CITY OF CHICAGO DEPARTMENT OF WATER MANAGEMENT STANDARD DETAILS FOR WATER MAIN INSTALLATIONS PREPARED BY: BUREAU OF ENGINEERING SERVICES April, 2009 City of Chicago Richard M. Daley Mayor Department of Water Management John F. Spatz, Jr. Commissioner This page intentionally left blank. TABLE OF CONTENTS GENERAL DETAILS G-1 PROJECT SIGN G-3 SAMPLE SYBOLOGY LEGEND G-4 (1 OF 2) LEGEND - SYMBOLS G-4 (2 OF 2) LEGEND – LINE STYLES WATER MAIN DETAILS D-2 FIRE HYDRANT SETTING DETAIL D-3 FIRE HYDRANT INSTALLATION DETAIL FOR VAULTED SIDEWALKS D-5 FIRE HYDRANT DRAIN DETAIL D-6 FIRE HYDRANT SUMP FOR RELOCATED HYDRANTS D-7 COLOR CODE FOR FIRE HYDRANTS D-8 WATER MAIN TRENCH DETAILS D-9 WATER MAIN TRENCH INSULATION DETAIL D-10 WATER MAIN POLYETHYLENE WRAP DETAIL D-11 THRUST RESTRAINT CONCRETE THRUST BLOCK DETAILS D-12 THRUST RESTRAINT RESTRAINED JOINT PIPE D-13 PRECAST VALVE BASIN FOR PIPES UP TO 16-INCH DIAMETER D-14 BRICK MASONRY VALVE BASIN D-16 TYPICAL 1-INCH TO 2-INCH WATER SERVICE D-18 CASING PIPE UNDER RAILROAD TRACK DETAIL D-19 (1 OF 2) WATER MAINS CROSSING OVER SEWERS AND HOUSE DRAINS D-19 (2 OF 2) WATER MAINS CROSSING UNDER SEWERS AND HOUSE DRAINS D-20 (1 OF 2) GENERAL NOTES WATER MAIN CONTRACTS D-20 (2 OF 2) GENERAL NOTES WATER MAIN CONTRACTS – CON’T D-23 NEW COPPER 1-INCH WATER SERVICE STANDARD METER VAULT D-24 NEW COPPER 1.5 N. & 2 IN. WATER SERVICE STANDARD METER VAULT D-25 3 INCH, 4 INCH, 6 INCH, 8 INCH & 12 INCH METER VAULTS D-26 12 INCH METER VAULT WITH CHECK VALVE D-27 TYPICAL METER INSTALLATION FOR 1 INCH WATER SERVICE WITH LAWN HYDRANT AND BACKFLOW PREVENTOR D-28 ELECTRICAL CONTINUITY BRACKET FOR TRANSITION COUPLING D-30 TYPICAL SERVICE RECONNECTION 3 INCH AND LARGER USING MJ RESILIENT WEDGE VALVE D-31 SERVICE PIPE INSULATION 1 FEEDER MAIN DETAILS FM-1 INSPECTION MANHOLE FM-4 PITOMETER TAP BASIN PRECAST CONCRETE FM-5 FIRE HYDRANT SETTING 16 INCH & LARGER WATER FM-13 BUTTERFLY VALVE FM-14 TORQUE OVERLOAD PROTECTOR FM-15 BUTTERFLY VALVE BASIN PRECAST CONCRETE FM-16 (1 OF 2) BUTTERFLY VALVE BASIN – MASONRY PLAN FM-16 (2 OF 2) BUTTERFLY VALVE BASIN – MASONRY SECTIONAL VIEW FM-18 (1 OF 2) TYPICAL BLOW-OFF FIRE CISTERN – MASONRY PLAN FM-18 (2 OF 2) TYPICAL BLOW-OFF FIRE CISTERN – MASONRY SECTIONAL VIEW FM-19 TYPICAL BLOW-OFF FIRE CISTERN – PRECAST CONCRETE 2 "WATER" OR "SEWER" AS APPROPRIATE 2’-0" 3’-0" BUILDING CHICAGO TOGETHER RICHARD M. DALEY, MAYOR DEPARTMENT OF WATER MANAGEMENT For information about this project, please call (312) 747-3570. 4’-0" 1/2 " PLYWOOD FOR CONSTRUCTION SIGN MOUNTED TO STAND 6" 2’-0" 6" 3’-0" 18" C L 18" 4" x 4" WOOD POSTS ANCHORED INTO GROUND AND BRACED AS REQUIRED OR AS CALLED FOR IN SPECIFICATIONS 4" 4" 3’-0" NOTES: 1. TWO SIGNS (ONE ON EACH END OF EACH PIPE PROJECT) MUST BE DISPLAYED FROM THE TIME CONSTRUCTION BEGINS TO THE TIME THAT PAVEMENT IS RESTORED. 2. THE LOCATION OF THE SIGN WILL BE DETERMINED FOR THE RESIDENT ENGINEER. 3. AFTER THE COMPLETION OF THE CONTRACT THE SIGN WILL BE PROPERTY OF THE CITY OF CHICAGO AND MUST BE DELIVERED TO THE APPROPRIATE DISTRICT YARD UNLESS ORDERED TO DISCARD BY THE COMMISSIONER. REV:04.07 PROJECT SIGN G -1 REV:04.07 SAMPLE SYMBOLOGY LEGEND G -3 VALVE BOX EXIST 1/32 WATER MAIN BEND EXIST WATER MAIN PITOMETER TAP WITH WATER VALVE EXIST 1/16 WATER MAIN BEND EXIST WATER MAIN TAP LEGEND - SYMBOLS POINT ELEVATION SIGNAL SIGNAL MANHOLE EXIST TELEPHONE POLE EXIST TELEPHONE PEDESTAL MANHOLE EXIST TRAFFIC SIGN MONUMENT EXIST TELEPHONE TELEPHONE SYMBOLS EXIST TRAFFIC EXIST TRAFFIC TRAFFIC SYMBOLS SURVEY TRAVERSE 100.5 EXIST STREET EXIST CONC I.D. MANHOLE SURVEY SYMBOLS EXIST STORM WATER EXIST SANITARY SEWER MANHOLE EXISTING WATER SIGNAL SYMBOL HANDICAPPED MANHOLE PIPE BREAK SYMBOL EXIST UTILITY POLE CONCRETE BLOCK EXIST FLAG POLE PROFILE RAILROAD TRACK MISCELLANEOUS SYMBOLS EXIST RAILROAD EXIST UNKNOWN IRON PIPE NORTH ARROW EXIST GUY WIRE COMMUNICATION RAILROAD CORNER RAMP DISABLED BRIDGE COLUMN MANHOLE EXIST SURVEY EXIST GAS VALVE MANHOLE MANHOLE FIRE ALARM BOX F MONITORING WELL DECIDUOUS EXIST TREE THRUST BLOCK CONCRETE HORIZONTAL EXIST BOLLARD CONIFEROUS EXIST TREE VEGETATION SYMBOLS EXISTING COM ED EXIST ELECTRIC ELECTRICAL SYMBOLS VALVE EXIST GAS MANHOLE-FEEDER MAIN TAP GRAVEL HATCH SOIL BORING EXISTING BUSH EXIST LIGHT POLE MANHOLE EXIST CABLE T.V. CONCRETE HATCH EXIST MAIL BOX STUMP EXIST TREE LIGHT CONTROL BOX EXIST. STREET S PEDESTAL EXIST CABLE T.V. CONCRETE HATCH GUARDRAIL EXIST MARSH SYMBOL LIGHT EXIST CARRIAGE EARTH HATCH PROPOSED WATER METER MAIN TEE NEW WATER MAIN BEND NEW 1/4 WATER SLEEVE PROPOSED WATER MAIN INSPECTION MANHOLE MAIN BEND NEW 1/32 WATER NEW REDUCER HYDRANT NEW FIRE PROPOSED WATER MAIN CABLE T.V. SYMBOLS PROPOSED WATER CAP OR PLUG MAIN BEND NEW 1/16 WATER CONNECTION NEW TAPPING BUFFALO BOX PROPOSED WATER NEW WATER MAIN MAIN BED NEW 1/8 WATER NEW WEDGE VALVE NEW WATER MAIN BEND PROPOSED WATER SYMBOLS EXIST 1/8 WATER EXIST INSPECTION GAS SYMBOLS EXISTING FLARED END INSPECTION MANHOLE PROPOSED STORM EXIST PROPERTY PIPE RISER UP CISTERN EXIST WATER MAIN MAIN BEND WEDGE VALVE EXIST FIRE EXIST 1/4 WATER EXIST WATER WATER CATCH BASIN PIPE RISER DOWN BLOWOFF EXIST WATER MAIN EXIST STAND PIPE RAILROAD SYMBOLS CROSS SURVEYED CHISLED SEWER MANHOLE PROPOSED PRESSURE GAGE MAIN CAP OR PLUG CONTROL BOX WAY MARKER EXIST RIGHT OF WATER INLET EXIST STORM MAIN 45 DEG BEND EXIST FEEDER REDUCER HYDRANT EXIST FIRE EXIST TRAFFIC T MONUMENT SURVEY CONCRETE WATER CATCH BASIN EXIST STORM (UP - DOWN) SEWER MANHOLE PRESSURE VALVE (RIGHT - LEFT) NO. BUTTERFLY VALVE EXIST WATER MAIN CROSS EXIST WATER MAIN METER CUT-OFF EXIST WATER EXIST WATER WATER SERVICES PRESSURE VALVE NO. CONNECTION EXIST TAPPING MAIN TEE EXIST WATER BUFFALO BOX EXIST WATER EXIST COMBINED SEWER SYMBOLS RESTRAINED JOINT PIPE EXIST WATER EXIST MANHOLE W EXISTING WATER SYMBOLS I REV:06.07 G -4 SHT. 1 OF 2 REV:06.07 LEGEND - LINE STYLES G -4 SHT. 2 OF 2 SYMBOL Existing-Gas Abandoned-Gas Abandoned-Sewer Proposed-Sediment Force Main Existing-Sediment Force Main Proposed-Sewer Lateral Proposed-Sewer Existing-Sewer Existing-Telephone Existing-Cable TV Existing-ComEd Existing-City Electric Proposed-Pavement Edge of Water Proposed-Ditches-Creeks- Proposed-Sidewalk Proposed-Curb Existing-Woods Tree Line Existing-Hedge Line Existing-City Press Electrical Existing-City Limits Boundary Line Existing-Chicago Park District Line Existing-Steam and Cooling Pipes Car Tracks Existing-Buried Street Existing-Railroads Existing-CTA Buried Electric Cables Existing-Fence Dead Ends-Retaining Walls Existing-Embankments- Existing-Edge of Pavement Edge of Water Existing-Ditches-Creeks- Proposed-ROW Existing-Easement Existing ROW (Elevated) Existing ROW (Vacated) Existing ROW Abandoned-Water Main (By Others) Proposed-Water Main B-Box to Property Proposed-New Water Services WM to B-Box Proposed-New Water Services Proposed-Water Main Existing-Sidewalk Existing-Water Services DESCRIPTION Existing-Curb SYMBOL Existing-Water Main DESCRIPTION WATERPROOFING 8" 1" SOFT COPPER WATER SERVICE TUBING TO STANDARD HYDRANT PIER DRAIN. JOINT OF SIDEWALK CURB OVER CENTER OF WALL ABOVE 3’-6" STONE ABOVE TO COME 3’-6" 8" 8" WATERPROOFING PLAN VIEW 1/4 " EXPANSION JOINT TOP FLANGE FILL WITH TAR SIDEWALK CURB PAVEMENT TO BE FILLED WITH SAND AFTER HYDRANT IS SET 6’-9" 8" 3’-6" BLOCKING WATERPROOFING I.D.O.T. ROADWAYS 1" FLEXIBLE COPPER 8" BRICK OR CONCRETE WALL 2’ OR 2.5’ ALONG TUBING TO DRAIN BLOCKING CONCRETE REINFORCED CONCRETE PIER SUPPORT BRACKET(S) TO SUIT CONDITIONS THIS DETAIL IS PROVIDED FOR REFERENCE PURPOSES ONLY SECTION VIEW AND IS NOT A C.D.W.M. WATER MAIN STANDARD FIRE HYDRANT INSTALLATION DETAIL REV:07.07 FOR VAULTED SIDEWALKS D -3 HYDRANT A BRANCH PROP. CURB & GUTTER 1 1/2 ’ EXIST. CURB 2’ & GUTTER 6" 2’ 9" 3/4 " STRAIGHT METER COUPLING A 2’-0" CITY ROADWAYS 2’-6" I.D.O.T. ROADWAYS PROP. CURB & GUTTER EXIST. CURB & GUTTER MECHANICAL JOINT IF TRANSITION SLEEVE REQ’D 6" PROVIDE CONCRETE THRUST BLOCK ON HYDRANT 3" OF BITUMINOUS HYDRANT BRANCH CONCRETE 8" MIN. 3’ 4’ x 4’ x 3’ SUMP SEE TILE DRAIN DETAIL 4’ VIEW "A-A" NOTE: WATER TABLE MUST BE BELOW BOTTOM OF DRAIN SUMP. FIRE HYDRANT SUMP DRAIN REV:04.07 FOR RELOCATED HYDRANTS D -6 CIRCULATED WATER MAINS 90’ 300’ 300’ 300’ 300’ 90’ OR OR LESS LESS B B B B B Y Y R R R R W W WATER MAINS LARGER THAN 16-INCH Y Y Y 12-14-16-INCH WATER MAINS Y R R Y R W 12 INCH OR LARGER WATER MAIN 6-INCH WATER MAINS W W W 4-INCH WATER MAINS UNCIRCULATED WATER MAINS-DEAD END 90’ 300’ 300’ 300’ 300’ 300’ 300’ 90’ OR OR LESS LESS B B B B W.M. LARGER THAN 16-INCH Y Y Y Y W W W W W W W W 6 OR 8 INCH (150 OR 200mm) WATER MAIN 8-INCH WATER MAINS 12-16-INCH W.M. Y R 8-INCH W.M. R W W 4-INCH W.M. R 8-INCH W.M. 6-INCH W.M. W R W R 6-INCH W.M. W W W W W W 4-INCH W.M. B-BLUE FLANGE Y-YELLOW FLANGE R-RED FLANGE W-WHITE FLANGE ALL PUBLIC FIRE HYDRANTS ARE TO BE PAINTED RED EXCEPT FOR THE TOP FLANGES WHICH MUST BE COLOR CODED. REV:04.07 COLOR CODE FOR FIRE HYDRANTS D -7 D+3’ 6" (MIN.) BACKFILL MATERIAL FINE SAND (FA7) MIN. 2’ WIDE BY 4" 4" THICK INSULATION BOARD (USE 2-2" THICK BOARDS). 6" 5 FEET OF COVER IS LESS THAN PROVIDE INSULATION WHEN DEPTH EXISTING SURFACE MASTIC AT ALL JOINTS EXTEND INSULATION BOARD D DOWN SIDES TO 6" BELOW 6" WATER MAIN OR SERVICE. 1’-6" (MIN.) WATER MAIN PIPE BEDDING MATERIAL NOTES: 1. INSULATION BOARD TO BE CLOSED CELL, EXTRUDED POLYSTYRENE FOAM MEETING ASTM 578, TYPE VI, 40 PSI COMPRESSING STRENGTH (ASTM D1621) 0.1% MAX. WATER ABSORPTION (ASTM C272). 2. BACKFILL MATERIAL AROUND INSULATION MUST BE FINE SAND FREE FROM ROOTS, ORGANIC MATTER, OR OTHER INJURIOUS MATERIALS. 3. OVERLAP ALL INSULATION BOARD JOINTS. REV:04.07 WATER MAIN TRENCH INSULATION DETAIL D -9 12" MIN. 4 MIL POLYETHYLENE WRAP 12" MIN. 2" ADHESIVE TAPE WATER MAIN PIPE 2" ADHESIVE TAPE 2" ADHESIVE TAPE CHART "A" POLYWRAP FLAT TUBE WIDTHS PIPE DIAMETER D.I.P. WITH PUSH-ON D.I.P. WITH (IN.) JOINTS (IN.) MECHANICAL JOINTS (IN.) 4 14 16 6 17 20 8 21 24 12 29 30 16 37 37 24 53 53 NOTES: 1. USE ONE LENGTH OF POLYETHYLENE TUBE WRAP FOR EACH LENGTH OF PIPE, OVERLAPPED AT PIPE JOINTS AND FOLD EXCESS OVER TOP OF TUBE FOR SLACK REDUCTION. 2. USE CHART "A" TO SELECT SIZE OF WRAP. WATER MAIN REV:04.07 POLYETHYLENE WRAP DETAIL D -10 2’ MINIMUM 2’ MIN. 2’ MIN. D W W D D PLAN VIEW PLAN VIEW PLAN VIEW DEAD END THRUST BLOCK BEND THRUST BLOCK TEE THRUST BLOCK H H H TRENCH 2’ MIN. 2’ MIN. 2’ MIN. PROFILE PROFILE PROFILE DEAD END THRUST BLOCK BEND THRUST BLOCK TEE THRUST BLOCK HORIZONTAL THRUST BLOCK DETAILS TABLE 1 PIPE HORIZONTAL HORIZONTAL DEAD END & TEE H SIZE 1/4 BEND 1/8 BEND INCH DIA. D H W CY D H W CY D H W CY 16 1 5.5 4.5 2 1 6.5 5 2.5 1 4.5 4 1.5 12 1 3.5 3.5 1 1 4 4 1.5 1 3 3 .75 8 .5 2.5 2.5 .5 .5 3 3 .5 .5 2 2 .3 PLAN VIEW PIPE HORIZONTAL SIZE " 12 D EPOXY COATED #5 REBARS (ASTM A615 GRADE 60) (TYP.) 1/16 BEND INCH DIA. D H W 16 1 3.5 12 1 8 .5 D H W CY 3.5 1 1 2.5 2.5 .6 2.5 2.5 .5 1 2 2 .4 1.5 1.5 .25 1.5 1.5 .25 .5 TABLE 2 W 2’ 1/32 BEND CY " 12 MIN. HORIZONTAL CONCRETE BLOCK PIPE VERTICAL VERTICAL SIZE 1/8 BEND 1/8 BEND BOTTOM INCH DIA. D H W CY D H W CY 16 7 6 6 11 2 4.5 4 2.25 12 5 6 5 7 2 3 3 1 8 4.5 4 4 3.5 2 2 2 .5 SIZE PER TABLE 2 UNDISTURBED SOIL D IS THE DIMENSION INTO UNDISTURBED GROUND IN FEET W CONCRETE BLOCK SIZE H IS HEIGHT OF THRUST BLOCK IN FEET PER TABLE 1 W IS WIDTH OF THRUST BLOCK IN FEET PROFILE ALL DIMENSIONS ARE MINIMUM. VERTICAL THRUST BLOCK DETAILS THRUST BLOCKS IN LOOSE FILL OR SAND AREAS ARE NOT INCLUDED IN THESE TABLES AND WILL REQUIRE ADDITIONAL ANALYSIS. NOTES: 1. FULL CONCRETE THRUST BLOCKS AS SHOWN ARE REQUIRED WHEN THRUST RESTRAIN IS NOT PROVIDED BY OTHER MEANS SUCH AS RESTRAINED JOINT PIPE. 2. WHEN THRUST RESTRAINT GLANDS ARE INSTALLED FOR THE CONNECTIONS, CONCRETE THRUST BLOCKS SHALL BE PROVIDED UP TO THE THE DOTTED LINE AS SHOWN. 3. ALL BOLTS, NUTS, THRUST RESTRAINT GLANDS AND FITTINGS SHALL BE WRAPPED WITH POLYETHYLENE TUBING TO PREVENT CORROSION AND CONCRETE ADHESION. 4. CONCRETE FOR THRUST BLOCKS MUST NOT CONTAIN FLY ASH. THRUST RESTRAINT REV:04.07 CONCRETE THRUST BLOCK DETAILS D -11 20’ 20’ 3’ 3’ L TEE SIZE L B 8" x 8" :(8", 12", 16" OR 24") x 12" 0 16" x 16" 42’ 36" x 24" 277’ B TEE HORIZONTAL TEES - LENGTH OF RESTRAINED JOINTS L1 PIPE SIZE 1/8 VERTICAL BENDS L2 L1 L2 8" 26’ 26’ 12" 37’ 11’ 16" 67’ 20’ 24" 67’ 20’ 1/8 VERTICAL BENDS - LENGTH OF RESTRAINED JOINTS DISTANCE OF RESTRAINED JOINTS REQUIRED EITHER SIDE OF BENDS L L PIPE SIZE L BEND SIZES 1/32 1/16 1/8 1/4 8" 3’ 6’ 12’ 29’ 12" 4’ 8’ 17’ 41’ 16" 7’ 15’ 30’ 73’ 24" 7’ 15’ 30’ 73’ HORIZONTAL BENDS - LENGTH OF RESTRAINED JOINTS NOTE: 1. MINIMUM LENGTHS OF PIPE REQUIRED TO RESTRAIN FITTINGS SHOWN. 2. LENGTHS BASED ON POLY-WRAPPED PIPE. THRUST RESTRAINT REV:04.07 RESTRAINED JOINT PIPE DETAILS D -12 FOR RESTRICTED HEADROOM, STANDARD FRAME AND USE ALTERNATE DESIGN W/ LID SET IN MORTAR BED PRE CAST FLAT SLAB TOP. DESIGN SLAB FOR H20 LOADING CONDITIONS. GRADE ADJUSTING RING(S) PRECAST REINFORCED CONCRETE MANHOLE CONCENTRIC CONE WITH MORTAR JOINT VARIES 24" BETWEEN RINGS 26" DEPTH VARIES 5’ DIA. SEAL JOINTS WITH MASTIC SEALANT WHEN MULTIPLE RISER PU SECTIONS ARE USED GATE VALVE 6 3/4 " FILL SPACE AROUND PIPE W/BRICK AND MORTAR A 1" TEST TAP 1" TEST TAP MORTAR JOINT MJ VALVE 1" THICK 8" EXPANSION WATER PIPE 8" B 32" MATERIAL LIFTING LIFTING LUG LUG 6" 8" 2" SIDE VIEW SEAL AROUND PIPE POURED CONCRETE OR CONCRETE BLOCK SUPPORT UNDER MAIN #4 EPOXY COATED REBARS COMPACTED 4" C/C BOTH WAYS GRANDULAR BEDDING A NOMINAL B PIPE SIZES OPENING DIMENSIONS A B 8" 11.0" 12.5" 12" 15.5" 16.5" 16" 19.5" 21.0" OPTIONAL SPLIT BOTTOM PRECAST VALVE BASIN REV:06.07 FOR PIPES UP TO 16" DIA. D -13 FOR RESTRICTED HEADROOM USE ALTERNATE DESIGN W/ PRE CAST FLAT SLAB TOP. DESIGN SLAB FOR H20 LOADING CONDITIONS. GRADE 36" MAX. 24" STANDARD FRAME AND LID 26" CORBELLED VARIABLE MAXIMUM CORBEL= 1 1/2 " 1" CORPORATION (2 REQ’D) 5’-0" DIA. PU OPENINGS TO BE TAPPED DRY. (NOT REQUIRED ON SIDE CONNECTIONS, SERVICE CONNECTIONS OR FIRE HYDRANT BRANCHES) GATE 1" EXPANSION MATERIAL VALVE 8" WATER PIPE 8" MORTAR JOINT 2" LUG 6" 6" LUG 7’-0" SIDE VIEW AROUND PIPE POURED CONCRETE OR CONCRETE BLOCK SUPPORT COMPACTED UNDER MAIN GRANULAR BEDDING FILL SPACE AROUND #4 EPOXY COATED REBARS 4" C/C BOTH WAYS PIPE W/ BRICK AND MORTAR NOTES: 1. PROVIDE 6" THICK COMPACTED CA-16 BEDDING 2. USE PRECAST CONCRETE BASE OR PROVIDE 6" (MIN.) THICK CONCRETE BASE POURED IN PLACE WITH #4 EPOXY COATED REBARS 4" C/C BOTH WAYS. 3. CUT LIFTING LUGS AFTER PLACING THE PRE-CAST SLAB IN POSITION. 4. ALL JOINTS AND BRICK MASONRY SHALL BE PLASTERED INSIDE AND OUTSIDE WITH 1:2 CEMENT MORTAR. 5. PRECAST CONCRETE TOP SLAB TO BE USED WHERE HEAD ROOM IS RESTRICTED. REV:04.07 BRICK MASONRY VALVE BASIN D -14 CONCRETE CURB VARIABLE GRADE STREET PAVEMENT ROUNDWAY (CURB STOP) DIRECT CONNECTION PROPERTY LINE CORPORATION COCK MIN. 5’-6" SHUT-OFF BOX WATER MAIN 12"x 12"x 2" PRE-CAST CONCRETE BLOCK CORPORATION COCK REV:04.07 SHUT-OFF BOX SIZE WEIGHT WEIGHT In. Lb. Lb. 1.0 3.00 7.25 1.5 10.00 7.25 2.0 16.50 7.25 TYPICAL 1" TO 2" WATER SERVICE D -16 PROPOSED D.I. RESTRAINED JOINT WATER PIPE C L RAILROAD TRACK OR OUTER MOST TRACK UNDER MULTIPLE TRACKS WITH SPACERS (SEE PLANS FOR NUMBER OF TRACKS) PROPOSED D.I. RESTRAINED JOINT WATER PIPE WITH SPACERS RECEIVING PIT 30’ MAIN TRACK OR PER PERMIT A PER PERMIT) ROAD 20’ SPUR TRACK 5.5’ ROAD (MIN. OR JACKING PIT A PROPOSED STEEL CASING END SEAL CASING PIPE (SEE NOTE 1) CASING END SEAL 10’ 10’ (SEE NOTE 1) SEE PLAN FOR LENGTH PROFILE N.T.S. CASING PIPE WATER MAIN STAINLESS STEEL CASING SPACER NON-CONDUCTIVE PLASTIC RUNNER SECTION A-A NOTES: 1. END SEAL - BRICK AND MORTAR OR SELF CURING RUBBER SEAL. 2. LENGTH OF CASING PIPES UNDER METRA TRACKS SHALL BE EXTENDED TO METRA R.O.W. LINES AND JACKING AND RECEIVING PITS ARE NOT TO BE LOCATED WITHIN TRACK R.O.W. THIS DETAIL IS PROVIDED FOR REFERENCE PURPOSES ONLY AND IS NOT A C.D.W.M. WATER MAIN STANDARD REV:07.07 CASING PIPE UNDER RAILROAD TRACK DETAIL D -18 GENERAL NOTES 1. LOCATION OF UTILITIES AND PROPERTY LINES ARE FROM THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND COMPLETENESS ARE NOT GUARANTEED. 2. THE CONTRACTOR MUST VERIFY THE LOCATION OF UNDERGROUND UTILITIES WITH THE UTILITY OWNERS PRIOR TO DOING ANY WORK IN THE VICINITY. THE CONTRACTOR MUST COMPLY WITH REQUIREMENTS OF UTILITY OWNERS REGARDING NOTICE OF WORK AND PROTECTION OF UTILITIES. THE CONTRACTOR MUST COMPLY WITH THE CITY OF CHICAGO, DEPARTMENT OF TRANSPORTATION DAMAGE PREVENTION PROTOCOL CITY INFRASTRUCTURE DEPARTMENTS. ALL UTILITIES MUST BE NOTIFIED AT LEAST 48 HOURS BEFORE CONSTRUCTION. (CALL DIGGER 312-744-7000). 3. TEST PITS MUST BE EXCAVATED IN ADVANCE OF PIPELINE CONSTRUCTION IN ORDER TO CONFIRM DEPTH AND LOCATION OF EXISTING UTILITIES AND WHEN DIRECTED BY THE DEPARTMENT MANAGER. NO ADDITIONAL PAYMENT WILL BE MADE FOR TEST PIT EXCAVATION. 4. IF ANY PUBLIC OR PRIVATE UTILITIES CROSS THE WATER MAIN TRENCH AND MUST REMAIN IN PLACE, THE CONTRACTOR MUST PROTECT SAID UTILITY IN CONFORMANCE WITH THE SPECIFICATIONS OR AS DIRECTED BY THE COMMISSIONER. 5. PROVIDE EROSION CONTROL IN ACCORDANCE WITH THE SPECIFICATIONS. 6. FITTINGS AND THEIR LOCATIONS INDICATED ON THE DRAWINGS ARE TENTATIVE. THE CONTRACTOR MUST COMPLETE THE INSTALLATION WITH THE NECESSARY FITTINGS DICTATED BY FIELD CONDITIONS. NO ADDITIONAL PAYMENT WILL BE MADE FOR DEVIATIONS FROM THE INDICATED FITTINGS. 7. WORK INDICATED ON THE PLANS AND NOT REFERENCED TO A BID ITEM IS CONSIDERED INCIDENTAL TO THE WORK TO WHICH IT APPLIES AND NO ADDITIONAL COMPENSATION WILL BE ALLOWED. 8. WATER MAIN AND FITTINGS LOCATIONS SHOWN ON THE DRAWINGS FOR THE NEW WATER MAINS AND APPURTENANCES MAY BE CHANGED BY THE COMMISSIONER DUE TO FIELD CONDITIONS. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR SUCH CHANGES, UNLESS PREVIOUSLY APPROVED BY THE COMMISSIONER. 9. THE CONTRACTOR MUST PROVIDE THRUST RESTRAINTS IN ACCORDANCE WITH THE SPECIFICATIONS. THE CONTRACTOR MUST FURNISH AND INSTALL MECHANICAL JOINT THRUST RESTRAINT GLANDS AT ALL FITTINGS AND MECHANICAL JOINTS. 10. THE CONTRACTOR MUST VERIFY THE OPERATION OF EVERY VALVE NECESSARY FOR THE REQUIRED WATER MAIN SHUT DOWN FOR EACH PIPE SECTION. FOR VALVES OR WATER MAINS UNDER 16-INCHES IN DIAMETER, THE WORK MUST BE DONE UNDER THE DIRECT SUPERVISION OF A DEPARTMENT REPRESENTATIVE AT LEAST 2 WEEKS PRIOR TO THE START OF THE JOB. A 24 HOUR ADVANCE NOTICE MUST BE GIVEN TO ALL CONSUMERS EFFECTED AND THE BUREAU OF OPERATIONS AND DISTRIBUTION. THE OPERATION OF ALL VALVES 16-INCHES IN DIAMETER AND LARGER MUST BE PERFORMED BY CITY FORCES PURSUANT TO A 72 HOUR ADVANCE NOTIFICATION TO THE DEPARTMENT. ANY VALVE FOUND NOT OPERABLE WILL BE REPAIRED OR REPLACED BY THE DEPARTMENT UNLESS DIRECTED OTHERWISE BY THE COMMISSIONER. 11. IN INSTANCES WHERE CHLORINATION IS TO BE DONE AGAINST ANY EXISTING VALVE, AT THE TIME THAT THE EXISTING WATER MAIN IS BREACHED FOR FINAL CONNECTION, THE CONTRACTOR IS TO VERIFY THAT THE EXISTING VALVES ARE IN GOOD OPERATING CONDITION AND DO NOT LEAK. ANY LEAKING VALVE SHOULD BE BROUGHT TO THE COMMISSIONERS’ ATTENTION AND BE REPAIRED OR REPLACED PRIOR TO MAKING PIPE CONNECTIONS TO THE EXISTING WATER MAIN. THE VALVE SHOULD REMAIN IN THE CLOSED POSITION UNTIL THE NEW WATER MAIN IS APPROVED FOR SERVICE. GENERAL NOTES REV:04.07 WATER MAIN CONTRACTS D -20 SHT. 1 OF 2 GENERAL NOTES (CONTINUED) ALL OPENINGS IN EXISITNG WATER MAINS MUST BE PLUGGED OR 12. CAPPED WITH DUCTILE IRON FITTINGS UNTIL THE MAIN IS ABANDONED. 13. ALL VALVE BASINS MUST BE CONSTRUCTED OF PRE-CAST REINFORCED CONCRETE UNLESS DIRECTED OTHERWISE BY THE COMMISSIONER. 14. NOTES INDICATING S.N.L., E.W.L., ETC., MEAN SOUTH OF THE NORTH PROPERTY LINE, EAST OF THE WEST PROPERTY LINE, ETC. AND ARE MEASURED FROM THE NEAREST STREET. 15. IF A STANDARD MECHANICAL JOINT SLEEVE DOES NOT FIT TO MAKE CONNECTION OF THE NEW PIPE TO THE EXISTING PIPE, A TRANSITION SLEEVE MUST BE USED. NO GRINDING OF THE EXISTING PIPE IS PERMITTED. 16. BURIED STREET CAR TRACKS ARE SHOWN FOR INFORMATIONAL PURPOSES ONLY. EXACT LOCATIONS AND DIMENSIONS ARE UNKNOWN UNLESS NOTED OTHERWISE. CAUTION SHOULD BE EXERCISED WHEN EXCAVATING IN THE STREETS CONTAINING BURIED STREET CAR TRACKS. BURIED TRACKS AND CABLES MAY BE USED FOR ELECTRICAL GROUNDING BY THE CHICAGO TRANSIT AUTHORITY OR MEMBERS OF THE CHICAGO AREA JOINT ELECTROLYSIS COMMITTEE STANDARDS. ELECTRICAL CONDUCTIVITY MUST BE MAINTAINED. 17. HOUSE DRAINS ARE NOT SHOWN ON THE DRAWINGS. THE CONTRACTOR MUST LOCATE ALL HOUSE DRAINS WITHIN THE AREA OF EXCAVATION AND MAKE ADJUSTMENTS AND/OR REPAIRS. 18. THE DEPARTMENT WILL PROVIDE THE NECESSARY I.E.P.A. WATER MAIN CONSTRUCTION PERMITS FOR THIS CONTRACT. 19. WORK WITHIN STATE ROUTES ARE NOTED ON THE DRAWINGS AND WILL REQUIRE I.D.O.T., REGION 1, UTILITY PERMITS. THE CONTRACTOR IS RESPONSIBLE FOR SECURING ALL PERMITS, INITIATED BY THE DEPARTMENT AND OBTAINING PERFORMANCE BONDS. ALL WORK MUST BE IN ACCORDANCE WITH I.D.O.T. PERMIT REQUIREMENTS. QUESTIONS SHOULD BE DIRECTED TO: I.D.O.T REGION ONE UTILITIES COORDINATOR AT (847) 705-4258. 20. ABANDON EXISTING WATER MAINS IN ACCORDANCE WITH THE SPECIFICATIONS. 21. SWAB PIPE AND FITTINGS THAT WILL NOT BE PRESSURE TESTED OR CHLORINATED WITH CHLORINE SOLUTION DURING INSTALLATION AND USE EXTRA PRECAUTION TO PREVENT SOIL AND DEBRIS FROM ENTERING THE PIPE. INCORPORATE UNTESTED PIPE INTO THE FLUSHING ROUTINE WHEN POSSIBLE. WHEN CONNECTING NEW PIPE TO THE EXISTING WATER SYSTEM, USE OPERATING PRESSURE TO VISUALLY INSPECT FOR LEAKS. WHEN FEASIBLE, PERFORM INSPECTION PRIOR TO BACKFILLING. COMPLY WITH ALL STANDARDS AND REQUIREMENTS OF THE BUREAU OF WATER QUALITY (312) 744-8190. GENERAL NOTES REV:04.07 WATER MAIN CONTRACTS D -20 SHT. 2 OF 2 A 58" E K 1’-6" 5" GRADE E J G H D FLOW 5’-0" MIN. D G F H INSIDE VAULT C I C 24" B B C C 1" METER VAULT VAULT CODE 11-8-200 A FRAME AND LID (NEENAH R1911C) B 1" TYPE K COPPER PIPE C FEMALE FLARED FITTING D 1" x 3/4 " BRASS BUSHING E F G 3/4 " BENT METER COUPLING METER FULL PORT CONTROL VALVE H MALE I.P.S. TO FLARED ADAPTER I 1" ROUNDWAY J SHUT-OFF BOX K EXTRA HEAVY SALT GLAZED VITRIFIED CLAY TILE PIPE NOTE: 1 1/2 " AND 2" METER VAULT CALL FOR 39" COVER. SEE NEXT PAGE. NEW COPPER 1" WATER SERVICE REV:04.07 STANDARD METER VAULT D -23 GRADE GRADE A B 30 " " 54 E M J 5" G 5" K F J J J C W M 54" FLO D J H K N J D G N I U SE I H G N O TI A FO A LT B U A E G V D SI IN F J J M M A B GRADE J 10 1/4 " C 54" 39" 5" 10 1/4 " 33 1/2 " J K FLOW I J H 15" I G H G 5’-0" J K F 54" N G E G COVER 25 1/4 "x 25 1/4 " A (NEENAH, R6662JP OR EQUAL) CENTERED OVER METER B PRECAST CONCRETE TOP C SOLID CONCRETE BLOCK OR PRECAST CONCRETE D ROUNDWAY E SHUT-OFF BOX F TYPE K COPPER G F.M. FLARED FITTING H MALE I.P.T. TO FLARED I FULL PORT CONTROL VALVE J BRASS NIP. K BRASS ELL. M BRASS UNION N METER NEW COPPER 1 1/2 " & 2" WATER SERVICES REV:04.07 STANDARD METER VAULT D -24 SIZE A 3" B 1’-0" C 1’-2" D 2’-6" E 1’-2" F SPOOL PIECE G H 1’-0" 8’-0" 6’-0" 1’-0" 8’-0" 6’-0" 1’-0" 10’-0" 6’-0" 1’-0" 10’-0" 6’-0" 1’-0" 10’-0" 6’-0" VARIES 1’-0" 4" 1’-2" 2’-6" 1’-2" SPOOL PIECE VARIES 1’-0" 6" 1’-2" 2’-6" 1’-2" SPOOL PIECE VARIES 1’-0" 8" 1’-2" 2’-6" 1’-2" SPOOL PIECE VARIES 12" 1’-0" 1’-2" 2’-6" 1’-2" SPOOL PIECE VARIES VAULT COVERS 14’ MAXIUM IF 8" 5’-0" CONCRETE COLLAR IS USED A B C E F SLEEVE W/LINK-SEAL (TYP.) 8" 9" 18" D SUMP PIT SUMP C FLOW H FLOW A D E STRAINER G D F METER 1" TAPS REQUIRED UPSTREAM AND DOWNSTREAM. ALL PIPES AND FITTINGS SHALL BE FLANGED AND SHALL CONFORM TO U.S.A. STANDARD A21.51-1965 (A.W.W.A.C. 151-65) AND SHALL HAVE ON OUTSIDE BITUMINOUS COATING OF EITHER COAL TAR OR ASPHALT BASE AND A CEMENT MORTAR LINING CONFORMING TO U.S.A. STANDARD A21.4-64 (A.W.W.A.C. 104-53). ALL METER VAULT COVERS AND LIDS SHALL BE HEAVY DUTY. 2 PIECE SHALL BE PLACED DIRECTLY ABOVE THE COMPOUND METER BYPASS. NO CENTER BRACE SHALL BE PERMITTED IN COVER FRAME. VAULT COVER SHALL MEASURE 49 1/2 " x 31 1/2 " AND COMPLY TO R6663NP NEENAH OR EQUAL. FOR METER READER ACCESS A 1’-11" COVER MUST BE INSTALLED IN CORNER OF VAULT ACCESS COVER TO CONFORM TO R1889 NEENAH OR EQUAL. LADDER TO BE DIRECTLY UNDERCOVER. FOR BLOCK CONSTRUCTION ON IRON RUNG LADDER ANCHORED TO WALL WITH STEPS 16" MAX. ON CENTER. FOR PRE-CAST VAULTS USE CAST IRON STEPS R1980-T. BOLTING TO BE INSTALLED IN VERTICAL AT 16" CENTERS. A SUMP PIT SHALL BE INSTALLED NEAR BUT NOT UNDER LADDER. NO MECHANICAL JOINT FITTING ALLOWED IN VAULT. BLOCK SUMP TO BE LOCATED NEAR ACCESS LADDER, BUT NOT UNDER LADDER. METER AND VAULTS ETC. TO BE CENTERED IN VAULT. REV:04.07 3", 4", 6", 8" & 12" METER VAULTS D -25 24" ROUND COVER OVER LADDER NEENAH R1900 C OR EQUAL 24"x 48" SPLIT COVER NEENAH R1877 E1 OR EQUAL PLAN VIEW ABOVE SURFACE 12’-0" 12" STRAINER TAP 12" VALVE 12" METER 5’-0" 2’-6" 12" CHECK VALVE 12" D.I. PIPE 2’-6" 12" VALVE 12" FLANGE TO MJ BELL ADAPTER 12" FLANGE TO MJ PE ADAPTER PLAN VIEW IN GROUND 12’-0" 9" 9" GRADE 2’-0" 24" REMOVEABLE ROOF SLAB 6" LINK-SEAL 16" SLEEVE POURED IN WALL 9" 2’-0" 6’-0" 7’-3" OF VAULT (TYP.) SUMP SUMP PIT SECTION VIEW IN GROUND NOTES: 1. ALL CONCRETE STRUCTURES SHALL BE WATER TIGHT, THE CONTRACTOR WILL BE REQUIRED TO TAKE SUCH MEANS NECESSARY TO CORRECT ANY AND ALL LEAKAGE THRU FLOORS OR WALLS OF STRUCTURE, WITHOUT ADDITIONAL COMPENSATION. 2. WALLS MAY BE CONSTRUCTED OF 8" CONCRETE BLOCK ON A CONCRETE FLOOR SLABS MAY BE PRECAST CONCRETE-OR THEY BE PRECAST CONCRETE REINFORCED AS REQUIRED. 3. METER AND PIPING TO BE SET BEFORE INSTALLING ROOF SLAB. 4. ALL METER VAULTS SHALL BE FURNISHED WITH GALVANIZED OR ALUMINUM LADDERS. ALL OPENINGS IN METER VAULTS SHALL BE SEALED WITH ’NO SHRINK’ GROUT. REV:04.07 12" METER VAULT WITH CHECK VALVE D -26 REV:04.07 TO PROTECT WATER SYSTEM FROM FREEZING 1 2 4 REMOVE AND STORE RPZ AND KEEP FROM FREEZING. OPEN LAWN HYDRANT AND LOOSEN METER NUT ON HOUSE SIDE OF METER A FRAME AND LID (NEENAH R1911C) B 1" TYPE K COPPER PIPE C FEMALE FLARED FITTING D 1"x 3/4 " BRASS BUSHING E BLOWOUT WATER LINES FROM RPZ TO METER AND FROM RPZ TO LAWN HYDRANT. 3/4 " BENT METER COUPLING F METER G FULL PORT CONTROL VALVE H MALE I.P.S. TO FLARED ADAPTER I 1" ROUNDWAY J SHUT-OFF BOX K EXTRA HEAVY SALT GLAZED VITRIFIED CLAY TILE PIPE IN SPRING REINSTALL RPZ AND ALSO HAVE RPZ TESTED BY LICENSED PERSONEL 5 WITH A PERMIT FROM WATER DEPT. IN CITY HALL. EACH RPZ MUST BE IDENTIFIED OR NUMBERED SO THAT RPZ WILL BE 6 REINSTALLED IN THE SAME LOCATION AT ALL TIMES. EACH LAWN HYDT. (HOSE CONNECTION) MUST BE MARKED 7 "NON POTABLE WATER DO NOT DRINK". BACKFLOW PREVENTOR ENCLOSURE NON POTABLE WATER STAMP ON LID LAWN HYDRANT STREET MIN. AND GUTTER BACKFLOW PREVENTOR 18" CURB REDUCED PRESSURE ZONE (RPZ) A GRADE CURB AND GUTTER STREET 2 3/4 " E K D BUFFALO BOX FLOW G E 2" PIPE CASING DEPTH OF H D F C INSIDE SUPPLY LINE BURY 5’-0" MIN. TYPICAL METER INSTALLATION FOR BLACKFLOW PREVENTOR 1" WATER SERVICE WITH LAWN HYDRANT AND 3 SHUTOFF WATER AT ROUNDWAY C VAULT 5’ MIN. RISER 24" GROUND DRAIN J TILE OR CORPORATION APPROVED COCK CONCRETE PIPE I MUST BE PLUGGED B 3/4 " I.P.S. B C D -27 C COMMON BRICK COMMON BRICK ROUNDWAY WATER MAIN I. INSTALLATION M.J. PLUG M.J. RESILIENT WEDGE VALVE TO BE BURIED (SIDEWAYS) SET: 1-4" 3BMJ TEE 1-8" MJ RESILIENT WEDGE VALVE 2-12" MJ RESTRAINT GLANDS 2-8" MJ RESTRAINT GLANDS 3BMJ TEE EXISTING 3’ OF 8" D.I.W.P. PROPOSED WATER MAIN SERVICE TEMPORARILY PLUG AND BRACE THE VALVE WITH:1-8" MJ PLUG EXISTING WATER MAIN NOTE: MINIMUM 4" TEE TO BE USED FOR 3" SERVICE CONNECTION. AFTER THE NEW WATER MAIN IS APPROVED, II. RECONNECTION CUT, CAP AND BRACE THE EXISTING 8" SERVICE WITH:1-8" MJ CAP 1-8" MJ RESTRAINT GLAND REMOVE TEMPORARY PLUG OF NOTE ABOVE AND CONNECT 8" SERVICE TO THE MJ RESILIENT WEDGE VALVE WITH:2-8"x 1/8 2BMJ BENDS 1-8" MJ SLEEVE MJ SLEEVE 7-8" MJ RESTRAINT GLANDS 8’ OF 8" D.I.W.P. 1/8 2BMJ BENDS SWAB THE NEW PIPE WITH HTH CHLORINE DURING THE INSTALLATION. BURY THE MJ RESILIENT WEDGE VALVE. MJ RESILIENT WEDGE VALVE CUT, CAP & BRACE TO BE BURIED (SIDEWAYS) THE EXIST. SERVICE 3BMJ TEE EXISTING SERVICE PROPOSED WATER MAIN NOTE: MECHANICAL JOINT THRUST RESTRAINT GLANDS OR APPROVED EXISTING WATER MAIN EQUIPMENT FITTINGS TO BE USED WITH ALL MJ FITTINGS. TYPICAL SERVICE RECONNECTION 3" AND REV:04.07 LARGER USING M.J. RESILIENT WEDGE VALVE D -30 6" 4" FINISHED GRADE 5’-0" 6" WATER MAIN SERVICE SIDE VIEW MIN. 2’ WIDE BY 4" 4" THICK INSULATION 4" 2’-0" BOARD TOP VIEW SERVICE PIPE INSULATION DETAILS NOTES: 1. BACK FILL MATERIAL AROUND INSULATION SHALL BE FINE SAND (FA7), FREE FROM ROOTS, ORGANIC MATTER, LEAVES OR OTHER INJURIOUS MATERIALS. 2. OVERLAP ALL INSULATION BOARD JOINTS. 3. INSULATION BOARD TO BE CLOSED CELL, EXTRUDED POLYSTYRENE FOAM MEETING ASTM 578, TYPE VI, 40 PSI COMPRESSING STRENGTH (ASTM D1621) 0.1% MAX. WATER ABSORPTION (ASTM C272). REV:04.07 SERVICE PIPE INSULATION DETAILS D -31 C L NEW INSPECTION MANHOLE ACCESS HOLE FOR FRAME/GRATE EXISTING FEEDER MAIN C L CREATE SUMP AT BOTTOM OF MANHOLE BY SLOPING FLOOR @ 1"/ft. SLOPE 6.7’ TYP. REDUCE IF REQUIRED TO CLEAR UTILITIES PLAN SEE INSPECTION MANHOLE C L FRAME AND LID DETAIL EXISTING GRADE 1’-6" SLAB TOP (SEE TOP HAVE FLAT 5’-0" (SEE VALVE BASIN DETAIL) (MIN.) WITH BRICK AND MORTAR MANHOLE TO 36" SEAL AREA AROUND PIPE 0’ TO 3’ VARIABLE SLAB SEE DETAIL SLAB DETAIL) PRECAST TOP 7" PRECAST HOLE/ARCH (MIN.) FOR TEE (IF C L REQUIRED TO ENLARGE USE MATERIAL CONCRETE SAW) PLACE CONCRETE FILL TO SLOPE BOTTOM OF MANHOLE TO PROVIDE 3’ EXPANSION VARIABLE (MAX.) SUMP AREA. 5’-0" SLO PE 6" COMPACTED BEDDING MATERIALS 8" PRECAST CONCRETE BASE SECTIONAL VIEW NOTE: ALL OPENINGS IN BASIN SHALL BE SEALED WITH "NO SHRINK" GROUT. REV:04.07 INSPECTION MANHOLE FM -1 USE CITY OF CHICAGO INSPECTION C L MANHOLE FRAME AND LID PRECAST CONCRETE 36" ADJUSTING RINGS GRADE GRADE 8" MIN. 34" 36" FILL CA-16 5’-0" (30" DIA. PIPE) VARIABLE * 6’-0" (36" DIA. PIPE) * 7’-0" (42" & 48" DIA. PIPE) 6" MIN. 6" MIN. PU C L 2" TEST TAP PIPE DIA. (SEE PLAN) PIPE O.D. 2’-3" MIN LUG 6" 6" LUG SECTIONAL VIEW SCALE: N.T.S. NOTE: 1. PROVIDE 6" THICK COMPACTED CA-16 BEDDING 4. PRECAST CONCRETE TOP SLAB TO BE USED WHERE HEAD ROOM IS REQUIRED. 2. USE PRECAST CONCRETE BASE OR PROVIDE 6" THICK IDOT CLASS ’SI’ CONCRETE BASE POURED IN PLACE WITH #4 EPOXY COATED REBARS 4" C/C BOTH WAYS. 5. THE LOCATION OF MANHOLE TO BE DETERMINED ON INDIVIDUAL BASIS. * 6. OPENING ON TOP SLAB TO BE CENTERED OVER 3. PROVIDE FOUR #4 REBAR LUGS FOR HANDLING. TEST TAP. CUT THE LUGS AFTER PLACING THE SLAB IN POSITION. PITOMETER TAP BASIN REV:07.07 PRECAST CONCRETE FM -4 A VALVE SIZE 24-INCH C B 18 5/8 " 18 5/8 " 30-INCH 21 1/2 " 36-INCH 25 7/16 " 42-INCH 29 7/8 " 48-INCH 34 1/16 " E 13 1/4 " 1 5/8 " 24 3/8 " 39" 18" 28 1/4 " 45 7/8 " 22" 32 7/8 " 53" 22" 37 1/8 " J OPERATOR SIZE D 31 9/16 " 59 7/8 " L N X 6 3/8 " 3/4 " 1 13/16 " 20 1" 36 7/8 " 10" 2" 24 1" 43 3/4 " 14" 2" 28 1 1/4 " 50 5/8 " 14" 2" 32 1 1/4 " 57 1/2 " 16" 24" M G 30" F 16 P Y Q VALVE NO.OF TURNS T-425 7 3/8 " 6" 7 1/8 " 6 7/8 " 9 1/2 " 6 5/8 " 24" 36" 75 T-425 8" 6 5/8 " 7 1/8 " 6 7/8 " 9 1/2 " 6 5/8 " 24" 48" 127 P 2 1/2 " SQ. NUT N COUNTER CLOCKWISE TO CLOSE UNLESS OTHERWISE SPECIFIED 4 7/8 " F = NO. AND SIZE OF BOLTS, H STRADDLE CENTERLINE. SPUR C = FLANGE O.D. G = BOLT CIRCLE Y GEAR TAGS E (TYP.) 4" MAX. D J A B X = LAYING LENGTH 3 1/2 " SPACE REQUIRED FOR THRUST BEARING COVER REMOVAL INSTALLATION DIAGRAM NOTE: 1. BUTTERFLY VALVES SHALL BE MANUFACTURED IN ACCORDANCE WITH AWWA SPECIFICATION C-504-87, CLASS 150B, SHORT BODY VALVE WITH MECHANICAL JOINT ACCESSORIES. 2. OPERATORS ARE EQUIPPED WITH OPEN/CLOSE INDICATING ARROW. ASSEMBLY OPEN CLOCKWISE. REV:07.07 BUTTERFLY VALVE FM -13 O PEN PAINT: TWO PART EPOXY PRIME COAT WITH TWO PART POLYURETHANE TOP COAT COLOR-U.S. PAINT #G9028 "SUN YELLOW" 2 7/16 " SEALANT: POLYURETHANE ADJUSTING SCREW: ALLOY STEEL 3" ANSI B18.6 NUT: CAST IRON ASTM A48 2 1/2 " SPRING GUIDE: ALLOY STEEL AISI 41L40 BEARING BALL: MFGS. STD. 9 1/8 " SPRING: CRV SPRING STEEL DIM 2093 GASKETS: CELLULOSE FIBER-STYRENE BUTADIENE DRIVE PLATE: CARBON STEEL AISI 1045 DRIVE ROLLER: ALLOY STEEL AISI 41L40 2 9/16 " RETAINER: CAST IRON ASTM A48 SPLINE HD SCREW: ALLOY STEEL ANSI B18.3 ENI PLATED WASHER: MOLYDISULFIDE FILLED NYLON SEAL RING: NITRILE BUTADIENE 4 1/2 " DETENT PIECE: SAE 123C CAST IRON SQ HD SET SCREW: ALLOY STEEL 1/2 " x 1" ANSI B18.6 ENI PLATED SOCKET HD SCREW: ALLOY STEEL ANSI B18.3 ENI PLATED 25 /8 " SOCKET: CAST IRON ASTM A48 REV:04.07 TORQUE OVERLOAD PROTECTOR FM -14 VALVE BUTTON C L C L + C L C L MASONRY SUPPORT C L C L C L USE CITY OF CHICAGO STANDARD FRAME WEIGHT 395 lbs. C L 26" AND STANDARD LID WEIGHT 152 lbs. 23" PRECAST CONCRETE GRADE LUG 6" 21" FILL CA-16 24" 5" 5" VARIABLE C L 5’ FILL CA-16 C L VALVE BUTTON WATER MAIN C L C L MJ BUTTERFLY VALVE MASONRY SUPPORT UNDER GEAR BOX LUG 6" 6" LUG NOTES: 1. PRECAST CONCRETE TOP SLAB TO BE USED WHERE HEAD ROOM IS REQUIRED. 5. THE LOCATION OF MANHOLE TO BE DETERMINED ON INDIVIDUAL BASIS. 2. PRECAST 6" THICK CONCRETE SLAB WITH #4 EPOXY 6. PROVIDE 6" THICK COMPACTED COATED REBARS 4" C/C BOTHWAYS. CA-16 BEDDING. 3. PROVIDE FOUR #4 REBAR LUGS FOR HANDLING. CUT THE LUGS AFTER PLACING THE SLAB IN POSITION. 4. PROVIDE 24-INCH DIAMETER OPENING IN THE CENTER OR AS REQUIRED. BUTTERFLY VALVE BASIN REV:07.07 PRECAST CONCRETE FM -15 > > VALVE BUTTON MJ BUTTERFLY > VALVE 8" > > > > > > > 3’-6" 3’-6" 7’-0" NOTES: 1. PROVIDE 6" THICK COMPACTED CA-16 BEDDING. 2. USE PRECAST CONCRETE BASE OR PROVIDE 6" THICK I.D.O.T. CLASS ’SI’ CONCRETE BASE POURED IN PLACE WITH #4 EPOXY COATED REBARS 4" C/C BOTH WAYS. 3. PROVIDE FOUR #4 REBAR LUGS FOR HANDLING. CUT THE LUGS AFTER PLACING THE SLAB IN POSITION. 4. ALL JOINTS AND BRICK MASONRY SHALL BE PLASTERED INSIDE AND OUTSIDE WITH 1:2 MORTAR TO MAKE THE STRUCTURE WATER TIGHT. 5. PRECAST CONCRETE TOP SLAB TO BE USED WHERE HEAD ROOM IS REQUIRED. BUTTERFLY VALVE BASIN - MASONRY REV:04.07 PLAN FM -16 SHT. 1 OF 2 USE CITY OF CHICAGO STANDARD FRAME WEIGHT 395 LBS. AND STANDARD LID WEIGHT 152 LBS. C L GRADE FILL CA-16 24" 36" MAX. FILL CA-16 TOP OF BASIN TO BE 26" CORBELED AS SHOWN VARIABLE MAXIMUM CORBEL= 1 1/2 " 5’ DIA. PU C L 8" VALVE BUTTON WATER MAIN C L MASONRY SUPPORT C L MJ BUTTERFLY UNDER GEAR BOX VALVE LUG 6" 6" LUG C L 7’ NOTES: 1. PROVIDE 6" THICK COMPACTED CA-16 BEDDING 2. USE PRECAST CONCRETE BASE OR PROVIDE 6" THICK I.D.O.T. CLASS ’SI’ CONCRETE BASE POURED IN PLACE WITH #4 EPOXY COATED REBARS 4" C/C BOTH WAYS. 3. PROVIDE FOUR #4 REBAR LUGS FOR HANDLING. CUT THE LUGS AFTER PLACING THE SLAB IN POSITION. 4. ALL JOINTS AND BRICK MASONRY SHALL BE PLASTERED INSIDE AND OUTSIDE WITH 1:2 CEMENT MORTAR TO MAKE THE STRUCTURE WATER TIGHT. 5. PRECAST CONCRETE TOP SLAB TO BE USED WHERE HEAD ROOM IS REQUIRED. BUTTERFLY VALVE BASIN - MASONRY REV:04.07 SECTIONAL VIEW FM -16 SHT. 2 OF 2 > 8" MJ VALVE 5’-0" DIA. 6’-4" DIA. 8" D.I.W.P. 7’-0" DIA. CENTER LINE CONCRETE OR 9’ BRICK MASONRY 1’-9" 8" THRUST BLOCK 8" 8" 4" 18" > 8"x 8" MJ TEE 4" 8" VERTICAL 16" D.I.W.P. SUMP DRAIN 6" HANDLE 2-1" DIA. HOLES 1/2 " THICK STEEL PLATE SUMP COVER PROVIDE 1/2 " THICK STEEL PLATE SUMP COVER 20" x 20" TRIM THE CORNERS AND BLUNT THE SHARP EDGES. MAKE 2- 1" DIA. HOLES FOR #4 BENT BAR HANDLE. NOTES: 1. 4. ALL JOINTS AND BRICK MASONRY SHALL BE PROVIDE 6" THICK COMPACTED CA-16 BEDDING PLASTERED INSIDE AND OUTSIDE WITH 1:2 CEMENT 2. USE PRECAST CONCRETE BASE OR PROVIDE MORTAR TO MAKE THE STRUCTURE WATER TIGHT. 6" THICK IDOT CLASS ’SI’ CONCRETE BASE 5. POURED IN PLACE WITH #4 EPOXY COATED REBARS PRECAST CONCRETE TOP SLAB TO BE USED WHERE HEAD ROOM IS REQUIRED. 4" C/C BOTH WAYS. 3. 6. PROVIDE 2" SLOPE TOWARDS THE SUMP. 7. PROVIDE 1/2 " THICK STEEL PLATE SUMP COVER. PROVIDE FOUR #4 REBAR LUGS FOR HANDLING. CUT THE LUGS AFTER PLACING THE SLAB IN POSITION. TYPICAL BLOW-OFF/FIRE CISTERN-MASONRY REV:04.07 PLAN FM -18 SHT. 1 OF 2 > GRADE USE CITY OF CHICAGO STANDARD FRAME WEIGHT 395 LBS. AND STANDARD LID WEIGHT 152 LBS. FILL CA 16 24" 26" FILL CA 16 36" MAXIMUM TOP OF BASIN TO BE CORBELED AS SHOWN MAXIMUM CORBEL= 1 1/2 " > > VARIABLE > 3BMJ TEE 5’ DIA. PU CONCRETE OR BRICK MASONRY THRUST BLOCK WATER MAIN REMOVE THE MJ PLUG TO DRAIN WATER FROM THE PIPE > 45 8"X8" MJ TEE 8" MJ VALVE VERTICAL W/MJ PLUG M.J. PLUG 8"x 1/8 1BMJ BEND 6" SLOPE 3’ MINIMUM SLOPE 24" 6" 1" EXPANSION MATERIAL 7’ 16" 16" D.I.W.P. CONCRETE OR BRICK MASONRY CONCRETE 3" 3" SUMP DRAIN BOTTOM SUPPORT NOTES: 1. PROVIDE 6" THICK COMPACTED CA 16 BEDDING 2. USE PRECAST CONCRETE BASE OR PROVIDE 6" THICK IDOT CLASS ’SI’ CONCRETE BASE POURED IN PLACE WITH #4 EPOXY COATED REBARS 4" C/C BOTH WAYS. 3. PROVIDE FOUR #4 REBAR LUGS FOR HANDLING. CUT THE LUGS AFTER PLACING THE SLAB IN POSITION. 4. ALL JOINTS AND BRICK MASONRY SHALL BE PLASTERED INSIDE AND OUTSIDE WITH 1:2 CEMENT MORTAR TO MAKE THE STRUCTURE WATER TIGHT. 5. PRECAST CONCRETE TOP SLAB TO BE USED WHERE HEAD ROOM IS REQUIRED. TYPICAL BLOW-OFF/FIRE CISTERN-MASONRY REV:04.07 SECTIONAL VIEW FM -18 SHT. 2 OF 2 PLAN 26" USE CITY OF CHICAGO STANDARD FRAME WEIGHT 395 Lbs. AND STANDARD LID WEIGHT 152 Lbs. 23" PRECAST CONCRETE GRADE LUG 21" 6" FILL CA-16 5" 8" MJ CAP VARIABLE 8" MJ VALVE 8" D.I. PIPE 3BMJ TEE 16" O.C. 5’-0" TYPE "X" LADDER RUNGS 24" 5" 8"x 8" 3BMJ TEE WATER MAIN 45%%d 8" MJ PLUG 6" 8"x 1/8 1BMJ BEND 6" 8" D.I. PIPE MASONRY SUPPORT 6" THICK COMPACTED CA-16 BEDDING. SECTIONAL VIEW NOTE: INSTALL MEGALUGS ON ALL MECHANICAL JOINTS. TYPICAL BLOW-OFF/FIRE CISTERN REV:04.07 PRECAST CONCRETE FM -19 This page intentionally left blank.