COE Installation Quality Bulletin Installation Quality Bulletin Number: 05-03 To: All Installation Suppliers / Design Engineering Representatives / Quality Managers / Field Engineering Representatives / Central Office Operations Representatives Date: Friday, April 15, 2005 From: QWEST Installation Quality Assurance Subject: Flooded Pure Lead and Lead-Calcium Battery Storage Recharge Instructions Action Required: NO: YES: Description of Bulletin: The purpose of this Quality Bulletin is to inform all Qwest-approved installation Service Suppliers and internal groups of the proper procedures required when recharging re-used flooded pure lead and lead-calcium cells in Qwest central offices. Due to the frequent re-use of flooded batteries in the Qwest Network, the following guidelines are compiled, edited, and abridged from Tech Pub 77385; IEEE 450 and 484; and the C&D, GNB-Exide, and Enersys (old and new) Installation, Operations, and Maintenance manuals. These guidelines apply to round cells and lead-calcium rectangular flooded cells. The general rule is that these batteries should not be stored for longer than 6 months at 77º F without receiving a freshening charge. The time notations listed in the tables of the pages that follow (refer to Tables A - ) equals the time since the batteries have been on any type of charge (float, equalize, boost, initial, or freshening). NOTE: Batteries should be shipped with shipping plugs installed, and the plugs must be removed (and replaced with normal vents) at the destination before any charging commences. The minimum charger ampacity is based on the AH rating of the batteries being charged. Table A lists the minimum size of charger per string being charged. Any rectifier or battery charger capable of the Voltage can be used. There are no specific Product ID (PID’d) full string chargers in AMMS. TABLE A Minimum Charger Size per String AH Rating 50 - 200 200 - 500 500 - 1000 1000 - 1700 1700 - 2400 3000 - 4000 DC Output 2A 5A 10 A 15 A 20 A 40 A When the extent of the storage period and storage temperature are unknown, take voltage measurements and charge as follows: TABLE B Unknown Storage Time and/or Temperature Avg Cell Open-Circuit (V) 2.05 - 2.06 V 2.03 - 2.05 V 2.02 - 2.03 V 2.00 - 2.02 V 1.98 - 2.00 V 1.92 - 1.98 V < 1.92 V Time @ 2.33V/cell Time @ Time @ Time @ 2.37V/cell 2.38 V/cell 2.39V/cell Time @ 2.45V/cel Time @ 2.50V/cell Freshening Charge Not Required — Install and Place on “Float” 48 hrs 24 hrs 20 hrs 18 hrs 14 hrs 12 hrs 72 hrs 36 hrs 32 hrs 30 hrs 20 hrs 18 hrs 96 hrs 48 hrs 44 hrs 40 hrs 30 hrs 24 hrs 120 hrs 72 hrs 64 hrs 56 hrs 40 hrs 34 hrs Do Not Use These Charging 250 hrs Voltages Send to Recycling NOTE: Batteries should be charged with any voltmeter capable of at least 2 decimal points in the 0-3 V range. Voltmeters with 3 decimal points in this range are preferred, but all Qwestapproved AMMS PID’d voltmeters meet this specification. If the cells have been stored at an average temperature of between 74-80º F, and the storage time is known, the following applies: TABLE C 74-80º F Storage Storage Period < 1 month 1-2 months 2-3 months 3-4 months Time @ Time @ Time @ Time @ Time @ Time @ 2.33 V/cell 2.37V/cell 2.38 V/cell 2.39V/cell 2.45V/cel 2.50V/cell no freshening charge required — install and place on float 48 hrs 24 hrs 20 hrs 18 hrs 14 hrs 12 hrs 72 hrs 36 hrs 32 hrs 30 hrs 20 hrs 18 hrs 96 hrs 48 hrs 44 hrs 40 hrs 30 hrs 24 hrs TABLE C (con’t) 74-80º F Storage Storage Time @ Time @ Time @ Time @ Period 2.33 V/cell 2.37V/cell 2.38V/cell 2.39V/cell 5-6 months 120 hrs 72 hrs 64 hrs 56 hrs 6-8 months 250 hrs 168 hrs 144 hrs 120 hrs Do not use these charging voltages. 8-24 Send to recycling if the open-circuit months voltage (before freshening charge) < 1.92 V > 2 years Send to Recycling Time @ 2.45V/cell 40 hrs 96 hrs 250 hrs Time @ 2.50V/cell 34 hrs 72 hrs If the cells have been stored at an average temperature of around 68-74º F, and the storage time is known, the following table applies: TABLE D 68-74º F Storage Storage Period < 6 weeks 6-9 weeks 2-3 months 3-4 months 5-6 months 6-8 months 8-10 months 10-24 months > 2 years Time @ Time @ Time @ Time @ Time @ Ttime @ 2.33V/cell 2.37V/cell 2.38V/cell 2.39V/cell 2.45V/cell 2.50V/cell Freshening Charge Not Required — Install and Place on “Float” 36 hrs 16 hrs 14 hrs 12 hrs 10 hrs 8 hrs 48 hrs 24 hrs 22 hrs 20 hrs 16 hrs 14 hrs 72 hrs 32 hrs 30 hrs 28 hrs 20 hrs 18 hrs 80 hrs 48 hrs 40 hrs 36 hrs 30 hrs 24 hrs 120 hrs 72 hrs 60 hrs 56 hrs 40 hrs 34 hrs 250 hrs 168 hrs 144 hrs 120 hrs 96 hrs 72 hrs Do Not Use These Charging 250 hrs Voltages Send to Recycling if the Open-Circuit V Before Freshening Charge < 1.92 V Send to Recycling If the cells have been stored at an average temperature of around 60-68º F, and the storage time is known, the following table applies: TABLE E 60-68º F Storage Storage Period < 2 mos. Time @ Time @ Time @ Time @ Time @ Time @ 2.33V/cell 2.37V/cell 2.38V/cell 2.39V/cell 2.45 V/cell 2.50V/cell Freshening Charge Not Required — Install and Place on “Float” - CONFIDENTIAL USE ONLY Disclose and distribute only to Qwest employees having a legitimate business need to know. Disclosure outside of Qwest is prohibited without authorization. TABLE E (Con’t) 60-68º F Storage Storage Period 2-3 mos. 3-4 mos. 5-6 mos. 6-8 mos. 8-10 mos. 10-12 mos. 1-2 years > 2 years Time @ 2.33V/cell 32 hrs 48 hrs 56 hrs 96 hrs 120 hrs 250 hrs Time @ 2.37V/cell 16 hrs 24 hrs 32 hrs 48 hrs 72 hrs 168 hrs Time @ 2.38V/cell 14 hrs 20 hrs 28 hrs 40 hrs 60 hrs 144 hrs Time @ 2.39V/cell 12 hrs 18 hrs 24 hrs 36 hrs 56 hrs 120 hrs Time @ Time @ 2.45 V/cell 2.50V/cell 10 hrs 8 hrs 14 hrs 12 hrs 18 hrs 16 hrs 30 hrs 24 hrs 40 hrs 34 hrs 144 hrs 120 hrs Do Not Use These Charging 250 hrs Voltages Send to Recycling if the Open-Circuit V Before Freshening Charge < 1.92 V Send to Recycling If the cells have been stored at an average temperature of around 50-60 degrees F, and the storage time is known, the following table applies: 50-60 Degree F Storage Storage time < 3 months 3-4 months 5-6 months 6-9 months 9-12 months 1-2 years > 2 years time @ time @ time @ time @ time @ time @ 2.33 2.37 2.38 2.39 2.45 V/cell 2.50 V/cell V/cell V/cell V/cell V/cell no freshening charge required — install and place on float 32 hrs 16 hrs 14 hrs 12 hrs 10 hrs 8 hrs 36 hrs 20 hrs 18 hrs 16 hrs 12 hrs 10 hrs 64 hrs 32 hrs 28 hrs 24 hrs 18 hrs 16 hrs 192 hrs 108 hrs 96 hrs 80 hrs 60 hrs 48 hrs don’t use these charging Voltages 250 hrs send to recycling if the open-circuit V before freshening charge is < 1.92 V send to recycling - CONFIDENTIAL USE ONLY Disclose and distribute only to Qwest employees having a legitimate business need to know. Disclosure outside of Qwest is prohibited without authorization. If the cells have been stored at an average temperature of less than degrees F, and the storage time is known, the following table applies: < 50 Degree F Storage Storage time < 5 months 5-7 months 7-9 months 9-12 months 12-15 months 15-24 months > 2 years time @ time @ time @ 2.33 2.37 2.38 V/cell V/cell V/cell no freshening charge required 32 hrs 16 hrs 14 hrs 36 hrs 20 hrs 18 hrs 64 hrs 32 hrs 28 hrs 192 hrs 108 hrs 96 hrs time @ time @ time @ 2.39 2.45 V/cell 2.50 V/cell V/cell — install and place on float 12 hrs 10 hrs 8 hrs 16 hrs 12 hrs 10 hrs 24 hrs 18 hrs 16 hrs 80 hrs 60 hrs 48 hrs don’t use these charging Voltages 250 hrs send to recycling if the open-circuit V before freshening charge is < 1.92 V send to recycling If the cells have been stored at an average temperature of around 80-86 degrees F, and the storage time is known, the following table applies: 80-86 Degree F Storage Storage time < 3 weeks 3-7 weeks 7-13 weeks 3-4 months 5-6 months 6-8 months 8-18 months > 18 months time @ 2.33 V/cell time @ time @ time @ time @ time @ 2.37 2.38 V/cell 2.39 2.45 2.50 V/cell V/cell V/cell V/cell no freshening charge required — install and place on float 72 hrs 36 hrs 30 hrs 24 hrs 18 hrs 16 hrs 96 hrs 54 hrs 48 hrs 40 hrs 30 hrs 24 hrs 144 hrs 72 hrs 66 hrs 60 hrs 40 hrs 32 hrs 180 hrs 108 hrs 96 hrs 84 hrs 60 hrs 48 hrs 250 hrs 216 hrs 180 hrs 132 hrs 108 hrs don’t use these charging Voltages 250 hrs send to recycling if the open-circuit V before freshening charge is < 1.92 V send to recycling - CONFIDENTIAL USE ONLY Disclose and distribute only to Qwest employees having a legitimate business need to know. Disclosure outside of Qwest is prohibited without authorization. If the cells have been stored at an average temperature of around 86-92 degrees F, and the storage time is known, the following table applies: 86-92 Degree F Storage Storage time < 2 weeks 2-4 weeks 1-2 months 2-3 months 3-4 months 5-6 months 6-15 months > 15 months time @ 2.33 V/cell time @ time @ time @ time @ time @ 2.37 2.38 V/cell 2.39 2.45 2.50 V/cell V/cell V/cell V/cell no freshening charge required — install and place on float 48 hrs 28 hrs 24 hrs 18 hrs 14 hrs 10 hrs 96 hrs 54 hrs 44 hrs 36 hrs 30 hrs 24 hrs 144 hrs 80 hrs 72 hrs 60 hrs 40 hrs 32 hrs 216 hrs 108 hrs 96 hrs 88 hrs 64 hrs 48 hrs 250 hrs 216 hrs 180 hrs 132 hrs 108 hrs don’t use these charging Voltages 250 hrs send to recycling if the open-circuit V before freshening charge is < 1.92 V send to recycling If the cells have been stored at an average temperature of around 92-98 degrees F, and the storage time is known, the following table applies: 92-98 Degree F Storage Storage time < 1 week 1-2 weeks 2-4 weeks 1-2 months 2-3 months 3-4 months 5-12 months > 1 year time @ 2.33 V/cell time @ time @ 2.37 V/cell 2.38 V/cell time @ time @ time @ 2.39 2.45 2.50 V/cell V/cell V/cell no freshening charge required — install and place on float 36 hrs 20 hrs 18 hrs 14 hrs 10 hrs 8 hrs 72 hrs 40 hrs 36 hrs 28 hrs 20 hrs 16 hrs 144 hrs 80 hrs 66 hrs 54 hrs 40 hrs 32 hrs 216 hrs 120 hrs 108 hrs 90 hrs 64 hrs 48 hrs 250 hrs 162 hrs 144 hrs 132 hrs 84 hrs 64 hrs don’t use these charging Voltages 250 hrs send to recycling if the open-circuit V before freshening charge is < 1.92 V send to recycling - CONFIDENTIAL USE ONLY Disclose and distribute only to Qwest employees having a legitimate business need to know. Disclosure outside of Qwest is prohibited without authorization. If the cells have been stored at an average temperature of around 98-104 degrees F, and the storage time is known, the following table applies: 98-104 Degree F Storage Storage time < 2 weeks 2-4 weeks 1-2 months 2-3 months 3-9 months > 9 months time @ 2.33 V/cell time @ time @ time @ time @ time @ 2.37 2.38 V/cell 2.39 2.45 2.50 V/cell V/cell V/cell V/cell 48 hrs 30 hrs 26 hrs 22 hrs 16 hrs 14 hrs 96 hrs 60 hrs 54 hrs 40 hrs 30 hrs 24 hrs 216 hrs 120 hrs 96 hrs 80 hrs 60 hrs 48 hrs 250 hrs 162 hrs 144 hrs 132 hrs 84 hrs 64 hrs don’t use these charging Voltages 250 hrs send to recycling if the open-circuit V before freshening charge is < 1.92 V send to recycling If the cells have been stored at average temperatures greater than 104 degrees F, and the storage time is known, the following table applies: > 104 Degree F Storage Storage time < 2 weeks 2-4 weeks 1-2 months 2-6 months > 6 months time @ 2.33 V/cell time @ time @ time @ time @ time @ 2.37 2.38 V/cell 2.39 2.45 2.50 V/cell V/cell V/cell V/cell 72 hrs 44 hrs 40 hrs 30 hrs 22 hrs 16 hrs 144 hrs 90 hrs 80 hrs 60 hrs 40 hrs 32 hrs 250 hrs 162 hrs 144 hrs 132 hrs 84 hrs 64 hrs don’t use these charging Voltages 250 hrs send to recycling if the open-circuit V before freshening charge is < 1.92 V send to recycling Acknowledgements to Curtis Ashton (Qwest AMC) for his contribution to the content of this Bulletin. Qwest Installation Quality Assurance Jeff Bostow 612-798-2460 mailto:Jeff.Bostow@qwest.com - CONFIDENTIAL USE ONLY Disclose and distribute only to Qwest employees having a legitimate business need to know. Disclosure outside of Qwest is prohibited without authorization.