specifications

advertisement

Specification

Kalzip® SolarPowerSystems

A separate additional offer can be made for equivalent alternatives.

Only flexible amorphous silicon thin-film modules that have 3 semiconductor layers, are permanently laminated on aluminium, are approved according to IEC 61646 and protection class II and identical in appearance are considered as equivalent alternatives.

Carrying out the described services is based on the installation manual of

Kalzip GmbH, as well as the IEC 60364-712 and basic electrical standards.

The safety and health protection rules for the construction industry are an integral part of the offer.

Kalzip® AluPlusSolar Module PVL-136 (number according to Systems specification)

0000 Building Integrated Photovoltaic Module a-SI thin-film modules, factory-laminated to the roofing

(aluminium profile boards) by the manufacturer

Module length: 5.50 m

Nominal output: 136 W

Operating voltage VMPP: 33.0 V

Operating current IMPP: 4.13 A

Open-circuit voltage VOC: 46.2 V

Open-circuit voltage VOC at -10°C and 1250 W/m2: 52.7 V

Short-circuit current ISC: 5.1 A

Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A

Fuse in series, nom./blocking diode, nom.: 8.0 A

Maximum system voltage DC: 1000 V

Connection: pre-assembled connecting cable plug/socket

Type: Kalzip® AluPlusSolar PVL-136

When installing the roofing, connect ready for use and wired up according to DC circuit diagram.

__ Item x Price per Item: .............€ = .............€

Kalzip® AluPlusSolar Module PVL 68 (number according to Systems specification)

0000 Building Integrated Photovoltaic Module a-SI thin-film modules, factory-laminated to the roofing

(aluminium profile boards) by the manufacturer

Module length: 2.85 m

Nominal output: 68 W

Operating voltage VMPP: 16.5 V

Operating current IMPP: 4.13 A

Open-circuit voltage VOC: 23.1 V

Open-circuit voltage VOC at -10°C and 1250 W/m2: 26.3 V

Short-circuit current ISC: 5.1 A

Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A

Fuse in series, nom./blocking diode, nom. : 8.0 A

Maximum system voltage DC: 1000 V

Connection: pre-assembled connecting cable plug/socket

Type: Kalzip® AluPlusSolar PVL-68

When installing the roofing, connect ready for use and wire up according to DC circuit diagram

__ Item x Price per Item: .............€ = .............€

1.1 Kalzip® SolarClad

1.1.1 Roof Parallel Installation (horizontal)

Kalzip® SolarClad Module PVL-136 (number according to Systems specification)

0000 Photovoltaic Module

Modules are made of painted aluminium edge profiles with laminated a-Si thin-film module

Module width: 0.46 m

Module length: 5.50 m

Nominal output: 136 W

Operating voltage VMPP: 33.0 V

Operating current IMPP: 4.13 A

Open-circuit voltage VOC: 46.2 V

Open-circuit voltage VOC at -10°C and 1250 W/m2: 52.7 V

Short-circuit current ISC: 5.1 A

Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A

Fuse in series, nom./blocking diode, nom.: : 8.0 A

Maximum system voltage DC: 1000 V

Connection: pre-assembled connecting cable plug/socket

Type: Kalzip® SolarClad PVL-136

Impermeable horizontal roof-parallel installation using beam notches and mounting rails that belong to the system; deliver, install, connect ready for use and wire according to

DC wiring diagram

__ Item x Price per Item: .............€ = .............€

Kalzip® SolarClad Module PVL 68 (number according to Systems specification)

0000 Photovoltaic Module

Modules made of painted aluminium edge profiles with laminated a-Si thin-film module

Module width: 0.46 m

Module length: 2.85 m

Nominal output: 68 W

Operating voltage VMPP: 16.5 V

Operating current IMPP: 4.13 A

Open-circuit voltage VOC: 23.1 V

Open-circuit voltage VOC at -10°C and 1250 W/m2: 26.3 V

Short-circuit current ISC: 5.1 A

Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A

Fuse in series, nom./blocking diode, nom.: : 8.0 A

Maximum system voltage DC: 1000 V

Connection: pre-assembled connecting cable plug/socket

Type: Kalzip® SolarClad PVL-68

Impermeable horizontal roof-parallel installation using beam notches and mounting rails that belong to the system

Deliver, install, connect ready for use and wire according to

DC wiring diagram

__ Item x Price per Item: .............€ = .............€

1.1.2 Roof Parallel Installation (vertical)

Kalzip® SolarClad Module PVL-136 (number according to Systems specification)

0000 Photovoltaic Module

Modules are made of painted aluminium edge profiles with laminated a-Si thin-film module

Module width: 0.46 m

Module length: 5.50 m

Nominal output: 136 W

Operating voltage VMPP: 33.0 V

Operating current IMPP: 4.13 A

Open-circuit voltage VOC: 46.2 V

Open-circuit voltage VOC at -10°C and 1250 W/m2: 52.7 V

Short-circuit current ISC: 5.1 A

Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A

Fuse in series, nom./blocking diode, nom.: : 8.0 A

Maximum system voltage DC: 1000 V

Connection: pre-assembled connecting cable plug/socket

Type: Kalzip® SolarClad PVL-136

Impermeable vertical roof-parallel installation using beam notches and mounting rails that belong to the system; deliver, install, connect ready for use and wire according to

DC wiring diagram

__ Item x Price per Item: .............€ = .............€

Kalzip® SolarClad Module PVL 68 (number according to Systems specification)

0000 Photovoltaic Module

Modules made of painted aluminium edge profiles with laminated a-Si thin-film module

Module width: 0.46 m

Module length: 2.85 m

Nominal output: 68 W

Operating voltage VMPP: 16.5 V

Operating current IMPP: 4.13 A

Open-circuit voltage VOC: 23.1 V

Open-circuit voltage VOC at -10°C and 1250 W/m2: 26.3 V

Short-circuit current ISC: 5.1 A

Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A

Fuse in series, nom./blocking diode, nom.: : 8.0 A

Maximum system voltage DC: 1000 V

Connection: pre-assembled connecting cable plug/socket

Type: Kalzip® SolarClad PVL-68

Impermeable vertical roof-parallel installation using beam notches and mounting rails that belong to the system

Deliver, install, connect ready for use and wire according to

DC wiring diagram

__ Item x Price per Item: .............€ = .............€

1.1.3 Elevated installation

Kalzip® SolarClad Module PVL-136 (number according to Systems specification)

0000 Photovoltaic Module

Modules are made of painted aluminium edge profiles with laminated a-Si thin-film module

Module width: 0.46 m

Module length: 5.50 m

Nominal output: 136 W

Operating voltage VMPP: 33.0 V

Operating current IMPP: 4.13 A

Open-circuit voltage VOC: 46.2 V

Open-circuit voltage VOC at -10°C and 1250 W/m2: 52.7 V

Short-circuit current ISC: 5.1 A

Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A

Fuse in series, nom./blocking diode, nom.: 8.0 A

Maximum system voltage DC: 1000 V

Connection: pre-assembled connecting cable plug/socket

Type: Kalzip® SolarClad PVL-136

Impermeable elevated installation using beam notches and elevated rear panel profile that belongs to the system

Deliver, install, connect ready to use and wire according to

DC wiring diagram

__ Item x Price per Item: .............€ = .............€

Kalzip® SolarClad Module PVL 68 (number according to Systems specification)

0000 Photovoltaic Module

Modules are made of painted aluminium edge profiles with laminated a-Si thin-film module

Module width: 0.46 m

Module length: 2.85 m

Nominal output: 68 W

Operating voltage VMPP: 16.5 V

Operating current IMPP: 4.13 A

Open-circuit voltage VOC: 23.1 V

Open-circuit voltage VOC at -10°C and 1250 W/m2: 26.3 V

Short-circuit current ISC: 5.1 A

Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A

Fuse in series, nom./blocking diode, nom.: 8.0 A

Maximum system voltage DC: 1000 V

Connection: pre-assembled connecting cable plug/socket

Type: Kalzip® SolarClad PVL-68

Impermeable elevated installation using beam notches and elevated rear panel profile that belongs to the system

Deliver, install, connect ready to use and wire according to

DC wiring diagram

__ Item x Price per Item: .............€ = .............€

2 Connection of the modules (wiring)

For Kalzip®AluPlusSolar and Kalzip SolarClad roof parallel: length = number of modules x 0,5 m

For Kalzip® Aluplussolar Elevated:

Length = number of modules x 1,0 m

0000 MODUL CABLING

(DC cables for the modules until the generator junction box)

PV module cable for DC wiring

Double protective isolation and protection type IP54

Temperature range -40°C to +80°C

Sizing: Piping loss < 1%

__ m x Price per m:............€ = .............€

Automatically 1 piece per each Inverter Typ IG 15 – IG 30

0000 GENERATOR TERMINAL BOX

Connections (input): max. 6 mm² screw terminals for 4 lines of modules

Connections (output): max. 16 mm2 screw terminals for each DC- and DC+ main lead

Protection type: IP44

Protection class: I I

Max. open circuit voltage: 500 V

Max. input current: 20 A (at 150 V), 7 A (at 400 V )

Max DC output current: 16 A

Type: Fronius DC isolating box for IG15-30

__ Item x Price / Item .............€ = .............€

Automatically 1 piece per each Inverter Typ IG 40 – IG 60

0000 GENERATOR TERMINAL BOX

Connections (input): max. 6 mm² screw terminals for 8 lines of modules

Connections (output): max. 25 mm2 screw terminals for each DC- and DC+ main lead

Protection type: IP54

Protection class: I I

Max. open circuit voltage: 530 V

Max. input current: 37 A (at 150 V), 14 A (at 400 V )

Max DC output current: 25 A

Type: Fronius DC isolating box for IG40-60

__ Item x Price / Item .............€ = .............€

Default: 10 m, otherwise questioned by the program

0000 PV DIRECT CURRENT MAIN LEAD

Generator terminal box connection to inverters

Double protective isolation and protection type IP54

Temperature range -40°C to +80°C

Sizing: Piping loss < 1%

__ m x Item Price .............€ = .............€

3 Inverter

0000 INVERTER

Photovoltaic inverter for supplying network with solar energy

Graphic display galvanic insulation with HF transformer,

Data communication option with plug-in cards, integrated

MSD,

Housing, DC connections as screw terminals for max 10 mm² cables without multicore cable end or 6 mm² with multicore cable end

Max. input current: 500 V

MPP voltage range: 150-400 V

PV output: 1300 – 2000 Wp

AC nominal output: 1300 W

Distortion factor: < 3.5 %

Power factor: 1

Ambient temperature: -20...+50°C

Installation: Indoor installation, with wall mounting

Protection type: IP21

Type:FRONIUS IG 15

__ Item x Price / Item .............€ = .............€

0000 INVERTER

Photovoltaic inverter for supplying network with solar energy.

Graphic display, galvanic insulation with HF transformer,

Data communication option using plug-in cards, integrated

MSD,

Housing, DC connections as screw terminals for max 10 mm² cables without multicore cable end or 6 mm² with multicore cable end

Max. input current: 500 V

MPP voltage range: 150-400 V

PV output: 1800 – 2700 Wp

AC nominal output: 1800 W

Distortion factor: < 3.5 %

Power factor: 1

Ambient temperature: -20...+50°C

Installation: Indoor installation, with wall mounting

Protection type: IP21

Type: FRONIUS IG 20

__ Item x Price / Item .............€ = .............€

0000 INVERTER

Photovoltaic inverter for supplying network with solar energy.

Graphic display, galvanic insulation with HF transformer,

Data communication option using plug-in cards, integrated

MSD,

Housing, DC connections as screw terminals for max 10 mm² cables without multicore cable end or 6 mm² with multicore cable end

Max. input current: 500 V

MPP voltage range: 150-400 V

PV output: 2500 – 3600 Wp

AC nominal output: 2500 W

Distortion factor: < 3.5 %

Power factor: 1

Ambient temperature: -20...+50°C

Installation: Indoor installation, with wall mounting

Protection type: IP21

Type: FRONIUS IG 30

__ Item x Price / Item .............€ = .............€

0000 INVERTER

Photovoltaic inverter for supplying network with solar energy.

Graphic display, galvanic insulation with HF transformer, internal master-slave operation of 2 power elements,

Data communication option using plug-in cards, integrated

MSD,

Housing, DC connections as screw terminals for max 10 mm² cables without multicore cable end or 6 mm² with multicore cable end

Max. input current: 500 V

MPP voltage range: 150-400 V

PV output: 3500 – 5500 Wp

AC nominal output: 3500 W

Distortion factor: < 3.5 %

Power factor: 1

Ambient temperature: -20...+50°C

Installation: Indoor installation, with wall mounting

Protection type: IP21

Type: FRONIUS IG 40

__ Item x Price / Item .............€ = .............€

0000 INVERTER

Photovoltaic inverter for supplying network with solar energy.

Graphic display, galvanic insulation with HF transformer, internal master-slave operation of 2 power elements,

Data communication option using plug-in cards, integrated

MSD,

Housing, DC connections as screw terminals for max 10 mm² cables without multicore cable end or 6 mm² with multicore cable end

Max. input current: 500 V

MPP voltage range: 150-400 V

PV output: 4600 – 6700 Wp

AC nominal output: 4600 W

Distortion factor: < 3.5 %

Power factor: 1

Ambient temperature: -20...+50°C

Installation: Indoor installation, with wall mounting

Protection type: IP21

Type: FRONIUS IG 60

__ Item x Price / Item .............€ = .............€

4 Data Communication

if only one Inverter in the system, you will need only one

0000 Datalogger Box easy

Datalogger in external housing;

The datalogger registers and saves the following data of one FRONIUS IG inverter: DC-current, DCvoltage, AC-current, AC-voltage, AC-power, daily yield, yearly yield, measuring values of the sensors connected to a FRONIUS IG Sensor Card/Box. Fault information via text message when a modem is connected. The inverter can be called up and maintained remotely;

Memory capacity:

Memory duration:

L x w x h:

Sockets:

540 kByte about 1000 days (memory cycle 30minutes)

197 x 110 x 57 mm

9-pole submin (RS232 interface for PC)

9- pole submin (RS232 interface for modem)

36-pole Pin-plug type connection

2 RJ 45 sockets for RS 485 transmission

Degree of protection:

Type:

IP 20

FRONIUS IG Datalogger Box easy (or comparable)

__ Item x Price / Item .............€ = .............€

if more than one inverter the number of Com cards is equal with the number of inverters

0000 Communication between the inverters

COM Card

Plug-in card for data connection;

Inverters data linked with one another, data transmitted onto the datalogger, power supply for the datalogger and other plug-in cards, galvanic separation between inverter and data communication;

Each inverter with data communication requires its own COM Card.

L x w x h:

Sockets:

Type:

140 x 100 x 33 mm

2x RJ 45 sockets for RS 485 transmission

FRONIUS IG COM Card (or comparable)

__ Item x Price / Item .............€ = .............€ always one piece

0000 Datalogger Box pro

Datalogger in external housing;

The datalogger registers and saves the following data (up to 100 FRONIUS IG): DC-current, DCvoltage, AC-current, AC-voltage, AC-power, daily yield, yearly yield, measuring values of the sensors connected to a FRONIUS IG Sensor Card/Box. Fault information via text message when a modem is connected; The inverter can be called up and maintained remotely;

Memory capacity:

Memory duration:

L x w x h:

Sockets:

Degree of protection:

Type:

540 kByte about 1000 days (1 FRONIUS IG and memory cycle 30 min)

197 x 110 x 57 mm

9-pole submin (RS232 interface for PC)

9- pole submin (RS232 interface for modem)

36-pole Pin-plug type connection

2 RJ 45 sockets for RS 485 transmission

IP 20

FRONIUS IG Datalogger Box pro (or comparable)

__ Item x Price / Item .............€ = .............€ always one piece

0000 Display Box

Plug-in card in an external housing for the visualisation of pv data on a large screen display; The

Public Display Box is compatible with the Public Display FRONIUS IG as well as with the whole display range of the company RiCo. Display and Box are connected with a standard cable. The cable is provided with the Public Display Box.

Dimensions (l x w x h): 197 x 110 x 57 mm

Sockets: 9-pole submin (RS232 interface for display)

2x RJ 45 sockets for RS 485 transmission

Degree of protection: IP 20

Type: FRONIUS IG Public Display Box (or comparable

__ Item x Price / Item .............€ = .............€

0000 Photovoltaic Display large screen for the indi cation of all data of the whole system ( Power output, Energy gain, CO² reduction)

The connection of a Public Display is only possible if the inverter(s) is (are) equipped with a COM

Card and a Datalogger.

Dimensions: 500 x 700

Display screen:

Typ: very bright LED (red)

Kalzip Solardisplay

__ Item x Price / Item .............€ = .............€

5 Miscellaneous

0000 LIGHTNING PROTECTION

Including the electrical lines on the building entrance

(junction of lighting protection zone 0 ->1) using a requirement class B lightning surge arrester in the equipotential bonding.

Flat rate x Item Price ............€ = .............€

0000 AC WIRING

Wiring up the inverters for AC side feed-in line according to the guidelines of the energy supply company for grid connection.

Sizing: Piping loss < 1%

Changing and expanding the existing meter cupboard for placing the feed meter.

Flat rate x Item Price .............€ = .............€

0000 PV COMMISSIONING

Documentation:

General circuit diagram (1-pole) and connection schemes with specifications about the type, manufacturer, wiring and function

Register at the appropriate energy supply company

Certification and commissioning

Flat rate x Item Price .............€ = .............€

Download