Section Cover Page Section 26 24 16 Distribution Panelboards 2010-11-01 Use this Section to specify all requirements for distribution panelboards for medium to large projects that incorporate molded case breakers or fused switches with bus capacities in the range from 400 to 1200 Amperes which subfeed branch circuit panelboards, motor control centres and other large point loads. This Master Specification Section contains: .1 This Cover Sheet .2 Data Sheets – Reference Documents .3 Data Sheets - Sample Schedules .4 Specification Section Text: 1. 1.1 1.2 1.3 1.4 1.5 1.6 General Related Requirements Reference Documents Source of Supply Product Data Coordination Delivery, Storage and Handling 2. 2.1 Products Distribution Panelboards 3. 3.1 3.2 Execution Installation Schedules BMS Basic Master Specification Alberta Infrastructure Master Specification System Page 0 Data Sheet - Sample Schedules Section 26 24 16 Distribution Panelboards 2010-11-01 Distribution Panelboard 6D1 347/600 Volt, 3 Phase, 4 Wire Bus: 1200 Amperes, Enclosure: Surface Load Brkr Frame Size (AMPS) Poles Trip GFP Feeder Panel P-6B 100 3 70 No 32 mm 4#3 X-L MCC No. 1 225 3 200 Yes 50 mm 4#1/0 XL Note: 3 - 3 pole, 100 Amp frame spaces 3 - 3 pole, 225 Amp frame spaces Distribution Panelboard 2D1 120/208 Volt, 3 Phase, 4 Wire Bus: 600 Amperes, Enclosure: Flush Load Brkr Frame Size (AMPS) Poles Trip GFP Feeder Panel 2A 100 3 100 No 32 mm 4#3 XL Note: 1 - 3 pole, 100 Amp frame spaces 4 - 3 pole, 225 Amp frame spaces BMS Basic Master Specification Alberta Infrastructure Master Specification System Page 02 Data Sheet - Sample Schedules Section 26 24 16 Distribution Panelboards 2010-11-01 Distribution Panelboards 347/600 Volt, 3 Phase, 4 Wire Panel Board CDP-1 CDP-2 Bus 400 800 Encl surface surface Brkr Frame Size/Tripd (AMPS) Poles Qty GFP Feeder 100 / 100 225 / 200 400 / 400 3 3 3 4 3 1 no no yes 225 / 3 (3) - 32 mm 4#3 X-L 50 mm 4#1/0 X-L 2 - 50 mm 4 # 3/0 X-L space only 100 / 70 225 / 150 400 3 3 3 3 2 (2) no no - 32 mm 4#6 X-L 50 mm 4#1/0 X-L space only Distribution Panelboards 347/600 Volt, 3 Phase, 4 Wire Panel Board Bus Encl CDP-3 800 surface BreakerF rame Size (AMPS) Poles Qty Trip GFP Feeder 100 400 3 3 3 3 100 300 225 3 (3) no yes - 32 mm 4#3 X-L 75 mm 4#300 MCM X-L spaces only END OF DATA SHEETS BMS Basic Master Specification Alberta Infrastructure Master Specification System Page 03 Section 26 24 16 Distribution Panelboards Page 1 Plan No: Project ID: 1. General 1.1 RELATED REQUIREMENTS .1 .2 .3 .4 .5 .6 .7 .8 .9 .10 1.2 Submittal Procedures: LEED Requirements: Waste Management and Disposal: Concrete Housekeeping Bases: Electrical General Requirements: Boxes and Fittings: Conduit: Electrical Identification: Testing, Adjusting and Balancing of Electrical Equipment and Systems: Overcurrent Protective Devices: Section 01 33 00. Section 01 35 18. Section 01 74 19. Section 03 30 00. Section 26 00 10. Section 26 05 33. Section 26 05 34. Section 26 05 53. Section 26 08 10. Section 26 18 16. REFERENCE DOCUMENTS .1 Canadian Standards Association (CSA) .1 1.2 CSA C22.2 No. 29M1989 (R2004) Panelboards and Enclosed Panelboards SOURCE OF SUPPLY .1 1.3 All distribution panelboards shall be by a single manufacturer. PRODUCT DATA .1 Comply with requirements of Sections 26 00 10. .2 Provide manufacturer's product data for all systems and components. .3 Provide data on manufacturer's recommended environmental conditions for equipment affected by temperature. 1.4 COORDINATION .1 1.6 Coordinate size and location of concrete housekeeping bases with work specified in Section 03 30 00. DELIVERY, STORAGE AND HANDLING .1 2010-11-01 BMS Version Separate waste materials for [reuse] [and] [recycling] in accordance with Section 01 74 19 - Waste Management and Disposal. Section 26 24 16 Distribution Panelboards Page 2 Plan No: Project ID: 2. Products 2.1 DISTRIBUTION PANELBOARDS .1 Distribution panelboards to CSA C22.2 No.29 and as follows: .1 Bus characteristics: .1 Construction: rectangular section [copper] [aluminum] [silver] [tin] plated joints. SPEC NOTE: Aluminum not permitted when bus capacity exceeds 600 Amperes. .2 .2 Bracing: [50,000] [ ] Amperes symmetrical. .3 Neutral: full capacity, solid neutral design. .4 Ground bus: copper. Enclosure: .1 .2 .3 Prefinished painted sheet steel. Uniform height, depth and width. [Drip cover.] SPEC NOTE: Specify drip cover only when distribution panelboard is installed in a room with sprinklers. .3 Trim: .1 [Hinged door on door construction] [Screw-on] [Hinged] cover dished back to device face with [no] [hinged locking] door, [2] [ ] keys per unit. SPEC NOTE: Specify hinged locking door when distribution panelboard is installed in a room with sprinklers. .4 Overcurrent Protective Devices: [bolt-in breakers] [fused switches] as specified in Section 26 18 16. 3. Execution 3.1 INSTALLATION .1 Install panelboards securely, plumb and square to adjoining surfaces. Mount panelboards 1800 mm and larger on 100 mm concrete base. .2 Install panelboards flush or surface as indicated. 2010-11-01 BMS Version Section 26 24 16 Distribution Panelboards Page 3 Plan No: Project ID: .3 Mount panelboards at not less than 1800 [ .4 Connect loads to feeder breakers as specified in distribution panelboard schedules. .5 [Breaker] [Fused switch] sizes as specified in distribution panelboard schedules. 3.2 ] mm to top of trim. SCHEDULES SPEC NOTE: Number Distribution Panelboard Schedules sequentially starting with the highest voltage in system and working down. SPEC NOTE: Following is the individual schedule format. Distribution Panelboard [ ] [347/600], [ ] Volt, [3] Phase, [4] Wire Bus: [ ] Amperes, Enclosure: [ ] Load Brkr Frame Size (AMPS) Poles Trip [GFP] Feeder [ ] [ [ ] [ [ [ ] ] ] ] SPEC NOTE: Following is the Summary Schedule Format. Distribution Panelboards [ ] Volt, [ ] Phase, [ ] Wire Panel Board Bus Encl [ ] [ ] [ 2010-11-01 BMS Version ] Breaker Frame Size (AMPS) Poles Qty Trip [GFP] Feeder [ [ ] [ ] [ [ [ ] ] ] ] Section 26 24 16 Distribution Panelboards Page 4 Plan No: Project ID: END OF SECTION 2010-11-01 BMS Version