15 — 7 1/2 20 30 50 — 10 25 50 50 — 10 20 40 60 125 20 50 75 125 250 30 60 100 150 350 5 10 20 40 50 19 Detailed Dimension Drawings Murray Type VBII Safety Switches Type 1 (Indoor) 30 Amp General Duty (2-Pole) 30 Amp General Duty (3-Pole) Figure 1 Knockout Conduit Code SIZE A (Concentric) .50 .75 B (Concentric) .50 .75 Figure 2 1.00 ( 20 Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to + 1/8 inch. ( Type 1 (Indoor) 30 Amp Heavy Duty Non-Fusible 60 Amp General Duty Non-Fusible 30 Amp Heavy Duty Fusible 60 Amp General Duty Fusible Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to + 1/8 inch. ➀ Dimensions shown apply to heavy duty switches only. Figure 3 Knockout Conduit Code SIZE A (Concentric) .50 .75 B (Tangential) .50 .75 1.00 Figure 4 21 Detailed Dimension Drawings Murray Type VBII Safety Switches Type 1 (Indoor) 60 Amp Heavy Duty Figure 5 KNOCKOUT CODE A (Tangential) .50 CONDUIT SIZE .75 1.00 100 Amp General and Heavy Duty Figure 6 KNOCKOUT CODE A (Tangential) .75 B (Tangential) 1.00 22 Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to + 1/8 inch. ➀ Dimensions shown apply to heavy duty switches only. 1.25 CONDUIT SIZE 1.00 1.25 1.50 1.25 2.00 1.50 Type 1 (Indoor) 200 Amp General and Heavy Duty Figure 7 KNOCKOUT CODE A (Tangential) 1.25 2.50 Figure 8 400 / 600 Amp General and Heavy Duty Non-Fusible KNOCKOUT CODE A (Tangential) Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to + 1/8 inch. ➀ Dimensions shown apply to heavy duty switches only. CONDUIT SIZE 1.50 2.00 CONDUIT SIZE 2.00 2.50 3.00 3.50 23 Detailed Dimension Drawings Murray Type VBII Safety Switches Type 1 (Indoor) 400 / 600 General and Heavy Duty Fusible Figure 9 14.68 [ 373 ] 24.65 [ 626 ] 2.07 [ 53 ] 13.44 [ 341 ] 20.50 [ 521 ] 9.23 [ 234 ] 2.50 [ 64 ] 18.77 E [ 477 ] 39.00C [ 991 ] 44.00B [ 1118 ] 44.57 [ 1132A ] DIMENSIONS SWITCH TYPE A .43 (4) .43DIADIA [ (4) 11 ] [ 11 ] STANDARD HEIGHT REDUCED B C D E 56.57[1437] 56.07[1424] 51.00[1295] 25.46[647] 18.77[477] 45.82[1164] 45.31[1151] 40.25[1022] 20.99[533] 12.49[317] 13.46D [ 342 ] KNOCKOUT CODE A 13.25 [ 337 ] CONDUIT SIZE 2.00 2.50 3.00 3.50 Figure 10 800 / 1200 Amp Heavy Duty Fusible 14.68 [ 373 ] 38.40 [ 975 ] 3.20 3.20 81 ]] [[ 81 2.79 2.79 71 ]] [ [71 13.44 [ 341 ] 32 32 813 ] ] [[ 813 24.02 [ 610 ] 40.00 40.00 1016 ] ] [ [1016 9.24 [ 236 ] 67.16 67.16 [ 1706 ]] [ 1706 61.25 [ 1556 ] 66.67 66.67 1693 ]] [ [1693 .25 [ 6] 30.46 [ 774 ] .56 Dia (4) [ 14 ] 13.25 13.24 337] ] [[ 336 24 Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to + 1/8 inch. No knockouts in the enclosures. Type 3R (Outdoor) 30 Amp General Duty (2-Pole) 30 Amp General Duty (3-Pole) Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to + 1/8 inch. Figure 11 KNOCKOUT CONDUIT CODE SIZE A (Concentric) .50 .75 B (Concentric) .50 .75 1.00 Figure 12 25 Detailed Dimension Drawings Murray Type VBII Safety Switches Type 3R (Outdoor) 30 Amp Heavy Duty Non-Fusible 60 Amp General Duty Non-Fusible 1.32 [ 34 ] SEE DETAIL C 7.91 [ 201 ] 1.35 [ 34 ] OF BOX .27 DIA (3) [ 7] Figure 13 .68 [ 17 ] 6.52 [ 166 ] A (2) B 1.50 [ 38 ] DE 1.50 [ 38 ] 4.34 [ 110 ] 1.71 [ 43 ] .95 [ 24 ] 1.04 [ 26 ] KNOCKOUT CONDUIT CODE SIZE A (Concentric) .50 .75 B (Tangential) .50 .75 1.00 Figure 14 30 Amp Heavy Duty Fusible 60 Amp General Duty Fusible KNOCKOUT CONDUIT CODE SIZE A (Concentric) .50 .75 B (Tangential) .50 .75 1.00 26 Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to + 1/8 inch. ➀ Dimensions shown apply to heavy duty switches only. Type 3R (Outdoor) 60 Amp Heavy Duty Figure 15 KNOCKOUT CODE A (Tangential) .50 CONDUIT SIZE .75 1.00 1.25 Figure 16 100 Amp General and Heavy Duty KNOCKOUT CODE A (Tangential) .75 B (Tangential) 1.00 Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to + 1/8 inch. ➀ Dimensions shown apply to heavy duty switches only. CONDUIT SIZE 1.00 1.25 1.50 1.25 2.00 1.50 27 Detailed Dimension Drawings Murray Type VBII Safety Switches Type 3R (Outdoor) 200 Amp General and Heavy Duty Figure 17 KNOCKOUT CODE A (Tangential) 1.25 CONDUIT SIZE 1.50 2.00 2.50 Figure 18 400 / 600 Amp Heavy Duty Non-Fusible KNOCKOUT CODE CONDUIT SIZE A (Tangential) 1.50 2.00 2.50 3.00 3.50 28 Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to + 1/8 inch. ➀ Dimensions shown apply to heavy duty switches only. Type 3R (Outdoor) 400 / 600 Amp General and Heavy Duty Fusible 14.68 [ 373 ] 26.00 [ 660 ] 2.07 [ 53 ] Figure 19 13.44 [ 341 ] 20.50 [ 521 ] .62 [ 16 ] 2.50 [ 64 ] 9.23 [ 234 ] DIMENSIONS SWITCH TYPE .83 [ 21 ] A STANDARD HEIGHT REDUCED B C D E 56.57[1437] 56.07[1424] 51.00[1295] 25.46[647] 18.77[477] 45.82[1164] 45.31[1151] 40.25[1022] 20.99[533] 12.49[317] 18.77 [ 477 E ] 51.00 C ] [ 1295 56.57 A ] [ 1437 56.07 B ] [ 1424 .43 DIA (4) [ 11 ] 25.46 D ] [ 647 KNOCKOUT CODE A (Tangential) CONDUIT SIZE 1.50 2.00 2.50 3.00 3.50 13.24 [ 336 ] (4) Figure 20 800 / 1200 Amp Heavy Duty Fusible 14.68 [ 373 ] 39.50 [ 1003 ] 2.50 [ 64 ] 2.07 [ 53 ] 34.25 [ 870 ] 38.40 [ 975 ] .83 [ 21 ] 13.44 [ 341 ] 24.02 [ 610 ] 40.45 [ 1027 ] 66.82 [ 1697 ] 61.25 [ 1556 ] 66.25 [ 1683 ] 9.24 [ 235 ] .25 [ 6] 38.40 [ 975 ] 30.46 [ 774 ] 39 96 Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to + 1/8 inch. 13.24 [ 336 ] No knockouts in the enclosures. 29 Detailed Dimension Drawings Murray Type VBII Safety Switches Type 4X (Stainless); 12 (Industrial) 30 Amp Heavy Duty Non-Fusible Figure 21 No knockouts in the enclosures. 30 Amp Heavy Duty Fusible No knockouts in the enclosures. 30 Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to + 1/8 inch. Figure 22 Figure 23 Type 4X (Stainless); 12 (Industrial) 60 Amp Heavy Duty No knockouts in the enclosures. 100 Amp Heavy Duty Figure 24 10.46 [ 266 ] 10.43 [ 265 ] SEE DETAIL A 8.45 [ 215 ] 3.52 [ 89 ] 4.74 [ 120 ] .42 [ 11 ] 12.02 [ 305 ] 25.00 [ 635 ] 23.16 [ 588 ] 21.96 [ 558 ] 24.16 [ 614 ] .27 DIA (4) [7] 6.80 [ 173 173 ] 9.65 [ 245 ] 8.73 [ 222 ] .35 [9] .27 DIA [7 ] .95 [ 24 ] 2.04 [ 52 ] 4.25 [ 108 ] 4.25 [ 108 ] 5.34 [ 136 ] DETAIL A .67 DIA [ 17 ] 8.59 [ 218 ] No knockouts in the enclosures. Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to + 1/8 inch. 31 Detailed Dimension Drawings Murray Type VBII Safety Switches Type 4X (Stainless); 12 (Industrial) 200 Amp Heavy Duty 15.39 [ 391 ] 12.58 [ 319 ] SEE DETAIL A 10.37 [ 263 ] 5.24 [ 133 ] 7.22 [ 183 ] .42 [ 11 ] Figure 25 16.95 [ 431 ] 8.45 [ 215 ] OF BOX 33.00 [ 838 ] 32.17 [ 817 ] 31.07 [ 789 ] 14.62 [ 371 ] 29.96 [ 761 ] .44 [ 11 ] 11.86 [ 301 ] .33 DIA (4) [9 ] 6.75 [ 171 ] .38 DIA [ 10 ] 1.14 [ 29 ] 4.60 [ 117 ] .75 DIA [ 19 ] DETAIL A 6.63 [ 168 ] 6.75 [ 171 ] 10.01 [ 254 ] No knockouts in the enclosures. 400 Amp Heavy Duty Non-Fusible 24.82 [ 630 ] .63 [ 16 ] 4.41 [ 112 ] 16.00 [ 406 ] Figure 26 14.64 [ 372 ] SEE DETAIL A 13.36 [ 339 ] 26.44 [ 672 ] 9.19 [ 233 ] 18.54 [ 471 ] 24.82 [ 630 ] 47.68 [ 1211 ] 46.43 [ 1179 ] 44.14 [ 1121 ] 44.57 [ 1132 ] 13.17 [ 335 ] 1.40 [ 36 ] 9.19 [ 233 ] No knockouts in the enclosures. 32 56 DIA Dimensions shown in inches and millimeters [ ]. Dimensions shown accurate to + 1/8 inch. .47 [ 12 ] 13.19 [ 335 ] DETAIL .56 DIA [ 14 ] A 1.00 DIA [ 25 ] E Double Throw C B A D CL This mounting hole omitted on 30-100A Type VBII Non-Fusible switches (6) ”F“ Dia. mounting holes (30-200A) (4) ”F“ Dia. mounting holes (400-1200A) C B Double Throw Dimensions - Inches Enclosure Catalog Number Mounting A B C D E F HDUN221, HDUN321, HDUN361, HDUN361R HDHN321, HDHN321AW HDUN222, HDUN322, HDUN362, HDUN362AW HDN322, HDHN322AW 24.50 29.12 24.88 33.45 9.53 9.53 11.50 11.50 6.09 6.09 6.09 6.09 19.00 23.50 19.00 27.50 6.75 6.75 9.38 9.38 0.268 0.268 0.268 0.268 HDUN223, HDUN323, HDUN363, HDUN323AW, HD363AW 27.62 12.18 6.09 19.36 8.00 0.268 HDHN222, HDHN323AW 36.44 12.18 6.09 28.11 8.00 0.268 HDUN224, HDUN324, HDUN224AW, HDUN324AW, HDUN364, HDUN364AW 36.00 19.12 6.42 31.00 15.00 0.44 HDHN324 49.44 19.12 6.42 44.50 15.00 0.44 HDHN325 73.54 28.22 9.44 65.50 16.00 0.56 HDUN225, HDUN225AW, HDUN325, HDUN365, HDUN365AW, HDUN366AW 57.7 28.22 9.44 49.75 16.00 0.56 30-600A Type 1 & 3R 33 Replacement Parts Murray Type VBII Safety Switch HNB623 HM6123 HBB612 HH6123 HFB612 HFB656 Ampere Rating Line Base Load Base Handle/Handle Guard General Duty Heavy Duty Mechanism Assembly Lugs 30A General Duty 2- and 3-Pole Fusible and Non-fusible ➄ 30 Fused, 2-Pole 30 Fused, 3-Pole 30 Non-fused W410472A W410473A W410473B – – – 240V Max – – – – – – Fusible 2 and 3-Pole 60-600A General Duty & 30-600A Heavy Duty ➄ 30 HD 240V 60 GD 60 HD 240V 100 200 400 600 800 1200 HFB21 ➁ HFB612 ➁ HFB22 ➁ HFB63 ➁ HFB64 ➁ HFB65 ➂➅ HFB66 ➂➅ HFB67A ➅➇ HFB68 ➅➇ HBB21 ➁ HBB612 ➁ HBB22 ➁ HBB63 ➁ HBB64 ➁ HBB656 ➂➅ HBB656➂➅ HBB67A ➅➇ HBB68 ➅➇ – GH223 – GH223 GH24 HH65678 HH65678 – – HH6123 ➆ – HH6123 ➆ HH6123 ➆ HH64 ➆ HH65678 ➆ HH65678 ➆ HH65678 ➆ HH68➆ –➀ –➀ –➀ – – – 240V Max HM6123 ➆ HM6123 HM6123 ➆ HM6123 ➆ HM64 ➆ HM65 HM66 HM67A HM678 HL612 ➀ HL612 ➀ HL612 ➀ HL63 ➀ HL64 ➀ HL65678 ➃ HL65678 ➃ HL67➈ ➈ Fusible 3-Pole Heavy Duty ➄ 30 600V 60 600V 60A Oversized 100 200 400 600 800 1200 HFB612 ➁ HFB62 ➁ HFB623 ➁ HFB63 ➁ HFB64 ➁ HFB65 ➂➅ HFB66 ➂➅ HFB67A ➅➇ HFB68 ➅➇ 600V Max HBB612 ➁ HBB62 ➁ HBB623 ➁ HBB63 ➁ HBB64 ➁ HBB656 ➂➅ HBB656 ➂➅ HBB67A ➅➇ HBB68 ➅➇ – – – – – – HH65678 – – HH6123 ➆ HH6123 ➆ HH6123 HH6123 ➆ HH64 ➆ HH65678 ➆ HH65678 ➆ HH65678 ➆ HH68➆ HM6123 ➆ HM6123 ➆ HM6123 HM6123 ➆ HM64 ➆ HM65 HM66 HM67A HM678 Non-Fusible 3-Pole 60-600A General Duty and 30-600A Heavy Duty ➄ 30 HD 60 GD 60 HD 100 200 400 600 800 1200 34 ➀ ➁ ➂ ➃ ➄ ➅ HNB612 ➁ HNB612 ➁ HNB623 ➁ HNB623 ➁ HNB64 ➁ HNB65 ➂➅ HNB66 ➂➅ HNB67A ➅➇ HNB68 ➅➇ – – – – – – – – – Three lugs included in kit. Includes lugs. Lugs are not included. One lug per kit. One per switch required unless otherwise noted. One required per pole. – GH223 – GH223 GH24 HH65678 HH65678 – – HH6123 ➆ – HH6123 ➆ HH6123 ➆ HH64 ➆ HH65678 ➆ HH65678 ➆ HH65678 ➆ HH68 HL612 ➀ HL612 ➀ – HL63 ➀ HL64 ➀ HL65678 ➃ HL65678 ➃ HL67➈ ➈ 600V Max HM6123 ➆ HM6123 HM6123 ➆ HM6123 ➆ HM64 ➆ HM65 HM66 HM67A HM678 ➆ For type 4 / 4X stainless steel switches add “S” to end of catalog number. ➇ Lugs included with line and load bases. ➈ One lug kit per pole for either line or load required. HL612 ➀ HL612 ➀ HL612 ➀ HL63 ➀ HL64 ➀ HL65678 ➃ HL65678 ➃ HL67➈ ➈ Fuse Application and Selection Data Murray Type VBII Safety Switch Murray enclosed safety switches are designed for fuse versatility. Although Murray is not a manufacturer of fuses, once the type of fuse needed for a particular application is determined, it’s easy to select an appropriate switch. The proper fuse type for the application is selected using the following parameters: • Voltage requirements • Conductor ampacity • Horsepower requirements • Maximum available RMS fault-current • UL Fuse Class when specified The compatible fusible safety switch is selected following these parameters: • System voltage requirements • Fuse amp ratings • Available fault current • UL Fuse Class • Environmental conditions • Number of poles required One-Time Fuses One-time fuses are standard for use in situations calling for 1200 amperes or less with maximum voltages for 250 or 600 volts. Simply designed, current carrying links are connected to contact pieces at the ends of the enclosure. When an overload occurs, the circuit quickly opens and the arc is quenched by granular insulating material that surrounds the current carrying links. Current Limiting Fuses This design offers the highest degree of circuit protection among fuses. Inside, usually copper or silver alloy links are imbedded in pure quartz sand between heavy copper end blocks. The special design is fast acting and interrupts during the first half cycle of a fault. This causes a limitation of both fault peak current and let-thru current. Dual-Element Time-Delay Fuses Dual-element fuses may have timedelay designation since these fuses employ two distinctly separate types of elements. One provides overload protection with time delay. (UL states that time delay means having a 10-second operating delay at 500 percent of fuse label rating.) The second provides short circuit protection similar to a single element fuse. Dual element fuses are most frequently used on motor loads. Available in Classes J, L, R, and T. Available in all Classes. 35 Fuse Applications and Dimensions Murray Type VBII Safety Switch Class R and H Fuses Class R Application: Overcurrent and short circuit protection of motors and transformers, service entrance equipment, feeder and branch circuits. (General Purpose Protection) A A B F B E D G Class R Rejection: A UL Class R Fuse Kit is required that rejects lower-rated fuses (H and K). D E C G C Blade Type 61-600A Ferrule Type 0-60A Class H Fuse Dimensions 250 Volts Ampere Rating 0-30 35-60 65-100 110-200 225-400 450-600 600 Volts A B C D E F G A B C D E F G 2 3 5 7/8 7 1/8 8 5/8 10 3/8 –– –– –– –– –– –– –– –– –– –– –– –– –– –– –– –– –– –– 9/16 13/16 3/4 1 1/8 1 5/8 2 –– –– 1/8 3/16 1/4 1/4 1/2 21/32 1 1 3/8 1 7/8 2 1/4 5 5 1/2 7 7/8 9 5/8 11 5/8 13 3/8 –– –– –– –– –– –– –– –– –– –– –– –– –– –– –– –– –– –– 13/16 1 1/16 3/4 1/8 1 5/8 2 –– –– 1/8 3/16 1/4 1/42 17/32 21/32 1 1 3/8 1 7/8 1/4 Class R Fuse Dimensions 250 Volts Ampere Rating A B C 0-30 35-60 61-100 101/200 201-400 401-600 2 3 5 7/8 7 1/8 8 5/8 10 3/8 5/32 3/16 1/2 11/16 15/16 1 1/8 5/64 3/32 9/32 9/32 13/32 13/32 D 3/8 5/8 23/64 35/64 51/64 63/64 600 Volts E 9/16 13/16 3/4 1 1/8 1 5/8 2 Class J Application: Current limiting protection to a wide variety of applications, Panelboards, Switchboards, Busway, Feeder Circuits. Rejection: Its unique dimensions prevent the substitution of another fuse. F G –– –– 1/8 3/16 1/4 1/4 1/2 21/32 1 1 3/8 1 7/8 2 1/4 A B C D E F G 5 5 1/2 7 7/8 9 5/8 11 5/8 13 3/8 3/16 1/4 1/2 11/16 15/16 1 1/8 3/32 3/32 9/32 9/32 13/32 17/32 5/8 7/8 23/64 35/64 51/64 53/64 13/16 1 1/16 3/4 1 1/8 1 5/8 2 –– –– 1/8 3/16 1/4 1/4 17/32 21/32 1 1 3/8 1 7/8 2 1/4 A C 1” MIN B Class J Ferrule Type 0-60A Class J Blade Type 61-600A Class J Fuse Dimensions Ampere Rating A B C D E 0-30 31-60 61-100 101-200 201-400 401-600 2 1/4 2 3/8 4 5/8 5 3/4 7 1/8 8 1/2 5/8 3 5/8 4 3/8 5 1/4 6 13/16 1 1/16 1 1/8 1 5/8 2 1/8 2 5/8 – – 3/4 1 1/8 1 5/8 2 – – 1/8 3/16 1/4 3/8 36 F – – 1 13/8 17/8 21/8 G – – 1/2 11/16 15/16 1 H – – 9/32 9/32 13/32 17/32 J – – 3/8 3/8 17/32 11/16 K – – 2 5/8 3 3 3/8 3 3/4 Class L Class T Application: Current limiting protection for service entrance equipment, feeder circuits and metering centers. Application: It combines two highly desirable features - highly current limiting and a small physical size. Panelboards, switchboards, metering centers. Rejection: Its unique dimensions prevent the substitution of another fuse. Rejection: Its unique dimension prevents the substitution of another fuse. 8 5/8 5 103/4 21 /8 /32 5 /8 5 113/32 /16 13/8 5 /8 8 1 11/8 2 7/16 /2 3 13/16 /8 5 3 /4 /8 3 2 7/16 15 1 11/8 3 15/32 /16 /2 13/8 3 13/16 /8 3 3 2 /8 7 2 7/8 1 3 15/32 /8 /4 5 /8 3 4 5/16 Class L Blade Type 601-800A Class L Blade Type 801-1200A Fuse Ratings Class Amperes H 1-600A K5* 1-600A J 1-600A RK1 1/10-600A 600V or less 250V or less RK5 1/10-600A (time delay) T 1-1200A 600V or less 250V or less T 1-800A L 601-6000A Volts 250 and 600V or less AC 250 and 600V or less AC 600V or less 300V AC 600V AC 600V or less Dimensions Int. Ratings I2t, Ip Circuits NEC standards Class H without rejection Diff. from Class H Class H with rejection feature Class H with rejection feature Diff. from Class H Diff. from Class H Bolt type 10,000A – 100,000A Less than 10,000A available I2t - RK5 up to 100A Ip - RK5 up to 100A I2t - Low Ip - Low I2t - Slightly>J Ip - Slightly>J 200,000A I2t - >RK-1 Ip - RK-1 General purpose circuits Feeder circuits Main & feeder circuits Main & feeder circuits(motor load small percent) Motor starting currents 200,000A I2t - <J Ip - <J I2t - =J Ip - =J I2t - Low Ip - Low Main & feeder circuits Main & feeder circuits Main & feeder circuits 200,000A 200,000A 200,000A 200,000A * Class K5 fuses do not prohibit the use of Class H type fuses in a switch. 37 Ratings and Test Requirements Murray Type VBII Safety Switch Enclosed Switch Load Ratings The primary functions of a fusible enclosed switch are to carry current continuously, to provide over current and short circuit protection, to be capable of disconnecting the circuit, and to provide means for mounting fuses. Safety switches may also have other capabilities covered by load break ratings (in contrast with no-load disconnect switches), such as standard and maximum horsepower ratings and the ability to withstand the maximum I2t energy let-throughs of fuses. All Murray safety switches are capable of continuously carrying their full-rated nameplate current at rated voltage. This capability is directly attainable in no-fuse switches and in fusible switches when the fuses are replaced with copper bars, without exceeding permissible temperature rise. Fuses are capable of carrying their rated current in open air. Under this condition the fuses will not open and will not exceed permissible temperature rise. When fuses are used in a switch or other enclosure, a higher ambient temperature is caused by the switch heat and fuse-generated heat. Since fuses are thermal acting by design, they will not carry full current rating at higher ambient temperatures. To assist users of fusible equipment, UL requires each fusible switch to carry the statement, “Continuous Load current not to exceed 80% of the rating of the fuses employed.” Good electrical practice may require even further de-ratings, depending on the type of fuse, load, altitude and ambient temperature of the switch location. 38 Load Break Ratings All Murray safety switches are load break rated. The load break rating is assigned by UL after the switching unit has successfully performed the following tests for general use enclosed switches: Load Break Ratings Number of Switch ON/OFF Ampere Operations Rating per Minute 30-100 200 400 600 800 1200 6 5 4 3 2 1 Number of Operations With Current Without Current Total 6000 6000 1000 1000 500 500 4000 2000 5000 4000 3000 2000 10000 8000 6000 5000 3500 2500 12X Current Rating In addition to the required UL overload testing, all Murray VBII switches have been tested at 12 times rated current at 600V AC to assure compliance to automotive and other heavy industry requirements. Horsepower Ratings All Murray safety switches, where appropriate, are horsepower rated. The assignment of such ratings is made by UL only after the switching unit has undergone tests to determine its acceptability. In addition, the unit must successfully perform on an overload test series which includes repeated interruption of the locked rotor current of the motor for which it is to be rated as follows: Horsepower Ratings Max. HP Rating 100 500 Number of ON/OFF Ops. per Minute 6 1 Number of Cycles of Operation 50 10 Most switches have two or more ratings for a particular voltage and current. Murray safety switches are UL listed for design E horsepower ratings. With Murray safety switches no derating is required in most cases. Depending on the switch and its application, various ratings have been achieved. All Murray switches include a complete list of the ratings on the inside of the cover. Horsepower Rating Charts The number and variety of horsepower ratings that can be applied to a switching unit makes it impractical, in most instances, to list all such ratings on the front of the unit. Murray does, however, provide this data by means of a chart on the inside cover. Horsepower Rating Range UL test procedure includes ratings up to 500 HP. Murray safety switch units in appropriate sizes have successfully passed the locked rotor current interrupting test series for ratings through 500 horsepower at both 480 and 600 volts AC and through 50 horsepower at 600 volts DC. Maximum Horsepower Ratings The maximum horsepower rating is based upon the largest rating of a time delay fuse: 1) which can be incorporated in the switch, and 2) which will permit the motor to be started. Since the fuse has extra time delay, it can hold the starting current of a larger motor longer than a standard fuse. Standard Horsepower Rating This rating is assigned to a switch after it has successfully completed the locked rotor test series, on the basis of the largest standard fuse rating: 1) which can be incorporated in the switch, and 2) which will permit the motor to be started. The standard fuse does not have a designed time delay to allow for motor starting currents. Murray Type VBII Safety Switch Multiple Voltage Horsepower Ratings A switch may have additional standard and maximum horsepower ratings for different voltages. A switch that is horsepower rated at 240V AC or 250V DC, may also have horsepower ratings for motors on 120V AC or 125V DC circuits. Multi-Pole Horsepower Ratings A switch may have horsepower ratings applicable to the same current and voltage ratings but with fewer poles, if the switch is investigated and found suitable for the assigned rating. Short Circuit Withstandability UL test procedures for switches and fuses have been expanded to provide realistic standards of performance with respect to clearing high-level fault currents. These revised standards deal with the control of destructive energy in the shorted circuit. Two types of potential damage are characteristic of high-level short circuits: mechanical and thermal. Mechanical damage is caused by the electromagnetic force surrounding conductors; thermal damage is the result of excessive current during the fault clearing time. The UL fuse standard defines maximum instantaneous peak letthrough current (lp) and maximum destructive energy let-through (I2t) for each fuse (except Class H). Applications of fuses and safety switches on systems having over 10,000A are available. Short circuits require selections of the proper UL-listed fuses and switches capable of withstanding I2t let-throughs. See chart below for withstand ratings on Murray switches. I2t Rated Suitability tests for service with Class H, R, J, L and T fuses have been conducted. Representative switches, with test fuses connected in series with each switch, were subjected to I2t let-through values in excess of the capacities of the largest fuses acceptable by the switches. To pass the test, the switch must remain operable after being closed into a high amp available short circuit current. The test fuse is sized so that higher levels of let-through current and energy will be reached than would ever occur during normal usage in the field. See chart below for I2t ratings on Murray switches. Horsepower Ratings I2t and Ip Ratings Fuse Rating Fuse Class Fusible Plug H K J R T H K J R Non-Fusible ① Short Circuit Rating General Duty Heavy Duty 10,000 10,000 10,000 100,000 100,000 100,000 10,000 10,000 100,000 100,000 – 10,000 10,000 200,000 200,000 200,000 10,000 10,000 200,000 200,000 Switch Rating Ampere I2t Rating (Amp2 x sec.) Ip Rating (Amp2 x sec.) 30 60 100 200 400 600 800 1200 50,000 200,000 500,000 2,000,000 6,000,000 12,000,000 10,000,000 12,000,000 10,000 26,000 32,000 50,000 75,000 100,000 80,000 100,000 ① With fuses in series with switch. All non-fusible switches are also rated 10,000 A/C when protected by a UL listed circuit breaker. Fuse or circuit breaker ampere rating cannot exceed switch ampere rating. 39 Murray Catalog Numbering System Type VBII Safety Switch Catalog Numbering System H HN 3 6 4 A Switch Type J Enclosure G = General Duty (Single Throw) H = Heavy Duty (Single Throw) J S W No Letter = Type 12 = Type 4X = Type 3R = Type 1 Neutral and/or Protector Lock ® Fuses A = Filler; To preserve spacing in case 7th position is used C = CR-H Receptacle — 60A 4W K = AH Receptacle — 30A 4W L = AH Receptacle — 60A 4W N = Insulated Groundable Neutral HN = Factory Set for Class ‘H’ Fuse LN = Factory Set for Class ‘L’ Fuse P = Plug Fuse Type UN = Unfused DHN = Fusible (Double Throw) DUN = Non-Fused (Double Throw) Wires Amperage Number of Wires Including Neutral 1-4 1 = 30A 2 = 60A 3 = 100A Voltage 1 = 120V AC 2 = 240V AC 6 = 480/600V AC NOTE: 6th & 7th positions omitted in case of no-neutral, Type 1. 4 = 200A 5 = 400A 6 = 600A 7 = 800A 8 = 1200A Murray Accessories Catalog Numbering System H N 6 4 Brand Labeling Switch Type H = Heavy Duty G = General Duty M = Murray Amperes Accessory Type A1 = A2 = G = N = R = T = Auxiliary Switch 1/NO and 1/NC Auxiliary Switch 2/NO and 2/NC Ground Lug Kit Neutral Class R - Fuse Clip Kit Class T - Fuse Kit M Maximum Voltage 2 = 240V Max 6 = 600V Max 1 = 30A 2 = 60A 12 = 30/60A 3 = 100A 23 = 60/100A 123 = 30/60/100A 1234 = 30/60/100/200A 4 = 200A 5 = 400A 56 = 400/600A 5678 = 400/600 800/1200A 6 = 600A 78 = 800/1200A Murray Electrical Products Siemens Energy & Automation, Inc. 5400 Triangle Parkway Norcross, GA 30092 For nearest sales office 1.800.241.3138 For product information 1.800.478.6346 www.murrayconnect.com © 2007 Siemens Energy & Automation, Inc. All Rights Reserved Murray is a registered trademark of Siemens Energy & Automation, Inc. Specifications are subject to change without notice Order # MYPS- MB03A-0307 15M0307CEG Printed in USA