VIVENDI WATER STI Eclipse Two Stage Deioniser Units Operational Instruction Models 150 & 300 REVISION A REF: MANU317530 106755469 Fisher Bioblock Scientific page 1 VIVENDI WATER STI IMPORTANT It is most important that this instruction book is retained with the appliance for future reference. Should the appliance be sold or transferred to another owner, or should you move premises and leave the appliance, always ensure that the book is supplied in order that the new owner can be acquainted with the functioning of the appliance and the relevant warnings. 106755469 Fisher Bioblock Scientific page 2 VIVENDI WATER STI Declaration of Conformity Manufacturer Name:Address:- USF Limited Harforde Court John Tate Road Hertford, SG13 7NW Machinery Description:Water Treatment Equipment Model:- ECLIPSE DEIONISER Part No:- ------------------------------ Serial No:- ------------------------------ Year of Manufacture:- ------------------------------ We declare that the equipment covered in this manual conforms with the essential Health and Safety requirements. Nick Broomfield Marketing Manager USF Limited Revision A: January 1997 Rev O: September 1995 Manual No: 317530 106755469 Fisher Bioblock Scientific page 3 VIVENDI WATER STI Health and Safety DEIONISER PRODUCT WARNINGS THESE WARNINGS ARE PROVIDED IN THE INTEREST OF SAFETY. YOU MUST READ THEM CAREFULLY BEFORE INSTALLING OR USING THE PRODUCT. Isolate the equipment and turn off the water if the system is not to be used for long periods of time. See shut down procedures in manual, under Operation. Any plumbing work to install this equipment should be carried out by a qualified plumber or competent person. Any electrical work required to install this equipment should be carried out by a qualified electrician or competent person. This equipment is designed to be operated by staff fully trained at the commissioning of the deioniser. Staff not fully trained or inexperienced should not be allowed to operate the product controls. This product should be serviced by VIVENDI WATER STI via the UK Service Network, and only genuine VIVENDI WATER STI spare parts should be used. This product must not be modified in any way without the express permission in writing from VIVENDI WATER STI Limited. Modification could cause failure to the product and create a Health and Safety Risk. Care must be taken to ensure that the equipment does not stand on or impede the electrical supply cable. VIVENDI WATER STI Deionisers are designed to be used for treating normal feed waters, free from iron, manganese, chlorine, suspended solids and any other substances which may affect the performance of the unit. Water that is contaminated by petrol, paint, steel or iron debris, must not be passed through the deioniser. Following any servicing work the control panel must be closed, as electricity is potentially hazardous. Under no circumstances must you open the electrical control panel whilst the equipment is in operation. Always turn of the equipment before carrying out any examinations. Similarly no mechanical work such as the removal of a fitting or valve should be undertaken, whilst the unit is under pressure. The system should be isolated from the main water supply and all feed pressure pumps, turned off. Under no circumstances should you attempt to repair the equipment yourself. Repairs carried out by inexperienced persons may cause injury and more serious malfunctioning. Refer to VIVENDI WATER STI Service department. Always insist on genuine VIVENDI WATER STI spare parts. 106755469 Fisher Bioblock Scientific page 4 VIVENDI WATER STI Health and Safety HEALTH AND SAFETY WARNINGS - DEIONISERS USE OF CHEMICAL AND SAFETY VIVENDI WATER STI are fully committed to the Health and Safety aspects of water treatment plant operation. This plant contains ion exchange resins and utilises hazardous chemical in its operation. We do not however, provide these chemicals as part of our supply and recommend that the user liaises directly with their chemical supplier to obtain specific recommendations. Health and Safety Data Sheets should be provided by chemical supplier. 106755469 Fisher Bioblock Scientific page 5 VIVENDI WATER STI Contents HEALTH AND SAFETY Deioniser Warnings .............................................................................................................................. 4 TECHNICAL DATA ............................................................................................................................. 7 DESCRIPTION Introduction .......................................................................................................................................... 8 Regeneration ........................................................................................................................................ 8 Chemicals ........................................................................................................................................... 8 Control Box .......................................................................................................................................... 9 Control Logic Diagram ......................................................................................................................... 10 INSTALLATION Installation Diagram.............................................................................................................................. Introduction .......................................................................................................................................... Initial Preparation ................................................................................................................................. Foundations and Drain ......................................................................................................................... Head Room and Operating Space........................................................................................................ Water Pressure .................................................................................................................................... Water Temperature .............................................................................................................................. Pipework Connections .......................................................................................................................... Electrical Supply ................................................................................................................................... Terminal Connection Diagram ............................................................................................................. 12 13 13 13 13 13 14 14 14 15 COMMISSIONING Introduction .......................................................................................................................................... Pre-Service Backwash ......................................................................................................................... Attachment of Carboys ......................................................................................................................... Putting into Service .............................................................................................................................. 16 16 17 18 OPERATION Introduction .......................................................................................................................................... Charging Acid and Caustic Soda Carboys ............................................................................................ Check List in Case of Difficulties .......................................................................................................... Adjustments ......................................................................................................................................... 19 19 19 20 AFTER SALES SERVICE After Sales Service ............................................................................................................................... 22 VIVENDI WATER STI Permutit Planned Maintenance ......................................................................... 23 Spares and Media Sales ...................................................................................................................... 24 GENERAL ARRANGEMENT DIAGRAM ............................................................................................. 26 106755469 Fisher Bioblock Scientific page 6 VIVENDI WATER STI Technical Data Maximum treated water flow Minimum treated water flow Maximum operating pressure Minimum operating pressure Maximum operating temperature Minimum operating temperature Pressure loss at maximum flow (ambient) Capacity based on 100 ppm Total Anion Load (As CaCO³ , including Silica and CO²) to 30 µS/cm using strong base anion resin Units m³/hr m³/hr bar bar °C °C bar 150 1.5 0.25 7.0 4.0 40 15 1.6 300 3.0 0.5 7.0 4.0 40 15 2.8 m³ 25 60 litres litres litres 11 10 10 26 24 24 m³/hr m³/hr 0.4 1.4 0.45 2.25 m³ m³ hours hours 0.3 1.0 2.5 2.1 240 volts 0.4 1.55 Regeneration 28% w/w hydrochloric acid 32% w/w hydrochloric acid 30% w/w caustic soda (preferred) Maximum flow to drain With rinse recycle Without rinse recycle Effluent volume per regeneration With final rinse cycle Without final rinse cycle Regeneration time 50Hz Regeneration time 60Hz Electrical supply Treated Water Quality TDS mg/l <10 50Hz Single phase Conductivity µS/cm <30 max <20 ave SPECIFICATION - CONSTRUCTION The fibre glass reinforced cation and anion vessels are mounted on an epoxy coated skid. The Eclipse management control system ensures fully automatic operation is supplemented by manual override to provide operational flexibility. A series of individual visual alarm indicators allows immediate identification of plant status. The Eclipse unit is supplied skid mounted, having been pressure tested and fully loaded with resin, prior to transportation. This considerably reduces installation costs and time, thus ensuring a highly reliable plant is put into service with minimum site disruption. Overall Dimensions Height Depth Width* Headroom (recommended) Approx. service weight (kg) Eclipse 150 1505 mm 670 mm 870 mm 1000 mm 480 kg Eclipse 300 1965 mm 670 mm 1070 mm 1000 mm 835 kg * Excludes chemical regeneration containers 106755469 Fisher Bioblock Scientific page 7 VIVENDI WATER STI Description INTRODUCTION The Eclipse Two Stage Automatic Deioniser is designed to produce high quality deionised water, and comprises two glass fibre ion exchange pressure vessels connected in series. The first vessel (on the left hand side when viewed from the front) contains a cation ion-exchange resin. The second, right hand vessel contains Anion ion-exchange resin. A control panel fitted at the top of the vessels houses an electronic controller that controls the Deioniser during service and resin regeneration, and provides interlock control functions with other plant. The water quality is monitored by a conductivity meter that is factory set to 30 microsiemens/cm. When the conductivity of the treated water rises to this level, the Deioniser outlet valve automatically closes, and the Deioniser commences a rinse to drain. If the conductivity at the end of the rinse period has returned to normal, the deioniser will return to service. If however, the conductivity remains above the set point, the control automatically commences the regeneration procedure. This pre-regeneration rinse prevents unnecessary regenerations should there be a temporary drop in water quality for some reason, and at the same time, ensures that only good quality water is passed to service, it is normally set to 8 minutes. However if the deioniser service automatically recycles to the break tank at times of low demand this rinse time is set to minimum. REGENERATION Regeneration consists of injecting dilute hydrochloric acid through the cation ion-exchange resin, and dilute caustic soda through the anion resin. In both cases, this is preceded by backwashing to remove any resin ‘fines’ that may have collected on top of the resin, and to loosen the resin bed prior to chemical injection, and is followed by a rinse to drain to remove residual chemical and regeneration product. The regeneration procedure is carried out automatically, and is initiated either by the conductivity meter as stated above, or manually by a push button located on the Control Panel. When both vessels have completed regeneration, (cation first, followed by the anion vessel) the Deioniser is rinsed to drain or recycled to the break pressure tank and the conductivity of the treated water monitored. When the conductivity drops below the set point i.e. when all the residual chemicals have been flushed from the vessels and pipework, the Deioniser automatically returns to service. CHEMICALS The required strength of the hydrochloric acid and caustic soda is given in the Technical Data, and the arrangements must be made to obtain regular supplies. The acid and caustic soda is drawn from carboys or regeneration tanks (optional) by the acid and caustic injectors which form an integral part of the vessel valve head assembly. WARNING: BOTH OF THESE CHEMICALS ARE CORROSIVE AND THEREFORE, CHEMICAL GOGGLES, RUBBER GLOVES, BOOTS AND PROTECTIVE CLOTHING MUST BE WORN WHEN 106755469 Fisher Bioblock Scientific page 8 VIVENDI WATER STI Description HANDLING AND CHANGING THE CARBOYS, AND THE STAFF MUST BE PROPERLY TRAINED. INSTRUCTIONS FOR FIRST AID AND THE HANDLING OF SPILT CHEMICALS SHOULD BE DISPLAYED IN THE AREA AND EVERYONE WHO HANDLES THESE CHEMICALS MUST BE CONTINUOUSLY CAUTIOUS, OBSERVANT AND ALERT. INFORMATION REGARDING SAFE HANDLING AND STORAGE OF THE CHEMICALS IS OBTAINABLE FROM YOUR SUPPLIER. CONTROL BOX The Control Box contains the electrical components necessary to carry out the following functions. Refer also to the Control Logic Diagram. Monitor and display the water quality. Close the outlet solenoid valve when sub-quality water is sensed. Pre-rinse the resins prior to regeneration. Initiate regeneration of the Cation and Anion vessels. Rinse the regenerated resins until good quality water is achieved. Control the raw water pump. Provide differential level control for the treated water tank. Give low level protection for the raw water pump. Interlock with any pre-treatment plant to prevent dry running. Une marque de VIVENDI WATER STI 106755469 Fisher Bioblock Scientific page 9 VIVENDI WATER STI Description 106755469 Fisher Bioblock Scientific page 10 VIVENDI WATER STI Description The following indicators and controls are provided in the control panel as shown. Conductivity Meter Indicates conductivity of treated water to 40µs/cm. Also indicates maximum acceptable water quality as set using set point adjuster and push button. ‘Push to set Point’ Push-button & Potentiometer For setting conductivity set point on conductivity meter, – small screwdriver required. Auto/Hand Switch In ‘Auto’ mode unit will automatically regenerate when conductivity exceeds the set point. In ‘Hand’ mode unit will stop water passing to service, initiate an alarm signal (flashing regen lamp) and await a manual initiation of regeneration. (If conductivity is good switch to hand first before initiating a regeneration). Reset/Initiate Button Hold in for 10 seconds to initiate a regeneration. Instant push and release will reset unit following power interruption or correction of an alarm condition. Mute Alarm Button Push to cancel alarm signal (does not reset alarm condition). 24v Control Lamp (Green) Indicates that power is available for controls. Duty Lamp (Green) Indicates that Service Solenoid Valve is open. Treated Water Demand Lamp (Amber) Indicates that demand switch is calling for water. Off when . tank full or emptying. Low Raw Water Lamp (Red) Indicates low raw water in break pressure tank, pump shut off (resets automatically on resumption of water supply) Low Chemical Lamp (Red) Indicates low Acid or Caustic Level. Regen Lamp (Red) Flashes on Power Up or resumption of Power. Steady - During regeneration. Rinse Lamp (Green) Indicates when the unit is in final system rinse recycle/drain. 106755469 Fisher Bioblock Scientific page 11 VIVENDI WATER STI Installation 106755469 Fisher Bioblock Scientific page 12 VIVENDI WATER STI Installation INTRODUCTION The work detailed below must be carried out by a competent plumber and electrician. When the installation work has been completed, the Deioniser can be commissioned (set to work). If the customer’s order includes for the services of a company engineer to commission the plant, he should contact the Service Office as listed in AFTER SALES SERVICE, and arrange for a regional engineer to call. The work necessary to commission the Deioniser is detailed under COMMISSIONING. INITIAL PREPARATION Because deionised water can be contaminated easily, it is advisable to have the plant located as close as possible to the point of use of the treated water. Hydrochloric acid and Sodium Hydroxide (caustic soda) used to regenerate the resins are very corrosive chemicals, and consequently must be kept out of the way of the public and uninformed staff. FOUNDATIONS AND DRAIN No special foundations are required, providing a firm and level surface capable of supporting the working weight of the Deioniser (see Technical Data) is available. An open gully capable of handling the 15% acidic and alkaline solutions and the maximum drain flow shown in the Technical Data must be available or constructed within 3 metres of the installation. Because of the corrosive nature of the waste effluent flowing to drain during the regeneration procedure, the local water authorities must be consulted before disposal into local river streams and municipal sewers. HEAD ROOM AND OPERATING SPACE When installing the Deioniser it is important to ensure there is: Access to the front of the Deioniser for controls operation. Adequate space to change and manoeuvre the acid and caustic soda carboys (or refill optional regenerant tanks). Access to the rear of the installation is available for maintenance work 300mm minimum. A height of 400mm above the unit. The overall dimensions of the plant are given in the Technical Data. WATER PRESSURE Minimum: Maximum: 3.5 bar 7.0 bar NOTE: The water to the Deioniser must be clean and free from suspended solids and organic matter. 106755469 Fisher Bioblock Scientific page 13 VIVENDI WATER STI Installation WATER TEMPERATURE Maximum Minimum Minimum 40°C (at maximum pressure) The Deioniser and drain pipework must not be subjected to freezing conditions. Ambient 15°C Note: The minimum ambient temperature is specified because below 15°C caustic soda becomes very viscous and starts to freeze, making chemical injection into the unit extremely difficult. PIPEWORK CONNECTIONS (TO BE PROVIDED BY CUSTOMER) Fit the inlet isolating, check and anti-vacuum valves or alternatively break pressure tank and booster pump and inlet isolating valve to the raw water supply pipework as shown diagrammatically on the schematic pipe connection diagram. Flush out all swarf and debris from newly made connections and pipework. Note: A break pressure tank is required to confirm to Local Water Authority regulations in the U.K. and may also be required to increase the raw water supply pressure. Information on suitable break pressure tanks is available on request from VIVENDI WATER STI. Fit the outlet isolating valve to the treated water pipework. All treated water pipework and fittings must be made in uPVC, PVC (Polyvinyl Chloride), ABS (Acrylonitrile Butadiene Styrene) Polypropylene, Stainless Steel or suitable lined piping - standard plumbing fittings such as copper or galvanised piping must not be used. Place the deioniser into position. The front face of the control panel must be accessible and easily observable. Make final connections between the inlet and outlet isolating valves and inlet and outlet connections. Direct the individual valve drains to a suitable drain or gully. The Final rinse drain should also be directed to the drain or gully unless final rinse recycle has been specified when it should be directed to the break pressure tank (see TECHNICAL DATA for connection details). ELECTRICAL SUPPLY AND TERMINAL CONNECTIONS The mains electrical supply is to be connected to the Deioniser control box terminals via a fused and earth connected switch. The 220/240V supply to the control box should be fused 1 amp or 3 amp for 110v/120v supply. Note: If unit has been supplied for 115v supply voltage, check links are correctly positioned as shown in terminal connection diagram. All wiring and electrical installation must comply with the B.I.E.E. Regulations 16th Edition or local rules. 106755469 Fisher Bioblock Scientific page 14 VIVENDI WATER STI Installation 106755469 Fisher Bioblock Scientific page 15 VIVENDI WATER STI Commissioning INTRODUCTION Before the Deioniser can produce treated water, the following Commissioning procedure must be carried out. If the services of a Commissioning Engineer are required, contact the Service Office as listed under After Sales Service, or the local agent to arrange for an engineer to call. PRE-SERVICE BACKWASH Check that the power supply is switched off and that the inlet and outlet isolating valves are closed. Remove the cover from the cation and anion control valve assemblies. Push the red knob in on the end of the cation control valve camshaft and rotate and camshaft anticlockwise until the arrow on the knob points to the annular segment of the backwash stage indicator diagram, then release the knob. Crack open the manual inlet isolating valve (do not open fully at this stage as opening the valve fully with air trapped in the vessel may bring resin over into the drain.) until water, free of air, flows from the cation regeneration drain and the rinse drain. This could take up to 10 minutes. When water free of air is flowing, push the red button in again and rotate the camshaft anticlockwise until the arrow is near the end of the annular segment of the final rinse stage diagram. Release the knob. Select Auto/Manual Switch to Manual. Turn on the electrical supply, the regen lamp will flash. Push the ‘Reset’ button. 106755469 Fisher Bioblock Scientific page 16 VIVENDI WATER STI Commissioning The valves will now rotate to the Service position. The regen lamp will start to flash again after a short time. Switch off the electrical supply. ATTACHMENT OF CARBOYS (OR OPTIONAL MEASURING TANKS) The required strength of hydrochloric acid and caustic soda is given in the TECHNICAL DATA. The acid and caustic soda is drawn by injectors which form an integral part of Deioniser valve assembly. WARNING: BOTH OF THESE CHEMICALS ARE CORROSIVE AND THEREFORE, CHEMICAL GOGGLES, RUBBER GLOVES, BOOTS AND PROTECTIVE CLOTHING MUST BE WORN WHEN HANDLING AND CHANGING THE CARBOYS. THE OPERATING STAFF MUST BE PROPERLY TRAINED AND INSTRUCTIONS FOR FIRST AID AND THE HANDLING OF SPILT CHEMICALS DISPLAYED IN THE AREA. Place the acid carboy on the left of the deioniser (when viewed from the front) and the caustic soda carboy on the right. Fill the carboys with chemicals as stated under acid and caustic carboy filling in the Operations Section. Remove the caps from the top of the carboys, and replace with the draw tube assemblies provided (see NOTE below). Leave about 25mm between the bottom of the stand pipe and the carboy as shown. NOTE: Ensure that the correct draw tube assembly is attached to the correct carboy. The connection from the Anion valve marked NaOH must be connected to the caustic soda carboy, and the connection from the Cation valve marked HCl to the Hydrochloric Acid carboy. CONNECTING TO OPTIONAL REGENERANT TANKS If optional regeneration tanks are to be fitted the drawtubes are simply connected to the compression fittings at the rear of the regeneration valves. Ensure that the tank marked Acid/HCI is connected to the Left Hand Valve (Cation) and the tank marked Caustic/NaOH is connected to the Right Hand Valve (Anion). If level switches have been supplied ensure that these are wired as shown in the wiring diagram, these tanks are normally to be filled using a Chemical transfer Pump (not supplied) care being taken to use the operating instructions supplied with any such pump and the safety instructions supplied by your chemical regenerant supplier. If the installation area is poorly ventilated, connect a tube between the carboy bung or tank breather and the outside to prevent the possibility of corrosive fumes building up. Note that this line must be free of kinks otherwise the plant will fail to regenerate. Alternatively a fume scrubber can be fitted to the carboy or regenerant tank. Contact the service office as listed under After Sales Service or your Local agent. 106755469 Fisher Bioblock Scientific page 17 VIVENDI WATER STI Commissioning Caustic soda starts to come out of solution at +15°C. Starts to freeze at +8°C and is completely solid at +5°C. The ambient temperature must be above 15°C. NOTE: ONLY LIQUID CAUSTIC IS TO BE USED 30% W/W PREFERRED, OR 46% W/W. PUTTING INTO SERVICE Ensure the Manual/Auto switch is set to Manual. Ensure the Inlet and Outlet Isolating valves are closed. SWITCH ON electrical supply. Slowly open the Inlet Isolating valve fully. Press the regeneration initiation push button until the regeneration lamp comes on (around 10 seconds) and allow the unit to regenerate. (Ensure chemical carboy or tank has been installed). At the end of approximately 2.5 hours, the unit will have finished regeneration. If the water quality is below the conductivity set point, the plant will be ready for service. If the water quality is above the conductivity set point, manually rinse the plant by operating the reset push button until good quality water is achieved. Set the Deioniser into Manual or Automatic mode as required. Slowly open the outlet isolating valve to allow treated water to service. The Deioniser is now in normal service. 106755469 Fisher Bioblock Scientific page 18 VIVENDI WATER STI Operation INTRODUCTION Once the Deioniser has been properly installed and set to work, the only regular attention will be to change the acid and caustic soda carboys, or refill the optional regenerant tanks. Ensure that the safety precautions outlined at the beginning of this manual are followed whilst carrying out the following procedures. CHANGING ACID AND CAUSTIC SODA CARBOYS When the level of chemical in the carboy approaches the bottom of the draw off stand pipe, the carboy must be changed. The quantity of chemical required for one complete regeneration is given under the Technical Data. If there is less than the required amount left above the stand pipe, the carboy must be changed. To change the carboy, remove the bung and stand pipe from the carboy and replace in a full carboy containing the same chemical. Confirm that breather tube is clear and unobstructed. REFILLING OPTIONAL REGENERANT TANKS When refilling optional regeneration tanks a proper acid/caustic transfer pump should be used in accordance with manufacturers safety and operating instructions. DO NOT OVERFILL. CAUSTIC LIQUOR FROM PEARL OR FLAKE The amount of 100% w/w caustic pearl/flake required per litre of deionised water is shown under technical data. Before mixing, read WARNINGS at front of manual. DO NOT mix in the caustic soda carboy or tank. The mixing must be done in a well ventilated and safe area. Add the caustic pearl/flake in 50 to 100 gram doses to the deionised water and thoroughly mix. Allow to cool between doses, see note below. Note: This mixing causes a reaction resulting in the solution becoming very hot (and can boil if added too quickly) therefore, use a mild steel or enamelled steel mixing container and implement. CHECK LIST IN CASE OF DIFFICULTIES If the Deioniser fails to deliver deionised water during the service run, or the service run is of short duration, carry out the following checks before requesting a visit by a service engineer. BYPASS VALVE Check that the manually operated bypass isolating valve is closed. If the valve was open, 106755469 Fisher Bioblock Scientific page 19 VIVENDI WATER STI Operation close it. Deionised water will then be available to service again, although it may take a little time for the treated water to displace all of the untreated water admitted via the bypass to the service line. INLET AND OUTLET ISOLATING VALVE Check that the Deioniser inlet and outlet isolating valves are open. If either of the valves is shut, open the valve. POWER FAILURE If the electrical supply has failed or has been inadvertently switched off during regeneration, the sequence controller will automatically hold in the part of the sequence where it stopped and the pump will stop. On resumption of power the regeneration lamp will flash. Pushing the ‘reset’ button will allow the unit to continue its regeneration, with the regeneration lamp on continuously until the regeneration is complete. If power fails during service, on resumption of power the ‘reset’ button should be pushed momentarily, the unit will then rinse to quality and return to service automatically if quality is good. FINAL RINSE FAILURE If the Deioniser fails to rinse down to good quality at the end of regeneration, the alarm lamp will flash, and the Deioniser will not return to service. The plant operator must then investigate the cause of the failure as shown on the Control Logic Diagram. When the cause has been rectified the Deioniser must be restarted as follows. MANUAL REGENERATION Select the Auto/Manual switch to Manual, press the Reset button and hold for 10 seconds. The regen lamp will light and regeneration has been initiated Select Auto/Manual switch to normal operating mode, unit will continue in normal service at the end of the regeneration assuming the regeneration has been successful. ACID AND CAUSTIC SODA CARBOYS OR OPTIONAL TANKS Check that the carboys/tanks contain chemical and that any sludge in the bottom of the carboy/tank is not obstructing the draw off stand pipe. Check that the vent in the stand pipe bung or tank top is not obstructed. If the above check fails to highlight the trouble, contact the Service Office as stated in After Sales Service, or your local agent. ADJUSTMENTS The conductivity set point, scale range, Rinse Check and Final Rinse times, and the chemical injection cams are preset at the factory, but can be readjusted as follows if necessary. However, these adjustments should normally be left alone and only altered on the advice of VIVENDI WATER STI. 106755469 Fisher Bioblock Scientific page 20 VIVENDI WATER STI Operation CONDUCTIVITY METER SET POINT This factory set to 30 microsiemens/cm and can be checked by pushing the ‘set level’ button fitted to the left and below the conductivity meter. ADJUSTING THE CONDUCTIVITY SET POINT This is set by pushing the ‘set level’ button in and adjusting the ‘set level’ potentiometer (fitted next to the button) clockwise for higher setting or anticlockwise for lower setting. TIMER ADJUSTMENTS Normally no adjustment is required, pre-regeneration rinse is set to minimum for units that are to continuously recycle treated water to the break pressure tank with conductivity override where a pre-regeneration quality rinse is required. This is adjustable from 2 to 15 minutes. Post regeneration quality rinse is factory set to a maximum of 40 minutes as this is overridden by good conductivity when this occurs. Acid and caustic times are adjusted by changing the draw cam. The cam fitted as standard will give correct draw times when the plant is operated between 4 and 4.5 bar. Where higher or lower pressure than this is present, a set of cams is available to replace the draw cams fitted at the factory. The higher the available pressure, the smaller the cam segment that should be used. Fine adjustment of Acid or Caustic Draws can be made using the draw line ball valves. 106755469 Fisher Bioblock Scientific page 21 VIVENDI WATER STI After Sales Service AFTER SALES SERVICE Sales and Service for VIVENDI WATER STI's Standard and Engineered Product ranges of water treatment units are handled by our Internal Sales Office or your local VIVENDI WATER STI Agent. Please see the address below for contact details for UK service; alternatively, please contact your local VIVENDI WATER STI Agent. VIVENDI WATER STI. Immeuble Gay Lussac 20, avenue E. HERRIOT 92350 LE PLESSIS ROBINSON FRANCE Telephone: +33 (1) 40 83 65 00 Fax: +33 (1) 40 83 64 50 SERVICE The VIVENDI WATER STI Internal Sales office is the first point of contact should you require any assistance in operating your plant. We provide skilled VIVENDI WATER STI Engineers to carry out commissioning, planned maintenance and perform repair and component replacement when required. We also provide on-site trouble shooting expertise. Our UK Engineers carry a wide range of spares packs, assemblies and components on their vehicles to assist in giving an efficient and reliable service. Our service office personnel provide a fast and efficient service and are able to quickly identify and arrange the supply of any component required in order to enable you to return your plant to service. Spare components and media replacements are supplied direct from our central warehouse facility to ensure that you are provided with genuine VIVENDI WATER STI components. Water Treatment Plant is highly specialised equipment which requires regular servicing at predetermined intervals in order to maintain the performance of the equipment and assure the production of optimum quality water. To satisfy this requirement VIVENDI WATER STI provide the following services: VIVENDI WATER STI Permutit Planned Maintenance Analytical Testing Recharge Packages Spares and Component Supply 106755469 Fisher Bioblock Scientific page 22 VIVENDI WATER STI After Sales Service VIVENDI WATER STI PERMUTIT PLANNED MAINTENANCE VIVENDI WATER STI Permutit Planned Maintenance, PPM, offers regular servicing at predefined intervals and includes regular replacement of identified service components. PPM is a preventative maintenance programme designed to minimise the amount of plant down time. Plant which is operated with inadequate service levels is liable to more frequent breakdowns. These are not only inconvenient, but can cause lost production and expensive down time. PPM enables you to operate the plant at peak efficiency, can eliminate excessive use of regenerants, and prevent damage to plant and production facilities which use the treated water. Our Engineers carry out a comprehensive series of designated checks and tests, as well as a detailed general inspection of the plant. Key working components are dismantled, cleaned and reassembled using new parts. Necessary adjustments are made to leave your plant working correctly and efficiently. PPM is a flexible service; the number and timing of visits can be adjusted to suit your particular site conditions and operating requirements. PPM provides a complete maintenance programme tailored to meet your needs: Regular planned visits by qualified VIVENDI WATER STI Engineers to carry out an identified service schedule. Detailed Engineer's report provided prior to leaving site advising work completed and recommending any future actions in order to enhance the operation of your plant. Service Spares Pack provided as part of the maintenance service. Strategic Spares recommended and provided at a preferential price to PPM customers. 24 or 48 Hour Guaranteed Fast Response (GFR) available. Breakdown site time inclusive (BSI) option available. Discount on replacement plant purchase. For further information on our VIVENDI WATER STI Permutit Planned Maintenance Service, please contact the VIVENDI WATER STI Service Office. 106755469 Fisher Bioblock Scientific page 23 VIVENDI WATER STI After Sales Service SPARES Replacement components and assemblies should be ordered from The VIVENDI WATER STI Service Office or your local VIVENDI WATER STI Agent. Details of the components supplied in the PPM Service and Strategic Spares Packs are available from VIVENDI WATER STI. We recommend their purchase. If you have any difficulty identifying the components required, please contact us. The Service Spares Pack contains components which should be replaced on an annual basis. This pack is provided as part of our PPM service. The Strategic Spares Pack contains identified commonly replaced components. These packs are available at a discount if you are one of our VIVENDI WATER STI Permutit Planned Maintenance customers. Where additional control boxes are installed the following electrical spare packs should also be purchased. MEDIA Should you need to replace the media in your unit (Recharge) we would be pleased to provide you with a quotation to carry out the complete recharge, including the provision of our Engineers to empty and refill the unit. 106755469 Fisher Bioblock Scientific page 24 VIVENDI WATER STI After Sales Service ANALYTICAL SERVICES VIVENDI WATER STI offers a complete range of Analytical Services to test and examine samples of media, raw and treated water, to assist with the identification and resolution of chemical and operational problems. We provide a full technical report of the sample analysed and give detailed recommendations. Once problems are correctly identified, we advise the correct action to resolve or prevent future occurrences. WATER ANALYSIS Regular analysis of inlet feed water supplies provides information regarding the level of solids being presented to the unit; this information will help you to operate your Water Treatment Plant efficiently. Analysis of the feed supply will also indicate whether contaminants are present and our report will advise you what actions should be taken to minimise or prevent future problems. Treated water samples are frequently analysed as part of our trouble shooting activities in order to determine how the media is performing and to indicate where problems are originating. MEDIA ANALYSIS Analysis of media samples, ion exchange resin and filter medias, provides information as to whether contaminants are accumulating within the media bed which may affect the quality and volume of water produced by your units. The results also provide information about the expected life of the media which can be related to your feed water quality and method of operation. If there is a problem, it is important to be able to diagnose it quickly and take appropriate action to rectify. A correct and early diagnosis can prevent unscheduled down time. The performance of the media can be monitored over time and replacement arranged to suit you. As the media ages, additional amounts of regenerant are required to produce the same volume and quality of treated water. Chemical regenerant costs can be saved by replacing the media at the optimum time. Please contact the VIVENDI WATER STI Service Office or your local VIVENDI WATER STI Agent should you require any analyses. 106755469 Fisher Bioblock Scientific page 25 VIVENDI WATER STI General Arrangement Diagram 106755469 Fisher Bioblock Scientific page 26