Series 7 Power Controllers

advertisement
Series 7 Power Controllers
Series 7 DIN Rail Mount Power Devices
Series 7 Power Devices put
12 to 80 Amps in a DIN rail
mount package that
provides precision machine
control for heater bands,
cartridge heaters, and other
resistive loads.
• DIN Rail or Wall Mounting
• Zero Crossing Control
• AC/DC ON-OFF or mA Proportional Inputs
• SCR or Triac Version
• No Need for External Wire Crimping
Introduction
The Series 7 Power Device family features a sleek design and robust performance
specifications which ensure that your tough heating requirements are surpassed. These
devices were developed to control resistive heating loads using the time proportional SSR
driver output or the linear output from a temperature controller. Specifically tuned to ensure
quick temperature ramping, precise operating control, and immediate temperature stabilization, all these features mean better product homogeneity, less wasted time and less scrap.
The Series 7 Power Device family consists of:
Model
7PT
7PD
7PA
7PL
7PM
7PE
7PB
7PF
Vac
240
400 & 600
400 & 600
400 & 600
400 & 600
400 & 600
400 & 600
400 & 600
Phase
Single
Single
Single
Single
Single
Three
Three
Three
Device
Triac
SCR
SCR
SCR
SCR
Two leg SCR
Two leg SCR
Two leg SCR
Control
On-off
On-off
On-off
On-off
Proportional
On-off
On-off
On-off
Input
Vdc
Vdc
100/240 Vac
24 Vac
4 to 20 mA
Vdc
100/240 Vac
24 Vac
Features
•
•
•
•
Thermal Protection Option
When the junction temperature reaches 125°C (257°F), a separator inhibits the command
signal and turns on the OH LED indicator. Once the heat sink temperature becomes
acceptable, the command signal is again enabled and the OH LED is turned off.
1415-DB-010-0-01
All models can be DIN rail or Panel mounted
Complete line and load connections provided for easy installation
All terminals accessible from the front
Common height for all models
Barber-Colman Company
1
Series 7 Power Controllers
Input
ON-OFF Control Mode
On
Off
Time
Line Output
Cycle time defined by controller
Time
In the On-Off control mode,
the output of the contactor
turns on only when the input is
turned on and the supply voltage is at a zero-crossing point.
If the input is turned on at a
non-zero point, the contactor
will simply wait for the next
zero-point to turn on. Unlike a
mechanical relay, the Series 7
with On-Off control eliminates
electrical switching disturbances and audible noise.
Fast Cycle Proportional Control Mode (7PM only)
Input
20 mA
12 mA
4 mA
Status
0
50
100
Time (Line Periods)
50
100
Time (Line Periods)
50
100
% Output
On
The Fast Cycle control mode
is a zero-crossing firing mode
that uses a fixed 100-cycle
time base for control. For example, 50 cycles on and 50
cycles off results in a 50%
output. Fast Cycle control is
best for loads that need the
slower, less frequent switching (i.e., resistive loads).
Line Output
Off
Input
Single Cycle Proportional Control Mode (7PM only)
20 mA
16 mA
12 mA
8 mA
4 mA
Status
0
% Output 25
50
75
100
On
Off
Line Period
@ 50 Hz = 20 ms
@ 60 Hz = 16.6 ms
Line Output
0 A1
B1
0 to A1 = 1 line period
0 to B1 = 4 line periods
2
0 A2 B2
0
0 to A2 = 1 line period
0 to B2 = 2 line periods
A3B3
Single Cycle control mode is a
zero-crossing firing mode that
uses a variable time base (ontime plus off-time) for control.
Based on the command level,
the time base is kept at a minimum, which improves control
compared to the Fast Cycle
control mode. For example,
one cycle on and one cycle off
results in a 50% output. Three
cycles on and one cycle off
results in a 75% output. Single
Cycle control is best for loads
that require faster, more precise control (i.e., low thermal
inertia loads).
0 to A3 = 3 line periods
0 to B3 = 4 line periods
Barber-Colman Company
1415-DB-010-0-01
Series 7 Power Controllers
Ordering Information
MODEL:
Field No.
7P
2 3
4
5
6
7
Field 1. RESERVED
Fields 2, 3, 4. BASE MODEL
7PT - Solid State Contactor, 1Ø, Triac, DC Volt, On/Off
7PD- Solid State Contactor, 1Ø, SCR, DC Volt, On/Off
7PA - Solid State Contactor, 1Ø, SCR, 100/240 Vac, On/Off
7PL - Solid State Contactor, 1Ø, SCR, 24 Vac, On/Off
7PM- Power Controller, 1Ø, SCR, 4 to 20 mA, Proportional
7PE - Solid State Contactor, 3Ø, SCR, DC Volt, On/Off
7PB - Solid State Contactor, 3Ø, SCR, 100/240 Vac, On/Off
7PF - Solid State Contactor, 3Ø, SCR, 24 Vac, On/Off
8
9
0-0-00
10
11 12
13 14 15
Fields 8, 9, 10. LOAD VOLTAGE
240 - 240 Volts/800 V Peak Reverse (7PT only)
400 - 400 Volts/1200 V Peak Reverse
600 - 600 Volts/1700 V Peak Reverse
Field 11. THERMAL PROTECTION
0 - None
1 - Over Temperature Protection
Fields 12 through 15. RESERVED
Fields 5, 6, 7. LOAD AMPERES
T12- 12 Amps (7PT only)
T18 -18 Amps (7PT only)
020 - 20 Amps (7PB, 7PE, 7PF)
025 - 25 Amps (7PA, 7PD, 7PL, 7PM)
035 - 35 Amps (7PA, 7PD, 7PL, 7PM)
040 - 40 Amps (7PB, 7PE, 7PF)
045 - 45 Amps (7PA, 7PD, 7PL, 7PM)
060 - 60 Amps (7PA, 7PB, 7PD, 7PE, 7PF, 7PL, 7PM)
080 - 80 Amps (7PA, 7PD, 7PL, 7PM)
Output Specifications
Model 7PT
Nominal Voltage
240V
Nominal Current*
12A
Non-repeatable Surge Current
160A
128
I2t for fusing (10 ms)
Non-repeatable Peak Voltage
900V
∆V/∆t
250V/µs
Peak Reverse Voltage
800V
18W
Total Power Dissipation (I=Imm)
Weight (grams)
510g
240V
18A
208A
259
900V
250V/µs
800V
27W
510g
Models 7PA , 7PL, 7PD and 7PM
Nominal Voltage
400V
Nominal Current*
25A
Non-repeatable Surge Current
280A
I2t for fusing (10 ms)
550
Non-repeatable Peak Voltage
1300V
∆V/∆t
500V/µs
Peak Reverse Voltage
1200V
Total Power Dissipation (I=Imm)
30W
Weight (grams)
630g
1415-DB-010-0-01
400V
35A
400A
860
1300V
500V/µs
1200V
45W
630g
400V
45A
400A
860
1300V
500V/µs
1200V
55W
900g
400V
60A
1200A
10180
1300V
500V/µs
1200V
75W
1100g
400V
80A
1200A
10180
1300V
500V/µs
1200V
100W
2000g
Barber-Colman Company
600V
600V
600V
600V
600V
25A
35A
45A
60A
80A
280A
400A
400A
1200A
1200A
550
860
860
10180
10180
1700V
1700V
1700V
1700V
1700V
1000V/µs 1000V/µs 1000V/µs 1000V/µs 1000V/µs
1600V
1600V
1600V
1600V
1600V
30W
45W
55W
75W
100W
630g
630g
900g
1100g
2000g
3
Series 7 Power Controllers
Models 7PB and 7PE and 7PF
Nominal Voltage
400V
Nominal Current*
20A
Non-repeatable Surge Current
280A
I2t for fusing (10 ms)
550
Non-repeatable Peak Voltage
1300V
∆V/∆t
500V/µs
Peak Reverse Voltage
1200V
Total Power Dissipation (I=Imm)
50W
Weight (grams)
1800g
400V
40A
400A
860
1300V
500V/µs
1200V
90W
1800g
400V
60A
1200A
10180
1300V
500V/µs
1200V
130W
1800g
600V
600V
600V
20A
40A
60A
280A
400A
1200A
550
860
10180
1700V
1700V
1700V
1000V/µs 1000V/µs 1000V/µs
1600V
1600V
1600V
50W
90W
130W
1800g
1800g
1800g
Input Specifications
Minimum
Holding
Current
Leakage
Current
Minimum
Latching
Voltage
Voltage Drop
on Power
Semiconductor
Control Type
Control Voltage
Input Current
Insulation
between
Power Circuit
and
Earth
Insulation
between
Command
and
Power Circuits
Insulation
Resistance
4
7PT
Single Phase
7PD
Single Phase
7PA
Single Phase
7PL
Single Phase
7PM
Single Phase
7PE
Three Phase
7PB
Three Phase
7PF
Three Phase
50 mA rms
50 mA rms
500 mA rms
500 mA rms
50 mA rms
50 mA rms
500 mA rms
500 mA rms
10 mA rms
10 mA rms
10 mA rms
10 mA rms
10 mA rms
10 mA rms
10 mA rms
10 mA rms
20V
20V
40V
40V
20V
20V
40V
40V
1.8V
1.2V
1.2V
1.2V
1.2V
1.2V
1.2V
1.2V
On/Off
Off
<2
On/Off
Off
<2
On/Off
Off
<2
On
4.5 to 35 Vdc
15 mA
15 mA
On/Off
Off
< 4 Vac
On
24 Vac
(±15%)
< 33 mA
Linear
On
4.5 to 35 Vdc
On/Off
Off
< 10 Vac
On
100 to 240 Vac
(±10%)
< 33 mA
4 to 20 mA
15 mA
On/Off
Off
< 10 Vac
On
100 to 240 Vac
(±10%)
< 33 mA
On/Off
Off
< 4 Vac
On
24 Vac
(±15%)
< 33 mA
1800 Vrms
for 1 minute
3000 Vrms
for 1 minute
2200 Vrms
for 1 minute
2200 Vrms
for 1 minute
3000 Vrms
for 1 minute
3000 Vrms
for 1 minute
2200 Vrms
for 1 minute
2200 Vrms
for 1 minute
7500 Vpk
for 1 minute
7500 Vpk
for 1 minute
3500 Vpk
for 1 minute
3500 Vpk
for 1 minute
7500 Vpk
for 1 minute
7500 Vpk
for 1 minute
3500 Vpk
for 1 minute
3500 Vpk
for 1 minute
>100MΩ
at 500 Vdc
>100MΩ
at 500 Vdc
>1MΩ at 500 Vdc
(400V)
>2MΩ at 500 Vdc
(600V)
>100MΩ
at 500 Vdc
On
9 to 35 Vdc
Operational
Temperature
0 to 50°C (32 to 122°F)
Humidity
20 to 85% RH, non-condensing
Storage
Temperature
-20 to 70°C (-4 to 158°F)
Protection
IP20
Mounting
Vertical; rear of board on wall or DIN rail
Terminals
Screw, with front access
Load Type
Resistive
Barber-Colman Company
1415-DB-010-0-01
Series 7 Power Controllers
Recommended Fusing
Contactor/Power Controller
Amps - Volts
12 - 240
Model 7PT
18 - 240
25 - 400
35 - 400
45 - 400
Model 7PA, 7PD, 7PL & 7PM
60 - 400
80 - 400
Fuse Model
6600.CP.URGB.14.51/20
Bussman
FWP.20B.14F
Ferraz
6600.CP.URGB.14.51/32
Bussman
FWP.30B.14F
Ferraz
6600.CP.URGA.22X58/32
Bussman
FWP.32A.22F
Gould
52443
Ferraz
6600.CP.URGA.22X58/50
Bussman
FWP.50A.22F
Gould
53251
Ferraz
6600.CP.URGA.22X58/50
Bussman
FWP.50A.22F
Gould
53251
Ferraz
6600.CP.URGA.22X58/80
Bussman
FWP.80A.22F
Gould
53259
Ferraz
6600.CP.URGA.22X58/100
Bussman
FWP.100A.22F
Gould
53263
20 - 600
Ferraz
6600.CP.URD.22X58/32
35 - 600
Ferraz
6600.CP.URD.22X58/50
45 - 600
Ferraz
6600.CP.URD.22X58/50
60 - 600
Ferraz
6600.CP.URD.22X58/80
80 - 600
20 - 400
40 - 400
Model 7PB, 7PE & 7PF
1415-DB-010-0-01
Supplier
Ferraz
Ferraz
6600.CP.URD.22X58/100
Ferraz
6600.CP.URGA.22X58/32
Bussman
FWP.32A.22F
Gould
52443
Ferraz
6600.CP.URGA.22X58/50
Bussman
FWP.50A.22F
Gould
53251
Ferraz
6600.CP.URGA.22X58/80
60 - 400
Bussman
FWP.80A.22F
Gould
53259
20 - 600
Ferraz
6600.CP.URD.22X58/32
40 - 600
Ferraz
6600.CP.URD.22X58/50
60 - 600
Ferraz
6600.CP.URD.22X58/80
Barber-Colman Company
5
Series 7 Power Controllers
Single Phase Wiring
WARNING!
The SSR assembly is not a replacement for a disconnect switch,
which must always be installed in the supply feeder!
Model 7PD, 7PM, 7PT
Power
Line
Model 7PA, 7PL
Power
Line
L1
N
Earth
Single Phase
Connection
1
Single Phase
Connection
2
1
L1
N
Earth
Barber-Colman
3
5
6
3
4
OH
SV
LOW
HIGH
AT
ON
3
LOW
OUT
4
HIGH
AT
A/C
Source
AT
FUNC
5 6
7SD
Three Phase
Without Neutral
Connection
1
2
1
Three Phase
Without Neutral
Connection
2
1
2
1
3
5
OH
SV
6
4
3
5
6
4
ON
OH
4
3
ON
LOW
OUT
AT
3
5 6
HIGH
7SD
3
4
3
ON
OH
4
3
5 6
Delta Connection
Star Connection
Without Neutral
Star Connection
Without Neutral
Power
Line
1
2
1
1
2
2
1
1
2
2
5
6
4
ON
4
5 6
1
R/L1
S/L2
T/L3
N
Earth
Three Phase
With Neutral
Connection
1
2
1
2
1
2
2
1
1
2
2
1
2
Controller
Barber-Colman
Barber-Colman
3
5
6
4
3
5
6
4
3
5
6
3
4
°F
SV
AT
5
6
4
3
5
6
4
3
5
6
4
°F
OH
3
ON
OH
4
3
ON
OH
4
3
FUNC
7SD
ON
ALM
Star Connection With Neutral
5 6
5 6
4
OUT
OH
SV
LOW
AT
5 6
Signal
6
A/C
Source
Delta Connection
R/L1
S/L2
T/L3
N
Earth
HIGH
6
Signal
Controller
LOW
AT
FUNC
5 6
Signal
Three Phase
With Neutral
Connection
5
OH
4
AT
AT
2
°F
SV
ALM
FUNC
7SD
OUT
1
Barber-Colman
3
ALM
2
2
Controller
°F
Power
Line
1
2
Barber-Colman
HIGH
4
5 6
2
1
1
Controller
LOW
3
Power R/L1
Line S/L2
T/L3
Earth
Power R/L1
Line S/L2
T/L3
Earth
AT
4
ON
Signal
Signal
OUT
6
OH
SV
ALM
FUNC
7SD
ALM
5
°F
°F
AT
2
Controller
Barber-Colman
OUT
2
1
2
Controller
ALM
1
HIGH
AT
FUNC
7SD
A/C
Source
3
ON
OH
4
3
5 6
5 6
ON
OH
4
3
ON
4
5 6
Signal
Star Connection With Neutral
Barber-Colman Company
1415-DB-010-0-01
Series 7 Power Controllers
Mounting
Model 7PT
Dimensions shown in inches (millimeters in parenthesis)
2
OH
5.31 (135)
1
4.92 (125)
2.52 (64)
1.77 (45)
4.65 (118)
3.82 (97)
3.39 (86)
ON
3
4
56
Ø 0.177
(04.5)
1 (25)
1.38 (35)
12 - 18 Amps
Model 7PD, 7PA, 7PL, 7PM
Dimensions shown in inches (millimeters in parenthesis)
2
4.65 (118)
1.77 (45)
4.92 (125)
1
1
2
3 564
OH
ON
3
4
5.31 (135)
2.52 (64)
4.78 (121.5)
4.33 (110)
56
Ø 0.177
(04.5)
1 (25)
1.38 (35)
25 - 35 Amps
1415-DB-010-0-01
Barber-Colman Company
7
Series 7 Power Controllers
Mounting (continued)
Model 7PD, 7PA, 7PL, 7PM
Dimensions shown in inches (millimeters in parenthesis)
2
4.65 (118)
1.77 (45)
4.92 (125)
1
1
5.31 (135)
2.52 (64)
4.78 (121.5)
4.33 (110)
2
3 564
OH
ON
3
4
56
1 (25)
2.07 (52.5)
Ø 0.177
(04.5)
45 Amps
Model 7PD, 7PA, 7PL, 7PM
Dimensions shown in inches (millimeters in parenthesis)
4.78 (121.5)
4.33 (110)
1
2
2
5.31 (135)
1
4.92 (125)
4.65 (118)
1.77 (45)
2.52 (64)
2.07 (52.5)
3 564
OH
ON
3
4
56
Ø 0.177
(04.5)
1 (25)
2.75 (70)
60 Amps
8
Barber-Colman Company
1415-DB-010-0-01
Series 7 Power Controllers
Mounting (continued)
Model 7PD, 7PA, 7PL, 7PM
Dimensions shown in inches (millimeters in parenthesis)
1 (25)
1 (25)
1.77 (45)
Ø 0.177
(04.5)
3
5.31 (135)
4.92 (125)
1
OH
2
ON
4
5.31 (135 )
80 Amps
1415-DB-010-0-01
Barber-Colman Company
9
Series 7 Power Controllers
Three Phase Wiring
WARNING!
The SSR assembly is not a replacement for a disconnect switch,
which must always be installed in the supply feeder!
Model 7PE
Model 7PB, 7PF
Power R/L1
Line S/L2
T/L3
Earth
Power R/L1
Line S/L2
T/L3
Earth
Three Phase
Without Neutral
Connection
1
3
Three Phase
Without Neutral
Connection
5
SV
AT
HIGH
OH
ON
°F
°F
LOW
5
Barber-Colman
Barber-Colman
ALM
3
Controller
Controller
OUT
1
AT
OH
ON
2
4
SV
ALM
LOW
OUT
6
HIGH
AT
FUNC
FUNC
A1A2
7SD
AT
7SD
A/C
Source
Signal
Signal
Delta Connection
Delta Connection
Star Connection
Without Neutral
Star Connection
Without Neutral
4
2
6
A1A2
Mounting
Model 7PB, 7PE, 7PF
Dimensions shown in inches (millimeters in parenthesis)
OH
2
0.177
(04.5)
10
3
5
5.31 (135)
1
4.92 (125)
1.77 (45)
4.65 (118)
2.52 (64)
4.78 (121.5)
4.33 (110)
ON
4
6
4.15 (105.5)
Barber-Colman Company
1 (25)
1415-DB-010-0-01
Series 7 Power Controllers
Formulas
Sizing
Power/nominal current conversion
The following formulas are provided to simplify model selection. These formulas enable you
to calculate the nominal current of each SSR when the total load power is known. The load
must be resistive so that in the following formulas, the cos ø will be considered equal to 1.
The formulas related with the three phase application are referred to a balanced three phase
system only.
Single Phase Connection
I RMS =
where:
P
VRMS
P = Power (in Watts)
VRMS = Phase to neutral or phase to phase voltage
IRMS = Nominal line current
Three Phase Without Neutral Connection (Star or Delta Application)
I RMS =
where:
P
VRMS • 3
P = Total load power (in Watts)
VRMS = Phase to phase voltage
IRMS = Nominal line current
Three Phase With Neutral Connection (Star Application)
I RMS =
where:
P
VRMS • 3
P = Total load power (in Watts)
VRMS = Phase to neutral voltage
IRMS = Nominal line current
Heat Generated by the Solid State Contactors
Full Load Current x 1.2 volts* x # of Legs of Control = Watts
*1.8 volts for 7PT
Example 7PE calculation: 60 amps x 1.2 volts x 2 = 144 Watts
1415-DB-010-0-01