01/29/16 DESIGN NO. _____ SECTION 15855 COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS [Designer Note: (Remove from the Specification) 15855 RTUs will only be used on CIP projects. (If approved for use on capacity projects, provide “Maintenance Contract” article from custom spec.) CIP projects that utilize digital controls will only have stand-alone digital controls. There will not be any network at all. The commercial RTUs must use OEM controllers which may be non-Lon controllers. For non-native Lon controllers, the A/E of Record needs to determine at design time and again at submittal time that a Lon gateway is available (but not provided) to be able to integrate the RTUs into a possible future Lon BMS/DDC network. RTUs that are not native Lon and for which there is no gateway presently available, should not be utilized on CIP projects.] 13 23 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK A. 1.02 14 COMMISSIONING REQUIREMENTS A. 1.03 1.05 During construction, the HVAC Contractor shall comply with the Indoor Air Quality (IAQ) Requirements indicated in Contract Specifications Section S01550. RELATED SECTIONS A. Division 15 Sections B. Division 16 Sections DESIGN REQUIREMENTS A. NYCSCA HVAC Contractor shall comply with the Commissioning Requirements of Contract Specification Section S01660. INDOOR AIR QUAILTY (IAQ) REQUIREMENTS DURING CONSTRUCTION A. 1.04 Provide packaged commercial type rooftop heating and cooling units as specified herein, as shown on the Drawings and as needed for a complete and proper installation. Product specific requirements are contained herein; Section 15501, General Provisions for Heating, Ventilating and Air Conditioning Work, shall be referred to for general requirements. Provide control devices as coordinated by the Mechanical Contractor (MC) and the Temperature Controls Contractor (TCC). All digital controls shall be able to function in a stand-alone mode without any network connections. There are various optional methods for achieving the required seamless integrated controls. COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 1 01/29/16 DESIGN NO. _____ B. It is recognized that controls furnished by other vendors and by trades other than mechanical necessitate that both the General Contractor (GC) and Mechanical Contractor (MC) actively facilitate the coordination of controls between all parties. It is the responsibility of each vendor furnishing, a digital controller for its proper operation, configuration, and compliance with all appropriate specification sections. It is the responsibility of each vendor to comply with the intent of this specification section relating to, but not limited to providing direct, technical assistance to the TCC to connect the field sensors, technical performance, warranties, services response, etc. The MC and the GC shall determine which combination of providing digital controls best meets the intent of the specification. The combination is the responsibility of the Mechanical Contractor however the final combination must comply with the specified requirements for each piece of mechanical equipment as described below and in the respective equipment specification. The required control interoperability remains identical for each of the following options, listed in decreasing desirability. 1. The OEM may furnish and install an approved nativeLonWorks controller and the specified control devices including all wiring internal within the unitary equipment, including all low-voltage power. The I/O points to be furnished are as described on the plans and specifications including the sequence of operation. The unit will be delivered to the site ready for connection of field-based control devices. The OEM shall furnish to the Authority a licensed fully-functional copy of the toolset necessary for communication with and the adjustment of their LonWorks controller. 2. Commercial unitary equipment OEMs may furnish and install an approved non-LonWorks controller together with the specified control devices, including all wiring internal to the unitary equipment, including all low-voltage power. The I/O points to be furnished are as described on the plans and specifications including the sequence of operation. The equipment will be delivered to the site ready for termination of field-based control devices. The OEM shall furnish to the Authority a licensed, full-functional copy of the toolset necessary for communication with and the adjustment of their controller. 7 1.06 SUPPLEMENTAL SUBMITTALS A. Product Data 1. NYCSCA Manufacturer’s product data COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 2 01/29/16 B. 8 9 DESIGN NO. _____ 2. Fan Curves 3. Compressor Efficiency Data 4. Gas Fired Unit Efficiency Data 5. Installation Instructions 6. Start-up Instructions 7. Radiated, supply discharge and return inlet computer generated sound power levels Shop Drawings 1. Include with the shop drawings mounting details for securing and flashing roof curb and/or duct penetrations to roof structure. Indicate coordination requirements with roof membrane system. 2. Wiring Diagrams: Submit manufacturer's electrical requirements for power supply wiring to packaged heating and cooling units by the Division 16 electrical contractor. Submit manufacturer's wiring diagrams for interlock and control wiring required for final installation of packaged heating and cooling units and controls. Clearly differentiate between portions of wiring that are factory-installed and portions to be field-installed by the Temperature Controls System Contractor (TCC). 3. Piping Diagrams: Submit manufacturer’s gas piping requirements for fuel supply piping for packaged rooftop units. Submit manufacturer’s diagrams for final installation of package rooftop units. Clearly indicate field tie in points and capacity requirements. 4. Provide gas train shop fabrication drawings. C. Coordination Drawings: Rooftop units to roof-curb mounting details drawn to scale, on which the following items are shown and coordinated with each other, based on input from installers of the items involved: size and location of rooftop unit mounting rails and anchor points and methods for anchoring units to roof curb; required roof penetrations for ducts, pipes, and electrical raceways, including size and location of each penetration. D. Test Reports 1. NYCSCA Manufacturers’ factory test results. COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 3 01/29/16 E. 22 F. DESIGN NO. _____ Certifications 1. Contractor’s start-up and demonstration affidavit. 2. Certification of operability for smoke control systems that are to remain operable following the design earthquake ground motion per Section 13.2.2 of ASCE 7-10. Maintenance Materials 1. 2. 1.07 G. Operation and Maintenance Data to include in emergency, operation, and maintenance manuals; and the maintenance data specified in Section 15501. H. Warranties specified in this Section SUPPLEMENTAL QUALITY ASSURANCE A. Codes and Standards 1. ARI Compliance: Provide capacity ratings for packaged heating and cooling units in accordance with ARI Standard 360: Standard for Commercial and Industrial Unitary Air-Conditioning Equipment. 2. Refrigeration system shall be constructed in accordance with ASHRAE 15-2010: Safety Standard for Refrigeration Systems as modified by Chapter 11 of the 2014 NYC Mechanical Code. 3. Refrigeration equipment shall be listed and labeled to UL 1995-1998. UL listing shall be indicated on the Shop Drawings. 4. 5. NYCSCA Spare Filters Spare Belts Packaged rooftop units shall comply with the EER requirements of the 2014 edition of the New York City Energy Conservation Code, ARI 340/360, and ASHRAE 90.1-2010 as modified by Appendix A of the 2014 NYCECC. All appliances regulated by the New York City Construction Codes shall be listed and labeled (reference Sections MC 301.4 and MC 301.6 of the 2014 NYC Mechanical Code). Testing of material shall be in accordance with Section §28-113 of the NYC Administrative Code (reference Section MC 301.5). Whenever the NYC Construction Codes or the Rules of the Department of Buildings requires that material be listed or labeled and material proposed to be used is not so listed or labeled, the use of such material shall be subject to prior approval by the Commissioner COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 4 01/29/16 DESIGN NO. _____ (Office of Technical Certification and Research OTCR) and such material shall be used only to the extent set forth in such approval. Materials that were previously approved by the Board of Standards and Appeal (BSA) or by the Department (MEA) before the effective date of the NYC Construction Codes may continue to be used, but only to the extent set forth in such approval, and only if such approval is not specifically amended or repealed by the Commissioner. B. 1.08 Before submitting any equipment shop the HVAC Contractor, Automatic Contractor and the Equipment Vendor coordinate the controls required for COORDINATION A. 9 1 Coordinate size, location, and installation of rooftop unit curbs and dunnage supports with roof installer. 1. 1.09 Coordinate installation of restrained vibration isolation and seismic roof-curbs (Reference Section 15503 or 15504). MAINTENANCE A. 1.10 Provide with each unit, one spare set of air filters. Suitable box and label spare as to their usage. Provide also spare belts for belt-driver equipment. WARRANTY A. 24 25 drawings for approval, Temperature Controls and Manufacturer shall the system. 1.11 In addition the warranties specified in Section G01740 and 15501, provide written warranty signed by manufacturer, agreeing to replace/repair motors/compressors that have inadequate and defective materials and workmanship including leakage, breakage, improper assembly, or failure to perform as required, within the warranty period. All warranties shall start at the Date of Substantial Completion. Five-(5) year warranty shall be provided for the refrigeration compressors. All total enthalpy energy recovery wheels shall be warranted for parts and labor by the manufacturer for a period of 60 months. Other components within the rooftop units shall have a two-(2) year warranty. PREVENTATIVE MAINTENANCE A. NYCSCA Provide a two (2) year full preventative maintenance contract on the rooftop unit (RTU) equipment equipped with furnaces and compressors. The two year term shall commence at Substantial Completion of the project or after submission of correctly completed applicable guarantee and warrantee documentation for the units, whichever is later. The Contractor shall perform all maintenance on the COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 5 01/29/16 DESIGN NO. _____ equipment contract. B. NYCSCA until start of the preventative maintenance 1. The firm engaged for the preventative maintenance contract must be authorized by the equipment manufacturer to provide such maintenance. The maintenance work shall be performed by trained personnel directly employed and supervised by manufacturer’s authorized maintenance contractor. 2. The cost of this preventative maintenance contract shall be included in the bid price. 3. This maintenance contract shall be managed administered by the Department of Education (DOE) 4. The preventative maintenance requirements for the specified equipment shall be in accordance with the equipment manufacturer’s preventative maintenance requirements (as defined in the manufacturer’s Installation and Operations Manual) and as specified herein. 5. Perform scheduled maintenance work during regular working hours. All work shall be coordinated with the Custodians Office. and Preventative Maintenance Procedures 1. Preventative maintenance procedures shall follow all safety and O.S.H.A. requirements. 2. The Contractor shall submit for the Designer of Record’s approval a preventative maintenance plan and schedule, conforming to either the equipment manufacturer’s preventative maintenance requirements and schedule or as indicated below, whichever is more rigorous and stringent. All system components requiring preventative maintenance shall be included. The plan shall identify: a. the equipment and manufacturer b. components requiring maintenance c. type and description performed. d. maintenance interval e. maintenance contractor approved by the equipment manufacturer (include certifying documentation by the equipment manufacturer) of maintenance to be COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 6 01/29/16 DESIGN NO. _____ f. component replacement schedule (i.e. belts, bearings, etc.) g. filter replacement schedule h. lubrication schedule i. lubrication types applicable 3. The plan shall include a copy of the equipment manufacturer’s published maintenance requirements and schedule. 4. The costs of all parts requiring periodic replacement (i.e. filters, belts, etc.) are to be included in the preventative maintenance contract. Supply all necessary lubricants, filters, refrigerants, cleaning materials, etc. as required to keep the system in good working order during the preventative maintenance period. 5. Maintenance of equipment and parts shall be either as per the manufacturer’s maintenance requirements and schedule as published in their Installation and Operations Manual or as indicated herein, whichever is more rigorous and stringent. Any preventative maintenance defined in the manufacturer’s Installation and Operations Manual for components not defined below shall be followed and included in the plan. The interval between preventative maintenance visits shall be as defined in the manufacturer’s Installation and Operations Manual, but in no case shall the interval between maintenance visits be greater than three (3) months. a. NYCSCA as RTU – Casing/Cabinet Integrity 1) Inspect for defective access doors, clogged screens. integral dampers, louvers and bird 2) Clean, align and lubricate as required. 3) Replace screws, linkage or latches and patch or replace gaskets. 4) Inspect for broken, loose or missing connections and parts. Correct as required. 5) Inspect for water leaks through rooftop unit enclosure. Seal as required. 6) Inspect for improper setting of outside air, recirculation and exhaust dampers. Correct COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 7 01/29/16 DESIGN NO. _____ as required by cleaning and lubricating pivot points and actuator mechanisms. 7) b. c. NYCSCA Inspect guards, casing, supports, platforms, and mounting bolts. RTU – Filters 1) Replace pre-filters and final filters as per manufacturer’s maintenance schedule, but as a minimum at every 6 months. 2) Check and log filter set. pressure drop across the RTU – Condenser, Supply and Return Fans & Motors 1) Perform maintenance at each visit. Report all findings and non-maintenance deficiencies to the custodian and note in the log. 2) Remove all debris from fan section and unit in general and check all fan safeties including but not limited to thermal overloads and static pressure sensors. Adjust as needed. 3) Visually inspect all fans. Make sure nothing is blocking the fan blades and check for obvious signs of damage. 4) Measure each fan’s flow by measuring the total static pressure change across the fan and measure fan shaft rotation with a tachometer. Use manufacturer’s fan curve to determine the flow based on measured fan speed and pressure change across the fan. 5) Verify that the fan motor amperage is compliant with manufacturer’s fan curves for the measured flow magnitude. Verify that the fan motor is running in the correct direction. 6) Check that the wire leads on the motor have not been switched. Monitor condenser fan cycling. Rapid on-off cycling of a condenser fan (three minutes or less) leads to poor control of the refrigeration system and can wear out the fan motor prematurely. 7) Check the settings on the condenser controller and adjust as required. fan COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 8 01/29/16 DESIGN NO. _____ d. NYCSCA 8) Check for excessive bearing temperatures, noise and vibration indicating inadequate lubrication of bearings and moving parts. 9) Fill all grease dispensers or oil cups at each visit. If fan bearings are sleeve bearings, lightly oil with the recommended lubricant (Do not over lubricate). Follow manufacturer’s lubrication interval and recommended lubricant type. Fans equipped with self-lubricating bearings (sealedcassette ball-bearing cartridges preloaded with grease) are not to be re-greased. 10) Grease any conventional ball bearings. Open the drain plug and inject grease through the fill fitting until clean grease comes out of the drain. 11) Clean fan/impeller blades. 12) Adjust belts to provide proper belt tension. Belts should be aligned with a straightedge to prevent lateral wear. Change belts as required depending on wear. All belts shall be replaced as a minimum at every year upon commencement of the maintenance contract. 13) Check fan vibration isolators. RTU - Refrigeration Cycle 1) Clean condenser coils at each visit. Power Wash with a cleaning solution in a highpressure water spray. (Spray-on cleaning solutions that are intended to be used with a brush and a hose are not adequate for condenser coils, even though they may brighten the outer surface.) 2) Clean evaporator coils at each visit. Clean/Brush with a quality cleaning solution allowing an appropriate dwell time necessary to effectively remove all microorganisms/ biofilms. The entire air flow path shall be treated with a germicide once it is cleaned to assure the unit remains free of microorganisms between cleanings. Check condensate drain piping (multiple connections) and verify condensate drain pans are clean. Log each coil air temperature change and each coil air pressure drop. COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 9 01/29/16 DESIGN NO. _____ 3) e. f. NYCSCA Check compressor. Check crank case heater operation and compressor oil level. Check expansion valves. Check positive pressure forced lubrication system. Check hot gas reheating coil with diverting modulating valves. Check high limit thermostat condition settings. Check refrigerant gas pressure. If below recommended level, add refrigerant of same type to the correct level. Check hot gas bypass controls. Log each coil air temperature change and each coil air pressure drop. Check compressor vibration isolators. Report all findings and non-maintenance deficiencies to the custodian and include in the maintenance log. RTU - Furnace 1) Perform during each maintenance visit. 2) Check gas piping connections. Verify secure connectivity & supports. Check gas pressure. 3) Check ignition control and burner operation sequence. Check and calibrate safety controls. Check power supply and tighten all electrical connections. Check air intake hoods and (screens). Check forced or induced draft blower/ motor assembly. Check spark detector. Inspect heat exchanger surfaces. Report all findings and non-maintenance deficiencies to the custodian and include in the maintenance log. RTU – Integral Smoke Detector/Smoke Damper/Fire Damper 1) Perform a minimum of twice a year. 2) Check and make sure smoke detectors and dampers are functioning properly in the RTU. Check smoke detectors with magnet or smoke can. Check dampers close upon activation from the Fire Alarm Control Panel. Report all findings and non-maintenance deficiencies to the custodian and include in the maintenance log. COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 10 01/29/16 DESIGN NO. _____ g. RTU – Piping 1) h. i. Inspect for corrosion at each visit and report all findings and non-maintenance deficiencies to the custodian and include in the maintenance log. RTU – Wiring/Power 1) Inspect for wiring and electrical defects at each visit. Inspect for loose connections; charred, frayed, broken, or wet insulation; short circuits; lose or weak contact springs; worn or pitted contacts; and other deficiencies. 2) Adjust settings; tighten connections; clean contacts and adjust alignment. 3) Inspect and test all power supplies. Record all voltage readings. Check all relays and terminal connections. Clean/wipe down panel face. Check variable frequency drives on units. 4) Variable Frequency Drives (VFD): Check integral cooling fan for functionality. Clean air inlet filter. Vacuum off dust from printed circuit boards. 5) Report all findings and non-maintenance deficiencies to the custodian and include in the maintenance log. RTU – Integral OEM Provided Sensors Check sensor calibration at each visit and recalibrate if necessary. NYCSCA maintenance 6. During each preventative maintenance visit and in addition to the preventative maintenance recommended by the equipment manufacturer, the qualified technician shall also activate and inspect all components of the equipment for wear, leaks, condition, operation, and report findings in the log and directly to the custodian. 7. During each preventative maintenance visit, the maintenance technician shall make all necessary adjustments as necessary to meet the performance requirements as specified in the manufacturer’s Installation and Operation Manual. COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 11 01/29/16 DESIGN NO. _____ C. The preventative maintenance contractor shall advise the custodian of every preventative maintenance visit, including any material that was used, as well as any deficiencies noted in the system. 1. 2. D. The technician shall maintain a visit log(s) indicating, for each unit covered under the maintenance contract, the following: a. date of visit b. the unit (name/location etc.) c. component(s) receiving the maintenance d. maintenance performed e. lubrication performed f. parts and filters replaced g. condition and operability of all components h. date of next required maintenance i. deficiencies noted and reported to the custodian. Copies of log(s) shall be kept in the custodian’s office. The originals shall be maintained by the maintenance contractor until the expiration date of the maintenance contract at which time the originals shall be turned over to the custodian. End of the Preventative Maintenance Contract Approximately three (3) months prior to the end of the maintenance contract term, the DOE and the preventative maintenance contractor shall make a thorough inspection of all rooftop unit equipment covered under the Contract. At the conclusion of this inspection, the DOE will give the preventative maintenance contractor written notice of any maintenance deficiencies for which the maintenance contractor was responsible. The preventative maintenance contractor shall be responsible for correction of these maintenance deficiencies within 30 days after receipt of such notice. Other than the referenced walk through prior to the end of preventative maintenance period, the DOE may conduct inspections during the 2-year preventative maintenance period and the preventative maintenance Contractor shall comply and clear any maintenance deficiencies found within 30 days after receipt of such notice. NYCSCA COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 12 01/29/16 DESIGN NO. _____ PART 2 - PRODUCTS 2.01 GENERAL A. 3 2.02 Provide rooftop air conditioners with gas fired heating, air-cooled, direct expansion refrigeration for cooling. Units shall be weatherproof and designed for outside mounting on a roof. Units shall supply the conditioned air and return the required air as shown on the Drawings. Condenser fan/coil section shall be designed with vertical discharge for minimum sound levels. COMMERCIAL ROOFTOP UNITS A. 2 12 24 B. Roof top unit gas fired heating and electric cooling: Factory assembled, piped, internally wired, fully charged and factory tested; designed for exterior installation; consisting of compressor, indoor and outside refrigerant coils, R-407C or R-410A refrigerant charge, supply fan, exhaust fan, outside coil fan, gas burner, electronic refrigeration, operating controls, filters, and dampers. Article 1.05 above describes the various options regarding how the controllers may be furnished and installed. Equipment manufacturer has the responsibility of verifying and providing the environmental conditions that the controllers must operate under. The equipment manufacturer shall provide auxiliary heating/cooling for the control panel enclosure and/or vestibule if required to guarantee that the required controller operating environmental conditions are provided during all occupied and unoccupied cycles when the equipment cycles intermittently to meet the setback/setup conditions. Casing: Galvanized-steel construction with enamel paint finish, removable panels or access doors with neoprene gaskets for inspection and access to internal parts, 1/2” minimum thermal insulation thickness, knockouts for electrical and piping connections, exterior condensate drain connection, and lifting lugs. All gas piping and electric power shall enter the unit cabinet at a single location. For units greater than 20 tons, provide doublewall galvanized sheet metal construction with minimum 1” thick thermal insulation, with perforated-metal liner. Thermal insulation may be a fiber-free polyamide open cell foam or fiberglass. If fiberglass lining is used, it shall be covered with a matte-faced neoprene covering and sealed with an acrylic polymer. Surface burning characteristics shall have a flame spread index less than 25 and smoke developed index less than 50 per ASTM E84. Lining shall be secured with pins or mechanical fasteners. Lining that is secured with adhesive only is not acceptable. Fiberglass lining shall conform to the erosion test method described NYCSCA COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 13 01/29/16 DESIGN NO. _____ in UL Publication No. 181. The fiberglass lining shall not support fungi or bacterial growth as per ASTM C1338, ASTM G21, and ASTM G22. Double walled units may be provided with rigid fiberglass boards that shall not erode. C. 1. 19 D. 5 Supply and Exhaust Fans: Forward curved, centrifugal, belt driven with adjustable motor sheaves, grease-lubricated ball bearings and motor. Smoke Control a. Per Section MC 513.10 equipment utilized in Smoke Control systems such as fans and automatic dampers shall be suitable for their intended use, suitable for the probable exposure temperatures and shall be as approved by the Commissioner. Fans shall be rated and certified by the manufacturer for the probable temperature rise to which the components will be exposed. This temperature rise is _______. Per Section BC 909.4.6 of the 2014 NYC Building Code, all portions of active smoke control systems shall be capable of continued operation after detection of the fire event for not less than 20 minutes or 1.5 times the calculated egress time, whichever is more. b. Per Section BC 909.10.6, Seismic Requirements, smoke control systems covered by Section BC 909 are life safety systems and are required to function after an earthquake. Such smoke control systems shall be seismically designed in accordance with Section BC 1613 and Section 13.2.2 of ASCE 7-10. The component importance factor, Ip, shall be taken as 1.5 in accordance with ASCE 7-10, Section 13.1.3. The smoke control system includes all components required for its operation. Smoke control systems in structures classified in Seismic Design Categories A or B shall have a component importance factor, Ip, of 1.0. Outside Coil Fan: Propeller permanently lubricated motor. type, directly driven by 16 E. Refrigerant Coils: Aluminum-plate fin and seamless copper tube in steel casing with equalizing-type vertical distributor. Provide corrosion-protection coating to both coils. F. Compressor: Hermetic reciprocating or scroll compressor (15 HP max - number as required to avoid the need for refrigeration operator’s license as per NYC Fire Department Code) with integral vibration isolators, internal overcurrent, overtemperature protection, internal pressure 6 NYCSCA COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 14 01/29/16 DESIGN NO. _____ relief and crankcase heater. Provide label in compressor section indicating rated horsepower and kilowatt equivalent for each compressor. G. Refrigerant System: Compressor(s); Outside coil and fan; Inside coil and fan; Expansion valves with replaceable thermostatic elements; Refrigerant dryers; High-pressure switches; Low-pressure switches; Thermostats or sensors for coil freeze-up protection during low-ambient temperature operation or loss of air; Brass service valves installed in discharge and liquid lines; Hot-gas bypass: factoryinstalled capacity modulating valves; Timed off control: automatic-reset control shuts compressor off after five minutes. The lead compressor shall have hot gas bypass control for additional capacity control in addition to compressor unloading or staging. Hot gas bypass capacity control shall use suction pressure controlled discharge bypass valve and isolation ball valve. The hot gas discharge bypass valves shall be Siemens M3FB LX Series or equal. Hot gas discharge bypass valve shall be normally closed, so that in the event of the failure of the valve, no hot gas bypass capacity modulation will be available. A spring shall close the bypass valves if power is switched off or fails. The hot gas bypass shall be limited according Article 6.5.9 of ASHRAE 90.1-10 and Section C403.4.7 of the 2014 NYCECC. Per Section MC 1101.1,2 refrigerant circuit access ports located outdoors shall be fitted with locking-type tamper-resistant caps requiring a special tool or key to open. H. Filters: Per Section MC 605, the filter section shall include a minimum efficiency MERV 11 filter. Provide filter for the outside air intake upstream of the total enthalpy wheel. Provide filter on the return side upstream of the total enthalpy wheel, upstream of the recirculation port. Filters shall be selected for a velocity not to exceed 500 fpm. Filters shall be listed and labeled per UL 900-2004. 24 I. NYCSCA Heat Exchanger: Aluminized-steel construction for natural gas-fired burners with the following controls: redundant dual gas valve with manual shutoff, spark-ignited intermittent safety pilot(1) ignition, electronic flame sensor, induced-draft blower and flame rollout switch. Gas Heater Module shall be in accordance with UL 795 or ANSI Z21.47 per Section FGC 618.1 of the NYC Fuel Gas Code. All burner operating and safety controls shall be provided by the rooftop unit manufacturer. Provide gas train in accordance with the guidelines of GE Global Asset Protection Services (formerly IRI). Provide internal gas pressure regulators. Provide manual reset high gas pressure switches and automatic reset low gas pressure switches. The vent piping for any normally open vent valves (if required by the GE GAP Guidelines) shall be 1” minimum diameter, standard weight schedule 40 black steel pipe. COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 15 01/29/16 21 DESIGN NO. _____ The vent piping for any normally open vent valves shall be caulked where it penetrates the unit exterior skin and shall be equipped with a utility approved weatherproof cap that has an insect resistant screen. Any normally open vent valve vents shall terminate at least 10’ away from any outside air intake openings. The furnace exhaust shall terminate at least 10’ away from any outside air intake openings. When the distance from the outside air intake port to any normally open vent valve terminal or to the furnace exhaust is less than 10’, the normally open vent valve vent terminal (if any) and the top of the furnace exhaust shall be terminated at least 3’ above the top of the outside air intake port per Section FGC 618.5. If the entire length of any normally open vent valve line can not be shipped as an integral part of the roof top unit assembly, the roof top unit manufacturer shall provide a supported capped line for subsequent field continuation by the plumber. (1) Provide pilot for burners with nominal capacity exceeding 400 MBH. For burners with nominal capacity equal to and less than 400 MBH, direct spark ignition may be provided. Provide a cool down cycle in the control system that allows air handler fan to operate for at least two (2) minutes after gas burner shut-down to dissipate residual heat. The unit manufacturer factory engineer shall supervise final adjustments. The unit manufacturer shall also provide technical support from the burner manufacturer at startup of the unit for supervision. Normally open vent valves, if required by the GE GAP Guidelines, shall be piped separately and directly to the outside of the enclosure. A UL listed valve proving system may be substituted for the normally open vent valve (when a normally open vent valve is otherwise required by the GE GAP Guidelines). The valve proving system shall be wired to operate on a call for startup locking out the burner prior to pilot ignition and/or after burner shutdown if an internal gas valve leak is detected. Wiring diagrams of the valve proving system shall be included with the burner submittal package. The following valve proving systems may be utilized: Karl Dungs model# VDK 200a/CM100 pressure module and control relay Siemens model# LDU11, LMV, WFM, LFL/LAL/LFE/LME valve pressure proving systems Honeywell RM7800L, RM7840L integral valve pressure proving system NYCSCA COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 16 01/29/16 DESIGN NO. _____ Per Section FGC 403.9.3, joints and connections shall be approved and of a type approved for natural gas piping systems. All threaded joints and connections shall be made tight with suitable lubricant or pipe compound. Pipe joint compounds and thread seal tape that utilize Teflon (PTFE) shall be approved for usage on natural gas lines. Provide gas train shop fabrication drawings when the units are delivered to the site. All gas train component parts shall be identified by manufacturer and by part number. Product data/cuts shall be submitted for all gas train component parts. Provide gas trains in accordance with the guidelines of GE Global Asset Protection Services (formerly IRI). Fabrication drawings shall illustrate (at a minimum) all regulators, modulating gas valves, safety shutoff valve(s), any normally open vent valves, high and low gas pressure switches and manual isolation valves. All details for any hard piped normally open vent valve venting shall be shown including pipe diameters, pipe materials and pipe routing. The gas train shall be complete and field ready for a singular connection to a natural gas supply with inlet gas pressure between 7" and 13.5" maximum W.C. J. Economizer: Provide recirculation and outside-air dampers with neoprene seals. Provide hood for outside air intake port. 1. Damper Motor: Provide outside air intake and recirculation dampers with fully modulating spring return with adjustable minimum position. 2. Control: Electronic-control system uses relative outside-air to return air enthalpy to determine economizer cycle. 3. Exhaust Damper: Provide two position power actuated with bird screen and hood. Provide air flow monitoring stations for intake, exhaust air and total supply air. 8 NYCSCA outside air Outside air, recirculation air, and exhaust air dampers shall have factory mounted fast acting spring return Belimo or approved equal, damper actuators. Outside air intake dampers and exhaust dampers shall be normally closed. Recirculation air damper shall be normally open. Outside air intake dampers and spill exhaust dampers shall close when the fans stop. Motorized dampers shall be Class 1 low leakage type, limiting leakage to 4 CFM/ft2 at a pressure differential of 1” when tested in accordance with AMCA 500D. COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 17 01/29/16 DESIGN NO. _____ K. Power Connection: Provide for single connection of power to unit with unit-mounted disconnect switch accessible from outside unit and control-circuit transformer with built-in circuit breaker. All unit power wiring shall enter the unit cabinet at a single location. L. The unit control system shall include all required temperature and pressure sensors, input/output boards, transformers, main microprocessor and Human Machine Interface (HMI) operator interface and shall perform all unit control function and safeties. Microprocessor based control system shall contain at least the following: 1. Supply fan on/off delay. 2. Default control to ensure proper operation after power interruption. 3. Service relay output. 4. Unit diagnostics and diagnostic code storage. 5. Field-adjustable control parameters. 6. Economizer control. 7. Gas valve delay between stage firing. 8. Low-ambient control, allowing operation down to 0°F. 9. Minimum run time. 10. 7-Day scheduling for occupied/un-occupied with Night setback mode. 11. Return-air temperature limit. 12. Low-refrigerant pressure control. control, 13. Human Machine Interface (HMI) digital display of outside temperature, supply-air temperature, returnair temperature, economizer damper position, CO2 24 indoor-air quality, and control parameters. NYCSCA 14. Thermostat or sensor: Programmable, digital electronic; with heating/cooling setback and setup respectively. OEM shall furnish and the Temperature Controls Contractor (TCC) shall install all field sensors/controllers. 15. Touch sensitive keyboard. 16. Automatic switching between heating and cooling. 17. Temperature readout. COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 18 01/29/16 DESIGN NO. _____ 18. LED indicators. 19. Hour/day programming. 20. Manual override capability. 21. Time and operational mode readout. 22. Status indicator (heat/cool). 23. Seventy two (72) hours battery backup. 24. System switch (on-heat-auto-cool) (auto-on). See item 28 below. 25. Fan proving to lock out unit if fan fails. 26. Dirty-filter Indication. 27. Loss of charge protection. and fan switch 28. OEM shall provide a furnace control Hand-Off-Auto toggle selector switch. In the “Auto” position, the furnace shall be controlled as defined in Section 15985 Sequence of Operation. In the “Off” position, the furnace shall be disabled. In the “Hand” position, the units’ DDC furnace operating controls shall be overridden and the furnace started and ramped up to the full heat output capacity. In all modes, the furnace operation shall be subject to all safety devices including but not limited to the manufacturer's high temperature cut-out safety and a unit airflow proving switch. Field controls (space thermostats or sensors, outside temperature thermostats or sensors, etc.) shall be furnished by OEM and field installed by Temperature Controls Contractor. DDC Controllers to be mounted in the rooftop unit (to accomplish the specified sequence of operation as defined in Section 15985) shall be furnished and installed by the OEM unit manufacturer. DDC Controllers shall be factory programmed/configured. DDC controllers shall be field commissioned by the OEM or OEM’s authorized field representative. The OEM or OEM’s authorized field representative shall provide all system passwords for system configuration and programming to the Department of Education on CD media. Two (2) copies of all system control data shall be provided; one maintained on site by the local school custodian and an additional copy for off-site storage by the Department of Education. For all proprietary manufacturer’s controllers providing safety interlocking, compressor staging, condenser fan operation, gas heat modulation, DX cooling reset and other NYCSCA COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 19 01/29/16 7 M. 9 N. 15 O. DESIGN NO. _____ internal control functions, a communications gateway shall be available (but not provided) to interface the manufacturer’s control system to a possible future LonWorks specified BMS/DDC network control system, as required. Accessories: 1. Cold-Weather Kit: Electric heater temperature in gas burner compartment. maintains 2. Condensate drain trap. 3. Hail guards of steel, painted to match casing 4. Vertical vent extension Roof Curb: Steel with corrosion-protection coating, gasketing, and factory-installed wood nailer; complying with NRCA standards; height as required by the manufacturer. Curbs shall be compliant with those defined in Section 15503. Approved Manufacturers Carrier Corp. McQuay International Trane YORK International Corporation. P. The maximum follows: Center Frequency (Hz) Band Designation 4 radiated sound power levels shall be as 63 125 250 500 1000 2000 4000 8000 1 2 3 4 5 6 7 8 DB The maximum supply discharge sound power levels shall be as follows: Center Frequency (Hz) Band Designation 4 63 125 250 500 1000 2000 4000 8000 1 2 3 4 5 6 7 8 DB NYCSCA COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 20 01/29/16 DESIGN NO. _____ The maximum return inlet sound power levels shall be as follows: Center Frequency (Hz) Band Designation 4 63 125 250 500 1000 2000 4000 8000 1 2 3 4 5 6 7 8 DB Q. Fire Alarm Interface Requirements: The packaged rooftop unit shall have UL 268A (per Section MC 606.1) manual reset listed type smoke detectors factory mounted and wired in the supply and return openings to the unit as required by the NYC Construction Codes and NYC Electrical Code. Upon detection of smoke, a signal shall be sent to the building fire alarm system and the fans shall stop. Installing Mechanical Contractor shall coordinate this interlock with the Division 16 Fire Alarm Contractor. Division 16 Fire Alarm Contractor shall furnish fire alarm system compliant photoelectric smoke detectors to the Mechanical Contractor who shall in turn furnish them to the rooftop unit manufacturer for factory installation. Detectors shall be rated from -4°F to 158°F and 100 fpm to 4,000 fpm and shall be furnished with a weatherized housing to prevent condensation from humidity. The packaged rooftop unit shall have terminal strips and interlocking relays factory mounted and wired to interlock with other components of the building. It is the responsibility of the installing contractor to advise the manufacturer of requirements for additional interlocks not covered in this specification. Smoke Dampers for Units of 15,000 CFM and Greater Capacity: NYCSCA 1. Each air conditioning unit of 15,000 CFM and greater capacity shall be factory provided with two-position smoke dampers installed in the unit supply discharge and in the return air stream immediately upstream of the return air modulating control damper. Smoke dampers shall be (NC) normally closed in the event of a power loss and shall close in response to activation of the fire alarm control panel. The fans shall not be permitted to start by the fire alarm control panel until the fire alarm panel has enabled the fan safety interlock motor starter circuit. 2. Smoke dampers shall meet or exceed the following specifications. Frame shall be a minimum of 12 gauge galvanized steel formed into a structural hat channel shape with tabbed corners, for reinforcement. Bearings shall be stainless steel sleeve turning in an extruded hole in the frame. The blades shall be COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 21 01/29/16 DESIGN NO. _____ aluminum airfoil shaped 0.080” minimum thickness double skin construction with internal structural support. Blade edge seals shall be silicone rubber, mechanically locked into the blade edge, designed to withstand minimum 250°F (per Section MC 513.5.2.1) and jamb seal shall be stainless steel flexible metal compression type. Blade action shall be parallel blade. Each smoke damper shall be classified by Underwriters Laboratory as a leakage rated damper for use in smoke control systems under the latest version (Rev. 4 or later) of UL555S and shall be minimum leakage Class II per Section MC 513.5.2.1. R. 3. The smoke dampers and their operator shall be qualified under UL555S (Rev 4 or later) to a minimum elevated temperature of 250°F per Section MC 513.5.2.1. Appropriate 120V electric operators shall be installed by the damper manufacturer at the time of damper fabrication. Damper and operator shall be supplied as a single entity which meets all applicable UL555S qualifications for both dampers and operators. Damper and operator assembly shall be factory cycled 10 times to assure operation. All wiring material required to interconnect the operator with the fire alarm control panel shall be provided as specified under Division 16, Electrical. Damper shall be Ruskin Model SD102 or approved equal. 4. Blade Position Indicators: Each smoke damper shall be equipped with Ruskin SP100 switch package or equal. The switch package shall include two position indicator switches linked directly to the damper blade to provide the capability of remotely indicating damper blade position (through the Fire Alarm System). 5. Electric operator shall be provided with damper by damper manufacturer and shall be UL listed as an assembly. Smoke damper operators shall be slow acting upon damper closure, with 60 second (adjustable) closure duration. Damper operators shall be model SQB12.1, as manufactured by Siemens Landis Division, or approved equal. Variable Frequency Manufacturer) 1. NYCSCA Drive (Provided by the Rooftop Unit Provide Variable Frequency Drive (VFD) for variable volume units. Also, provide Variable Frequency Drive (VFD) for constant volume units to aid in the balancing process. Packaged rooftop unit fan motors shall be provided with solid state variable frequency drives to convert three phase, 60 hertz power to adjustable frequency and voltage three phase power for COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 22 01/29/16 DESIGN NO. _____ step-less motor speed control from 0% to 100% of base speed. Input voltage shall be 460-3-60 or 208-3-60 as available. The VFD shall be capable of operating within the range of 10% over to 10% under the rated input voltage. The VFD shall be designed for use on variable torque loads and shall be capable of providing sufficient torque to start motor from rest with initial influx of power. The VFD operation shall be fully factory tested by the drive manufacturer prior to shipment and installation. The VFD controller shall have the following features: isolated power for control circuits, automatic type reset faults for over-current, under-voltage, over-voltage, phase loss or over-temperature, fault counter reset, adjustable current limiting circuitry, independent acceleration and deceleration time adjustment, 4-20 mA control signal interface, 0-10 Vdc output signal, and automatic frequency adjustment. VFD shall be provided with digital read output meter indicating percent speed and load, local/remote selector switch, power/on, diagnostic, and fault trip indicating lights, Hand/Off/Auto selector switch, manual by-pass switch, by-pass starter, and manual speed control adjustment. The complete drive shall be tested to ANSI C37.90.1 and UL Standard 508 and be ETL or UL listed. Power line noise distortion shall be limited to voltage distortion factor and line notch depth defined in IEEE Standard 519-1981. Total voltage distortion shall not exceed 5%. VFD shall be provided with two normally open and two normally closed dry contacts rated at 120 volts, 10 amps, 60 Hz for remote indication of the following: controller shutdown with automatic restart, system shutdown with automatic restart, and system running condition. Controller shall include a door interlock fused safety disconnect or circuit breaker that will disconnect all input power. The VFD supply and exhaust fan package shall be selected with inverted rated duty motors and motor winding insulation complying with IEC Part 34.17. 2. Variable Frequency Drive (VFD) LonWorks Card The VFD drive for variable speed fan shall be able to be provided with a LonWorks interface card to provide the LonTalk open protocol (ANSI approved standard EIA/CEA-709.1-A-1999) for control communications with “plug & play” capabilities for a possible future LonWorks BMS/DDC network. The LonWorks interface card need not be provided as part of the CIP project. Hand/Off/Auto functionality shall be built into the VFD digital operator keypad for operation from remote NYCSCA COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 23 01/29/16 DESIGN NO. _____ (Auto) or local (Hand) signals. A copy function shall be provided for set-up parameters when programming multiple drives. Factory “default” parameters shall be user selectable for typical fan applications and shall be able to be field refined for custom applications. The VFD shall be provided with a PI controller that shall maintain setpoint for control of the fans based on pressure, flow or temperature regulation. 3. Acceptable Manufacturers Yaskawa Asea Brown Boveri (ABB) Siemens Danfoss Vacon GE Fuji Square D Or approved equal 24 S. Total Enthalpy Wheel Heat Exchanger 1. NYCSCA Wheel Matrix: Rotor shall be constructed of rotating honeycomb matrix consisting of a highly selective desiccant permanently bonded to aluminum (with prototype performance tested in accordance with ASHRAE Standard 84-91 and ARI Standards 1060-01). Moisture as well as sensible energy shall be transferred between the two airstreams. The desiccant material shall be a molecular sieve with pore diameter of 3A to minimize the carryover of undesirable gases. Corrugated media shall provide individual flutes to channel the airflow and thus minimize cross contamination and ensure rated performance under all differential pressure conditions. The desiccant coating shall provide corrosion resistance against attack from laboratory chemicals, etc. and protection in coastal and marine environments. Wheel rotor media that is 72” diameter or smaller can be either segmented or single piece construction. Wheel rotor media larger than 72” diameter shall be segmented. If segmented, each segment shall consist of media supported by spokes and tensioned in place by the rim. Wheels shall have a flatness of + 1/32”. No adhesives or silicone shall be necessary to secure the media in place in order to allow for future replacement in the event of damage to a segment. The structural frame, casing and rotor shall be designed and manufactured so as to allow a maximum rotor deflection of 1/32”, as measured at the outer radius, during maximum rated airflow conditions. The media shall have a flame spread of 0 and a smoke developed of 5 or less when rated in accordance with ASTM E84-07. COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 24 01/29/16 DESIGN NO. _____ 2. Wheel Casing: The wheel frames shall consist of evenly spaced extruded aluminum or corrosion resistant polyurethane coated galvanized steel or epoxy painted heavy duty structural steel spokes, extruded aluminum or corrosion resistant polyurethane coated galvanized steel or epoxy painted heavy duty structural steel outer band, and a rigid center hub. The wheel construction shall allow for wheel alignment. The wheel seals shall be easily adjustable. Seals shall be included to separate fresh air from exhaust air across entire surface of air entering side, air leaving side and outer band (all four planes). Additionally, the entire circumference of the rotor shall include seal to minimize air bypass. The case construction shall be aluminum or corrosion resistant polyurethane coated galvanized steel or epoxy painted heavy duty structural steel. Bearings shall be outboard-flanged ball bearing with concentric locking collars or tapered roller bearings with double setscrew locking collars. Bearings shall be provided with easily accessible grease fittings for maintenance. Bearings shall provide a minimum L-10 life of 100,000 hours of operation. Sealed bearings are also acceptable. Drive system shall consist of a belt driven heavy-duty inverter rated AC motor. The drive system shall have a minimum life expectancy of 50,000 hours. The speed control system shall be a variable frequency drive (VFD) capable of operating the rotor from nominally 1/4 RPM to 20 RPM or to the required speed for the type of media used. The OEM controller for the drive system shall be integrated with the temperature control system to provide the required dry and wet bulb temperatures. The OEM temperature controller shall monitor entering and leaving temperatures for the exhaust and supply air. Adjustable set points shall be provided for wheel frost control. 3. Energy wheel shall be arranged within the heat recovery system so as to minimize differential pressure while keeping the exhaust side negative in comparison to fresh air side. The wheel shall have the thickness required to achieve at least a nominal 75% effectivity and shall have a pressure drop not exceeding that as indicated on the Drawings. 4. Wheel Accessories: a. NYCSCA OEM controls and factory set (but field adjustable) purge system shall be provided to remove exhaust air from the depth of the wheel as it revolves from exhaust to outside air. The purge system shall be provided to eliminate transfer of exhaust air into the supply air. COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 25 01/29/16 DESIGN NO. _____ 5. b. Provide rotation detector, wheel RPM readout and wheel stoppage alarm contacts. c. Provide variable speed drive. The wheel will stop rotation in the economizer mode and modulate in the frost control mode. Wheel shall run full speed in the occupied cooling mode and occupied heating mode. Wheel shall be deactivated while the unit is running in the morning warm up, preoccupied pull down, pre-occupied purge and unoccupied modes when the wheel is bypassed by the recirculation dampers. Maintenance: a. 6. The entire rotor and wheel assembly shall require only limited maintenance and shall be manufactured not to require more than biannual greasing of the main bearings and inspection of the drive system. Manufacturers a. Subject to compliance with requirements, provide enthalpy wheel heat exchangers from one of the following manufacturers (or equal). “Equal” indicates that all capacities, dimensions, weights, materials, and performance criteria are equal or better than that described herein. Thermotech Enterprises TC-Series Thermowheel Des Champs Thermo-Wheel AIRotor Innergy Tech ERW3000 PART 3 - EXECUTION 3.01 INSTALLATION A. Install packaged heating and cooling units in accordance with manufacturer's installation instructions. Install units plumb and level, firmly anchored in locations indicated, and maintain manufacturer's recommended clearances. 1. 9 NYCSCA The roof curb shall be designed to mate with the unit and provide support and a watertight installation when installed properly. The roof curb design shall allow field-fabricated rectangular supply/return ductwork to be connected directly to the curb. Curb design shall comply with NRCA requirements. Curb shall be shipped knocked down for field assembly and shall include wood nailer strips. COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 26 01/29/16 DESIGN NO. _____ B. Electrical Wiring: The Division 16 Electrical Contractor shall install electrical devices furnished by manufacturer but not specified to be factory-mounted. Furnish copy of manufacturer's wiring diagram submittal to Electrical. 1. Verify that electrical wiring installation is in accordance with manufacturer's submittal and installation requirements of Division-16 Sections. Do not proceed with equipment start-up until wiring installation is acceptable. C. Ductwork: Refer to Section 15891: Metal Ductwork. Connect supply and return ducts to unit with flexible duct connections. Provide transitions to exactly match unit duct connection size. D. Gas Piping: Connect gas supply piping to unit as indicated on the drawings with unions and shutoff valves. E. Drain Piping: Connect primary unit drain to splash block. Provide trap at primary drain pan; construct primary pan at least 1" deeper than fan pressure in inches of water. 17 F. For curb mounted units, per Section MC 307.2.3, Mechanical Contractor or manufacturer shall provide a [primary pan overflow drain line] [auxiliary drain pan and associated drain line] as shown on the Drawings for each DX evaporator coil (when the unit is curb mounted, not dunnage mounted) to avoid damage to any building component as a result of overflow from the primary equipment drain pan or stoppage in the primary condensate drain piping. One of the following methods shall be used: 18 17 17 NYCSCA 1. Mechanical Contractor shall coordinate with sheet metal subcontractor to provide (or manufacturer shall provide) an auxiliary drain pan as shown on the Drawings with a separate drain under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal (as shown on the Drawings) to alert occupants in the event of a stoppage of the primary drain. The auxiliary pan shall have a minimum depth of 1.5”, shall not be less than 3” larger than the unit or the coil dimensions in width and length and shall be constructed of corrosion-resistant material. Auxiliary metallic pans shall have a minimum thickness of 0.0236” (No. 24 gage) for galvanized sheet metal pans, .0179” (No. 26 gage) for stainless steel pans, or 0.0320” (No. 20 gage) for aluminum pans. Nonmetallic pans shall have a minimum thickness of not less than 0.0625” or 1. Mechanical Contractor (or manufacturer) shall provide a separate overflow drain line connected to the primary drain pan provided with the equipment. Such COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 27 01/29/16 DESIGN NO. _____ overflow drain shall discharge to a conspicuous point of disposal (as shown on the Drawings) to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the primary drain pan at a higher level than the primary drain connection or 2. Alternate Acceptable Installation: Mechanical Contractor shall coordinate with sheet metal subcontractor to provide (or manufacturer shall provide) an auxiliary drain pan without a separate drain line under the coils on which condensate will occur. Mechanical Contractor shall coordinate with the Temperature Controls subcontractor to provide (or manufacturer shall provide) a hard-wired water-level detection device for the auxiliary pan that will shut off the equipment served prior to overflow of the auxiliary pan. The auxiliary pan shall have a minimum depth of 1.5”, shall not be less than 3” larger than the unit or the coil dimensions in width and length and shall be constructed of corrosion-resistant material. Auxiliary metallic pans shall have a minimum thickness of 0.0236” (No. 24 gage) for galvanized sheet metal pans, .0179” (No. 26 gage) for stainless steel pans, or 0.0320” (No. 20 gage) for aluminum pans. Nonmetallic pans shall have a minimum thickness of not less than 0.0625” or 17 2. Alternate Acceptable Installation per Section MC 307.2.3.1 water-level monitoring devices: On downflow units and all other coils that do not have a secondary drain or provisions to install a secondary or auxiliary drain pan, a water-level monitoring device shall be installed by the Mechanical Contractor or Temperature Controls Contractor inside the primary drain pan. This device shall shut off the equipment served in the event that the primary drain becomes restricted. Devices installed in the drain line shall not be permitted. 17 3.02 SIGNS, NAMEPLATES INSTRUCTIONS A. NYCSCA AND OPERATION AND EMERGENCY SHUTDOWN Signs, nameplates, and operation and emergency shutdown instructions for refrigeration systems shall comply with the following (per Section MC 1101.11): 1. Sections 9.15, 11.2.1, 11.2.2 and 11.7 of ASHRAE 15-10 as identified below. 2. Each refrigeration unit or system shall be provided with a nameplate indicating the “rated” horsepower of the prime mover or compressor and the equivalent of such horsepower in kilowatts. COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 28 01/29/16 DESIGN NO. _____ 3. Section MC 1105.11 which states that emergency signs shall comply with the following: a. B. Refrigeration units or systems having a refrigerant circuit containing more than 220 pounds of Group A1 or 30 pounds of any other group refrigerant shall be provided with approved emergency signs, charts, and labels in accordance with NFPA 704. Per ASHRAE 15-10, Section 9.15: Nameplate: Each unit system and each separate condensing unit, compressor, or compressor unit sold for field assembly in a refrigerating system shall carry a nameplate marked with the manufacturer’s name, nationally registered trademark or trade name, identification number, the design pressures, and the refrigerant for which it is designed by the refrigerant number (R number as shown in Table 1 or Table 2 of ASHRAE 34-10). C. Per ASHRAE 15-10, Section 11.2.1: Installation Identification: Each refrigerating system erected on the premises shall be provided with a legible permanent sign, securely attached and easily accessible, indicating (a) the name and address of the installer, (b) the refrigerant number and amount of refrigerant, (c) the lubricant identity and amount, and (d) the field test pressure applied. D. Per ASHRAE 15-10, Section 11.2.2: Controls and Piping Identification: Systems containing more than 110 lb (50 kg) of refrigerant shall be provided with durable signs having letters not less than 0.5 in. in height designating: (a) valves or switches for controlling the refrigerant flow, the ventilation, and the refrigeration compressor(s), and (b) the kind of refrigerant or secondary coolant contained in exposed piping outside the machinery room. Valves or piping adjacent to valves shall be identified in accordance with ANSI A13.1, Scheme for Identification of Piping Systems. E. Per ASHRAE 15-10, Section 11.7: Responsibility for Operation and Emergency Shutdown: For a refrigerating system containing more than 55 lb (25 kg) of refrigerant, provide a schematic drawing or panel giving directions for the operation of the system at a location that is convenient to the operators of the equipment. Emergency shutdown procedures, including precautions to be observed in case of a breakdown or leak, shall be displayed on a conspicuous card located as near as possible to the NYCSCA COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 29 01/29/16 DESIGN NO. _____ refrigerant compressor. These precautions shall address (a) instructions for shutting down the system in case of emergency; (b) the name, address, and day and night telephone numbers for obtaining service; and (c) the names, addresses, and telephone numbers of all corporate, local, state, and federal agencies to be contacted as required in the event of a reportable incident. 3.03 FIELD QUALITY CONTROL A. 3.04 3.05 Start-up packaged heating and cooling units, in accordance with manufacturer's start-up instructions and in the presence of a manufacturer's representative. Test controls and demonstrate compliance with requirements. Replace damaged or malfunctioning controls and equipment. Contractor shall submit written affidavit indicating that the equipment is operating as designed. The Temperature Controls Contractor shall test the digital DDC system and demonstrate compliance with the requirements of the Specifications to the satisfaction of the Authority’s representative. The Contractor shall perform necessary Interdisciplinary Tests and Functional Performance Tests according to the manufacturer’s procedures. TRAINING A. Provide services of manufacturer's technical representative for two days to instruct the Department of Education Custodial Staff and DOE Maintenance Representative in the operation and maintenance of the packaged heating and cooling units. B. Schedule training with the Authority. Provide at least 2days notice of training date to the Custodian and DOE Maintenance Representative. C. The documentation for each controller shall include an accurate graphic flow diagram of the software program for future owner reference. INTERDISCIPLINARY TESTS AND FUNCTIONAL PERFORMANCE TESTS A. Interdisciplinary Pre-Start-Up and Start-Up Tests: The Contractor shall conduct interdisciplinary pre-start up and start up tests as per the manufacturer’s start up procedures. Contractor shall submit signed start up affidavit signed by the factory authorized service representative indicating that all of the manufacturer’s pre-start up and start up procedures have been successfully completed. NYCSCA COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 30 01/29/16 B. DESIGN NO. _____ Functional Performance Tests Contractor shall also submit signed functional performance testing affidavit signed by the factory authorized service representative indicating that all of the manufacturer’s functional performance tests have been successfully completed. 3.06 COMMISSIONING OF ROOFTOP HVAC UNITS A. 14 HVAC Contractor shall comply with the Commissioning Requirements of Contract Specification Section S01660 for rooftop HVAC units. END OF SECTION * * * BB:JV:RE:AK 01/29/16 Notes to Specifier (Delete from Specification) 1. Edit as required. Section 15503 is to be utilized if the project involves construction of a New Building or Addition to building in Seismic Design Category C or D. Section 15503 is also to be utilized if project involves retrofit work in Existing Buildings in Seismic Design Category C or D constructed after LL17/1995 went into effect. Use Section 15504, Vibration Isolation, (without seismic restraints) for retrofit work on Existing Buildings constructed prior to the effective date of LL17/1995 and for any buildings in Seismic Design Category B. 2. Note deleted. 3. Architect/Engineer of Record shall engage the services of an acoustical consultant during the design of the project. The report findings of the acoustical consultant shall be submitted to the Authority. Acoustical consultant shall address the possible need for the following (including but not limited to): The need for sound traps and/or acoustical lining upstream and downstream of the air conditioning units Mounting the rooftop equipment on dunnage in lieu of curb mounting (especially for NC 25 Auditoriums) Locating the units over non-critical spaces where possible (e.g. corridors, storage spaces) The need to run commercial rooftop unit ductwork externally on the roof NYCSCA COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 31 01/29/16 DESIGN NO. _____ The need to provide acoustic noise barrier walls around the rooftop units in special circumstances The need to provide floating slabs Internal isolation of all rotating components Insulation of void spaces within roof curbs (where curbs are used in lieu of dunnage) Individual acoustical jackets for each compressor 4. The Architect/Engineer of Record (through his/her Acoustical sub-consultant) shall provide the maximum acceptable radiated, supply discharge, and return inlet sound power levels of each of the rooftop units based on the particular construction (nature of roof deck, type of suspended ceiling if any, type of rooftop unit mounting (roof curb or dunnage), proximity to adjacent buildings, routing of ductwork, possible presence of acoustical duct lining, thickness of possible acoustical duct lining, sound trap attenuation capabilities, etc. 5. Coils that are exposed to a marine environment (i.e. school is located near the shore) shall utilize copper fins in lieu of aluminum fins. Edit the section as required. 6. Edit as required. Architect/Engineer of Record shall determine if the factory provided isolators sufficiently attenuate the vibration considering the flexibility and nature of the structural roof (beam frame spacing, deck construction, etc.). If it is determined that the factory provided isolators are insufficient, equipment shall be provided without factory vibration isolators (or shipping hold down bolts shall remain secured thus defeating the factory isolators). Architect/Engineer of Record shall define the required field erected vibration isolators (stiffness, static deflection, etc.) and reflect the field erected isolators on the Schedule of Equipment on the Drawings. Contractor’s registered professional engineer shall be responsible for the seismic restraints of all equipment. Contractor’s registered professional engineer may elect to provide the equivalent vibration isolators in combined vibration isolator/seismic restraint supports. Architect/Engineer of Record’s vibration analysis shall be submitted to their acoustical sub-consultant for review. Reference Section 15503 and Section 15504. 7. Edit the custom rooftop unit points list to reflect the points list for the commercial rooftop units. Also edit the custom rooftop unit sequence of operation to reflect the commercial rooftop unit sequence of operation in Section 15985. Non-native LonWorks controllers may be provided on CIP projects if there exists an available gateway to Lon. The gateway is not to be provided at the time of the construction of the CIP project. The NYCSCA COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 32 01/29/16 DESIGN NO. _____ availability of a gateway is required to be determined for a connection to a possible future LonWorks BMS/DDC network. 8. Post fire smoke purge systems need not be on emergency power. Smoke control systems that must function for a minimum of 20 minute duration or 1.5 times the calculated egress time, whichever is more per Section BC 909.4.6, during the fire are to be on standby power per Sections BC 909.11, BC 2702.2.2 and MC 513.11. 9. Refer to Building Envelope Design Requirement 4.4 for cases when dunnage, curbs, platforms and ladders are to be provided. Edit as required. 10. All rooftop units mounted on a fluid applied protective membrane roofing system shall be provided with adjacent pavers to allow for service access. Depending on location within the roof, provide double or triple layer of pavers to ensure all servicing shall be able to be performed above the maximum possible water line when a roof detention/fluid applied protective membrane roofing system is used. Provide protection pads adjacent to the rooftop units to grant access when the rooftop units are mounted on a built-up roofing system. HVAC Engineer of Record shall coordinate with all other required related design disciplines. All details shall be reflected on the bid drawings. 11. Not used. 12. Edit as required. 13. MERV 13 filters, reheat coils for ASHRAE Standard 55 humidity control are required for projects subject to LL86/05. Standard commercial units may only be used for non-LL86/05 projects. For LL86/05 projects, units exceeding 6,000 cfm must be full custom units as described in Sections 15853 and 15854. For LL86/05 projects, units less than 6,000 cfm must still provide all of the above features but other full custom characteristics may be omitted resulting in “semi-custom” units. “Semi-custom” units may require external sound control wall with acoustic louvers due to the reduced integral sound attenuation package. Belt driven fans may only be available in lieu of direct driven fans. The integral “semi-custom” unit vibration isolators may be inadequate thus requiring external isolators. 4” MERV 13 cartridge filters may have to be used in lieu of 12” MERV 13 cartridge filters. 18 gauge exterior galvanized panels may have to be used in lieu of 16 gauge exterior panels. 20 gauge galvanized steel interior panels may have to be used in lieu of 16 gauge interior panels. Custom supply/return plenum sections may have to be reduced to smaller “semi-custom” plenum sections. Condenser section fans may not be available with variable speed drives. Compressors may not be available with acoustic jackets. Walk-in vestibules for maintenance may have to be eliminated. LL86/05 projects with units less than 6,000 cfm may be “semicustom” units as provided by Coolbreeze or equivalent. For leased building projects subject to LL86/05, “semi-custom” units NYCSCA COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 33 01/29/16 DESIGN NO. _____ may be utilized for all sizes subject to approval by the Authority. Edit Sections 15853 and 15854 as required to reflect the “semi-custom” unit characteristics. 14. This paragraph is intended for projects that must comply with the NYC Green Schools Rating System (generally all capacity projects) and the following CIP projects: a. b. HVAC upgrades (boiler replacements/ DDC-only systems/ AC upgrades, etc) Temperature Control systems BMS/DDC Systems 15. Any of the approved manufacturers listed in the Custom Rooftop Unit Sections, (15853 and 15854) can be considered as approved manufacturers for commercial unit applications. Verify the usage of such custom units is within the project’s budget. 16. If the air velocity exceeds 500 fpm when delivering the required volumetric flow and the unit dimensions can not be enlarged due to physical space limitations, provide mist eliminators in order to limit condensate carryover (Mistop or approved equal), nominally 1” thick, stainless steel with 0.1” wc pressure drop at 500 fpm. Provide mounting clips and frames to secure and support the mist eliminators. Edit section as required. Designer is to verify that fans have adequate static pressure capability to deliver the required volumetric flow considering the additional pressure losses associated with the mist eliminators. Designer is to show any required mist eliminators on the Drawings. 17. Edit as required. For curb mounted units (not dunnage mounted units), designer shall show drain line for auxiliary pan (and shall show auxiliary pan, minimum depth 1.5”, not less than 3” larger than the unit or coil dimensions per Section MC 307.2.3) or overflow drain line for primary pan. Show routing and diameter of all drain lines. An option is to use a sight glass in the drain line from the auxiliary pan or primary pan overflow drain line to achieve the “conspicuous point of disposal” effect referred to in Section MC 307.2.3. Designer shall indicate on the Drawings that there are alternate design options of providing an auxiliary drain pan (without an additional drain line) with a Temperature Controls Contractor (TCC) provided (or manufacturer provided) water level detection device or providing a primary drain pan with a Temperature Controls Contractor (TCC) provided (or manufacturer provided) water level detection device which will shut down the unit upon an overfill condition. Show all details on the Drawings and identify the acceptable water level detection device alternate designs. Designer to select appropriate paragraph 1 with corresponding appropriate paragraph 2. 18. Edit as required. Delete for dunnage mounted units. Specify which units are curb mounted where this Article applies. NYCSCA COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 34 01/29/16 DESIGN NO. _____ 19. Delete article if smoke control systems are not used on the project. Components of smoke control fans shall be rated and certified by the manufacturer for the probable temperature rise to which the components will be exposed. This temperature rise shall be computed by the designer in accordance with Section MC 513.10. Edit the Section by defining the probable temperature rise and insert into Article. Verify that when the submittals are received, the components are suitable for the probable exposure temperature. Fans shall be selected for stable performance based on normal temperature and, where applicable, elevated temperature. Calculations and manufacturer's fan curves shall be part of the documentation procedures. 20. Note deleted. 21. For any normally open vent valve line, show field continuation from RTU manufacturer’s capped line to terminal of any normally open vent valve line on the Plumbing Drawings if the RTU manufacturer can not ship the normally open vent valve line as an integral part of the RTU assembly. 22. Delete submittal for CIP projects and if smoke control systems are not used on a capacity project. 23. For PA spaces, per Section 6.4.3.10 of ASHRAE 90.1-2010 and Section C403.3.3 of the 2014 NYCECC, single zone VAV systems (SZVAV) are required when the cooling capacity at AHRI conditions is greater than or equal to 110,000 BTUH. If single zone VAV systems are required instead of constant volume systems, edit Section as required. See control details and associated points list (1598512f). 24. Provide Energy Recovery Wheel (ERW) per 90.1-2010 and Section C403.2.6 of the Controlled Ventilation (DCV) per Section 2010 and Section C403.2.5.1 of the 2014 required. 25. Delete for CIP projects unless a full installed. Discuss with the Authority. Section 6.5.6 of ASHRAE 2014 NYCECC or Demand 6.4.3.9 of ASHRAE 90.1NYCECC. Edit section as BMS system is being * * * NYCSCA COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 35 01/29/16 DESIGN NO. _____ LIST OF SUBMITTALS SUBMITTAL DATE SUBMITTED DATE APPROVED Product Data: ______________ 1. Manufacturers Product Data 2. Fan Curves 3. Compressor Efficiency Data 4. Gas Fired Unit Efficiency Data 5. Installation Instructions 6. Start-up Instructions 7. Radiated, supply discharge and return inlet computer generated sound power levels ____________ Shop Drawings: 1. Mounting Details 2. Wiring Diagrams 3. Piping Diagrams 4. Gas Train Shop Fabrication Drawings ______________ ____________ Test Reports: 1. Manufacturers’ Factory Test Results: _____________ ____________ ______________ ____________ Maintenance Material: 1. Spare Filters: 2. Spare Belts (Omit for direct drives) ____________ __________ Maintenance Data: 1. Maintenance Manual ______________ ____________ Preventative Maintenance Plan and Schedule ______________ ____________ Warranties ____________ __________ Certificates: 1. Contractor’s Start-Up and Demonstration Affidavit 2. Seismic certificate 22 of operability * * * NYCSCA COMMERCIAL PACKAGED ROOFTOP HEATING AND COOLING UNITS 15855 - 36