AR No. __ - Install Occupancy Sensors Estimated Electric Energy Savings = 108,928 kWh/yr; 371.8 MMBtu/yr Estimated Electric Energy Cost Savings = $2,590/yr Estimated Electric Demand Savings = 161.1 kW/yr Estimated Electric Demand Cost Savings = $1,220/yr Estimated Total Cost Savings = $3,810/yr Estimated Implementation Cost = $27,530 Simple Payback = 7.2 years Recommended Action Circulating pumps should be installed to provide agitation for the galvanizing pre-treatment line. By eliminating the current practice of compressing air and then expanding it back to a lower pressure, circulating the tank fluid can provide equivalent agitation with reduced electrical consumption. Background Chemical treatment tanks often require agitation to prevent settling and thermal stratification. Traditionally, fluid motion has been induced by mechanical stirrers or bubbling air through the solution. An alternative method is to circulate the solution with a pump. The pumped fluid is forced through a specially designed nozzle at high velocity, inducing additional flow through the nozzle exhaust. Thus, pumping one gallon creates five gallons of fluid flow, effectively increasing the agitation. Using the tank fluid for agitation provides several benefits over the other methods of agitation. 1. Pumping requires less energy than either mechanical or pneumatic agitation. 2. A smoother fluid surface is maintained, thus reducing surface heat losses and evaporation. 3. Misting and fumes caused by air agitation are eliminated. 4. Contamination of the solution from oil and particulates in the compressed air is eliminated. A 150 hp compressor supplies air to the galvanizing building. A significant amount of the air supplied by the compressor is used to agitate the caustic clean, caustic rinse and pickling tanks. The compressor operating pressure during the site visit was 125 psig (138.8 psia), but the pressure at the pre-galvanizing line is estimated to be 110 psig. Anticipated Savings Energy savings, ES, and energy cost savings, ECS, due to the use of pumped fluid agitation rather than compressed air are estimated as follows: ES PC PP H C 1 ECS ES avoided cost of electricity where PC = power consumed by compressor to agitate tank, hp PP = H = C1 = power consumed by the pump to agitate tank, hp operating hours, h/yr conversion factor, 0.746 kW/hp The power required to compress the volume of free air Vf needed for agitation from atmospheric pressure to the compressor discharge pressure can be calculated as follows1: k 1 k Po N k Pi C 2 V f 1 N C 3 P k 1 i PC E ac E mc where Pi C2 Vf k N C3 Po Eac Emc = = = = = = = = = inlet (atmospheric) pressure, psia conversion constant, 144 in2/ft2 volumetric flow of free air, cfm specific heat ratio of air, 1.4 (no units) number of stages, no units conversion constant, 3.03 x 10-5 hpmin/ftlb pressure at compressor outlet, psia air compressor isentropic (adiabatic) efficiency, 0.82 no units compressor motor efficiency, no units The compressor's rated capacity is approximately 665 cfm. During the site visit, two 3/4" and four 1/2" diameter hoses were used for the agitation of the three tanks. Internal diameters are estimated to be 3/8" and 1/4". Calculations based on a line pressure of 110 psig and the hose diameters estimated a total air flow of 625 cfm. It seems unlikely that tank agitation uses 94% of the compressor capacity. This analysis assumes tank agitation consumes 300 cfm or approximately 45% of the compressor capacity. The compressor motor efficiency is 92.8%. Thus, the power that is currently consumed by the compressor to provide air for tank agitation is estimated as follows: PC 13.8 144 300 1.4 1 3.03 10 5 0.4 0.82 0.928 0.4 1.4 138.8 1 13.8 78 hp Plant personnel can determine the actual air usage by measuring the compressor cycle time when no other pneumatic equipment is operating. During the site visit, measurement of the compressor motor speed indicated a motor power draw of about 102 hp. Thus, this analysis assumes tank agitation accounts for about 76% of the compressor power draw. 1 Chapters 10 and 11, Compressed Air and Gas Handbook, Fifth Edition, Compressed Air and Gas Institute, New Jersey, 1989. The power consumption of the proposed pumping system depends upon the flow requirements, and pump sizes. The pumping flow rate, Q, required for effective agitation is calculated from the following equation:2 PF where TV = TO = C4 = TV TO C 4 5 tank volume, ft3 turnover, the number of times the tank volume will be circulated per hour, 1/h conversion constant, 0.125 gpm/cu. ft per hour Assuming that ten turnovers could provide adequate agitation for the cleaning tank, the pumped flow for the caustic cleaning tank can be calculated as follows: PF 5.5 5 48 10 0.125 330 gals/m in 5 The dimensions, turnover rate and required flow rate for all the tanks considered are shown in the table below. Pumping Flow Rates Required for Agitation Pump Depth Width Length Turnover Flow Tank ft ft ft gpm Caustic 5.5 5 48 10 330 Caustic Rinse 5.5 5 48 10 330 Pickling 6.5 7 48 10 546 The required flows could be provided with two 7.5 hp motors for each of the caustic clean and caustic rinse tanks, and two 15 hp motors for the pickling tank, for a total rated power of 60 hp. The galvanizing line operates 8,112 h/yr. Assuming the pump motors operate at their rated capacity, the energy savings that can be realized by using pumped fluid instead of compressed air to provide agitation is estimated as follows: ES 78 60 8,112 0.746 108,928 kWh/yr ECS 108,928 kWh/yr $0.0238/kWh $2,590/yr The demand savings, DS, and demand cost savings, DCS, can be estimated as follows: 2 From Serfilco '94-'95 Catalog "U" pp. 132 - 134 DS PC PP C 1 C 5 CF DUF DCS DS avoided cost of electric demand where C5 = CF = DUF = conversion constant, 12 months/yr fraction of rated power contributing to the facility peak demand, per month fraction of the year equipment contributes to peak demand, no units The tanks require agitation during all working hours, so CF = 1.0/month. The plant operates all year, so DUF = 1.0. Thus, DS 78 - 60 0.746 12 1.0 1.0 161.1 kW/yr DCS 161.1 kW/yr $7.55/kW $1,220/yr Thus, the total estimated electrical cost savings are $3,810/yr. Additional energy savings will result from reduced heating requirements for the tanks. Implementation Cost Implementation of this AR involves purchase and installation of circulating pumps, piping and the eductor nozzles. The estimated implementation cost is shown in the table below. Unit Cost Total Cost Tank System Caustic Clean 12 Eductor systems: 4 ft. long CPVC w/ 4 x 3/4" eductors $157.95 $1,895 2 Pump/motors (7.5 hp each), rated at 215 gpm @ 50 ft. $3,857.21 $7,714 TDH Caustic Rinse 12 Eductor systems: 4 ft. long CPVC w/ 4 x 3/4" eductors $157.95 $1,895 2 Pump/motors (7.5 hp each), rated at 215 gpm @ 50 ft. $3,857.21 $7,714 TDH Pickling 16 Eductor systems: 3 ft. long CPVC w/ 3 x 3/4" eductors $127.04 $2,033 2 Pump/motors (15 hp each), rated at 350 gpm @ 75 ft. $3,140.42 $6,281 TDH TOTAL $27,532 The total implementation cost is $27,530. Thus, the cost savings of $3,810/yr will pay for the implementation cost in about 7.2 years. Contact Information Vendor contact name: Vendor company name: Address: City: State: Phone: Fax: E-mail: Internet: Make and Model Number: Other Info: