11 By Denis Mitchell and Patrick Paultre Seismic Design 11.1 11.2 11.3 11.4 11.4.1 11.4.2 11.4.2.1 11.4.2.2 11.4.3 11.4.4 11.4.4.1 11.4.4.2 11.4.4.3 11.4.4.4 11.4.4.5 11.4.4.6 11.4.4.7 11.4.5 11.4.5.1 11.4.5.2 11.4.5.3 11.4.5.4 11.4.5.5 11.4.5.6 11.4.6 11.4.6.1 11.4.6.2 11.4.6.3 11.4.6.4 11.5 11.5.1 11.5.2 11.5.3 11.5.3.1 Introduction..................................................................................... 11–3 Seismic Design Considerations ..................................................... 11–5 Loading Cases ............................................................................... 11–5 Design of a Six-Storey Ductile Moment-Resisting Frame Building ............................................................................... 11–6 Description of Building and Loads.................................................. 11–6 Determination of Design Forces..................................................... 11–7 Gravity Loading .............................................................................. 11–7 Seismic Loading ............................................................................. 11–8 Deflections, Drift Ratios and Torsional Sensitivity........................ 11–12 Design of Ductile Beam................................................................ 11–12 Determination of Design Moments............................................... 11–13 Moment Redistribution and Moment Envelopes .......................... 11–13 Design of Flexural Reinforcement at Critical Sections ................. 11–14 Design of Transverse Reinforcement in Beams .......................... 11–17 Checking Extent of Plastic Hinging .............................................. 11–19 Bar Cut-offs .................................................................................. 11–19 Splice Details................................................................................ 11–19 Design of Interior Ductile Column ................................................ 11–21 Column End-Actions from Analysis .............................................. 11–21 Factored Axial Loads and Moments............................................. 11–22 Preliminary Selection of Column Reinforcement.......................... 11–22 "Strong Column - Weak Beam" Requirement .............................. 11–23 Design of Transverse Reinforcement in Column ......................... 11–24 Splice Details................................................................................ 11–28 Design of Interior Beam-Column Joint ......................................... 11–28 Determination of Factored Forces in Joint ................................... 11–28 Check Factored Shear Resistance of Joint.................................. 11–30 Transverse Reinforcement Required in Joint............................... 11–30 Bond of Beam Bars ...................................................................... 11–31 Analysis of a Ductile Core-Wall Structure .................................... 11–31 Description of Building and Loads................................................ 11–31 Analysis Assumptions .................................................................. 11–32 Seismic Loading ........................................................................... 11–32 Minimum Lateral Earthquake Force ............................................. 11–33 11–2 Seismic Design 11.5.3.2 11.5.3.3 11.5.3.4 11.5.3.5 11.5.3.6 11.5.4 11.5.5 11.5.5.1 11.5.5.2 11.5.5.3 11.5.6 11.5.6.1 11.5.6.2 11.5.6.3 11.5.6.4 11.5.6.5 11.5.6.6 Accidental Torsion........................................................................ 11–35 Degree of Coupling ...................................................................... 11–35 Check on Structural Irregularity.................................................... 11–36 Dynamic Analysis ......................................................................... 11–36 Deflections and Drift Ratios.......................................................... 11–40 Design Forces .............................................................................. 11–40 Design of Coupling Beams........................................................... 11–45 Design Forces for Coupling Beams ............................................. 11–45 Design and Detailing of Coupling Beams..................................... 11–46 Ductility of Coupling Beams ......................................................... 11–47 Design of Ductile Walls ................................................................ 11–47 Design Forces in E-W Direction ................................................... 11–47 Design Forces in N-S Direction .................................................... 11–49 Design of Base of Wall for Flexure and Axial Load...................... 11–49 Ductility of Walls ........................................................................... 11–53 Checking Wall Thickness for Stability (Clause 21.6.3) ................ 11–53 “Buckling Prevention” Ties for Concentrated Reinforcement (Clause 21.6.6.9).......................................................................... 11–54 11.5.6.7 Design for Shear at Base of Walls (Clause 21.6.9) ..................... 11–54 11.5.6.8 Checking Sliding Shear Resistance at Construction Joints (Clause 21.6.9.4).......................................................................... 11–56 11.5.6.9 Determination of Plastic Hinge Region (Clause 21.6.2) ............... 11–57 11.5.6.10 Changes in Horizontal Distributed Reinforcement Over the Height of the Walls (Clause 21.6.5) ............................................. 11–57 11.5.6.11 Changes in Vertical Distributed Reinforcement Over the Height of the Walls (Clause 21.6.5) ............................................. 11–58 11.5.6.12 Changes in Concentrated Vertical Reinforcement Over the Height of the Walls (Clause 21.6.6) ............................................. 11–58 11.5.7 Frame Members Not Considered Part of the SFRS .................... 11–58 11.5.7.1 Slab-Column Connections (Clause 21.12.3) ................................ 11–58 11.5.7.2 Check on Design And Detailing of Columns (Clause 21.12)........ 11–59 11.5.8 Comparisons With the Design Using the 1994 CSA Standard .... 11–59 11.5.9 References ................................................................................... 11–59 CAC Concrete Design Handbook 11.1 11–3 Introduction The 2005 National Building Code of Canada (NBCC) gives the minimum lateral earthquake force for the equivalent static force procedure as: V = S (Ta ) M v I E W S (2.0 )M v I E W ≥ Rd Ro Rd Ro and for a Seismic Force Resisting System (SFRS) with an R d equal to or greater than 1.5 , 2 S (0.2)IEW V need not be taken greater than 3 Rd Ro where: S (Ta ) = Mv IE Ta = = = W = Rd = Ro = design spectral response acceleration, expressed as a ratio to gravitational acceleration for a period of Ta factor to account for higher mode effect on base shear earthquake importance factor for the structure fundamental period of vibration of the building in seconds in the direction under consideration dead load, plus 25% of the design snow load, plus 60% of storage load and the full contents of any tanks. Minimum partition load need not exceed 0.5 kPa ductility-related force modification factor that reflects the capability of a structure to dissipate energy through inelastic behaviour overstrength-related force modification factor that accounts for the dependable portion of reserve strength in a structure. The designer chooses the type of SFRS, with the corresponding force modification factors, R d and R o . The values of R d and R o are a function of the type of lateral load resisting system and the manner in which the structural members are designed and detailed. Table 11.1 provides a guide for the required design and detailing provisions of CSA Standard A23.3 associated with the corresponding factors, R d and R o . 11–4 Seismic Design Table 11.1 Design and Detailing Provisions Required for Different Reinforced Concrete Structural Systems and Corresponding R d and R o Factors Type of SFRS Rd Ro Ductile moment resisting frames 4.0 1.7 Moderately ductile moment resisting frames Ductile coupled walls 2.5 1.4 4.0 1.7 Ductile partially coupled walls 3.5 1.7 3.5 1.6 Moderately ductile shearwalls Conventional construction: Moment resisting frames 2.0 1.4 1.5 1.3 Conventional construction: Shearwalls 1.5 1.3 Ductile shearwalls Summary of design and detailing requirements in CSA A23.3-04 Beams capable of flexural hinging with shear failure and bar buckling avoided. Beams and columns must satisfy ductile detailing requirements. Columns properly confined and stronger than beams. Joints properly confined and stronger than beams. Beams and columns must satisfy detailing requirements for moderate ductility. Beams and columns to have minimum shear strengths. Joints must satisfy moderate ductility detailing requirements and must be capable of transmitting shears from beam hinging. At least 66% of base overturning moment resisted by wall system must be carried by axial tension and compression in coupled walls. Coupling beams to have ductile detailing and be capable of flexural hinging or resist loads with diagonal reinforcement (shear failure and bar buckling avoided). Walls must have minimum resistance to permit attainment of nominal strength in coupling beams and minimum ductility level. Coupling beams to have ductile detailing and be capable of flexural hinging or resist loads with diagonal reinforcement (shear failure and bar buckling avoided). Walls must have minimum resistance to permit attainment of nominal strength in coupling beams and minimum ductility level. Walls must be capable of flexural yielding without local instability, shear failure or bar buckling. Walls must satisfy ductile detailing and ductility requirements. Walls must satisfy detailing and ductility requirements for moderate ductility. Walls must have minimum shear strength. Beams and columns must have factored resistances greater than or equal to factored loads. Columns and beams must satisfy minimum detailing requirements for conventional construction. Closely spaced hoops required in columns unless factored resistance of columns greater than factored resistance of beams or if R d R o = 1.0 . Walls must have factored resistances greater than or equal to factored loads. Factored shear resistance must exceed shear corresponding to factored flexural resistance or shear corresponding to R d R o = 1.0 . Walls must satisfy minimum detailing requirements for conventional construction. Other SFRS(s) 1.0 1.0 CAC Concrete Design Handbook 11.2 11–5 Seismic Design Considerations Seismic design is concerned not only with providing the required strength but also with providing minimum levels of ductility and choosing appropriate structural systems. These goals may be achieved by: (i) choosing structural systems which are as symmetrical as possible in plan and as uniform as possible in elevation (minimizing structural irregularities); (ii) designing the primary lateral load resisting structural components so that desirable energy dissipating systems will form (e.g., "weak-beam strong-column"); (iii) detailing the energy dissipating regions of the primary lateral load resisting components to ensure that substantial inelastic deformations can be achieved without significant loss of strength, and (iv) ensuring that secondary members which are not part of the lateral load resisting system can maintain their gravity load carrying capacity as they undergo the required lateral deformations. In the design of ductile members it is necessary to determine the hierarchy of strengths of different members. To ensure that certain hierarchy of strengths are achieved the CSA Standard defines "probable", "nominal" and "factored" resistances. Table 11.2 summarizes the various types of flexural resistances used in the CSA Standard and suggests approximate relationships between these resistances. Table 11.2 Factored, Nominal and Probable Moment Resistances Type of flexural resistance Calculated using Where used M r = factored resistance φ c = 0.65 φ s = 0.85 All members must satisfy M r ≥ M f M n = nominal resistance φ c = 1.0 φ s = 1.0 To ensure columns stronger than beams M p = probable φ c = 1.0 φ s = 1.0 resistance Approximate relationships for flexure M n ≈ 1.2M r M p ≈ 1.47M r fs = 1.25f y Note: the relationship between M n and M r for the case of flexure and axial load depends on the level of axial load 11.3 Loading Cases For loading combinations including earthquake, the factored load combinations shall include: Principal loads: 1.0D + 1.0E and either of the following combinations of principal and companion loads: 1) For storage occupancies, equipment areas and service rooms: 1.0D + 1.0E + 1.0L + 0.25S 2) For other occupancies: 1.0D + 1.0E + 0.5L + 0.25S 11–6 Seismic Design 11.4 11.4.1 Design of a Six-Storey Ductile Moment-Resisting Frame Building Description of Building and Loads The six-storey reinforced concrete frame building shown in Fig. 11.1 is located in Vancouver and is to be designed as a ductile moment resisting frame structure. The six-storey reinforced concrete office building has 7 - 6 m bays in the N-S direction and 3 bays in the E-W direction which consist of 2 - 9 m office bays and a central 6 m corridor bay. The interior columns are all 500 x 500 mm while the exterior columns are 450 x 450 mm. The one-way slab floor system consists of a slab 110 mm thick spanning in the E-W direction supported by beams in the N-S direction. The secondary beams supporting the slab are 300 mm wide x 350 mm deep (from top of slab to bottom of beam). The beams of both the N-S and E-W frames are 400 mm wide x 600 mm deep for the first three storeys and 400 x 550 mm for the top three storeys. Material Properties Concrete: normal density concrete with f c′ = 30 MPa Reinforcement: f y = 400 MPa Live loads Floor live loads: 2 2.4 kN/m on typical office floors 2 4.8 kN/m on 6 m wide corridor bay Roof load 2 2.2 kN/m snow load, accounting for parapets and equipment projections 2 1.6 kN/m mechanical services loading in 6 m wide strip over corridor bay Dead loads 3 self-weight of reinforced concrete members calculated as 24 kN/m 2 1.0 kN/m partition loading on all floors 2 0.5 kN/m mechanical services loading on all floors 2 0.5 kN/m roofing Wind loading 2 1.84 kN/m net lateral pressure for top 4 storeys 2 1.75 kN/m net lateral pressure for bottom 2 storeys The fire-resistance rating of the building is assumed to be 1 hour. CAC Concrete Design Handbook 11–7 Fig. 11.1 Six-storey structure located in Vancouver 11.4.2 Determination of Design Forces 11.4.2.1 Gravity Loading To determine the member forces, the structure was analyzed using ETABS. To make allowances for cracking, member stiffnesses were assumed to be 0.4 of the gross I for all beams as required by CSA A23.3. To account for the influence of the axial load level on the column stiffnesses, average estimated cracked moments of inertia of 0.6 and 0.7 of I g were used for the columns in the top three storeys and bottom three storeys, respectively (Clause 21.2.5.2). The analysis models and the gravity loading are illustrated in Fig. 11.2. 11–8 Seismic Design To illustrate the requirements for the design of a ductile moment-resisting frame, components of a typical interior E-W frame will be designed in the following examples. Fig. 11.2 Unfactored loading cases considered in design of typical interior frame 11.4.2.2 Seismic Loading Minimum Lateral Earthquake Force The structure is located in Vancouver and is founded on very dense soil and soft rock. Therefore the site classification is “C” and the acceleration-based and velocity-based site coefficients are Fa = 1.0 and Fv = 1.0 , respectively. The seismic response factor, S, is dependent on the fundamental period, T, of the structure. The 5% damped spectral response accelerations, Sa (0.2) , Sa (0.5 ) , Sa (1.0 ) and Sa (2.0 ) are 0.94, 0.64, 0.33 and 0.17, respectively. The design spectral response accelerations are given by the product of the site coefficients and S a as shown in Fig. 11.3. Figure 11.3 Design spectral response acceleration The empirical fundamental lateral period, Ta , for concrete moment frames is given by: Ta = 0.075hn3 / 4 = 0.075 × 21.9 3 / 4 = 0.759 s CAC Concrete Design Handbook 11–9 The calculated period for this structure, using the computer program ETABS is 1.35 s. The value of the fundamental lateral period cannot be taken greater than 1.5 × 0.759 = 1.139 , and hence use Ta = 1.14 s. The corresponding value of S (Ta ) is 0.308 (see Fig. 11.3). For this office building, the earthquake importance factor, I E = 1.0 . The values of M v and J depend on the ratio of Sa (0.2) / Sa (2.0 ) = 0.94 / 0.17 = 5.53 and the value of Ta . For this case M v = 1.0 and J = 1.0 . For this ductile moment resisting frame structure R d = 4.0 and R o = 1.7 . Hence the seismic base shear, V, is: V = S (Ta ) Mv IEW 0.308 × 1.0 × 1.0 × W = = 0.0453W Rd Ro 4.0 × 1.7 Vmin = S (2.0 ) Mv I EW 0.17 × 1.0 × 1.0 × W = = 0.025W Rd Ro 4.0 × 1.7 Vmax = 2 S (0.2)IEW 2 0.94 × 1.0 × W = = 0.092W 3 Rd Ro 3 4.0 × 1.7 For this structure, W = 44,765 kN. Hence, V = 0.0453W = 0.0453 × 44,765 = 2026 kN. The portion of V concentrated at the top of the building is kN, but need not be taken greater Ft = 0.07Ta V = 0.07 × 1.139 × 2026.1 = 161.5 than 0.25V = 0.25 × 2026.1 = 506.5 kN. The calculations of the seismic lateral forces at each floor level are summarized in Table 11.3. Table 11.3 Lateral Load Calculations for Each Floor Level Floor 6 roof 5 4 3 2 1 0 Total hx , m 21.90 18.25 14.60 10.95 7.30 3.65 0.00 - Wx , kN 7457 7365 7365 7526 7526 7526 44,765 hxW x , kN·m 163,308 134,411 107,529 82,410 54,940 27,470 570,068 Fx , kN 696 440 352 270 180 90 0 2,026 Vx , kN 0 696 1,135 1,487 1,757 1,936 2,026 - Tx , kN·m 2953 1866 1493 1144 763 381 8601 Accidental Torsion The 3-D model shown in Fig. 11.4 was used to calculate accidental torsional effects by applying the lateral forces Fx (see Table 11.3) at an accidental eccentricity of ±0.1D nx , where Dnx is the plan dimension of the building at level x, perpendicular to the direction of seismic loading. This gives an accidental torsional eccentricity of 4.245 m, from the centre of mass (same as centre of rigidity) for loading in the E-W direction. The resulting floor torques, T x , are given in Table 11.3. 11–10 Seismic Design Dynamic Analysis This symmetrical structure has no structural irregularities in the vertical or horizontal directions and in addition is not sensitive to torsion (see Section 11.4.3). Therefore, In accordance with NBCC a dynamic analysis is not required. However, a dynamic analysis was carried to determine the lateral period of vibration (see above). This dynamic analysis was also used to determine the design forces for the members and to estimate the lateral displacements. The purpose of carrying out a dynamic analysis in this example is to illustrate the approach required and to obtain a more realistic design force distribution. The first step is to determine Ve from a linear dynamic analysis. The design base shear Vd is obtained from: Vd = Ve IE Rd Ro However for this regular structure, Vd shall not be taken less than 0.8V . All forces and deflections obtained from the linear dynamic analysis are scaled by the factor Vd / Ve to obtain the design values. However, in order to obtain realistic values of anticipated deflections and drifts, the design values need to be multiplied by R d R o / I E . Fig. 11.4 shows the 3-D model for the dynamic analysis, using ETABS. In the analysis, rigid end offsets were used to simulate the dimensions of the joints and rigid diaphragms were assumed. The total mass for each floor was concentrated at the centre of mass (coincident with the centre of rigidity for this structure). To account for sway effects (P-Delta) the ETABS program option, accounting for second order effects by the addition of the so-called geometric stiffness, which is a function of the compression forces in the columns from gravity loads, was used. These compressive forces were obtained from the consistent loading case of 1.0D + 0.5L + 0.25S , with live load reduction factors. The first three lateral modes in the E-W direction are shown in Fig. 11.5, together with the associated periods of vibration and the modal participating mass ratios. Note that the sum of these ratios is 96.9% of the total mass and hence exceeds the minimum required ratio of 90% of the total mass (NBCC). Spectral modal superposition, using SRSS for the first three modes in the E-W direction was used to determine all forces and deformations. CAC Concrete Design Handbook 11–11 Figure 11.4 3-D Model used for dynamic analysis Mode 1 T = 1.349 MPMR = 0.82 Mode 2 T = 0.453 MPMR = 0.11 Mode 3 T = 0.250 MPMR = 0.04 Figure 11.5 Mode shapes, corresponding lateral periods of vibration and modal participating mass ratios The base shear determined by dynamic analysis is Ve = 10690 kN. Therefore: 10690 1.0 = 1572 kN 4.0 × 1.7 However for this regular building Vd shall not be taken less than 0.8V = 0.8 × 2026 .1 = 1620.9 kN. Hence, all forces and deflections obtained from the dynamic analysis shall be multiplied by Vd / Ve = 1620 .9 / 10690 = 0.152 . Vd = 11–12 11.4.3 Seismic Design Deflections, Drift Ratios and Torsional Sensitivity The deflections obtained from the dynamic analysis need to be multiplied by the factor 0.152 to account for the total anticipated displacements, including the inelastic effects. It is necessary to multiply these deflections by the factor R d R o / I E to obtain the design values. Note that the deflections obtained from dynamic analysis include P-Delta effects. The deflections arising from accidental torsional eccentricity shall be added to the deflections from the dynamic analysis. To determine if the structure is sensitive to torsion, the value of B x is determined from the maximum and average displacements of the structure at level x in the E-W and N-S directions. The maximum value, B , of the B x values is at the first floor level for loading in the E-W direction (an average displacement of 5.1 mm and a maximum displacement of 6.8 mm), giving: δ 6.8 B = max = = 1.35 5.1 δ ave Because B is less than 1.7, the structure is not sensitive to torsion. The maximum interstorey drift ratio occurs in Frames 1 and 8 in the second storey for the EW direction of loading. From the dynamic analysis the maximum interstorey drift ratio is 0.0015 and the interstorey drift ratio from accidental torsion at this level is 0.0007, for a maximum interstorey drift ratio of 0.0022. Therefore the anticipated interstorey drift ratio, including inelastic effects is 0.0022 × 4.0 × 1.7 / 1.0 = 0.0146 . This anticipated maximum interstorey drift ratio is less than the NBCC limit of 0.025. 11.4.4 Design of Ductile Beam To illustrate the procedures involved in designing a beam in a ductile moment-resisting frame, a typical first storey interior beam will be designed below. For illustration purposes frame 2 will be designed. This frame, although it has a smaller torsional shear than frame 1, will require more reinforcement than frame 1 because it carries larger dead and live loads. The details of the beam and column framing are given in Fig. 11.6. Fig. 11.6 Typical beam and column framing CAC Concrete Design Handbook 11–13 11.4.4.1 Determination of Design Moments The moments in the beams resulting from dead load, D, live load, L, and earthquake loading, E, as determined from frame analyses, are in Fig. 11.7. Note that the moments are given at the face of the columns. Since most of the gravity loading in beams AB, BC and CD is introduced at the locations of the secondary beams, the small uniformly distributed loading has been approximated by additional concentrated loads at the secondary beam locations. Fig. 11.7 Loading cases on typical interior beam at second floor level Table 11.4 gives the unfactored moments at critical locations and also gives the factored moment combinations which need to be considered. 11.4.4.2 Moment Redistribution and Moment Envelopes Instead of designing each of the critical sections for the maximum factored moments given in Table 11.4, moment redistribution will be used to reduce some of the maximum design moments. Since the beams in a ductile moment-resisting frame structure are designed and detailed to exhibit considerable ductility the maximum redistribution of 20%, permitted by Clause 9.2.4, will be used. While it is possible to redistribute the earthquake moments, care must be exercised to ensure that the total column shears in any one storey remain unchanged after redistribution. A simpler approach is to redistribute only the dead load and live load moments. In order to reduce the magnitude of the negative moments at location BA, the dead and live load support moments are reduced at this location by the maximum permitted amount (20%). The positive moments in span AB are increased by the appropriate amounts. The resulting moments are summarized in Table 11.5. 11–14 Seismic Design Table 11.4 Moments at Critical Locations (kN·m) Before Redistribution D L Accidental Torsion E without accidental torsion E with accidental torsion 1.25D+1.5L 1.0D+1.0E 1.0D-1.0E 1.0D+0.5L+1.0E 1.0D+0.5L-1.0E AB -167 -66 ± 30 ± 98 a +119 +50 ± 11 ± 36 b +105 +45 ±9 ± 30 BA -206 -90 ± 28 ± 92 BC -104 -79 ± 41 ± 131 c +29 +41 ± 15 ± 48 ± 128 ± 47 ± 39 ± 120 ± 172 ± 63 -308 -39 -295 -72 -328 +224 +166 +72 +191 +97 +199 +144 +66 +167 +88 -393 -86 -326 -131 -371 -249 +68 -276 +29 -316 +98 +92 -34 +112 -13 Note: controlling load combinations shown in bold Table 11.5 Moments at Critical Locations (kN·m) after Redistribution D L Accidental Torsion E without accidental torsion E with accidental torsion 1.25D+1.5L 1.0D+1.0E 1.0D-1.0E 1.0D+0.5L+1.0E 1.0D+0.5L-1.0E AB -167 -66 ± 30 ± 98 a +132 +56 ± 11 ± 36 b +133 +57 ±9 ± 30 BA -165 -72 ± 28 ± 92 BC -104 -79 ± 41 ± 131 c +29 +41 ± 15 ± 48 ± 128 ± 47 ± 39 ± 120 ± 172 ± 63 -308 -39 -295 -72 -328 +249 +180 +85 +208 +113 +252 +172 +94 +201 +122 -314 -45 -284 -81 -320 -249 +68 -276 +29 -316 +98 +92 -34 +112 -13 Note: controlling load combinations shown in bold It is noted that, after redistribution, earthquake loading governs at all negative moment sections at the second floor level. 11.4.4.3 Design of Flexural Reinforcement at Critical Sections Top bars at column faces In deciding on the appropriate top reinforcement, note that Clause 21.5.5.6 limits the diameter, db, passing through the joint to l j / 24 for this normal density concrete structure and uncoated bars. Thus for this case the maximum diameter of beam bars passing through the interior columns is 500 / 24 = 21 mm. Hence the maximum beam bar size is 20M. At column A, a factored moment resistance of at least 328 kN·m is required. Assuming a flexural lever arm of 0.75h = 0.75 × 0.600 = 0.450 m, the required area of top bars would be 2 328 × 1000 / (0.450 × 0.85 × 400 ) = 2144 mm . If it is assumed that slab reinforcement within a distance of 3hf from the sides of the beam is effective, then 4–10M bars in the slab are effective. CAC Concrete Design Handbook 11–15 It is assumed that these 10M bars in the flange are effective under reversed cyclic loading even though there is no anti-buckling reinforcement for these bars. Note that larger bars may not be 2 effective. The additional reinforcement required is then 1744 mm . Note that it is unwise to be too conservative when designing the top reinforcement since beam shears, joint shears, column moments and column shears are all increased if the flexural capacity at the end of the beam is increased. Let us try an arrangement of 6–20M bars as shown in Fig. 11.8. Keeping in mind that the positive moment resistance of the beam needs to be at least one-half of the negative moment resistance, try using 4–20M bars on the bottom of the beam. Fig. 11.8 Beam cross section near column face Accounting for the presence of the compression reinforcement, the depth of compression, c, is found to be 92 mm and the factored negative moment resistance is 359 kN·m. Hence the moment capacity is satisfactory. The required minimum top and bottom reinforcement, As ,min , from Clause 21.3.2.1 is: 2 As ,min = 1.4bw d / f y = 1.4 × 400 × 527 / 400 = 738 mm ≤ 1200 mm 2 O.K. The maximum reinforcement permitted is: 2 0.025bw d = 0.025 × 400 × 527 = 5270 mm ≥ 2200 mm 2 O.K. Note that in choosing the arrangement of the beam bars at column faces the following factors must be considered: (a) the need to restrain the longitudinal bars from buckling by providing lateral restraint in the form of hoops and ties. (b) the need to pass the beam bars through the column cage, and (c) the need to provide adequate space between top bars to permit placement and vibration of concrete. Since the magnitudes of the negative moment resistances required at column faces AB, BA and BC are all about the same, we will use the same reinforcing arrangement at these three locations. 11–16 Seismic Design Bottom bars for positive moment regions Span BC: For span BC, the effective compressive flange width is 1600 mm (see Clause 10.3.3). For 2 4–20M bars ( As = 1200 mm ), M r at the column face, accounting for the large amount of top reinforcement, is 229 kN·m which is larger than one half of 359 kN·m (i.e., M r at column face 2 where As = 2200 mm ). As 4–20M bottom bars are provided at column faces AB, BA and BC, use 4–20M bars in span BC. The positive moment resistance M r is 229 kN·m in the midspan regions of span BC. As 229 kN·m exceeds 112 kN·m (Table 11.5), 4-20M bars will be satisfactory. Span AB: For span AB, the effective compressive flange width is 2200 mm (see Clause 10.3.3). For M r ≥ 252 kN·m (Table 11.5) try 6- 20M bottom bars. Neglecting the top reinforcement, the depth of the equivalent rectangular stress block is 18 mm and M r = 315 kN·m (see Fig. 11.9). Accounting for the large amount of top reinforcement, the positive moment M r at the column face is 246 kN·m. Fig. 11.9 Positive and negative moment capacities of beam CAC Concrete Design Handbook 11–17 11.4.4.4 Design of Transverse Reinforcement in Beams Shear requirements Determine the shears corresponding to the development of flexural hinging at both ends of the beam. For the chosen reinforcement at the beam ends the probable moment resistances are: (i) − Probable negative moment resistance, M pr − Using a strain compatibility approach to calculate M pr results in a depth of compression, − c = 95 mm, a stress block depth of 85 mm and M pr = 528 kN·m (see Fig. 11.9). Note that the probable moment resistance of the beams can be estimated by multiplying M r by the ratio 1.25 / 0.85 = 1.47 . In this case M pr would be 359 × 1.47 = 528 kN·m. This simple approach is sufficiently accurate for design purposes. (ii) + Probable positive moment resistance, M pr The factored moment resistance at the ends in span BC is 229 kN·m and hence we can + estimate the probable moment resistance as M pr = 1.47 × 229 = 337 kN·m. Similarly, the probable moment resistance at the ends of span AB is 1.47 × 246 = 362 kN·m. (iii) Determine factored shears The shear diagrams shown in Fig. 11.10 are drawn for lateral forces acting in the west direction. For lateral forces acting in the east direction the shear diagrams will be "mirror images" of those shown (e.g., the shear at B would be 234 kN). Fig. 11.10 Determinaton of shears corresponding to flexural hinging 11–18 Seismic Design Using θ = 45° and β = 0 gives (Clause 21.3.4.2): Vr = φs Av f y d v / s At the column faces the transverse reinforcement consists of 4–10M legs, hence 2 Av = 400 mm . At the ends A and B the required spacing for shear is: s= 0.85 × 400 × 400 × 0.9 × 527 = 276 mm 234 × 1000 At the ends B and C the required spacing for shear is: s= 234 × 276 = 247 mm. 262 2 If 2-legged 10M stirrups are used as transverse reinforcement ( Av = 200 mm ) the required spacings in the middle regions of beams AB and BC are 344 mm and 228 mm, respectively. Other shear design requirements: (i) Maximum shear (Clause 11.3.3) Vr ,max = 0.25φ c f c′ bw d v = 0.25 × 0.65 × 30 × 400 × 0.9 × 527 = 925 kN (ii) Minimum amount of stirrups (Clause 11.2.8.2): for 4 stirrup legs: s≤ Av f y 0.06 f c′ bw = 400 x 400 0.06 30 x 400 = 1217 mm for 2 stirrup legs: s ≤ 608 mm (iii) Spacing limits (Clause 11.3.8.3): Since V f < 0.125 φ c f c′ bw d v = 0.125 x 0.65 X 30 x 400 x 0.9 × 527 = 462 kN Then s max = 600 mm or 0.7d v = 0.7 × 0.9 × 527 = 332 mm. Note that near the ends of the beams the stirrup spacing required for shear cannot exceed 276 and 247 mm for spans AB and BC, respectively. "Anti-buckling” requirements (Clause 21.3.3.2) Hoops to prevent buckling of longitudinal bars are required over a length of 2d from the face of the columns. The spacing of the hoops shall not exceed: (i) d / 4 = 527 / 4 = 132 mm (ii) 8d bl = 8 × 20 = 160 mm (iii) 24d bh = 24 × 10 = 240 mm (iv) 300 mm Note that the 4-legged arrangement of transverse reinforcement satisfies Clause 21.3.3.3. Hence use a spacing of 130 mm for 4-legged hoops over a length of at least 2d = 2 × 527 = 1054 mm. CAC Concrete Design Handbook 11–19 11.4.4.5 Checking Extent of Plastic Hinging The moment diagrams corresponding to plastic hinging at both ends of beams AB and BC are shown in Fig. 11.10. Hinging can spread over a distance of about 3.43 m from the face of column B in beam AB. Since the earthquake loading can reverse, provide 4-legged hoop reinforcement spaced at 130 mm as shown in Fig. 11.11. The bottom 4-20M bars can only be spliced near midspan of the beam (Clause 21.3.2.3). Therefore, to satisfy the maximum spacing requirements of Clause 21.3.2.3 for regions of lap splices, provide 2-legged hoops spaced at 100 mm in the middle region of beam AB (see Fig. 11.11). For span BC, provide 4-legged hoops at a spacing of 130 mm over a distance of 2d (1054 mm) from the column faces. Outside of these regions, the provision of 2-legged hoops at a spacing of 100 mm satisfies both the shear requirements and the confinement requirements for lap splices (see Fig. 11.11). 11.4.4.6 Bar Cut-offs The locations of bar cut-offs are determined from the moment diagrams corresponding to the formation of plastic hinges at the ends of the beams. The theoretical cut-off location is located at a distance of 1.51 m from the face of the column (see Fig. 11.10). From Clause 12.10.4 it is required to provide an embedment length beyond the theoretical cut-off point of at least d or 12db. Hence the minimum length required is 1510 + d = 1510 + 527 = 2037 mm. Continue the 6–20M top bars a distance of 3 m from the column face such that the bars are terminated in a region of lower shear. For span BC, extend the 6-20M top bars a distance of 2.0 m from the face of the column. 11.4.4.7 Splice Details Flexural reinforcement cannot be spliced within a distance of 2d from the column face nor within a distance d from of a potential plastic hinge location (Clause 21.3.2.3). In evaluating cutoff locations, d was taken as 527 mm. In determining locations of bar cut-offs and splices we will consider the moment diagram corresponding to the formation of hinges at the ends of the beams (see Fig. 11.10). The splices for the top bars will be located in a region of the beam where the bars are predicted to remain in compression. However, as it is required to have a minimum negative and positive moment resistance at the face of the joint (Clause 21.3.2.2) the splice length will be calculated as for a tension splice. (a) Splicing of the 2–20M "continuous" top bars The required minimum moment capacity along the length of the beam (Clause 21.3.2.2) is 0.25 × 359 = 90 kN·m. M r for 2-20M top bars is 175 kN·m. Hence for the classification of tension lap splices in accordance with Clause 12.15.2 (As provided)/ As required) is 175 / 90 = 1.94 . Hence Class B splices are required. The development length l d for these top bars from Table 12-1 is: fy 400 l d = 0.45k 1k 2 k 3 k 4 d b = 0.45 × 1.3 × 1 × 1 × 0.8 × × 20 = 684 mm f c′ 30 Thus the splice length is 1.3 × 684 = 890 mm. (b) Splicing of the 4–20M "continuous" bars ld The development length for these bottom bars is: fy 400 = 0.45k 1k 2 k 3 k 4 d b = 0.45 × 1 × 1 × 1 × 0.8 × × 20 = 526 mm f c′ 30 11–20 Seismic Design Thus the splice length is 1.3 × 526 = 684 mm. The details of the reinforcement in the beam are illustrated in Fig. 11.11. Fig. 11.11 Reinforcement details in beams CAC Concrete Design Handbook 11.4.5 11–21 Design of Interior Ductile Column To illustrate the procedures involved in designing a column in a ductile moment resisting frame a typical first storey interior column in Frame 2 or 7 of the building described in Section 11.4 will be designed. The column that will be designed is shown in Fig. 11.12. Fig. 11.12 Beam-column framing 11.4.5.1 Column End-Actions from Analysis The column end actions obtained from analysis are summarized in Table 11.6. The earthquake forces given are those for lateral seismic forces acting in the E-W direction. For the live load values, pattern loading and live load reduction values were considered. Table 11.6 Column End Actions nd 2 floor bottom of column st 1 floor top of column st 1 floor bottom of column PD kN 1598 PL kN 486 PE kN ±106 MD kN·m +41 ML kN·m +28 ME kN·m ±147 VD kN +20 VL kN +13 VE kN ±92 1704 556 ±137 -53 -37 ±112 +28 +19 ±94 1704 556 ±137 +32 +22 ±183 +28 +19 ±94 11–22 Seismic Design 11.4.5.2 Factored Axial Loads and Moments The column must be designed to resist the appropriate combinations of axial load and moment. From Table 11.6, it is evident that the factored moments at the base of the column will be larger than that at the top. For the base of the column at the ground floor level the factored axial load and moment combinations are given in Table 11.7. Table 11.7 Factored Axial Load and Moments at Column Bases Pf kN Mf kN·m Case 1 1.25D +1.5L Case 2 1.0D +1.0E Case 3 1.0D -1.0E Case 4 1.0D+0.5L +1.0E Case 5 1.0D+0.5L -1.0E -2964 -1841 -1567 -2119 -1845 +73 +216 -151 +226 -140 Note that for this member Ag fc′ / 10 = (500 × 500 ) × 30 / 10 = 750 kN. As Pf exceeds this value, the requirements of Clause 21.4 apply (Clause 21.4.1.1). 11.4.5.3 Preliminary Selection of Column Reinforcement In selecting the column bars, recall that the diameter of these bars must satisfy the requirements that d b ≤ l j / 24 = 600 / 24 = 25 mm (Clause 21.5.5.6) for this normal density concrete and for uncoated bars. Hence the maximum bar size is 25M. Try using 8-25M bars as shown in Fig. 11.13. Fig. 11.13 Column reinforcement details 2 For this arrangement of reinforcement Ast = 8 × 500 = 4000 mm . From Clause 21.4.3.1 2 the minimum area of longitudinal steel is 0.01 × 500 × 500 = 2500 mm and the maximum area of longitudinal steel outside of lap splice regions (assuming lap splicing with an equal area of steel) 2 is 0.03 × 500 × 500 = 7500 mm . Hence this steel arrangement satisfies these requirements. CAC Concrete Design Handbook 11–23 Checking Column Capacity The axial load-moment interaction diagram for the chosen column section is shown in Fig. 11.14. It can be seen that the column has adequate capacity to resist the various combinations of Pf and M f which occur at the base of the column. Fig. 11.14 Pr - M r interaction diagram for column section Although there is a considerable excess of moment capacity in the column, this additional capacity is needed at the top of the column in order to ensure that the columns are stronger than the beams (see below). 11.4.5.4 "Strong Column - Weak Beam" Requirement The flexural capacity of the columns must exceed the flexural capacity of the beams so that ∑M nc ≥ ∑M pb Hence it is necessary to first determine the probable resistances of the beams framing into the column. 11–24 (a) Seismic Design − Probable negative moment resistance, M pb Note that the probable resistance, − M pb , can be approximated as 1.47M r = 1.47 × 359 = 528 kN·m. This simple approach is sufficiently accurate for design purposes as can be seen from Fig. 11.9. (b) + Nominal positive moment resistance, M pb + = 1.47 × 246 = 362 kN·m. M pb (c) Determination of To determine ∑M ∑M nc nc for a particular loading case we need to calculate the nominal moment resistance of the column above and below the beam-column joint. The lowest flexural resistance will occur at either the highest or lowest axial load, that is, load cases 3 and 4 need to be investigated (load case 1 does not involve lateral load). The axial load corresponding to cases 3 and 4 are given in Fig. 11.15 along with the column nominal moment resistances corresponding to these axial loads (from the P-M interaction diagram). Fig. 11.15 Capacity design of columns and factored loads on column Thus the requirement that ∑M nc ≥ ∑M pb is satisfied. Note that for simplicity the above calculations have neglected the influence of the beam and column shears acting at the joint faces. 11.4.5.5 Design of Transverse Reinforcement in Column Shear requirements The column must have a factored shear resistance, Vr, which exceeds the column shear corresponding to the probable moment resistance in the beams and which exceeds the shear CAC Concrete Design Handbook 11–25 forces due to factored loads (Clause 21.4.5.1). From Table 11.6, load case 4 (1.0D + 0.5L + 1.0E ) gives the maximum factored shear of 132 kN. The moment at the top of the column corresponding to the development of the probable moment resistances of the beams may be estimated from: Kc 1 / 3.05 + − M c = M pr + M pr × = (362 + 528 ) × = 445 kN·m 2 × 1 / 3.05 Kc ( ) ∑ However since we are designing a ground storey column a different approach is required at the base of this column. It is assumed that the column frames into a substructure that is considerably stronger and stiffer than the column and hence the possibility of hinging at the column base must be accounted for. To ensure adequate column shear capacity, it is necessary to determine the maximum probable moment resistance corresponding to all axial loads. Because the axial loads for all the seismic load cases are close to the balanced axial load level, the moment at the base of the column will be taken as the probable moment resistance corresponding to the balanced loading conditions (i.e., the highest probable moment resistance possible). The calculations involved in determining this moment resistance are summarized in Fig. 11.16. Fig. 11.16 Determination of factored shear strength in ground storey column 11–26 Seismic Design The column actions which will correspond to the formation of hinges in the beams at the top of the column and the formation of a hinge at the base of the column are shown in Fig. 11.16. From Clause 21.4.5.2 the shear carried by the concrete is determined with values of β and θ taken from Clause 11 but limited to a maximum of 0.10 and a minimum of 45°, respectively. For this column containing greater than minimum amounts of transverse reinforcement and subjected to axial compression, Clause 11.3.6.3 applies, but the limits for β and θ given above control. The shear resistance attributed to the concrete, assuming that d v = 0.72h , is: Vc = φ c λβ f c′ bw d v = 0.65 × 0.10 × 30 × 500 × 0.72 × 500 = 64.1 kN The required Vs is equal to 359 − 64.1 = 294.9 kN. Using the transverse reinforcement arrangement shown in Fig. 11.13 with square and diamond shaped hoops, the effective area of 2 shear reinforcement is Av = 2 + 2 cos 45 o × 100 = 3.41× 100 = 341 mm . Hence, the required stirrup spacing can be found from Equation (11-7) as: ( s= φ s Av f y d v cot θ Vs = ) 0.85 × 341 × 400 × 0.72 × 500 × cot 45 o = 142 mm 294.9 × 1000 Since Vf of 359 kN is less than 0.125λφ c fc′bw d v = 439 kN, then from Clause 11.3.8.1, the maximum spacing of the shear reinforcement is the smaller of 0.7 × 0.72 × 500 = 252 mm or 600 mm. In order to satisfy the minimum shear reinforcement requirements of Clause 11.2.8.2, the maximum spacing of the 10M stirrups is: s= Av f y 0.06 f c′ bw = 341 × 400 0.06 × 30 × 500 = 830 mm Therefore for shear a spacing of 142 mm controls. (b) Confinement requirements Since the column under consideration is at the base of the structure confinement reinforcement must be provided over the full height of the column (Clause 21.4.4.6). From Clause 21.4.4.2, the total cross-sectional area of rectangular hoop reinforcement depends on the following factors: kn = nl 8 = = 1.33 nl − 2 8 − 2 ( ) ( ) Po = α1fc′ Ag − Ast + fy Ast = 0.805 × 30 500 2 − 4000 + 400 × 4000 = 7541 kN k p = Pf / Po = 2119 / 7541 = 0.281 Hence, the total area of confinement reinforcement is: Ash = 0.2k n k p Ag f c′ 500 2 30 shc = 0.2 × 1.33 × 0.281 × × × 420s = 3.34s 2 Ach f yh 400 420 but not less than: Ash = 0.09shc 2 f c′ 30 = 0.09 × 420 × s = 2.84s f yh 400 For Ash = 341 mm , s = 341 / 3.34 = 102 mm. CAC Concrete Design Handbook 11–27 From Clause 21.4.4.3 the spacing of the hoops shall not exceed: (i) h / 4 = 500 / 4 = 125 mm (ii) 6d b = 6 × 25 = 150 mm (iii) s x = 100 + (350 − hx ) / 3 = 100 + (350 − 187.5 ) / 3 = 154 mm Hence use 10M hoops at 100 mm centres as shown in Fig. 11.17. The chosen arrangement of hoops and longitudinal reinforcement also satisfies Clauses 21.4.4.4 and 7.6.5. The details of the first-storey column reinforcement are given in Fig. 11.17. Fig. 11.17 Details of reinforcement in first-storey column 11–28 Seismic Design 11.4.5.6 Splice Details We will splice the column bars at mid-height of the column with tension lap splices in accordance with Clause 21.4.3.2. The development length, l d , can be found from Table 12-1 as: l d = 0.45k 1k 2 k 3 k 4 fy f c′ d b = 0.45 × 1 × 1 × 1 × 1 × 400 30 × 25 = 822 mm Provide a lap length of 1.3l d = 1.3 × 822 = 1068 mm (see Fig. 11.17). 11.4.6 Design of Interior Beam-Column Joint To illustrate the procedures involved in designing a beam-column joint in a ductile momentresisting frame, an interior joint in the structure described in Section 11.4 will be designed. A description of the joint details is given in Fig. 11.18. Fig. 11.18 Geometry of interior beam-column joint 11.4.6.1 Determination of Factored Forces in Joint In accordance with Clause 21.5.1.2, assume that the tensile force in the beam reinforcement is 1.25 As f y . CAC Concrete Design Handbook 11–29 To estimate the corresponding shear, Vcol , in the column above the joint, assume that flexural hinging occurs in the beams at the first and second storey levels. The calculations are summarized in Fig. 11.19. Fig. 11.19 Determination of factored shear resistance in joint 11–30 Seismic Design 11.4.6.2 Check Factored Shear Resistance of Joint Since four equal depth beams frame into the joint and each covers more than 3/4 of each face of the joint, the joint is considered to be externally confined (Clause 21.5.4.1). Hence the factored shear resistance of the joint is taken as: V r = 2.2λφ c f c′ A j = 2.2 × 0.65 30 × 500 × 500 = 1958 kN As the design shear in the joint of 1408 kN is less than 1958 kN, the shear resistance of the joint is adequate. 11.4.6.3 Transverse Reinforcement Required in Joint As the joint is framed by four equal depth beams which provide confinement, only one-half of the confinement steel required for the column is required through the joint (Clause 21.5.2.2). The spacing required for confinement in the joint is therefore 200 mm. However the spacing limits of Clause 21.4.4.3 control ( s max = h / 4 = 125 mm). Hence provide 3 sets of 10M hoops between the flexural bars in the beams as shown in Fig. 11.20. Fig. 11.20 Details of joint reinforcement CAC Concrete Design Handbook 11–31 11.4.6.4 Bond of beam Bars As the beam bars pass through the joint their bond characteristics are checked by the requirement in Clause 21.5.5.6 that the bar diameters be not greater than l j / 24 = 500 / 24 = 21 mm (normal density concrete and uncoated bars). Since this exceeds the actual bar diameter of 20 mm this requirement is met. 11.5 11.5.1 Analysis of a Ductile Core-Wall Structure Description of Building and Loads The twelve-storey reinforced concrete building shown in Fig. 11.21 is located in Montreal and is founded on stiff soil. Fig. 11.21 Plan and elevation of twelve-storey office building 11–32 Seismic Design The twelve-storey reinforced concrete office building has a centrally located elevator core. Each floor consists of a 200 mm thick flat plate with 6 m interior spans and 5.5 m end spans. The columns are all 550 x 550 mm and the thickness of the core wall components 400 mm. The 400 mm thick wall thickness was initially chosen such that it exceeds l u / 14 = 4650 / 14 = 332 mm (Clause 21.6.3). This value is checked in Section 11.5.6.5. The core wall measures 6.4 m by 8.4 m, outside to outside of the walls. Two 400 mm wide x 900 mm deep coupling beams connect the two C-shaped walls at the ceiling level of each floor. The core walls extend one storey above the th th roof at the 12 floor level forming an elevator penthouse at the 13 floor level. The slab has a 100 mm overhang. Material Properties Concrete: normal density concrete with fc′ = 30 MPa Reinforcement: f y = 400 MPa Gravity and Wind Loadings Floor live load: Roof load: 2 2.4 kN/m on typical office floors 2 4.8 kN/m on 12 m by 12 m corridor area around core 2 2.2 kN/m full snow load 2 1.6 kN/m mechanical services loading in 6 m wide strip over corridor bay 3 Dead loads: self-weight of members calculated at 24 kN/m 2 1.0 kN/m partition loading on all floors 2 0.5 kN/m ceiling and mechanical services loading on all floors 2 0.5 kN/m roofing Wind loading: varies from 1.1 to 1.37 kN/m net lateral pressure over the height of the building 2 The building is to be designed with a fire-resistance rating of 2 hours. 11.5.2 Analysis Assumptions To determine the forces in the walls and the coupling beams and the periods of vibration, the three-dimensional core wall system was analyzed using ETABS. To make allowances for cracking, member stiffnesses were based on effective properties equal to 0.25I g for the moment of inertia and 0.45 Ag for the shear area for all diagonally reinforced coupling beams as required by Clause 21.2.5.2.1. The walls were modeled with an effective flexural stiffness of 0.7EI g and an effective axial stiffness of 0.7EAg , determined as a function of the axial loading at the base of the walls (see Clause 21.2.5.2.1). 11.5.3 Seismic loading For the force modification factors, Rd and Ro , we will assume that the core-wall system will take 100% of the lateral loads as allowed by the NBCC. In the N-S direction we will design and detail the walls as ductile shear walls and hence Rd = 3.5 and Ro = 1.6 . In the E-W direction we will design and detail the coupling beams and walls as a ductile coupled wall system and hence Rd = 4.0 and Ro = 1.7 . In order for the E-W direction to qualify as a ductile coupled wall system we must check the degree of coupling as determined by analysis of the structure. CAC Concrete Design Handbook 11–33 11.5.3.1 Minimum Lateral Earthquake Force The structure is located in Montreal and is founded on stiff soil. Therefore the site classification is “D”. The acceleration-based site coefficient Fa = 1.124 and the velocity-based site coefficient Fv = 1.360 . The seismic response factor, S (Ta ) , is dependent on the fundamental period, Ta , of the structure. The 5% damped spectral response accelerations, Sa (T ) , for Montreal are given in Table 11.8. Table 11.8 also gives the design spectral response accelerations, S (T ) , obtained from the product of the site coefficients and S a as shown in Fig. 11.22. Table 11.8 Spectral response accelerations and design spectral response accelerations T ≤ 0.2 T = 0.5 T = 1.0 T = 2.0 T ≥ 4.0 Sa (T ) 0.69 0.34 0.14 0.048 0.024 S (T ) 0.776 0.462 0.190 0.065 0.033 Figure 11.22 Design spectral response acceleration The empirical fundamental lateral period, Ta , for this shear wall structure in the N-S and E-W directions, is given by: Ta = 0.05hn3 / 4 = 0.05 × 45.0 3 / 4 = 0.869 s N-S Direction The calculated period for this structure in the N-S direction, using the computer program ETABS, is 1.83 s. Note that a 3-D model including the walls, the slabs and the columns was also analysed and resulted in a period of 1.75 s. Because this period is within 15% of the periods of the walls alone, then a period of 1.83 s was used. The value of the fundamental lateral period cannot be taken greater than 2 × 0.869 = 1.74 and hence use Ta = 1.74 s. From linear interpolation, S (Ta ) = 0.0981 (see Fig. 11.22). The values of M v and J depend on the ratio of Sa (0.2) / Sa (2.0 ) = 0.69 / 0.048 = 14.4 and the value of Ta . It is necessary to interpolate the value of S (Ta ) Mv and the value of J between periods of 1.0 and 2.0 s and 0.5 and 2.0 s, respectively. This interpolation results in S (Ta ) Mv = 0.170 , Mv = 1.736 and J = 0.505 . 11–34 Seismic Design This office building has an earthquake importance factor, I E = 1.0 . For this ductile shear wall Rd = 3.5 and Ro = 1.6 . Hence the seismic base shear, V, is: V = S (Ta ) Mv IEW 0.0981× 1.736 × 1.0 × W = = 0.0304W Rd Ro 3.5 × 1.6 Vmin = S (2.0 ) Mv I EW 0.0653 × 2.5 × 1.0 × W = = 0.0291W Rd Ro 3.5 × 1.6 Vmax = 2 S (0.2)IEW 2 0.7756 × 1.0 × W = = 0.0923W 3 Rd Ro 3 3.5 × 1.6 For this structure, W = 90590 kN. Hence V = 0.0304W = 0.0304 × 90590 = 2756 kN. The portion of V concentrated at the top of the building is Ft = 0.07TaV = 0.07 × 1.737 × 2755.6 = 335 kN, but need not be taken greater than 0.25V = 0.25 × 2755.6 = 688.9 kN. The calculations of the seismic lateral forces at each floor level are summarized in Table 11.9. E-W Direction The calculated period for this structure in the E-W direction, using the computer program ETABS is 1.72 s. It is noted that this period may be used because the period for the full 3-D structure (walls, slabs and columns) is within 15% of this value. The value of the fundamental lateral period cannot be taken greater than 2 × 0.869 = 1.74 and hence use Ta = 1.72 s. From linear interpolation, S (Ta ) = 0.101 (see Fig. 11.22). It is necessary to interpolate the value of S (Ta ) Mv and the value of J between periods of 1.0 and 2.0 s and 0.5 and 2.0 s, respectively. This interpolation results in S (Ta ) Mv = 0.110 , Mv = 1.093 and J = 0.757 . For the ductile coupled wall system in the E-W direction Rd = 4.0 and Ro = 1.7 . Hence the seismic base shear, V, is: V = S (Ta )Mv IEW 0.101× 1.093 × 1.0 × W = 0.0162W = Rd Ro 4.0 × 1.7 Vmin = S (2.0 ) Mv I EW 0.065 × 1.2 × 1.0 × W = 0.0115W = Rd Ro 4.0 × 1.7 Vmax = 2 S (0.2)IEW 2 0.776 × 1.0 × W = = 0.0760W 3 R d Ro 3 4.0 × 1.7 For this structure W = 90590 kN. Hence V = 0.0162W = 0.0162 × 90590 = 1466 kN. The portion of V concentrated at the Ft = 0.07TaV = 0.07 × 1.72 × 1466 = 176.2 kN, but need 0.25V = 0.25 × 1466 = 366.5 kN. top of the not be taken building is greater than CAC Concrete Design Handbook 11–35 The calculations of the seismic lateral forces at each floor level using the equivalent static force procedure are summarized in Table 11.9. The weight of the penthouse has been included at the roof level. Table 11.9 Lateral Load Calculations for Each Floor Level Floor N-S E-W hi , m Wi , kN hi Wi , kN·m Fx Tx Fx Tx 12 45.00 8154 366930 727.1 2163 385.1 1146 11 41.35 7467 308761 329.8 981 175.8 523 10 37.70 7467 281506 300.7 895 160.3 477 9 34.05 7467 254251 271.6 808 144.7 431 8 30.40 7467 226997 242.5 721 129.2 384 7 26.75 7467 199742 213.4 635 113.7 338 6 23.10 7467 172488 184.3 548 98.2 292 5 19.45 7467 145233 155.2 462 82.7 246 4 15.80 7467 117979 126.0 375 67.2 200 3 12.15 7467 90724 96.9 288 51.7 154 2 8.50 7467 63470 67.8 202 36.1 108 1 4.85 7766 37665 40.2 120 21.4 64 90590 2265745 2756 8198 1466 4362 0 Total 11.5.3.2 Accidental Torsion The 3-D model shown in Fig. 11.23 was used to calculate accidental torsional effects by applying the lateral forces Fx (see Table 11.9) at an accidental eccentricity of ±0.1Dnx , where Dnx is the plan dimension of the building at level x, perpendicular to the direction of seismic loading. This gives an accidental torsional eccentricity of 2.975 m, from the centre of mass (same as centre of rigidity) for loading in the N-S and E-W directions. The values of Tx are given in Table 11.9. The structure was analysed with a 3-D model of the core-wall structure for both wind and seismic loading, with and without eccentricity. In these analyses the participation of the flat plate and columns was neglected. 11.5.3.3 Degree of Coupling In the calculations of the base shear it was assumed that there was sufficient coupling of the walls in the E-W direction to qualify this wall system as a ductile coupled wall system rather than a partially coupled wall system. To check the degree of coupling by the wall system in the E-W direction, the base overturning moment resisted by axial tension and compression forces in the walls (resulting from shear in the coupling beams), divided by the total base overturning moment is determined. Although the design forces were obtained from dynamic analysis, it is not 11–36 Seismic Design appropriate to use these values to determine the degree of coupling because the values obtained from modal combination (e.g., SRSS or CQC) does not satisfy static equilibrium. The degree of coupling was determined using static analysis with the Fx forces from the equivalent static force procedure, giving: Tl 5513 × 6.5 = = 0.74 M1 + M 2 + Tl 2 × 6400 + 5513 × 6.5 where T l = axial tension and compression acting at centroid of coupled walls = distance between centroids of coupled walls, equal to 6.5 m for this example The degree of coupling is 74%, which is exceeds the minimum limit for ductile coupled walls of 66%. Hence Rd = 4.0 and Ro = 1.7 , as assumed above. 11.5.3.4 Check on Structural Irregularity To determine if the structure is sensitive to torsion, the values of B need to be determined at all levels from the maximum and average displacements of the structure at in the E-W and N-S directions. The maximum value, B (determined at the extreme points of the structure), in the N-S direction occurs in the first storey, with a displacement due to accidental torsion of 1.04 mm and a displacement due to Fx of 1.30 mm. Hence: B= δ max 1.04 + 1.30 = = 1.80 1.30 δ ave Because B is greater than 1.7, the structure is sensitive to torsion and hence is designated as irregular. The maximum value of B in the E-W direction occurs in the first storey and is 1.66. Note that a 3-D analysis of the structure, including the columns and slabs as well as the actual mass distributions indicates that the first and fourth modes of vibration are torsional with periods of 1.89 and 0.54 s, respectively. This confirms that the structure is indeed torsionally sensitive. This design example illustrates the steps necessary to design this common type of structure, that is torsionally sensitive. 11.5.3.5 Dynamic Analysis The NBCC requires that the Dynamic Analysis Procedure be used except that the Equivalent Static Force Procedure may be used for structures that meet any one of the three conditions in parts (a), (b) and (c) of Clause 4.1.8.7. For this building, the term I E FaSa (0.2 ) is greater than 0.35 and hence the condition in part (a) is not satisfied. The presence of the structural irregularity due to torsion sensitivity means that the Equivalent Static Force Procedure cannot be used (part (b) of 4.1.8.7). Part (c) of 4.1.8.7 is also not satisfied. Accordingly, the Equivalent Static Force Procedure is not permitted as an alternative to the Dynamic Analysis Procedure for this example building. The first step is to determine Ve from a linear dynamic analysis. The design base shear Vd is obtained from: Vd = Ve IE Rd Ro CAC Concrete Design Handbook 11–37 Because this is an irregular structure, that requires dynamic analysis (NBCC 4.1.8.7), Vd shall not be taken less than 1.0V rather than 0.8V , permitted for a regular structure. All forces and deflections obtained from the linear dynamic analysis are scaled by the factor Vd / Ve to obtain the design values. However, in order to obtain realistic values of anticipated deflections and drifts, the design values need to be multiplied by R d R o / I E . Fig. 11.23 shows the 3-D ETABS model that considers only the core wall system (SFRS) and is used for the dynamic analysis. The second model used is the entire structure including the frame members not considered part of the SFRS (columns and the slabs) to check the ductility and strength of these members subjected to seismically induced deformations. The total mass for each floor was concentrated at the centre of mass (same as centre of rigidity for this example) and rigid diaphragms were assumed at each floor level. Sway effects (P-Delta) were included using the ETABS program option. For this analysis, compressive loads on the walls were obtained from the consistent loading case of 1.0D + 0.5L + 0.25S , with live load reduction factors. The first three lateral modes in the N-S and E-W directions are shown in Fig. 11.24, together with the associated periods of vibration and the modal participating mass ratios. Note that the sum of these ratios is 94.9% and 93.8% of the total mass in the N-S and E-W directions, respectively. These ratios exceed the minimum required ratio of 90% of the total mass (NBCC). Spectral modal superposition, using SRSS for the first three modes in the both directions was used to determine all forces and deformations. The base shear in the N-S direction determined by dynamic analysis is Ve = 14159 kN. Therefore: Vd = 14159 × 1.0 = 2528 kN 3.5 × 1.6 However for this irregular building Vd shall not be taken less than V = 2755.6 kN. Hence, all forces and deflections obtained from the dynamic analysis shall be multiplied byVd / Ve = 2755.6 / 14159 = 0.195 in the N-S direction. The base shear in the E-W direction determined by dynamic analysis is Ve = 11021 kN. Therefore: Vd = 11021 × 1.0 = 1621 kN 4.0 × 1.7 However for this irregular building Vd shall not be taken less than V = 1466.1kN. Hence, all forces and deflections obtained from the dynamic analysis shall be multiplied by Vd / Ve = 1621 / 11021 = 0.147 in the E-W direction. 11–38 Seismic Design Figure 11.23 3-D Model used for dynamic analysis CAC Concrete Design Handbook Mode 1 T = 1.830 MPMR = 0.67 11–39 Mode 2 T = 0.339 MPMR = 0.22 Mode 3 T = 0.143 MPMR = 0.07 Mode 2 T = 0.435 MPMR = 0.17 Mode 3 T = 0.199 MPMR = 0.05 (a) N-S direction Mode 1 T = 1.717 MPMR = 0.72 (b) E-W direction Figure 11.24 Mode shapes, corresponding lateral periods of vibration and modal participating mass ratios in the N-S and E-W directions 11–40 Seismic Design 11.5.3.6 Deflections and Drift Ratios The deflections obtained from the dynamic analysis are multiplied by the factor 0.195 in the N-S direction and 0.147 in the E-W direction. To account for the total anticipated displacements, including the inelastic effects it is necessary to multiply these deflections by the factor R d R o / I E to obtain the design values. Note that the factor Vd Rd Ro is equal to 1.0 unless Vd is controlled Ve I E by the value of V , as in the N-S direction in this example (see 11.5.3.5). The deflections obtained from dynamic analysis include P-Delta effects. The deflections arising from accidental torsional eccentricity are added to the deflections from the dynamic analysis. The maximum total interstorey drift in the N-S direction occurs in the eighth storey. From the dynamic analysis the interstorey drift in this storey is 0.00060 and the interstorey drift from accidental torsion at this level is 0.00041, for a maximum interstorey drift of 0.0010. Therefore the anticipated interstorey drift, including inelastic effects, is 0.0010 × 3.5 × 1.6 / 1.0 = 0.0056 . Similarly the maximum anticipated interstorey drift in the E-W direction is 0.0047. These anticipated maximum interstorey drift ratios are less than the NBCC limit of 0.025. 11.5.4 Design Forces The results from the 3-D analyses for both seismic and wind loading are summarized in Tables 11.10, 11.11, 11.12 and 11.13. It is noted that for wind loading, the case with eccentric wind loading does not govern. Table 11.10 gives the forces from seismic loading analysis in the N-S direction, without and with accidental torsion effects. Table 11.11 gives the forces from seismic loading analysis in the E-W direction, without accidental torsion effects. Table 11.12 gives the forces from accidental torsion due to seismic loading analysis in the EW direction. It is noted that accidental torsion is resisted by shear flow around the components of the C-shaped walls and by shear in the coupling beams. The accidental torsion does not create any global moments, axial loads or shears in the C-shaped walls, but results in local moments, axial loads and shears in the component parts, AB, BC and CD (see Fig. 11.27). CAC Concrete Design Handbook 11–41 Table 11.10 Results of Seismic Loading Analyses (1.0E) in N-S direction for one wall, including accidental torsion Storey 13 top 13 bot 12 top 12 bot 11 top 11 bot 10 top 10 bot 9 top 9 bot 8 top 8 bot 7 top 7 bot 6 top 6 bot 5 top 5 bot 4 top 4 bot 3 top 3 bot 2 top 2 bot 1 top 1 bot Wall moment without torsion, kN·m Wall moment with torsion, kN·m Wall shear without torsion, kN Wall shear with torsion, kN 0 0 0 1484 1484 3689 3689 6022 6022 8037 8037 9504 9504 10391 10391 10831 10831 11097 11097 11647 11647 13033 13033 15567 15567 20396 492 907 1503 2611 3297 4839 5623 7040 7922 8797 9767 9890 10931 10494 11375 11548 11212 12582 11514 14090 13107 16685 15859 20803 20210 28332 0 0 406 406 605 605 647 647 589 589 518 518 515 515 596 596 738 738 923 923 1119 1119 1283 1283 1378 1378 114 114 509 509 787 787 898 898 902 902 886 886 934 934 1062 1062 1249 1249 1478 1478 1719 1719 1943 1943 2057 2057 11–42 Seismic Design Table 11.11 Results of Seismic Loading Analyses (1.0E) in E-W direction (Coupled Wall) for one wall Storey 13 top 13 bot 12 top 12 bot 11 top 11 bot 10 top 10 bot 9 top 9 bot 8 top 8 bot 7 top 7 bot 6 top 6 bot 5 top 5 bot 4 top 4 bot 3 top 3 bot 2 top 2 bot 1 top 1 bot Wall moment, kN·m Wall axial load, kN Wall shear, kN Coupling beam shear without torsion, kN Coupling beam shear with torsion, kN 452 452 1078 309 1086 618 945 1135 1019 1515 1280 1720 1527 1815 1708 1859 1826 1860 1820 1889 1597 2205 1303 3090 1957 5577 139 139 332 332 596 596 913 913 1251 1251 1583 1583 1895 1895 2188 2188 2469 2469 2753 2753 3047 3047 3341 3341 3588 3588 0 0 252 252 390 390 441 441 438 438 430 430 440 440 466 466 508 508 581 581 678 678 764 764 810 810 69.6 113.0 96.3 149.0 132.2 192.8 159.5 228.9 173.6 251.6 179.3 265.1 184.6 276.7 194.6 290.7 210.2 307.4 228.9 323.3 242.9 329.8 237.3 310.4 191.8 244.3 CAC Concrete Design Handbook 11–43 Table 11.12 Local forces due to accidental torsion (1.0E) in E-W direction (Coupled Wall Direction) in different components of C-shaped wall Storey 13 top 13 bot 12 top 12 bot 11 top 11 bot 10 top 10 bot 9 top 9 bot 8 top 8 bot 7 top 7 bot 6 top 6 bot 5 top 5 bot 4 top 4 bot 3 top 3 bot 2 top 2 bot 1 top 1 bot Wall component AB or CD ( ± ) 3.2 m long segments Wall component BC ( ± ) 6.4 m long segment Moment, kN·m Axial load, kN Shear, kN Moment, kN·m Axial load, kN Shear, kN 90.4 -44.4 115.0 -86.8 142.0 -113.5 168.2 -140.2 191.0 -165.9 209.9 -189.6 224.2 -210.6 233.2 -228.4 235.9 -242.4 231.0 -251.8 217.2 -256.7 189.4 -243.9 221.8 -361.0 -58.0 -58.0 -94.9 -94.9 -106.4 -106.4 -105.9 -105.9 -95.3 -95.3 -75.6 -75.6 -47.1 -47.1 -9.0 -9.0 40.1 40.1 102.9 102.9 183.4 183.4 286.1 286.1 457.3 457.3 -36.9 -36.9 -55.3 -55.3 -70.0 -70.0 -84.5 -84.5 -97.8 -97.8 -109.4 -109.4 -119.1 -119.1 -126.5 -126.5 -131.0 -131.0 -132.3 -132.3 -129.8 -129.8 -118.7 -118.7 -120.2 -120.2 -81.1 131.3 232.9 30.2 330.6 -26.6 398.0 -93.7 442.9 -169.1 468.1 -252.1 475.1 -343.8 464.1 -446.1 433.9 -562.7 382.1 -699.3 304.9 -861.8 190.8 -1089.6 248.5 -1493.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 58.2 58.2 -55.6 -55.6 -97.9 -97.9 -134.7 -134.7 -167.7 -167.7 -197.3 -197.3 -224.4 -224.4 -249.4 -249.4 -273.0 -273.0 -296.3 -296.3 -319.7 -319.7 -350.8 -350.8 -359.1 -359.1 11–44 Seismic Design Table 11.13 Results of Wind Loading Analyses (1.4W) Storey 13 top 13 bot 12 top 12 bot 11 top 11 bot 10 top 10 bot 9 top 9 bot 8 top 8 bot 7 top 7 bot 6 top 6 bot 5 top 5 bot 4 top 4 bot 3 top 3 bot 2 top 2 bot 1 top 1 bot N-S Direction E-W Direction (Coupled Wall Direction) Wall moment, kN·m Wall moment, kN·m Wall axial load, kN Coupling beam shear, kN 0 0 -74 122 47 577 503 1287 1212 2263 2190 3498 3427 4990 4923 6734 6672 8726 8670 10962 10915 13433 13396 16161 16136 20087 159 159 444 178 633 72 735 -84 800 -281 827 -508 819 -767 770 -1060 665 -1402 473 -1823 130 -2385 -496 -3233 -1669 -5599 49 49 119 119 241 241 426 426 679 679 1001 1001 1391 1391 1845 1845 2358 2358 2918 2918 3504 3504 4073 4073 4546 4546 24.5 38.9 64.4 95.7 128.8 162.5 195.5 227.0 255.5 278.3 290.5 281.5 233.3 The design forces for both seismic and wind loading are given in Fig. 11.25. The distribution of wall moments for wind loading is typical for a coupled wall system. The distribution of wall moments for seismic loading was obtained from modal combinations (SRSS) and therefore the moments obtained are absolute values. CAC Concrete Design Handbook 11–45 Fig. 11.25 Results of analyses for seismic and wind loading 11.5.5 Design of Coupling Beams 11.5.5.1 Design Forces for Coupling Beams The maximum coupling beam shear due to factored wind loading is 290.5 kN and due to earthquake effects (including accidental torsion) is 329.8 kN. Hence the seismic loading case governs the design of the coupling beams. These maximum shears occur in the coupling beams in the third storey (see Tables 11.11 and 11.13). In designing the coupling beams we can account for redistribution of moments between the beams and hence the factored shear resistance required for earthquake loading would be the sum of the shears in the coupling beams divided by the number of coupling beams. This would require a factored shear resistance of 3283 / 13 = 252.5 kN for seismic loading. The coupling beams have a depth of 900 mm and a clear span of 2000 mm and hence satisfy the dimensional limitation that the depth must not be greater than twice the clear span (Clause 21.6.8.5). The ductile coupling beams must be designed with diagonal reinforcement, rather than longitudinal bars and vertical hoops, because the clear span of each beam is not equal to or greater than four times the effective depth (see Clauses 21.6.8.6 and 21.3.1.1). Since the design torsions arise only from accidental torsional eccentricity, which can act in either direction, the same coupling design forces and beam details will be used on the north and south sides of the core wall. 11–46 Seismic Design 11.5.5.2 Design and detailing of coupling beams Fig. 11.26 shows the details of the diagonal reinforcement in a coupling beam. From the geometry of the reinforcement, the angle α between the centroidal axis of one set of diagonal bars and the horizontal is 19.4û. Fig. 11.26 Coupling beam reinforcing details If 4-20M bars are provided in each set of diagonal bars then the factored shear resistance is: Vr = 2φs As fy sin α = 2 × 0.85 × 4 × 300 × 400 × sin 19.4 = 271.0 kN If this reinforcement is placed in the lower storeys, then a moment redistribution of 17.8% would be required in the coupling beam with maximum moment due to seismic loading and 6.7% redistribution would be required for wind loading. Clause 9.2.4 permits a moment redistribution up to 20%. The diagonal reinforcement must have closely spaced hoops as required in Clause 21.6.8.7 with a maximum spacing given by the smaller of: (a) 6d bl = 6 × 20 = 120 mm (b) 24d bh = 24 × 10 = 240 mm (c) 100 mm CAC Concrete Design Handbook 11–47 Hence use 10M hoops spaced at 100 mm. The diagonal reinforcement must extend into the wall at each end a minimum distance of 1.5l d = 1.5 × 526 = 789 mm. Hence use an embedment length of 800 mm. In addition to the diagonal reinforcement, provide minimum transverse and longitudinal reinforcement, as shown in Fig. 11.26, but only in the clear span of the beam. Although a designer might choose to use the same coupling beams details, with 4-20M diagonal bars, over the full height of this building, reducing the amount of reinforcement in the coupling beams near the top of the structure is advantageous whenever possible. This approach is illustrated below. If the reinforcement in the coupling beams is reduced to 4-15M near the top of the structure, then the factored resistance per beam is: Vr = 2φs As fy sin α = 2 × 0.85 × 4 × 200 × 400 × sin 19.4 = 180.7 kN. The beams with 4-15M bars would require a hoop spacing of 90 mm. Provide coupling beams with 4-20M bars for storeys 1 to 11 and beams with 4-15M bars for the top two coupling beams. This arrangement gives a total shear capacity of the 13 beams of: ∑V r = 11× 271.0 + 2 × 180.7 = 3342 kN This shear resistance of the thirteen coupling beams exceeds the required shear resistance of 3283 kN. Hence provide diagonally reinforced coupling beams with 4-20M for the first 11 storeys and beams with 4-15M diagonal bars for the top two coupling beams. 11.5.5.3 Ductility of coupling beams The inelastic rotational capacity of the coupling beams must be greater than the rotational demand. The rotational demand is given by (Clause 21.6.8.4): ∆ f Rd Ro hw θ id = l cg 0.019 × 4.0 × 1.7 6.5 = 0.0093 = 45.0 2.0 lu The rotational capacity of diagonally reinforced coupling beams (Clause 21.6.8.4) is 0.04. Hence the coupling beams have sufficient ductility. 11.5.6 Design of Ductile Walls 11.5.6.1 Design Forces in E-W Direction The design forces in the walls are determined from a capacity design approach. It is desired that the walls be strong enough such that flexural hinging occurs in the coupling beams, which are the primary energy dissipators of the structural system. In order to determine the design forces in the walls we will consider a “push-over” type of loading on the coupled wall system. For this analysis it is required that the factored resistance of the walls be at least equal to the moment corresponding to the development of flexural hinging in the beams. The “push-over” approach used for this twelve-storey coupled wall structure provides a conservative design approach to the requirements of Clause 21.6.8.12. For taller coupled wall structures the provisions of Clause 21.6.8.12 should be used. The nominal shear resistance, Vn , for the coupling beam containing 4-20M diagonal reinforcing bars is: Vn = 2φs As f y × sin α = 2 × 1.0 × 1200 × 400 × sin 19.4 = 318.9 kN Similarly the nominal resistance for the beams containing the 4-15M bars is 212.6 kN. 11–48 Seismic Design In order to satisfy the capacity design requirement, the factored wall moments will be increased at each level x by the factor γ bx , determined as: γ bx = ∑V ∑V n f where: ∑V n = sum of the shears corresponding to the nominal flexural resistance of coupling f beams above level x = sum of factored shears above level x ∑V The beam overstrength factors, cumulative dead and live loads and the factored axial loads and factored moments in each wall multiplied by γ bx are shown on Table 11.14. The values of ∑V f are taken as the wall axial loads given in Table 11.14, since the axial load wall is the sum of the shears in the coupling beams. Table 11.14 Coupling Beam Overstrength Factors and Dead and Live Loads per Wall Storey 13 top 13 bot 12 top 12 bot 11 top 11 bot 10 top 10 bot 9 top 9 bot 8 top 8 bot 7 top 7 bot 6 top 6 bot 5 top 5 bot 4 top 4 bot 3 top 3 bot 2 top 2 bot 1 top 1 bot γ bx Vn , kN 212.6 Vf , kN 113.0 1.88 212.6 149.0 1.62 318.9 192.8 1.64 318.9 228.9 1.55 318.9 251.6 1.48 318.9 265.1 1.42 318.9 276.7 1.37 318.9 290.7 1.32 318.9 307.4 1.28 318.9 323.3 1.24 318.9 329.8 1.21 318.9 310.4 1.19 318.9 244.3 1.20 PD , kN -945 -945 -1701 -1701 -2457 -2457 -3213 -3213 -3969 -3969 -4725 -4725 -5481 -5481 -6237 -6237 -6993 -6993 7749 7749 8506 8506 9262 9262 9797 9797 PL , kN 0 0 -196 -196 -394 -394 -513 -513 -621 -621 -725 -725 -825 -825 -924 -924 -1020 -1020 1115 1115 1208 1208 1301 1301 1393 1393 Pn , kN ± 425 ± 425 ± 850 ± 850 ± 1488 ± 1488 ± 2126 ± 2126 ± 2764 ± 2764 ± 3402 ± 3402 ± 4039 ± 4039 ± 4677 ± 4677 ± 5315 ± 5315 ± 5953 ± 5953 ± 6591 ± 6591 ± 7228 ± 7228 ± 7866 ± 7866 γ bx M1 , kN·m 851 851 1750 501 1777 1012 1469 1765 1506 2239 1814 2438 2088 2483 2259 2459 2338 2382 2259 2344 1929 2664 1550 3676 2345 6682 CAC Concrete Design Handbook 11–49 The required moment capacity at the base of each wall, given in Table 11.14, is 6682 kN·m for seismic loading without accidental torsion. It is noted that the required moment at the base of each wall due to wind (see Table 11.13) is 5599 kN·m. Hence the seismic capacity design requirements control the design. From Table 11.14, the minimum axial force at the base of the "tension wall" corresponding to development of flexural hinges in the coupling beams is: Ps + Pn = −9797 + 7866 = −1931 kN, that is a compressive load. The maximum axial force at the base of the "compression wall" corresponding to development of flexural hinges in the coupling beams is: Ps + Pn = −9797 − 0.5 × 1393 − 7866 = −18360 kN. To account for the local forces (see Table 11.12) from accidental torsion a simplified approach will be taken. Although the axial loads and moments on parts AB and CD have opposite signs it will be assumed that the C-shaped wall is subjected to an additional axial load of twice the axial tension or compression acting on segments AB or CD and an additional moment of twice the moment acting in these segments. For example, at the base of the structure the additional axial load for design is 2 × ±457 = ±914 kN and the additional moment is 2 × ±361 = ±722 kN·m. 11.5.6.2 Design Forces in N-S Direction From Tables 11.10 and 11.13, the base moment in each wall due to lateral seismic loading is 28332 kN·m (including accidental torsion) and the base moment due to factored wind loading is 20087 kN·m, respectively. Hence, for flexural design in the N-S direction, the earthquake loading controls. The corresponding axial load for the two walls is 2(PD + 0.5PL ) = 2(− 9797 − 0.5 × 1393 ) = 2 × −10494 = −20988 kN. 11.5.6.3 Design of base of wall for flexure and axial load Preliminary choice of vertical reinforcement (a) Minimum area of concentrated reinforcement (Clause 21.6.6.4) In the 3.2 m long walls in the E-W direction: As = 0.0015 bw l w = 0.0015 × 400 × 3200 = 1920 mm 2 2 Therefore try 4–25M bars ( As = 2000 mm ) as concentrated reinforcement at one end of the 3.2 m long wall (segments AB and CD). In the 6.4 m long wall (segment BC) in the N-S direction As = 0.0015 bw l w = 0.0015 × 400 × 6400 = 3840 mm 2 For the case of flanged walls, concentrated reinforcement at the ends of the effective flanges may supply up to one half of the required minimum wall web concentrated reinforcement (Clause 21.6.6.5). Hence the required concentrated reinforcement at the web-flange intersection is 2 0.5 × 3840 = 1920 mm . Hence try 4-25M at the intersection of the two walls. Outside the plastic hinge regions, only two-thirds of this area of the concentrated reinforcement is required. Provide a clear cover for the hoops of 40 mm, resulting in a clear cover of 50 mm for the main vertical reinforcement in the wall, as required for a two-hour fire-resistance rating. In regions of plastic hinging, the uniformly distributed horizontal reinforcement must be anchored within the region of concentrated reinforcement to develop 1.25f y (Clause 21.6.5.5). 11–50 Seismic Design The development length required for the 10M bars, using the simplified equation in Clause 12.2.3 is: 1.25fy 500 l d = 0.45k1k 2 k 3 k 4 d b = 0.45 × 1× 1× 1× 0.8 × 10 = 329 mm fc′ 30 The length provided in the region of concentrated reinforcement (see Fig. 11.27) is 320 mm. With the significant cover provided on the bars and the additional confinement provided in this region of concentrated reinforcement, the development length can be shown to be less than 320 mm using Eq. 12-1 in Clause 12.2.2. Hence, the hoop configuration shown in Fig. 11.27 is adequate. (b) Maximum area of concentrated reinforcement (Clause 21.6.4.3) Clause 21.6.4.3 limits the reinforcement ratio, including regions with lap splices, to 0.06. With the layout of the 4-25M bars at the ends of the flanges and at the web-flange junctions, as shown in Fig. 11.27, the percentage of steel equals (4 × 500 ) / (400 × 400 ) = 0.0125 . This arrangement allows for lap splicing of the reinforcement without exceeding the limit of 0.06. Fig. 11.27 Details of reinforcement in walls. At the base of the walls the spacing of the horizontal distributed reinforcement must be decreased to 120 mm in component BC and to 150 mm in components AB and CD (see Section 11.5.6.7). (c) Maximum bar diameters (Clause 21.6.4.4) In the 400 mm thick walls, the maximum diameter of reinforcement is 400 / 10 = 40 mm. CAC Concrete Design Handbook 11–51 (d) Distributed reinforcement (Clauses 21.6.5) In the plastic hinge region, the spacing of the distributed reinforcement must not exceed 300 mm in each direction. Outside of this region, the maximum spacing is 450 mm. The distributed reinforcement ratio must be greater than 0.0025 in each direction. In the 400 mm thick wall elements, the maximum spacing, assuming two curtains of 10M reinforcing bars is (2 × 100 ) / (0.0025 × 400 ) = 200 mm. Hence, at the base of the walls, use 2 curtains of 10M bars at 200 mm spacing in the horizontal and vertical directions. In the regions of plastic hinging, two curtains of reinforcement must be provided in the N-S direction if the design shear in one wall exceeds (Clause 21.6.5.3): 0.18λφc fc′ Acv = 0.18 × 0.65 × 30 × 400 × 6400 = 1641 kN. Two curtains of reinforcement must be provided in the E-W direction if the design shear in one wall exceeds: 0.18λφc fc′ Acv = 0.18 × 0.65 × 30 × 800 × 3200 = 1641 kN. Calculation of M r at base of walls The factored moment resistances for different loading cases were determined using the stress block factors of Clause 10.1.7, strain compatibility and a maximum concrete compressive strain of 0.0035. Table 11.15 summarizes the results. Table 11.15 Predicted Factored Moment Resistances and Depths of Compression per Wall at the base (Global wall forces) Load Case E-W (1 “C-shaped” wall) “tension” 1.0D + 1.0E wall “compression” wall Nf kN Mf kN·m Nr kN Mr kN·m c mm -1931 6682 -1931 15058 493 1.0D + 1.0E -17663 6682 -17663 21773 226 1.0D + 0.5L + 1.0E -18360 6682 -18360 22280 233 1.0D + 1.0E -9797 28332 -9797 49058 290 1.0D + 0.5L + 1.0E -10494 28332 -10494 51097 303 N-S (per wall) The required moment capacity in the E-W direction from analysis is 6682 kN·m per wall. As can be seen from Table 11.15, the “tension” wall has a factored moment resistance of 15058 kN·m, while the compression wall has a factored moment resistance of 22280 kN·m. Hence the factored flexural resistance exceeds the required factored moment. Figure 11.28 illustrates the moment resistances for the walls in the E-W direction. It is noted that the total forces in the E-W tension wall, including global (Table 11.15) and local (Table 11.12) forces at its base is: N f = −1931 + 914 = −1017 kN and M f = 6682 + 722 = 7405 kN·m. For this level of axial load the factored moment resistance is 13385 kN·m. Hence the wall strength is adequate for both global and local forces. It can be shown, in a similar way, that the factored resistance of the compression wall is adequate for global and local forces. Clause 21.6.8.8 requires that the walls at each end of a coupling beam be designed so that the factored moment resistance of the wall about its centroid, calculated using axial loads Ps + Pn , 11–52 Seismic Design exceeds the moment corresponding to the nominal resistance of the coupling beam. This requirement will be satisfied at all the different levels of the structure because the “push-over” analysis summarized in Table 11.14 already considers the attainment of the nominal resistances of the coupling beams over the entire height of the structure. Hence all of the design moments and axial forces correspond to these conditions. In the N-S direction, the factored moment resistance for both load cases significantly exceeds the required moment (see Table 11.15 and Fig. 11.29). Fig. 11.28 Factored moment resistances of ductile coupled walls (E-W direction) Fig. 11.29 Factored moment resistance of ductile shear walls (N-S direction) CAC Concrete Design Handbook 11–53 11.5.6.4 Ductility of walls E-W Direction - Ductile Coupled Walls (Clause 21.6.8) For ductile coupled walls, the inelastic rotational demand θ id is taken as: θ id = ∆ f Ro Rd 0.019 × 1.7 × 4.0 = = 0.0029 ≥ 0.004 hw 45.0 The inelastic rotational capacity θ ic , taking l w as the length of the coupled wall system (Clause 21.6.8.3) and assuming ε cu = 0.0035 is: ε l 0.0035 × 8.4 − 0.002 = 0.0278 ≤ 0.025 θ ic = cu w − 0.002 = c 2 × 2 0 . 493 Because the rotational capacity of 0.025 exceeds the rotational demand of 0.004, sufficient ductility is provided. N-S Direction - Ductile Shear Walls (Clause 21.6.7) For ductile shear walls, the ratio of the nominal flexural resistance to the factored flexural resistance, M f , at the base is 1.95 and hence the inelastic rotational demand θ id is taken as: θ id = (∆ f Ro Rd − ∆ f γ w ) (0.028 × 1.6 × 3.5 − 0.028 × 1.95 ) = = 0.0024 ≥ 0.004 l 6.4 hw − w 45.0 − 2 2 The inelastic rotational capacity θ ic , assuming ε cu = 0.0035 is: ε cu l w 0.0035 × 6.4 − 0.002 = − 0.002 = 0.0350 ≤ 0.025 2c 2 × 0.303 θ ic = Because the rotational capacity of 0.025 exceeds the rotational demand of 0.004, sufficient ductility is provided. Confinement of concentrated reinforcement (Clause 21.6.7.3) Because the inelastic rotational capacities of the walls in the E-W and N-S directions were determined using ε cu = 0.0035 , it is not necessary to check the confinement requirements of Clause 21.6.7.4 for the concentrated reinforcement in the walls. 11.5.6.5 Checking wall thickness for stability (Clause 21.6.3) Clause 21.6.3 requires a wall thickness of l u / 10 in those parts of a wall that, under factored vertical and lateral loads, are more than half way from the neutral axis to the compression face of the wall section. The 3200 mm long portions of the E-W "tension wall" may be considered as simple rectangular wall elements as shown in Fig. 11.28 with a neutral axis depth of 493 mm. Since the neutral axis depth is less than 4bw = 4 × 400 = 1600 mm and is less than 0.3l w = 0.3 × 3200 = 960 mm, the l u / 10 limit need not apply (see Clause 21.6.3.4). According to Clause 21.6.3.2 the wall thickness in the plastic hinge region must not be less than l u / 14 = 4650 / 14 = 332 mm. Hence the wall thickness of 400 mm is adequate. 11–54 Seismic Design For the 6400 mm long portion of the E-W "compression wall", it is noted that c / 2 = 233 / 2 = 117 mm, which is less than the wall thickness, and furthermore, the wall is laterally supported at its ends by the 3200 mm wall portions. Hence, this portion of the wall need not have a thickness of l u / 10 (see Clause 21.6.3.5). For stability considerations for the wall loaded in the N-S direction, the value of c / 2 = 303 / 2 = 152 mm is smaller than the 400 mm thickness of the flanges. Therefore the 400 mm wall dimension is adequate and the width of the flange of 3200 mm, greatly exceeds l u / 5 (see Clause 21.6.3.5). Therefore all of the stability requirements are satisfied. 11.5.6.6 “Buckling prevention” ties for concentrated reinforcement (Clause 21.6.6.9) The concentrated reinforcement should have buckling prevention ties in accordance with Clause 7.6 and the ties must be detailed as hoops (Clause 21.6.6.9). In plastic hinge regions, the hoop spacing shall not exceed: (i) 6d bl = 6 × 25 = 150 mm (ii) 24d bh = 24 × 10 = 240 mm (iii) one-half the wall thickness = 400 / 2 = 200 mm. Hence provide 10M hoops at a spacing of 150 mm as shown in Fig. 11.27. 11.5.6.7 Design for shear at base of walls (Clause 21.6.9) The walls must be designed to resist the shear corresponding to the formation of plastic hinges at their bases (Clause 21.6.9.1). Determine probable moment resistances of walls In order to determine the probable moment resistances of the walls, axial load-moment calculations were carried out with φc = φs = 1.0 and using an equivalent "yield" strength of steel of 1.25fy . In the E-W direction, we only need to determine the probable moment resistance of the "compression wall" subjected to an axial load corresponding to 1.0E + 1.0D + 0.5L , since it results in the larger resistance. From calculations, the probable moment resistance of the wall, M pw , is 26235 kN·m in the E-W direction and 60679 kN·m per wall in the N-S direction. It is assumed that earthquake loading causes plastic hinging at the base of the walls. Assuming that the ratio of the shear to moment at the base of a wall remains constant as the moment increases to the probable resistance, the shear at the base as the wall develops a plastic hinge will be: M pw V = × Vf Mf N-S direction: V = M pw Mf × Vf = 60679 × 2057 = 4406 kN 28332 In calculating the shear capacity of the wall, the effective shear depth d v is taken as 0.9d = 0.9 × 6200 = 5580 mm, but need not be taken less than 0.8l w = 0.8 × 6400 = 5120 mm (Clause 21.6.9.3). CAC Concrete Design Handbook 11–55 In the region of expected plastic hinging, at the base of the wall, the inelastic rotational demand θ id is less than 0.005 and hence the factored shear demand cannot exceed: 0.15φc fc′bw d v = 0.15 × 0.65 × 30 × 400 × 5120 = 5990 kN The factored shear demand of 4406 kN is less than this upper limit. Because the inelastic rotational demand θ id is less than 0.005, the factored shear resistance is calculated using β = 0.18 . The axial load on the “tension” wall is -10494 kN (compression). This axial load is less than: 0.1fc′ Ag = 0.1× 30 × (3200 × 800 + 5600 × 400 ) = 14400 kN. Hence θ is taken as 45° (Clause 21.6.9.6). The factored shear resistance (Clauses 11.3.4 and 11.3.5), assuming pairs of 10M bars at 120 mm spacing is: Vr = φ c β f c′ bw d v + φ s Av f y d v cot θ s = 0.65 × 0.18 30 × 400 × 5580 + 0.85 × 200 × 400 × 5580 cot 45 o 120 = 1430 + 3162 = 4592 kN Hence the shear resistance is adequate with pairs of 10M horizontal bars spaced at 120 mm. It is noted that the accidental torsion causes shear in segments AB and CD. This shear, due to accidental torsion, must be considered in design, accounting for the fact that the critical flange will be in tension and have large flexural cracks due to the attainment of plastic hinging for loading in the N-S direction. A method to check the shear resistance of these segments, accounting for large cracks and possible redistribution of shear resisting torsion, is described in the calculations below for loading in the E-W direction. E-W direction: In the E-W direction it is necessary to first determine the shear from seismic loading and include accidental torsion effects. The shear at the base without accidental torsion is 810 / 2 = 405 kN in segment AB. The analysis including accidental torsion indicates a shear force of 120 kN on wall segments AB and CD (see Table 11.12). In accordance with Clause 21.6.8.13 it may be necessary to redistribute the shear force of 359 kN in the segment BC because under plastic hinging this wall segment will experience large tensile strains and cracks. If the torsion arising from this 359 kN force is redistributed to wall segments AB and CD, then an additional shear force will be necessary. This additional shear force is: ∆VAB = VBC × 8.0 8.0 = 359 × = 479 kN in two segments 6.0 6.0 Hence the total shear in segment AB is 405 + 120 + 479 / 2 = 765 kN. In lieu of redistributing the torsional shear from wall segment BC, a more detailed analysis will be conducted (Clause 21.6.8.13). Wall component BC is lightly loaded in shear but must resist the shear with large cracks in this tension wall. In order to determine the shear resistance under these conditions the “dowel action” resistance will be determined, considering the resistance of the reinforcement only. From Paulay and Priestley (1992) the dowel resistance can be taken as: Vr = 0.25φ s Av f y = 0.25 × 0.85 × 27 × 200 × 400 = 459 kN. Because this resistance exceeds the shear force of 359 kN, redistribution of the shear from the tension wall BC to wall AB is not necessary. Hence the total shear in segment AB is 405 + 120 = 525 kN. 11–56 Seismic Design The design shear for segment AB, including torsional effects is: V = M pw Mf × Vf = 26235 × 525 = 1860 kN 6682 + 722 For segment CD, the shear from accidental torsion acts in the opposite direction from that in segment AB. Hence the total shear for segment CD is 405 − 120 = 285 kN. This results in a design shear for this segment of: V = M pw Mf × Vf = 26235 × 285 = 1010 kN. 6682 + 722 Segments AB and CD must both be designed for the larger shear of 1860 kN because the accidental torsion can reverse. In calculating the shear capacity of the wall, in accordance with Clause 21.6.9.3, we will assume an effective shear depth, dv = 0.8l w = 0.8 × 3200 = 2560 mm. In the region of expected plastic hinging, at the base of the wall, the inelastic rotational demand θ id is less than 0.005 and hence the factored shear demand in one segment cannot exceed: 0.15φc fc′bw dv = 0.15 × 0.65 × 30 × 400 × 2560 = 2995 kN The factored shear demand of 1860 kN is less than this upper limit. Because the inelastic rotational demand θ id is less than 0.005, the factored shear resistance is calculated using β = 0.18 . The axial load on the tension wall is -1017 kN. This axial load is less than: 0.1fc′ Ag = 0.1× 30 × (3200 × 800 + 5600 × 400 ) = 14400 kN. Hence θ is taken as 45° (Clause 21.6.9.6). The factored shear resistance (Clauses 11.3.4 and 11.3.5) for wall segment AB at the base with pairs of 10M bars at a spacing of 150 mm is: Vr = φ c β f c′ bw d v + φ s Av f y d v cot θ s = 0.65 × 0.18 30 × 400 × 2560 + 0.85 × 200 × 400 × 2560cot 45 o 150 = 656 + 1161 = 1817 kN Segment AB is overstressed by only 2%, while segment BC is very lightly loaded and hence a portion can be redistributed to this segment. Hence the shear strength in the E-W direction is adequate with 2-10M bars at 150 mm spacing. Extend the 10M horizontal reinforcement into the confined core of the region of concentrated reinforcement as close to the outside surface of the walls as cover will permit (see Fig 11.27 and Section 11.5.6.3). 11.5.6.8 Checking sliding shear resistance at construction joints (Clause 21.6.9.4) In accordance with Clause 21.6.9.4, we must check the sliding shear resistance of the construction joints. Since the vertical uniformly distributed reinforcement is constant over the height of the walls, the most critical situation is at the base of the walls. CAC Concrete Design Handbook 11–57 N-S direction: In the N-S direction, the required shear strength is 4406 kN per wall. If the construction joint is intentionally roughened, the factored shear stress resistance from Clauses 11.5.1 and 11.5.2 is: N v r = φc c + µ ρv fy + Ag 9797 × 1000 = 0.65 0.50 + 1.0 0.0025 × 400 + 800 × 3200 + 400 × 5600 = 2.302 MPa Hence, the sliding shear resistance is: 2.302 × Acv = 2.302 × 400 × 6400 = 5893 kN Since the sliding shear resistance exceeds the shear corresponding to plastic hinging, sliding shear will be prevented. E-W direction: In the E-W direction, the required shear strength of segment AB is 1860 kN. It will be assumed that the net compressive axial load is acting on the segments AB and CD (the segment BC is in tension). If the construction joint is intentionally roughened, the factored shear stress resistance from Clause 11.5 is: N v r = φc c + µ ρv f y + Ag 1931 × 1000 = 0.65 0.50 + 1.0 0.0025 × 400 + 800 × 3200 = 1.465 MPa Hence, the sliding shear resistance of segment AB is: 1.465 × Acv = 1.465 × 400 × 3200 = 1875 kN. The sliding shear resistance is adequate. 11.5.6.9 Determination of plastic hinge region (Clause 21.6.2) As the wall cross sectional dimensions remain constant over the 48.65 m height of the wall and provided that the main flexural reinforcement is appropriately curtailed, only one plastic hinge region will form, near the base of the walls. The height over which plastic hinging could take place from the base of the wall is governed by the longer, N-S, wall (Clause 21.6.2.2) and is taken as 1.5 × 6.4 = 9.6 m. Therefore detail the first three storeys as plastic hinge regions. 11.5.6.10 Changes in horizontal distributed reinforcement over the height of the walls (Clause 21.6.5) The maximum spacing of the 2–10M horizontal bars, outside of the plastic hinge region is 200 mm, since the minimum reinforcement ratio of 0.0025 must be satisfied. Therefore use 2 10M bars at 200 mm spacing above the plastic hinge region. 11–58 Seismic Design 11.5.6.11 Changes in Vertical distributed reinforcement over the height of the walls (Clause 21.6.5) Once again, the minimum reinforcement ratio of 0.0025 governs the selection of vertical distributed reinforcement. Hence use 2-10M bars at 200 mm spacing over the entire height of the wall. 11.5.6.12 Changes in concentrated vertical reinforcement over the height of the walls (Clause 21.6.6) The minimum area of concentrated reinforcement which can be used outside the plastic hinge region is 0.001bw l w (Clause 21.6.6.3). At one end of the 3200 mm long wall, the minimum 2 amount of concentrated reinforcement is 0.001× 400 × 3200 = 1280 mm . Similarly, the minimum amount of concentrated reinforcement required at the intersection of the wall components is 2 2560 − 1280 = 1280 mm (Clause 21.6.6.5). Note that in deciding on the changes to the concentrated reinforcement over the height of the structure, it is necessary to ensure that the factored moment resistance at each floor level is sufficient to develop the plastic hinging at the base of the structure. This check should be made with due consideration for the effect of lap splices in the reinforcement. An example of the calculations necessary to ensure adequate flexural strength is given in Reference 1. 11.5.7 Frame Members Not Considered Part of the SFRS Clause 21.12 provides design requirements for members that are not considered part of the seismic force resisting system. The shear walls and coupled wall system were designed to take 100% of the seismic loading effects. The slabs and the columns must be checked to determine if the levels of ductility and strength of these important vertical load carrying members are sufficient. 11.5.7.1 Slab-column connections (Clause 21.12.3) The reduction factor, RE , on two-way slab shear stress is a function of the interstorey drift. th The maximum drifts at the extremities of the structure including torsional effects is 0.00565 (8 th storey) in the N-S direction and 0.0047 (8 storey) in the E-W direction. Hence the reduction factor is: 0.005 RE = δi 0.85 0.005 = 0.00565 0.85 = 0.901 Interior slab-column connection: For an interior slab-column connection, the gravity load two-way shear stress (excluding shear from unbalanced loading and determined using the seismic load combinations (1.0D + 0.5L ) can be determined for a first interior columns location as follows: ( ) Vf = [1.0(4.8 + 1.5 ) + 0.5(2.4 )]× 5.75 × 6.0 − 0.712 = 255 kN A clear cover of 25 mm and 15M top bars are assumed for the slab. The corresponding shear stress is: vf = Vf 255 × 1000 = = 0.561 MPa bo d 4 × (550 + 160 ) × 160 CAC Concrete Design Handbook 11–59 The limiting shear stress obtained by multiplying RE by the two-way shear stress for this square column from Clause 13.3.4.1 is: v c = 0.38φc fc′ RE = 0.38 × 0.65 30 × 0.901 = 1.219 MPa Hence, no shear reinforcement is required. Corner slab-column connection: Applying the same principles to a corner slab-column connection gives a factored shear of: ( ) Vf = [1.0(4.8 + 1.5 ) + 0.5(2.4 )] × 3.125 2 − 0.73 2 = 69.2 kN vf = Vf 69.2 × 1000 = = 0.296 MPa bo d 2 × (100 + 550 + 160 / 2) × 160 The limiting shear stress obtained by multiplying RE by the one-way shear stress for this corner column from Clause 13.3.6 and 11.3.6.2 is: v c = 0.21φc fc′ RE = 0.21× 0.65 30 × 0.901 = 0.674 MPa Hence, no shear reinforcement is required. 11.5.7.2 Check on design and detailing of columns (Clause 21.12) Clauses 21.12.1 to 21.12.2 provide detailed requirements for the columns which are not considered part of the seismic force resisting system. Minimum design and detailing requirements must be applied or the columns must be analyzed to determine if the factored moments in the columns exceed their nominal resistances when the structure is deformed laterally to the design displacements. 11.5.8 Comparisons with the Design Using the 1994 CSA Standard The structure designed in this chapter is the same structure designed in Reference 2, except that the structure designed in this chapter was for a foundation on soil of site Class D (stiff soil), whereas the structure in Reference 2 was for the same structure founded on rock. In addition, 900 mm deep diagonally reinforced coupling beams were used, instead of 600 mm deep coupling beams with conventional reinforcement. It is noted that, for this structure, the design force levels using the 2005 NBCC are somewhat lower than those using the 1995 NBCC. 11.5.9 References 1. Mitchell, D. and Collins, M.P., "Chapter 11 - Seismic Design", Concrete Design Handbook, Canadian Portland Cement Association, Ottawa, 1985, pp. 11-1 – 11-31. 2. Mitchell, D., Paultre, P. and Collins, M.P., "Chapter 11 - Seismic Design", Concrete Design Handbook, Cement Association of Canada, Ottawa, 1995, pp. 11-1 – 11-33. 3. Paulay, T., Priestley, M.J.N., “Seismic Design of Reinforced Concrete and Masonry Buildings”, John Wiley and Sons, NY, 1992, 744p. 11–60 Seismic Design