9/16/2011 Load Models Simplified Power System Modeling • Balanced three phase systems can be analyzed using per phase analysis • A “per unit” normalization is simplify the analysis of systems with different voltage levels. • To provide an introduction to power flow analysis we need models for the different system devices: – Transformers and Transmission lines, generators and loads • Transformers and transmission lines are modeled as a series impedances Energy Systems Research Laboratory, FIU Generator Models • Engineering models depend upon application • Generators are usually synchronous machines • For generators we will use two different models: – a steady-state y model,, treating g the ggenerator as a constant power source operating at a fixed voltage; this model will be used for power flow and economic analysis – This model works fairly well for type 3 and type 4 wind turbines – Other models include treating as constant real power with a fixed power factor. Energy Systems Research Laboratory, FIU Per Unit Conversion Procedure, 1 1. Pick a 1 VA base for the entire system, SB 2. Pick a voltage base for each different voltage level, VB. Voltage bases are related by transformer turns ratios. Voltages are line to neutral. 3 Calculate 3. C l l the h impedance i d base, b ZB= (VB)2/SB 4. Calculate the current base, IB = VB/ZB 5. Convert actual values to per unit Note, per unit conversion on affects magnitudes, not the angles. Also, per unit quantities no longer have units (i.e., a voltage is 1.0 p.u., not 1 p.u. volts) • Ultimate goal is to supply loads with electricity at constant frequency and voltage • Electrical characteristics of individual loads matter, but usually they can only be estimated – actual loads are constantly changing, changing consisting of a large number of individual devices – only limited network observability of load characteristics • Aggregate models are typically used for analysis • Two common models – constant power: Si = Pi + jQi – constant impedance: Si = |V|2 / Zi Energy Systems Research Laboratory, FIU Per Unit Calculations • A key problem in analyzing power systems is the large number of transformers. – It would be very difficult to continually have to refer impedances to the different sides of the transformers • Thi This problem bl is i avoided id d by b a normalization li i off all ll variables. • This normalization is known as per unit analysis. quantity in per unit actual quantity base value of quantity Energy Systems Research Laboratory, FIU Three Phase Per Unit Procedure is very similar to 1 except we use a 3VA base, and use line to line voltage bases 1. Pick a 3 VA base for the entire system, S B3 2. Pick a voltage base for each different voltage level, VB. Voltages are line to line. 3. Calculate the impedance base ZB VB2, LL S B3 ( 3 VB , LN ) 2 3S 1B VB2, LN S 1B Exactly the same impedance bases as with single phase! Energy Systems Research Laboratory, FIU Energy Systems Research Laboratory, FIU 1 9/16/2011 Three Phase Per Unit, cont'd 4. Calculate the current base, IB I3B S B3 3 S 1B S 1B I1B 3 VB , LL 3 3 VB , LN VB , LN Exactly the same current bases as with single phase! 5. Convert actual values to per unit Energy Systems Research Laboratory, FIU Bus Admittance Matrix or Ybus • First step in solving the power flow is to create what is known as the bus admittance matrix, often call the Ybus. gives the relationships p between all the bus • The Ybus g current injections, I, and all the bus voltages, V, I = Ybus V • The Ybus is developed by applying KCL at each bus in the system to relate the bus current injections, the bus voltages, and the branch impedances and admittances Energy Systems Research Laboratory, FIU Power Flow Analysis • When analyzing power systems we know neither the complex bus voltages nor the complex current injections • Rather, we know the complex p ppower being g consumed by the load, and the power being injected by the generators plus their voltage magnitudes • Therefore we can not directly use the Ybus equations, but rather must use the power balance equations Energy Systems Research Laboratory, FIU Power Flow Analysis • We now have the necessary models to start to develop the power system analysis tools • The most common power system analysis tool is the power flow (also known sometimes as the load flow) – power flow determines how the power flows in a network – also used to determine all bus voltages and all currents – because of constant power models, power flow is a nonlinear analysis technique – power flow is a steady-state analysis tool Energy Systems Research Laboratory, FIU Ybus General Form •The diagonal terms, Yii, are the self admittance terms, equal to the sum of the admittances of all devices incident to bus i. •The off-diagonal terms, Yij, are equal to the negative of the sum of the admittances joining the two buses. •With large systems Ybus is a sparse matrix (that is, most entries are zero) •Shunt terms, such as with the line model, only affect the diagonal terms. Energy Systems Research Laboratory, FIU Power Flow Slack Bus • We can not arbitrarily specify S at all buses because total generation must equal total load + total losses • We also need an angle reference bus. • To solve these problems we define one bus as the "slack" bus. This bus has a fixed voltage magnitude and angle, and a varying real/reactive power injection. • A “slack bus” does not exist in the real power system. Energy Systems Research Laboratory, FIU 2 9/16/2011 Power Balance Equations From KCL we know at each bus i in an n bus system the current injection, I i , must be equal to the current that flows into the network Ii I Gi I Di Pi n YikVk k 1 Energy Systems Research Laboratory, FIU Newton-Raphson Method (scalar) f ( xˆ ) 0 (v) , define Vi Vk (cos ik j sin ik )(Gik jBik ) Qi n Vi Vk (Gik cos ik Bik sin ik ) PGi PDi k 1 n Vi Vk (Gik sin ik Bik cos ik ) QGi QDi k 1 Newton-Raphson Method, cont’d 3. Approximate f ( xˆ ) by neglecting all terms f ( xˆ ) 0 f ( x( v ) ) x ( v ) xˆ - x ( v ) 2. Represent f ( xˆ ) by a Taylor series about f ( x ) f ( xˆ ) f ( x ( v ) ) df ( x ( v ) ) ( v ) x dx 1 d 2 f ( x( v ) ) x ( v ) 2 dx 2 2 higher order terms Energy Systems Research Laboratory, FIU df ( x (v ) ) (v ) x dx 4. Use this linear approximation to solve for x( v ) 1 df ( x( v ) ) (v) x ( v ) f (x ) dx 5. Solve for a new estimate of x̂ x (v 1) x ( v ) x (v ) Energy Systems Research Laboratory, FIU Newton-Raphson Example Use Newton-Raphson to solve f ( x) x 2 - 2 0 The equation we must iteratively solve is 1 x ( v ) k 1 except the first two 1. For each guess of xˆ , x x k 1 Energy Systems Research Laboratory, FIU G en eral fo rm o f p ro b lem : F in d an x su ch th at (v) n Resolving into the real and imaginary parts k 1 The network power injection is then Si Vi I i* n k 1 Iik n Si Pi jQi Vi Yik*Vk* Vi Vk e jik (Gik jBik ) n Since I = Ybus V we also know Ii I Gi I Di Real Power Balance Equations df ( x( v ) ) (v ) f (x ) d dx 1 ( v ) (( x ( v ) ) 2 - 2) 2x Newton-Raphson Example, cont’d 1 x( v 1) x( v ) ( v ) (( x ( v ) ) 2 - 2) 2x Guess x (0) 1. Iteratively solving we get v x(v) f ( x(v ) ) x ( v ) 0.5 0 1 1 1 1.5 0.25 0.08333 3 x (v 1) x ( v ) x ( v ) 2 1.41667 6.953 10 1 x (v 1) x ( v ) ( v ) (( x ( v ) ) 2 - 2) 2x 3 1.41422 6.024 106 Energy Systems Research Laboratory, FIU 2.454 103 Energy Systems Research Laboratory, FIU 3 9/16/2011 Newton-Raphson Comments • When close to the solution the error decreases quite quickly -- method has quadratic convergence • f(x(v)) is known as the mismatch, which we would like to drive to zero • Stopping criteria is when f(x(v)) < • Results are dependent upon the initial guess. What if we had guessed x(0) = 0, or x (0) = -1? • A solution’s region of attraction (ROA) is the set of initial guesses that converge to the particular solution. The ROA is often hard to determine Energy Systems Research Laboratory, FIU Multi-Variable Newton-Raphson Next we generalize to the case where x is an ndimension vector, and f (x) is an n-dimension function x1 x 2 x x n Again define the solution xˆ so f (xˆ ) 0 and x xˆ x Energy Systems Research Laboratory, FIU Multi-Variable Case, cont’d The Taylor series expansion is written for each fi (x) f1 (xˆ ) f1 (x) f1 (x) f (x) x1 1 x2 x1 x2 f1 (x) g order terms xn higher xn f n (xˆ ) f n (x) f n (x) f (x) x1 n x2 x1 x2 f n (x) xn higher order terms xn Energy Systems Research Laboratory, FIU Jacobian Matrix The n by n matrix of partial derivatives is known as the Jacobian matrix, J (x) f1 (x) x 1 f 2 (x) J (x) x1 f (x) n x1 f1 (x) f1 (x) x2 xn f 2 (x) f 2 (x) x2 xn f n (x) f n (x) x2 xn Energy Systems Research Laboratory, FIU f1 (x) f ( x) 2 f ( x) f ( x) n Multi-Variable Case, cont’d This can be written more compactly in matrix form f1 (x) x 1 f1 (x) f (x) f 2 (x) 2 x1 f (xˆ ) f ( x) n f (x) n x1 f1 (x) f1 (x) x2 xn x1 f 2 (x) f 2 (x) x x2 xn 2 xn f n (x) f n (x) x2 xn higher order terms Energy Systems Research Laboratory, FIU Multi-Variable N-R Procedure Derivation of N-R method is similar to the scalar case f (xˆ ) f (x) J (x)x higher order terms f (xˆ ) 0 f (x) J (x)x x J (x) 1 f (x) x(v 1) x(v ) x( v ) x(v 1) x(v ) J (x( v ) ) 1 f (x( v ) ) Iterate until f (x( v ) ) Energy Systems Research Laboratory, FIU 4 9/16/2011 Multi-Variable Example x Solve for x = 1 such that f (x) 0 where x2 f1 (x) 2 x12 x22 8 0 f 2 (x) x12 x22 x1 x2 4 0 First symbolically determine the Jacobian f1 (x) x 1 J (x) = f ( 2 x) x1 f1 (x) x2 f 2 (x) x2 specified tolerance 0.1556 f (x ) 0.0900 If = 0.2 then we would be done. Otherwise we'd continue iterating. (2) Energy Systems Research Laboratory, FIU Newton-Raphson Power Flow In the Newton-Raphson power flow we use Newton's method to determine the voltage magnitude and angle at each bus in the power system. We need to solve the power balance equations Vi Vk (Gik cos ik Bik sin ik ) PGi PDi Vi Vk (Gik sin ik Bik cos ik ) QGi QDi k 1 Energy Systems Research Laboratory, FIU 1 f1 (x) x1 2 x2 f 2 (x) 1 1 2 x2 1 4 2 5 2.1 1 3 1 3 1.3 Energy Systems Research Laboratory, FIU 1 Qi 2 x2 x1 2 x2 1 2.1 8.40 2.60 2.51 1.8284 x(2) 1.3 5.50 0.50 1.45 1.2122 Each iteration we check f (x) to see if it is below our k 1 n x1 4 x1 x 2 x x 2 1 2 x(1) Multi-variable Example, cont’d Pi 4 x1 J (x) = 2 x1 x2 Then Arbitrarily guess x(0) Energy Systems Research Laboratory, FIU n Multi-variable Example, cont’d Real Power Balance Equations n n k 1 k 1 Si Pi jQi Vi Yik*Vk* Vi Vk e jik (Gik jBik ) n Vi Vk k 1 (cos ik j sin ik )(Gik jBik ) Resolving into the real and imaginary parts Pi Qi n Vi Vk (Gik cos ik Bik sin ik ) PGi PDi k 1 n Vi Vk (Gik sin ik Bik cos ik ) QGi QDi k 1 Energy Systems Research Laboratory, FIU Power Flow Variables Assume the slack bus is the first bus (with a fixed voltage angle/magnitude). We then need to determine the voltage angle/magnitude at the other buses. 2 n x V 2 Vn P2 (x) PG 2 PD 2 Pn (x) PGn PDn f ( x) Q (x) QG 2 QD 2 2 x Q ( ) Q Q n Gn Dn Energy Systems Research Laboratory, FIU 5 9/16/2011 N-R Power Flow Solution The power flow is solved using the same procedure discussed last time: Set v 0; make an initial guess of x, x( v ) While f (x ) Do (v) x( v 1) x(v ) J (x( v ) ) 1 f (x(v ) ) v v 1 End While Energy Systems Research Laboratory, FIU Power Flow Jacobian Matrix The most difficult part of the algorithm is determining and inverting the n by n Jacobian matrix, J (x) f1 (x) x 1 f 2 (x) J (x) x1 f (x) n x1 f1 (x) f1 (x) x2 xn f 2 (x) f 2 (x) x2 xn f n (x) f n (x) x2 xn Energy Systems Research Laboratory, FIU Power Flow Jacobian Matrix, cont’d Jacobian elements are calculated by differentiating each function, fi (x), with respect to each variable. Two Bus Newton-Raphson Example For the two bus power system shown below, use the Newton-Raphson power flow to determine the voltage magnitude and angle at bus two. Assume that bus one is the slack and SBase = 100 MVA. For example, if fi (x) is the bus i real power equation fi ( x) fi ( x) i n Vi Vk (Gik cosik Bik sin ik ) PGi PDi k 1 n One Vi Vk (Gik sin ik Bik cosik ) k 1 k i fi ( x) Vi V j (Gik sin ik Bik cos ik ) ( j i ) j Energy Systems Research Laboratory, FIU Two Bus Example, cont’d General power balance equations Pi Qi n Vi Vk (Gik cosik Bik sin ik ) PGi PDi k 1 n i ik Bik cos ik ) QGi QDi Vi Vk (Gik sin k 1 Bus two power balance equations V2 V1 (10sin 2 ) 2.0 0 V2 V1 ( 10cos 2 ) V2 (10) 1.0 0 2 Energy Systems Research Laboratory, FIU Line Z = 0.1j 0 1j 1.000 pu Two 0 MW 0 MVR 1.000 pu 200 MW 100 MVR 2 j10 j10 x Ybus j10 j10 V2 Energy Systems Research Laboratory, FIU Two Bus Example, cont’d P2 (x) V2 (10sin 2 ) 2.0 0 Q2 (x) V2 (10cos 2 ) V2 (10) 1.0 0 2 Now calculate the power flow Jacobian P2 (x) 2 J ( x) Q 2 (x) 2 P2 (x) V 2 Q2 (x) V 2 10 V2 cos 2 10 V2 sin 2 10sin 2 10 cos 2 20 V2 Energy Systems Research Laboratory, FIU 6 9/16/2011 Two Bus Example, First Iteration 0 Set v 0, guess x(0) 1 Calculate V2 (10sin 2 ) 2.0 2.0 f(x(0) ) 2 1.0 V2 (10 cos 2 ) V2 (10) 1.0 10 V2 cos 2 J (x(0) ) 10 V2 sin 2 10sin 2 10 0 10 cos 2 20 V2 0 10 1 0.2 0.9 0 10 0 2.0 Solve x(1) 1 0 10 1.0 Energy Systems Research Laboratory, FIU Once the voltage angle and magnitude at bus 2 are known we can calculate all the other system values, such as the line flows and the generator reactive power output One -200.0 MW -100.0 MVR Line Z = 0.1j 1.000 pu Two 0.855 pu -13.522 Deg 200.0 MW 168.3 MVR 200 MW 100 MVR Energy Systems Research Laboratory, FIU Three Bus PV Case Example P2 ( x) PG 2 PD 2 f ( x) P3 ( x) PG 3 PD3 0 Q2 (x) QD 2 Line Z = 0.1j 0 1j 0.941 pu One 170.0 MW 68.2 MVR 1.000 pu Line Z = 0.1j Three Two Line Z = 0.1j 1.000 pu 30 MW 63 MVR Energy Systems Research Laboratory, FIU 1 0.2 8.82 1.986 0.212 0.233 x(2) 0.8586 0.9 1.788 8.199 0.279 0.0145 0.236 x (3) f(x (2) ) 0.0190 0.8554 0.0000906 f(x (3) ) 0.0001175 Done! V2 0.8554 13.52 PV Buses • Since the voltage magnitude at PV buses is fixed there is no need to explicitly include these voltages in x or write the reactive power balance equations – the reactive power output of the generator varies to maintain i t i the th fixed fi d terminal t i l voltage lt (within ( ithi limits) li it ) – optionally these variations/equations can be included by just writing the explicit voltage constraint for the generator bus |Vi | – Vi setpoint = 0 Energy Systems Research Laboratory, FIU For this three bus case we have 2 x 3 V2 0.9(10sin(0.2)) 2.0 0.212 f(x (1) ) 2 0.9( 10cos( 0.2)) 0.9 10 1.0 0.279 8.82 1.986 J (x(1) ) 1.788 8.199 Energy Systems Research Laboratory, FIU Two Bus Solved Values 200.0 MW 168.3 MVR Two Bus Example, Next Iterations -7.469 Deg 200 MW 100 MVR Solving Large Power Systems • The most difficult computational task is inverting the Jacobian matrix – inverting a full matrix is an order n3 operation, meaning the amount of computation increases with the cube of the size size – this amount of computation can be decreased substantially by recognizing that since the Ybus is a sparse matrix, the Jacobian is also a sparse matrix – using sparse matrix methods results in a computational order of about n1.5. – this is a substantial savings when solving systems with tens of thousands of buses Energy Systems Research Laboratory, FIU 7 9/16/2011 “DC” Power Flow Five Bus Power Flow Example • The “DC” power flow makes some approximations to the power balance equations to simplify the problem 5 400 MVA 15/345 kV 345 kV 100 mi Line 1 400 MVA 15 kV • This makes the power flow a linear set of equations, -1 which can be solved directly = B P • While the DC power flow is approximate, it is widely used to get a feel for power system MW flows. Energy Systems Research Laboratory, FIU T2 800 MVA 4 345/15 kV Line 3 345 kV 50 mi Line 2 – completely ignore reactive power, assume all the voltages are always 1.0 per unit, ignore line conductance, assumes angles l across the th lines li are small. ll – Line flow is then approximated as (i – j)/Xij T1 1 3 520 MVA 800 MVA 15 kV 40 Mvar 80 MW 345 kV 200 mi 2 280 Mvar 800 MW Single-line diagram Energy Systems Research Laboratory, FIU 37 Bus Power Flow Example DC Power Flow Example Metropolis Light and Power Electric Design Case 2 • For the system shown in the previous slide with bus 1 as the system slack and with the below B matrix (100 MVA base) numbered from buses 2 to 5, determine the bus angles using the DC power flow approximation the and the flow on the line between bus 1 and 5, 5 which has a pu X of 0.02. SLA CK3 4 5 A MVA A MVA 2 2 0 MW 5 2 Mvar RA Y 3 4 5 1 .0 3 pu slack System Losses: 10.70 MW 1 .0 2 pu T IM3 4 5 A A MVA MVA A SLA CK1 3 8 MVA RA Y1 3 8 1 .0 2 pu A A 1 .0 3 pu A MVA MVA 33 MW 1 3 M var T IM1 3 8 1 .0 0 pu A A MVA 3 9 MW 1 3 Mvar H A NNA H 6 9 60 MW 1 9 M var 1 .0 0 pu A 5 8 MW 4 0 Mvar MVA 1 .0 0 pu 2 0 MW 1 2 Mvar UIUC6 9 1 .0 0 pu 1 2 .8 Mvar KYLE69 A 1 .0 0 pu A A MVA 1 .0 2 pu H O MER6 9 1 .0 1 pu 2 0 MW 3 M var 1 .0 0 pu A BLT 1 3 8 1 .0 0 pu A MVA 0 .0 M var 1 .0 0 pu A 2 0 MW 2 8 Mvar PA T T EN6 9 MVA MVA 1 4 MW 4 5 MW 0 Mvar WEBER6 9 2 2 MW 1 5 Mvar MVA 1 0 MW 5 Mvar RO GER6 9 2 Mvar 1 4 MW 3 Mvar A MVA 1 .0 2 pu LA UF1 3 8 1 .0 1 pu A A 1 .0 0 pu 1 .0 1 pu 2 3 MW 6 Mvar A MVA 1 .0 0 pu 1 .0 1 pu MVA A MVA LA UF6 9 1 .0 2 pu A MVA A 7 .3 Mvar SA VO Y 6 9 BUCKY1 3 8 1 .0 2 pu A JO 1 3 8 3 8 MW 3 Mvar MVA A MVA 1 .0 1 pu A A MVA 1 5 MW 5 Mvar 55 MW 2 5 M var A MVA MVA 1 .0 2 pu SH IMKO 6 9 7 .4 Mvar A MVA MVA 36 MW 1 0 M var A 60 MW 1 2 M var MVA 14 MW 4 Mvar MVA BLT 6 9 1 .0 1 pu H A LE6 9 MVA A LYNN1 3 8 1 3 M var 16 MW -1 4 Mvar A MVA A MVA A A BO B6 9 56 MW 124 MW 4 5 M var A MVA MVA 25 MW 3 6 M var A M A NDA 6 9 MVA A MVA MVA MVA 25 MW 1 0 M var B O B1 3 8 A MVA A MVA A 1 .0 1 pu DEM A R6 9 A 0 .9 9 pu WO LEN6 9 4 .9 Mvar 2 8 .9 M var MVA A MVA 1 .0 1 pu 12 MW 3 M var 1 4 .2 M var 0 .9 9 pu 1 3 Mvar FERNA 6 9 PET E6 9 A 12 MW 5 M var A MVA A MVA A MVA H ISKY 6 9 3 7 MW 1 7 MW 3 Mvar MVA GRO SS6 9 1 .0 1 pu A MVA MO RO 1 3 8 RA Y 6 9 1 .0 2 pu PA I6 9 1 .0 1 pu T IM6 9 A MVA A 1 .0 3 pu MVA 1 8 MW 5 Mvar A MVA MVA 1 .0 2 pu 2 3 MW 7 Mvar A MVA MVA A 1 5 .9 Mvar JO 3 4 5 A SA VO Y 1 3 8 1 5 0 MW 0 Mvar MVA A MVA MVA 1 5 0 MW 0 Mvar A P15 = (1 – 5)/X15 = 0.072/0.02 = 3.6 pu = 360 MW Energy Systems Research Laboratory, FIU Good Power System Operation MVA 1 .0 2 pu A 1 .0 3 pu MVA Energy Systems Research Laboratory, FIU Looking at the Impact of Line Outages Metropolis Light and Power Electric Design Case 2 • Good power system operation requires that there be no reliability violations for either the current condition or in the event of statistically likely contingencies A MVA slack T IM 3 4 5 A MVA A SLA CK1 3 8 MVA RA Y1 3 8 1 .0 3 pu A MVA MVA 33 MW 1 3 M var T IM1 3 8 1 .0 1 pu A A MVA 1 .0 2 pu 1 6 .0 M var 3 9 MW 1 3 Mvar H A NNA H6 9 60 MW 1 9 M var 0 .9 0 pu FERNA 6 9 P ET E6 9 DEM A R6 9 KYLE69 A 1 .0 0 pu A 20 MW 1 2 M var UIUC6 9 1 .0 0 pu 1 2 .8 Mvar A MVA 25 MW 3 6 M var A M A NDA 6 9 5 6 MW 124 MW 4 5 M var A SH IM KO 6 9 7 .3 Mvar A MVA A A P A T T EN6 9 2 2 MW 1 5 Mvar 10 MW 5 M var MVA LA UF1 3 8 BUCKY1 3 8 ROGER6 9 2 M var A MVA SA V OY6 9 1 .0 2 pu A 3 8 MW 9 M var JO 1 3 8 MVA A MVA 14 MW 1 4 MW 3 M var 1 .0 1 pu 1 .0 0 pu MVA MVA 45 MW 0 M var WEBER6 9 1 .0 0 pu 23 MW 6 Mvar A 80% 1 .0 1 pu MVA 1 .0 0 pu MVA LA UF6 9 1 .0 1 pu A MVA 15 MW 5 Mvar A MVA A 7 .2 M var 1 .0 0 pu 1 .0 2 pu MVA 55 MW 3 2 M var A MVA 3 6 MW 1 0 Mvar MVA A 0 .9 9 pu A BLT 6 9 MVA 60 MW 1 2 M var 20 MW 4 0 M var MVA A MVA 1 .0 1 pu H A LE6 9 MVA A 0 .0 M var LYNN1 3 8 14 MW 4 M var A BLT 1 3 8 1 .0 0 pu MVA A 135% 20 MW 3 M var 0 .9 4 pu A MVA 1 3 Mvar 16 MW -1 4 M var A MVA A 1 .0 1 pu MVA BO B6 9 1 .0 2 pu A MVA A MVA MVA MVA MVA A MVA 25 MW 1 0 M var BOB1 3 8 MVA A 0 .9 0 pu MV A WOLEN6 9 A 1 .0 1 pu 2 8 .9 Mvar MVA A 110% HO MER6 9 1 3 M var 1 .0 1 pu A MVA 1 .0 0 pu A MVA 12 MW 3 M var 4 .9 M var 58 MW 4 0 M var 1 1 .6 M var 37 MW 17 MW 3 M var A MVA MVA A 12 MW 5 M var RA Y6 9 1 .0 2 pu A GROSS6 9 A H ISKY6 9 MO RO1 3 8 1 .0 3 pu MVA 1 .0 1 pu A MVA A MVA 18 MW 5 M var P A I6 9 1 .0 1 pu T IM6 9 2 3 MW 7 M var A MVA MVA A MVA A • North American Electric Reliability Corporation now has legal authority to enforce reliability standards (and there are now lots of them). See http://www.nerc.com for details (click on Standards) A MVA 1 .0 2 pu A A 1 .0 0 pu 2 2 7 MW 4 3 Mvar RA Y3 4 5 1 .0 3 pu System Losses: 17.61 MW MVA • Reliability requires as a minimum that there be no transmission line/transformer limit violations and that bus voltages be within acceptable limits (perhaps 0.95 0 95 to 1.08) 1 08) • Example contingencies are the loss of any single device. This is known as n1 reliability. SLA CK3 4 5 A MVA 1 .0 2 pu 1 .0 1 pu A MVA SA V OY1 3 8 JO3 4 5 A 150 MW 4 Mvar MVA A MVA 150 MW 4 Mvar A MVA 1 .0 2 pu A 1 .0 3 pu MVA Opening one line (Tim69-Hannah69) causes an overload. This would not be allowed (i.e., we can’t operate this way when line is in. Energy Systems Research Laboratory, FIU Energy Systems Research Laboratory, FIU 8 9/16/2011 Contingency Analysis Generation Changes and The Slack Bus Contingency analysis provides an automatic way of looking at all the statistically i i ll likely contingencies. In this example the contingency set Is all the single line/transformer outages Energy Systems Research Laboratory, FIU • The power flow is a steady-state analysis tool, so the assumption is total load plus losses is always equal to total generation • Generation mismatch is made up at the slack bus • When doing generation change power flow studies one always needs to be cognizant of where the generation is being made up • Common options include system slack, distributed across multiple generators by participation factors or by economics Energy Systems Research Laboratory, FIU Generation Change Example 1 Generation Change Example 2 SLA CK3 4 5 A SLA CK3 4 5 A MVA A MVA A MVA MVA 0 .0 0 pu sla ck 0 .0 0 pu T IM 3 4 5 A MVA MVA SLA CK1 3 8 T IM1 3 8 0 MW 0 M var A A T IM6 9 MVA 0 .0 0 pu 0 MW 0 Mvar RA Y6 9 A A HISKY6 9 MVA A 0 MW 0 M var 0 .0 0 pu DEMA R6 9 MVA 0 MW 0 Mvar HA NNA H6 9 0 MW 0 M var -0 .2 Mvar A MVA 0 MW 0 M var 0 .0 0 pu 0 MW 0 M var A M A NDA 6 9 0 MW 0 M var MVA A -0 .0 1 pu 0 .0 0 pu MVA A 0 MW 0 Mvar MVA MVA 0 .0 Mvar 0 MW 0 M var 0 .0 0 pu 0 MW 0 Mvar A 0 MW 4 M var 0 .0 0 pu 0 .0 0 pu BUCKY1 3 8 1 9 MW 5 1 M var A A MVA 0 MW 0 Mvar A A MVA A 0 .0 0 pu MVA 0 .0 0 pu 0 .0 0 pu 0 MW 0 Mvar A P A T T EN6 9 0 MW 0 M var 0 .0 0 pu BUCKY1 3 8 0 .0 0 pu 4 2 MW -1 4 M var JO1 3 8 MVA 0 .0 0 pu A MVA SA VOY 1 3 8 JO3 4 5 A 0 MW 0 Mvar MVA A MVA 0 MW 0 Mvar A MVA 0 .0 0 pu 0 .0 0 pu A A MVA SA VOY 6 9 A A 0 MW 2 Mvar 0 .0 0 pu RO GER6 9 0 M var 0 MW 0 M var 0 .0 0 pu MVA 0 MW 2 Mvar MVA A MVA MVA 0 MW 0 MW 0 M var WEBER6 9 0 MW 0 M var MVA LA UF1 3 8 MVA A MVA 0 .0 0 pu MVA A 0 .0 Mvar A 0 .0 0 pu JO3 4 5 A SA VOY 1 3 8 MVA 0 .0 0 pu SHIM KO6 9 -0 .1 Mvar MVA MVA MVA JO1 3 8 0 MW 3 M var LYNN1 3 8 0 MW 0 M var A BLT 6 9 -0 .0 1 pu 0 MW 0 Mvar LA UF6 9 A 99 MW -2 0 Mvar 0 .0 0 pu A 0 .0 0 pu A HA LE6 9 MVA 0 .0 0 pu A MVA SA VOY 6 9 MVA A MVA A 0 .0 M var MVA RO GER6 9 0 M var 0 MW 0 M var 0 .0 0 pu -0 .0 1 pu MVA 0 MW 0 MW 0 M var 0 MW 0 M var 0 M var A MVA A MVA MVA 0 MW 0 Mvar MVA A P A T T EN6 9 WEBER6 9 0 MW 0 M var MVA LA UF1 3 8 0 MW 0 MW 0 Mvar B LT 1 3 8 -0 .0 3 pu MVA A 0 .0 0 pu 0 .0 0 pu 0 MW 0 Mvar A MVA MVA -1 5 7 M W -4 5 M var A A MVA A A A MVA LA UF6 9 0 .0 0 pu BOB6 9 MVA A 0 .0 0 pu MVA 0 .0 0 pu 0 .0 M var 0 MW 0 M var A A MVA A 0 .0 0 pu -0 .1 Mvar MVA A M A NDA 6 9 0 MW 0 M var A MVA 0 MW 0 Mvar A UIUC6 9 MVA 0 .0 0 pu A MVA MVA 0 MW 5 1 M var A MVA MVA 0 MW 0 M var A MVA MVA HA LE6 9 A BLT 6 9 MVA 0 .0 0 pu A MVA 0 .0 0 pu HO MER6 9 MVA MVA A A A SHIM KO6 9 0 .0 M var MVA MVA 0 .0 0 pu A 0 MW 0 M var 0 .0 0 pu -0 .2 Mvar A A MVA A HO MER6 9 DEMA R6 9 0 MW 0 Mvar -0 .1 Mvar -0 .0 0 3 pu 0 MW 0 M var MVA A A WO LEN6 9 A BO B1 3 8 -0 .0 3 pu P ET E6 9 MVA LYNN1 3 8 A B LT 1 3 8 -0 .0 3 pu 0 Mvar 0 .0 0 pu 0 .0 0 pu A 0 MW 0 M var 0 MW 0 Mvar A MVA A MVA 0 MW 0 M var HA NNA H6 9 0 MW 0 M var MVA -1 5 7 M W -4 5 M var A MVA MVA MVA MVA 0 .0 0 pu 0 MW 0 MW 0 M var FERNA 6 9 A 0 MW 0 Mvar BOB6 9 0 .0 0 pu A 0 .0 0 pu -0 .1 Mvar A A A -0 .0 0 2 pu RA Y6 9 A MVA MVA 0 .0 M var MVA MVA UIUC6 9 -0 .1 Mvar A MVA MVA 0 .0 0 pu A MVA GROSS6 9 0 .0 0 pu A 0 .0 0 pu A 0 MW 0 Mvar P A I6 9 HISKY6 9 MVA BO B1 3 8 -0 .0 3 pu P ET E6 9 MVA 0 .0 0 pu MVA 0 MW 0 M var A -0 .0 1 pu A 0 .0 0 pu MVA A MVA A A 0 MW 0 Mvar -0 .1 Mvar 0 .0 0 pu A 0 MW 0 M var MO RO1 3 8 WO LEN6 9 0 .0 0 pu 0 MW 0 M var MVA -0 .1 Mvar MVA A A MVA FERNA 6 9 MVA A T IM6 9 0 .0 0 pu 0 Mvar MVA A MVA A MVA RA Y1 3 8 MVA 0 MW 0 M var MVA MVA 0 MW 0 MW 0 M var MVA GROSS6 9 0 .0 0 pu A MVA -0 .0 1 pu A P A I6 9 0 .0 0 pu A 0 MW 0 M var MO RO1 3 8 MVA A A -0 .1 Mvar MVA MVA 0 .0 0 pu A MVA A SLA CK1 3 8 A T IM1 3 8 0 .0 0 pu MVA MVA A -0 .0 1 pu A MVA 0 .0 0 pu A 0 .0 0 pu sla ck T IM 3 4 5 MVA RA Y1 3 8 A 0 MW 3 7 Mvar RA Y3 4 5 A 0 .0 0 pu A -0 .0 1 pu A MVA 0 .0 0 pu 1 6 2 MW 3 5 Mvar RA Y3 4 5 A A 0 .0 0 pu MVA MVA Display shows “Difference Flows” between original 37 bus case, and case with a BLT138 generation outage; note all the power change is picked up at the slack Energy Systems Research Laboratory, FIU Display repeats previous case except now the change in generation is picked up by other generators using a participation factor approach Energy Systems Research Laboratory, FIU What does the Future Hold for Wind? Sitting New Wind Generation Example MVA 1.02 pu System Losses: 1.02 pu RAY345 sl 8.73 MW TIM345 A A M VA M VA A SLACK138 1.01 pu A A MVA MVA M VA RAY138 1.03 pu A TIM138 1.00 pu M VA A 1.02 pu MVA 1.02 pu A A MVA MVA 1.02 pu PAI69 1.01 pu TIM69 1.01 pu A M VA A MORO138 GROSS69 A FERNA69 M VA 1.00 pu 12 MW 3 Mvar M VA HISKY69 PETE69 M VA A M VA 1.01 pu M VA 0.99 pu 12 MW 5 Mvar 1.00 pu A M VA A A A M VA RAY69 A M VA HANNAH69 DEMAR69 Wind69 BOB138 A A MVA 1.00 pu UIUC69 1.00 pu 50 MW 20 MW 12 Mvar MVA BOB69 1.01 pu A M VA 1.00 pu A A MVA MVA 56 MW 0 MW 0 Mvar 13 Mvar A A A M VA A HOMER69 0.99 pu MVA -2 Mvar AMANDA69 1.00 pu 1.00 pu MVA SHIMKO69 M VA M VA 1.01 pu A A BLT138 A A MVA A BLT69 MVA MVA HALE69 M VA A 1.01 pu A MVA A MVA A 1.01 pu A MVA MVA M VA 1.00 pu A 1.00 pu A M VA LAUF69 1.02 pu A A Energy Systems Research Laboratory, FIU PATTEN69 MVA 14 MW 1.01 pu WEBER69 2 Mvar A ROGER69 • Wind has experienced rapid growth over the last decade; but with a large drop in installations expected for 2010. • Nuclear and renewal generation are running into strong “head winds” causedd bby low l natural gas prices. • Expiring tax credits is a continual concern. • State renewable portfolio standards will help with growth. Energy Systems Research Laboratory, FIU 9 9/16/2011 Hurricanes Impact Energy Prices Hurricanes Impact Energy Prices • Many oil refineries and natural gas pipelines off the coast • Need to be shut down and evacuated • Takes time to get the systems back up and running afterwards Hurricane Ike, Sept. 2008 http://tonto.eia.doe.gov/oog/special/hurricanes/ gustav_091308.html http://www.eia.doe.gov/emeu/steo/pub/special/pdf/2008_sp_03.pdf Energy Systems Research Laboratory, FIU Energy Systems Research Laboratory, FIU What does the Future Hold for Wind? Distributed Generation (DG) Vestas to Cut 3000 Jobs (14%) (10/26/10) Vestas Stock Price Over Last Five Years • Small-scale, up to about 50 MW • Includes renewable and non-renewable sources • May M bbe iisolated l t d from f the th grid id or gridid connected • Usually near the end user Closed at 176 on Wednesday and 169.4 on Thursday! Long-term the outlook for wind is probably good. On 9/1/10 EIA reduced their 2010 forecast for US capacity additions to 4.3 GW in 2010 and 6.5 GW in 2011; the totals for 2007 were 5.2 GW, 2008 8.4 GW and 2009 10.0GW Energy Systems Research Laboratory, FIU Energy Systems Research Laboratory, FIU Pluggable Hybrid Electric Vehicles (PHEVs) as Distributed Generation Integrated Generation, Transmission, Buildings, Vehicles • Can charge at night when electricity is cheap Renewables Grid kWh kWh PHEV Smart meters Vehicle-to-Grid Heat N. Gas Energy Systems Research Laboratory, FIU kWh Combined Heat and Power (CHP) Source: Masters Source: http://www.popularmechanics.com/automotive/new_cars/4215489.html • Can provide services back to the grid Energy Systems Research Laboratory, FIU Source: www.calcars.org 10 9/16/2011 DG Technologies, Excepting Solar San Francisco charging stations, 2009 • • • • • • http://en.wikipedia.org/wiki/File:Charging_stations_in_SF_City_Hall_02_2009_02.jpg Energy Systems Research Laboratory, FIU Energy Systems Research Laboratory, FIU Terminology Reasons for Distributed Generation • • • • • Microturbines Reciprocating Internal Combustion Engines Biomass y Micro-Hydro Fuel Cells (we’ll be skipping) Concentrated solar power is talked about in Chapter 4, but we’ll skip until after we cover Chapter 7. • Cogeneration and Combined Heat and Power (CHP) Good for remote locations Renewable resources Reduced emissions Can use the waste heat Can sell power back to the grid – capturing and using waste heat while generating electricity • When fuel is burned one product is water; if water vapor exits stack then its energy is lost (about 1060 Btu per ppound of water vapor) p ) • Heat of Combustion for fuels – Higher Heating Value (HHV) – gross heat, accounts for latent heat in water vapor – Lower Heating Value (LHV) – net heat, assumes latent heat in water vapor is not recovered – Both are used - Conversion factors (LHV/HHV) in Table 4.2 Energy Systems Research Laboratory, FIU Energy Systems Research Laboratory, FIU HHV and LHV Efficiency Microturbines • Find LHV efficiency or HHV efficiency from the heat rate: HHV( LHV ) 3412 Btu/kWh Heat Rate (Btu/kWh) HHV( LHV ) • Convert to get the other LHV efficiency: HHV LHV HHV (3.16) • Small natural gas turbines, 500 W to 100s kW • Only one moving part • Combined heat and power 80% CHP • High overall efficiencyEfficiency (4.1) 230 kW fuel 120 kW hot water output 65 kW electrical output 45 kW waste heat Capstone 65 kW Microturbine Note the LHV is less than the HHV Source: http://www.capstoneturbine.com Energy Systems Research Laboratory, FIU Energy Systems Research Laboratory, FIU 11 9/16/2011 Microturbines Microturbines and Renewable Energy 1. Incoming air is compressed 2. Moves into cool side of recuperator & is heated 3. Mixes with fuel in combustion chamber 4. Expansion of hot gases spins shaft 5. Exhaust leaves Figure 4.1 Energy Systems Research Laboratory, FIU Biomass – Current Conditions • Biomass, including waster, currently provides about 4% of the US total energy, a value that is projected to grow to about 7% by 2030. • In 2008 the 3.85 quad of biomass was split between biofuels such as ethanol (1.37 quad), waste such as landfill gas (0.436 quad) and wood (2.04 quad). – About 1/10 of the wood was used to produce electricity, primarily by the paper industry; total generation capacity in US is about 11.3 GW – We are not considering liquid fuels for non-electricity use in ECE 333; ethanol usage was growing at 30% per year • Little to no fuel cost for wood waste but little growth Energy Systems Research Laboratory, FIU Biomass – Future Possibilities for Electricity • A full consideration of biomass is beyond our scope of since it gets into agricultural economics issues • Miscanthus can be harvested at rates of about 15 tons per acre in Illinois Once established it does not need to be replanted. Illinois. replanted This allows the energy potential of about 225 Mbtu per acre; income depends on energy price, say $2/Mbtu = $450 per acre. For comparison corn can yield up to 200 bushels per acre at say $5.50/bushel = $1100 per acre • Microturbines are not a renewable energy source since they ultimately use natural gas as their fuel. But when used for combined heat and electricity they can be quite efficient and emit significantly less CO2 than coal. • A possible scenario: If natural gas prices remain low, commercial/industrial entities will increasingly go “off grid.” Hence they will not be subject to state renewable portfolio standards or utility taxes. This will mean renewable energy subsidies will increasingly be born by residential customers. Average residential price per therm is $0.57 in October in Illinois; with a heat rate of 8.5 this gives electricity at 4.8 cents/kWh. Energy Systems Research Laboratory, FIU Biomass – Future Possibilities for Electricity • Newer crops are being considered for future biomass, including various grasses (such as Miscanthus and Switch Grass) along with algae • Potential uses include both fuel to create t electricity l t i it (primarily ( i il the th grasses), and conversion to liquid fuels such as ethanol. – On campus 320 acres in the South Farms are devoted to biofuel research Energy Systems Research Laboratory, FIU Cofiring • Burn biomass and coal • Modified conventional steam-cycle plants • Allows use of biomass in plants with higher efficiencies ffi i i • Reduces overall emissions – Energy yield is about 225/15 = 15 Mbtu/ton which is similar to coal – Not a native species so containment could be an issue Energy Systems Research Laboratory, FIU Energy Systems Research Laboratory, FIU 12 9/16/2011 Gas Turbines and Biomass • Cannot run directly on biomass without causing damage • Gassify the fuel first and clean the gas before combustion • Coal-integrated gasifier/gas turbine (CIG/GT) systems • Biomass-integrated gasifier/gas turbine (BIG/GT) systems Energy Systems Research Laboratory, FIU Biomass and Transportation • A key issue associated with biomass is the transportation costs – these grasses are quite bulky. • A rough estimate of the cost per ton for transportation is about $1 + 0.1 * round trip distance in miles + h harvesting ti costs t off about b t $22 per ton. t So S if the th power plant is 50 miles distant, total cost would be $33 per ton, or about $33/ton/($15 Mbtu/ton) = $2.2 per Mbtu • Total US corn planting is about 87 million acres, which if planted in grass could yield about 20 quad of energy. – Won’t meet all our needs but could play a major role Energy Systems Research Laboratory, FIU A Biomass plant Energy Systems Research Laboratory, FIU 13