Instron Model 8802, 8803, 8804, 8805 and 8806 Load Frames

advertisement
Instron
Model 8802, 8803, 8804, 8805 and 8806
Load Frames
Reference Manual - Pre-Installation
M21-28800-70
Revision B
www.instron.com
Electromagnetic Compatibility
Where applicable, this equipment is designed to comply with International Electromagnetic
Compatibility (EMC) standards.
To ensure reproduction of this EMC performance, connect this equipment to a low impedance ground
connection. Typical suitable connections are a ground spike or the steel frame of a building
Proprietary Rights Notice
This document and the information that it contains are the property of Instron Corporation. Rights to
duplicate or otherwise copy this document and rights to disclose the document and the information that
it contains to others and the right to use the information contained therein may be acquired only by
written permission signed by a duly authorized officer of Instron Corporation.
© Copyright 2001 Instron Corporation
Preliminary Pages
General Safety Precautions
Materials testing systems are potentially hazardous.
Materials testing involves inherent hazards from high forces, rapid motions and stored
energy. You must be aware of all moving and operating components that are potentially hazardous, particularly the actuator in a servohydraulic testing system or the
moving crosshead in an electromechanical testing system.
Whenever you consider that safety is compromised, press the Emergency Stop button
to stop the test and isolate the testing system from hydraulic or electrical power.
Carefully read all relevant manuals and observe all Warnings and Cautions. The term
Warning is used where a hazard may lead to injury or death. The term Caution is used
where a hazard may lead to damage to equipment or to loss of data.
Ensure that the test set-up and the actual test you will be using on materials, assemblies or structures constitutes no hazard to yourself or others. Make full use of all
mechanical and electronic limits features. These are supplied to enable you to prevent
movement of the actuator piston or the moving crosshead beyond desired regions of
operation. Limits provide protection for your specimen and machine and reduce
potential hazard.
The following pages detail various general warnings that you must heed at all times
while using materials testing equipment. You will find more specific Warnings and
Cautions in the text whenever a potential hazard exists.
Your best safety precautions are to obtain training in the testing equipment that you
are using and to read your Operating Instructions and Reference Manual(s) to gain a
thorough understanding of that equipment.
iii
Preliminary Pages
M21-28800-70
Warnings
Hazard - Protect electrical cables from damage and inadvertent
disconnection.
The loss of controlling and feedback signals that can result from a disconnected or
damaged cable causes an open loop condition that may drive the actuator or crosshead
rapidly to its extremes of motion. Protect all electrical cables, particularly transducer
cables, from damage. Never route cables across the floor without protection, nor suspend cables overhead under excessive strain. Use padding to avoid chafing where
cables are routed around corners or through wall openings.
High/Low Temperature Hazard - Wear protective clothing when handling
equipment at extremes of temperature.
Materials testing is often carried out at non-ambient temperatures using ovens, furnaces or cryogenic chambers. Extreme temperature means an operating temperature
exceeding 60 °C (140 °F) or below 0 °C (32 °F). You must use protective clothing,
such as gloves, when handling equipment at these temperatures. Display a warning
notice concerning low or high temperature operation whenever temperature control
equipment is in use. You should note that the hazard from extreme temperature can
extend beyond the immediate area of the test.
Crush Hazard - Take care when installing or removing a specimen, assembly
or structure.
Installation or removal of a specimen, assembly or structure involves working inside
the hazard area between the grips or fixtures. Keep clear of the jaws of a grip or fixture
at all times. Keep clear of the hazard area between the grips or fixtures during actuator
or crosshead movement. Ensure that all actuator or crosshead movements necessary
for installation or removal are slow and, where possible, at a low force setting.
Hazard - Do not place a testing system off-line from computer control
without first ensuring that no actuator or crosshead movement will occur
upon transfer to manual control.
The actuator or crosshead will immediately respond to manual control settings when
the system is placed off-line from computer control. Before transferring to manual
control, make sure that the control settings are such that unexpected actuator or crosshead movement cannot occur.
iv
Preliminary Pages
Warnings
Robotic Motion Hazard - Keep clear of the operating envelope of a robotic
device unless the device is de-activated.
The robot in an automated testing system presents a hazard because its movements are
hard to predict. The robot can go instantly from a waiting state to high speed operation
in several axes of motion. During system operation, keep away from the operating
envelope of the robot. De-activate the robot before entering the envelope for any purpose, such as reloading the specimen magazine.
Hazard - Set the appropriate limits before performing loop tuning or running
waveforms or tests.
Limits are included within your testing system to provide a safe way of limiting actuator movement. Failure to set these limits appropriately could result in injury to personnel or damage to equipment.
Electrical Hazard - Disconnect the electrical power supply before removing
the covers to electrical equipment.
Disconnect equipment from the electrical power supply before removing any electrical safety covers or replacing fuses. Do not reconnect the power source while the covers are removed. Refit covers as soon as possible.
Rotating Machinery Hazard - Disconnect power supplies before removing
the covers to rotating machinery.
Disconnect equipment from all power supplies before removing any cover which
gives access to rotating machinery. Do not reconnect any power supply while the covers are removed unless you are specifically instructed to do so in the manual. If the
equipment needs to be operated to perform maintenance tasks with the covers
removed, ensure that all loose clothing, long hair, etc. is tied back. Refit covers as
soon as possible.
Hazard - Shut down the hydraulic power supply and discharge hydraulic
pressure before disconnection of any hydraulic fluid coupling.
Do not disconnect any hydraulic coupling without first shutting down the hydraulic
power supply and discharging stored pressure to zero. Tie down or otherwise secure
all pressurized hoses to prevent movement during system operation and to prevent the
hose from whipping about in the event of a rupture.
v
Preliminary Pages
M21-28800-70
Warnings
Hazard - Shut off the supply of compressed gas and discharge residual gas
pressure before you disconnect any compressed gas coupling.
Do not release gas connections without first disconnecting the gas supply and discharging any residual pressure to zero.
Explosion Hazard - Wear eye protection and use protective shields or
screens whenever any possibility exists of a hazard from the failure of a
specimen, assembly or structure under test.
Wear eye protection and use protective shields or screens whenever a risk of injury to
operators and observers exists from the failure of a test specimen, assembly or structure, particularly where explosive disintegration may occur. Due to the wide range of
specimen materials, assemblies or structures that may be tested, any hazard resulting
from the failure of a test specimen, assembly or structure is entirely the responsibility
of the owner and the user of the equipment.
Hazard - Ensure components of the loadstring are correctly preloaded to
minimize the risk of fatigue failure.
Dynamic systems, especially where load reversals through zero are occurring, are at
risk of fatigue cracks developing if components of the loadstring are not correctly preloaded to one another. Apply the specified torque to all loadstring fasteners and the
correct setting to wedge washers or spiral washers. Visually inspect highly stressed
components such as grips and threaded adapters prior to every fatigue test for signs of
wear or fatigue damage.
vi
Preliminary Pages
Table of Contents
Chapter 1
Chapter 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
Responsibilities. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Customer Responsibilities. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2
Site Plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2
Three-Phase Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2
Single-Phase Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2
Water Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3
Floor Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3
Noise Suppression . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3
Cable Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3
Pipe Runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4
Instron Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5
Insurance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5
Hydraulic System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5
Initial Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6
Chapter 3
Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Load Frame - General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Two-Column Load Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3
Four-Column Frames . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-8
Hydraulic Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-13
Electronic Control Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-14
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-15
vii
Preliminary Pages
Load Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-15
Hydraulic Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-16
Electronic Control Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-17
Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-18
Environmental Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-20
Air Cushion Isolators (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-21
Air Blast Coolers (Optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-22
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-22
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-22
Power Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-23
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-24
Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-24
Chapter 4
Lifting and Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
Load Frame. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2
Raising the Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2
Transporting the Frame using a Fork-Lift Truck . . . . . . . . . . . . . . . . . . . . . . .
4-6
Electronic Control Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-9
Hydraulic Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-10
Type 3410 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-10
Type 3411 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-10
Type 3420 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-10
Type 3470 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-10
Air Cushion Isolators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-14
Chapter 5
viii
M21-28800-70
Essential Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Electrical Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2
Load Frame and Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2
Hydraulic Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2
Impedance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3
Voltage and Frequency Variations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3
Hydraulic Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4
Water Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-8
Cooling Water Flow Rates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-8
Preliminary Pages
Water Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-9
Water Quality. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-9
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-10
Noise Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-11
Environmental Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-12
ix
Preliminary Pages
List of Illustrations
Figure 3-1. Two-Column Load Frame Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Figure 3-2. Load Frame Daylight Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Figure 3-3. Four-Column Load Frame Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Figure 3-4. Load Frame Daylight Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Figure 3-5. Air Blast Cooler Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
Figure 4-1. Lifting a Two-Column Load Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Figure 4-2. Lifting a Four-Column Load Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Figure 4-3. Maximum tilt angle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Figure 4-4. Transporting the Frame on a Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Figure 4-5. Transporting the Frame with forks under the Crosshead . . . . . . . . . . . . . . . . 4-8
Figure 4-6. Lifting the Type 3410 Hydraulic Power Supply. . . . . . . . . . . . . . . . . . . . . . . 4-11
Figure 4-7. Lifting the Type 3411 Hydraulic Power Supply . . . . . . . . . . . . . . . . . . . . . . . 4-12
Figure 4-8. Lifting the Type 3420 Hydraulic Power Supply. . . . . . . . . . . . . . . . . . . . . . . 4-13
xi
Preliminary Pages
List of Tables
Table 3-1.
Table 3-2.
Table 3-3.
Table 3-4.
Table 3-5.
Table 3-6.
Table 3-7.
Table 3-8.
Table 3-9.
Table 3-10.
Table 3-11.
Table 3-12.
Table 3-13.
Table 3-14.
Table 3-15.
Table 3-16.
Table 3-17.
Table 3-18.
Table 3-19.
Table 3-20.
Table 3-21.
Table 3-22.
Table 3-23.
Table 5-1.
Table 5-2.
Table 5-3.
Table 5-4.
Table 5-5.
Table 5-6.
Two-Column Load Frame Dimensions / mm (in)
(Refer to Figure 3-1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Two-Column Frame Overall Height / mm (in). . . . . . . . . . . . . . . . . . . . . . . 3-5
Two-Column Frame Daylight Dimensions
(See Figure 3-2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Four-Column Load Frame Dimensions / mm (in)
Actuator in Table (Refer to Figure 3-3). . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Four-Column Frame Overall Height / mm (in) . . . . . . . . . . . . . . . . . . . . . 3-10
Four-Column Frame Daylight Dimensions (see Figure 3-4). . . . . . . . . . . 3-12
Crated Hydraulic Power Supply Dimensions (Types 3410 and 3411) . . . 3-13
Crated Hydraulic Power Supply Dimensions(Type 3420) . . . . . . . . . . . . 3-13
Type 3410 and 3411 Hydraulic Power Supply Dimensions . . . . . . . . . . . 3-13
Type 3420 Hydraulic Power Supply Dimensions . . . . . . . . . . . . . . . . . . . 3-14
Type 3470 Hydraulic Power Supply Dimensions . . . . . . . . . . . . . . . . . . . 3-14
Electronic Control Equipment Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Two-Column Frame Weight and Stiffness . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Four-Column Frame Weight and Stiffness . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Types 3410 and 3411 Hydraulic Power Supply Weights . . . . . . . . . . . . . 3-16
Type 3420 Hydraulic Power Supply Weights . . . . . . . . . . . . . . . . . . . . . . 3-16
Type 3470 Hydraulic Power Supply Weights . . . . . . . . . . . . . . . . . . . . . . 3-16
Electronic Control System Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
Maximum Earth Fault Loop Impedance (Zs) for circuit supplying
electrical equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Air Cushion Isolator Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
Air Blast Cooler Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
Air Blast Cooler Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
Air Blast Cooler Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
Maximum Earth Fault Loop Impedance (Zs) for circuit supplying
electrical equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Hydraulic Hose Sets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Hose Thread Ends . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
SAE Hose Fitting to Actuator Manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
SAE Hose Fitting to Hydraulic Power Supply
(Types 3410 and 3411) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Extended Drain Hydraulic Pipe Run Dimensions . . . . . . . . . . . . . . . . . . . . 5-7
xiii
Preliminary Pages
Table 5-7.
Table 5-8.
Table 5-9.
Table 5-10.
Table 5-11.
Table 5-12.
Table 5-13.
Table 5-14.
Table 5-15.
Table 5-16.
xiv
M21-28800-70
Cooling Water Flow Rate Requirements for Type 3410 and 3411
Hydraulic Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Cooling Water Flow Rate Requirements for Type 3420
Hydraulic Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Cooling Water Flow Rate Requirements for Type 3470
Hydraulic Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Types 3410 and 3411 Hydraulic Power Supply Ventillation Requirements 5-10
Type 3420 Hydraulic Power Supply Ventillation Requirements . . . . . . . . 5-10
Type 3470 Hydraulic Power Supply Ventillation Requirements . . . . . . . . 5-10
Types 3410 and 3411 Hydraulic Power Supply Noise Levels . . . . . . . . . 5-11
Type 3420 Hydraulic Power Supply Noise Levels . . . . . . . . . . . . . . . . . . 5-11
Type 3470 Hydraulic Power Supply Noise Levels . . . . . . . . . . . . . . . . . . 5-11
Recommended Environmental Specifications . . . . . . . . . . . . . . . . . . . . . 5-12
Outline
This chapter describes the purpose of this manual and outlines the services and
utilities necessary for installing the Model 8800 Testing System.
Purpose
The purpose of this manual is to detail the various requirements that must be met
for the correct installation of the Model 8800 Servohydraulic Testing System. This
will ensure that the full range of services are available to the correct specification,
and that all necessary checks are completed before delivery of the system.
Terminology
The following terms are used within this manual:
STD — Standard height Frame
EXT — Extra height Frame
EXT-EXT — Extra-extra height frame
Note:
All references to “gallons” refer to U.S. gallons (3.78 litres), not U.K. gallons
(4.54litres).
1-1
Introduction
Chapter 1
Introduction
M21-28800-70
1-2
Responsibilities
Chapter 2
Responsibilities
Outline
The purpose of this chapter is to detail the responsibilities of both the customer
and Instron to ensure that the proposed testing area is suitable for the installation
and operation of the testing system.
2-1
Customer Responsibilities
M21-28800-70
Customer Responsibilities
It is the responsibility of the customer to ensure that all required support services
are available, and that all necessary checks are made to allow the correct
installation of the testing system.
These services and checks are detailed in this chapter.
Site Plan
A site plan must be available, which indicates the proposed positioning of the load
frame and control console. A copy of the site plan should be sent to the Instron
Area Office in advance.
Three-Phase Power Supply
The hydraulic power supply requires a three-phase supply of 220V, 380/420V or
460V, at either 50Hz or 60Hz as specified for the type of power supply ordered.
Note:
Different pump motors are used for 50 Hz and 60Hz supplies — the frequency is
not variable.
The supply should be terminated with a suitably-rated, lockable, fused isolator as
near as possible to the hydraulic power supply, and with access to adequate
earthing terminations. This must still be accessible once the hydraulic power
supply has been installed. Refer to Chapter 5, Essential Services, for details of the
earthing requirements. The electrical connection to the hydraulic power supply
must be of flexible sheathed cable, chosen to suit local regulations to be supplied
by the customer.
Single-Phase Power Supply
Single phase power point, 230 V ±10% at 50 Hz, or 115 V ±10% at 50/60Hz as
required, must be available for mains supply to the load frame, and for general
use.
Water Supply
If you require a water-cooled hydraulic power supply, a water supply must be
available, together with sufficient piping. Chapter 5, Essential Services, details the
water supply rate, quality and temperature requirements for the various types of
pump.
2-2
Customer Responsibilities
Ventilation
Responsibilities
If you require an air-cooled hydraulic power supply, then adequate ventilation is
essential. Chapter 5 details the ventilation requirements for the various types of
hydraulic pump.
Air blast coolers are available if necessary.
Floor Loading
The site floor should be checked for weight loading. The local architect or
flooring specialist should be consulted.
The maximum weights of the load frames and console are given in Chapter 3,
Specifications. Remember that in high performance installations large dynamic
loadings may occur, thus the load capacity should be in excess of three times the
combined weight of the system and operator.
Cyclic and shock loads may require the use of anti-vibration mountings.
Noise Suppression
When siting the hydraulic power supply, consideration should be given to the
noise emission level. It is usually more convenient if the hydraulic pump is sited
in a separate room adjacent to the operating location. If special rooms have to be
built, materials suitable for sound insulation should be used. Chapter 5, Essential
Services, details the noise emission levels for the various types of hydraulic power
supply.
Cable Specification
The local electricity supply authority should be consulted for advice on cable
specifications, with consideration being given to motor start up current surges.
Chapter 5, Essential Services, gives advice on maximum current levels for various
types of hydraulic power supply.
Pipe Runs
All hydraulic pipe runs must be clean to Thermal Control Class 2 (U.K.) or ISO
Solid Contaminant Code 13/10 (U.S.A.) or NAS Class 4. Details of the required
standard are given in all individual hydraulic power supply manuals.
All pipe runs should be tested to the following pressures:
•
Pressure line — 560bar (8000psi)
2-3
Customer Responsibilities
•
Return line — 140bar (2000psi)
•
Drain line — 20 bar (150 psi)
M21-28800-70
Cleanliness and pressure checks should be carried out immediately before
installation is started. It should be noted that higher proof pressure may be
required to meet local standard practice, or the demands of the customer’s
insurers.
When the hydraulic pump is to be situated at a distance greater than 6metres from
the load frame, steel pipe runs should be provided. Refer to Chapter 5, Essential
Services, for details of the requirements for drain line bore and maximum pipe run
length. Instron can supply the flexible pipes for both ends of the pipe run in either
3 or 6 metre lengths.
Where steel pipes are used, it will be necessary to clamp the pipe to avoid excess
noise and vibration, especially when operating the testing system with large
actuator excursion. The pipes should be clamped firmly in rubber cushion blocks.
Hoses must have adequate packing to avoid chafing and must be firmly supported
by clamps when routed other than along the floor.
Handling
Unless specifically arranged otherwise, it is the customer’s responsibility to
arrange for off-loading, unpacking and moving the testing system to the final
operating location. This includes insurance and safety responsibilities.
2-4
Instron Responsibilities
The equipment and services provided by Instron as part of the contract to supply
the 8800 Series Testing System are as given below. Where special conditions
apply, the corresponding equipment and services should be the subject of a
separate and specific quotation.
Insurance
Instron will provide insurance cover from the manufacturing site in the U.K. to the
customer’s premises in the U.K.. In the U.S.A. insurance cover from the
manufacturing site to the customer’s premises is usually the responsibility of the
carrier. Outside of these areas all purchase orders must indicate specifically which
party is to effect marine insurance cover. In the absence of this indication, Instron
will arrange insurance cover at the customer’s expense.
Handling
On arrival at the customer’s premises, Instron will, upon special request, supervise
the off-loading and transportation onto the site, this being a special condition as
mentioned above.
Installation
Once components are on the site and in position, Instron will be responsible for
making all electrical and hydraulic connections between the load frame, hydraulic
power supply and control system. Where steel pipes are used for hydraulic
connections, Instron will connect both ends of such runs with flexible hoses as
ordered by the customer.
Hydraulic System
Instron will provide the first fill of all necessary oils and lubricants, and will be
responsible for carrying out flushing of the hydraulic system where a complete
system has been supplied. If the customer’s own hydraulic oil installation is used,
Instron will not connect until the required standards of cleanliness have been
achieved by the customer at their expense. In those cases where the customer
desires to use an existing hydraulic supply or has incorporated steel pipe runs in a
package system but has not flushed the system to ISO Solid Contaminant Code
13/10 (U.S.A.), NAS Class 4, or Thermal Control Class 2 (U.K.). Instron will,
upon special request, carry out flushing and contamination checks on such
systems.
2-5
Responsibilities
Instron Responsibilities
Instron Responsibilities
Note:
M21-28800-70
Flushing and contamination checking equipment for new or existing installations
may be purchased from Instron.
Initial Operation
Having made all necessary connections, Instron will be responsible for running up
the system and for a calibration check and customer demonstration. Following the
initial demonstration of the equipment, further training can be given to the
customer by initially contacting the local Instron area office who will be happy to
advise.
Documentation
Instron will provide all necessary documentation. Further copies may be supplied
as itemised on the customer’s order.
2-6
Chapter 3
Specification
This chapter details the specifications of the testing system components. This is to
ensure that you have chosen a suitable site for your testing system.
3-1
Specification
Outline
Dimensions
M21-28800-70
Dimensions
Load Frame - General
There are several different configurations of table height, column length and
actuator mounting height available to suit customer requirements. Standard or
extra height columns, standard or extra height tables and table or crosshead
mounted actuators are available for all frame sizes.
Daylight dimensions and table height measurements for the two-column load
frames are independent of the location of the actuator, but for the four-column
frames these dimensions are dependent upon the actuator position.
Figures 3-1 to 3-4, and Tables 3-1 to 3-8 detail the dimensions of the Series 8800
Load Frames.
3-2
Dimensions
Two-Column Load Frame
Specification
Refer to Table 3-1
Figure 3-1. Two-Column Load Frame Dimensions
3-3
Dimensions
M21-28800-70
Table 3-1. Two-Column Load Frame Dimensions / mm (in)
(Refer to Figure 3-1)
Frame Type
3-4
Dimension
Description
8802 B1
8802 B2
8803 B1
8803 B2
A
Column Spacing
664 (26)
664 (26)
778 (31)
788 (31)
B
Column
Diameter
76 (3)
76 (3)
101 (4)
101 (4)
C
Column Length
1780 (70)
2240 (88)
2240 (88)
1680
(106)
D
Crosshead
Depth
275 (11)
275 (11)
350 (14)
350 (14)
E
Crosshead
Length
200 (8)
200 (8)
275 (11)
275 (11)
F
Crosshead Width
1030 (41)
1030 (41)
1230 (48)
1230 (48)
G
Table Depth
150 (6)
150 (6)
200 (8)
200 (8)
H
Table Length
300 (12)
300 (12)
380 (15)
380 (15)
J
Table Width
870 (34)
870 (34)
1030 (41)
1030 (41)
K
Table Height
910 (36)
1115 (44)
1015 (40)
1220 (48)
L
Overall Width
1060 (42)
1060 (42)
1270 (50)
1270 (50)
M
Overall Length
1120 (44)
1120 (44)
1220 (48)
1220 (48)
N
Base Width
120 (5)
120 (5)
150 (6)
150 (6)
P
Base Depth
80 (3)
80 (3)
100 (4)
100 (4)
R
Hole Diameter
14 (0.6)
14 (0.6)
18 (0.7)
18 (0.7)
Dimensions
For the B3 height option, the column lengths are as follows:
8802 – 2640mm (104 in).
8803 – 3040mm (120 in).
If air cushion isolators are fitted, add 89 mm (3.5 in) to dimension K.
Table 3-2. Two-Column Frame Overall Height / mm (in)
Frame Configuration
Frame Type
Actuator in Table
8802
8803
Std Table, B1 Column
2790 (110)
3355 (132)
Std Table, B2 Column
3250 (128)
3795 (149)
Std Table, B3 Column
3650 (144)
4155 (163)
Ext Table, B1 Column
2995 (118)
3560 (140)
Ext Table, B2 Column
3455 (136)
4000 (158)
Ext Table, B3 Column
3855 (152)
4360 (172)
Actuator in Crosshead
8802
8803
100 kN Frame, B1 Column
3606 (142)
N/A
100 kN Frame, B2 Column
4066 (160)
N/A
100 kN Frame, B3 Column
4466 (176)
N/A
250 kN Frame, B1 Column
3626 (143)
4191 (165)
250 kN Frame, B2 Column
4086 (161)
4631 (182)
250 kN Frame, B3 Column
4486 (177)
4991 (197)
500 kN Frame, B1 Column
N/A
4245 (167)
500 kN Frame, B2 Column
N/A
4685 (185)
500 kN Frame, B3 Column
N/A
5045 (199)
Specification
Note:
3-5
Dimensions
M21-28800-70
Note:
If air cushions are fitted, add 89 mm (3.5 in).
The figures shown for the actuator in the crosshead are based upon the ±125 mm
(5 in) stroke actuator. For the ±75 mm (3 in) actuator, subtract 204 mm (8 in) from
the height. For the ±50 mm (2 in) stroke actuator, subtract 306 mm (12 in) from the
height.
Table 3-3. Two-Column Frame Daylight Dimensions
(See Figure 3-2)
Frame Type
Dim
Description
8802
8803
A
Load Cell Depth
50 KN (11 kip)
100 KN (22 kip)
250 KN (55 kip)
500 KN (110 kip)
97 (3.8)
97 (3.8)
128 (5.0)
N/A
N/A
N/A
128 (5.0)
232 (9.1)
B
Piston Length
Retracted
100 KN (22 kip)
250 KN (55 kip)
500 KN (110 kip)
66 (2.6)
66 (2.6)
N/A
N/A
66 (2.6)
68 (2.7)
C
Hydraulic Grip Depth
100 KN (22 kip)
250 KN (55 kip)
500 KN (110 kip)
132 (5.2)
195 (7.7)
N/A
N/A
195 (7.7)
265 (10.4)
D
Pre-Load Washer
Depth
M30 x 2
M48 x 2
M72 x 3
27 (1.1)
27 (1.1)
N/A
N/A
27 (1.1)
48 (1.8)
E
Table Height
Std
Ext
910 (38.5)
1115 (43.9)
1015 (40)
1220 (48)
316
316
316
231
231
231
(12.4)
(12.4)
(12.4)
(9.1)
(9.1)
(9.1)
1515
1975
2375
1900
2340
2700
(59.6)
(77.6)
(93.5)
(74.8)
(92.1)
(106)
111
111
111
16
16
16
(4.4)
(4.4)
(4.4)
(0.6)
(0.6)
(0.6)
1515
1975
2375
1900
2340
2700
(59.6)
(77.8)
(93.5)
(74.8)
(92.1)
(106)
B1
B2
B3
B1
B2
B3
Min (std)
Max (std)
F
X-Head To Table
Distance
Min (ext)
Max (ext)
COLUMN LENGTH
3-6
Specification
Dimensions
Figure 3-2. Load Frame Daylight Dimensions
Note:
For dimension ‘G’ (see Figure 3-3), calculate thus:
‘F’ (Max or Min) – (A+B+2C+2D).
3-7
Dimensions
M21-28800-70
Four-Column Frames
Refer to Table 3-4
Figure 3-3. Four-Column Load Frame Dimensions
3-8
Dimensions
Table 3-4. Four-Column Load Frame Dimensions / mm (in)
Actuator in Table (Refer to Figure 3-3)
Frame Type
Description
8804 B1
8804 B2
8805 B1
8805 B2
8806 B1
8806 B2
A
Column Spacing
664 (26)
664 (26)
788 (31)
788 (31)
822 (32)
822 (32)
B
Column Spacing
306 (12)
306 (12)
410 (16)
410 (16)
514 (20)
514 (20
C
Column Diameter
76 (3)
76 (3)
102 (4)
102 (4)
152 (6)
152 (6)
D
Column Length
E
Crosshead Depth
254 (10)
254 (10)
305 (12)
305 (12)
305 (12)
305 (12)
F
Crosshead Length
558 (22)
558 (22)
712 (28)
712 (28)
940 (37)
940 (37)
G
Crosshead Width
1030 (41) 1030 (41)
1230 (49)
1230 (49)
1400 (55)
1400 (55)
H
Table Depth
150 (6)
150 (6)
200 (8)
200 (8)
345 (14)
345 (14)
J
Table Length
558 (22)
558 (22)
712 (28)
712 (28)
940 (37)
940 (37)
K
Table Width
870 (34)
870 (34)
1030 (41)
1030 (41)
1145 (45)
1145 (45)
L
Table Height
1005 (40) 1240 (49)
1160 (46)
1360 (54)
1656 (65)
1856 (73)
M
Overall Width
1080 (43) 1080 (43)
1325 (56)
1325 (56)
1500 (59)
1500 (59)
N
Overall Length
1000 (39) 1000 (39)
1220 (48)
1220 (48)
1500 (59)
1500 (59)
Note:
2240 (88) 2640 (104) 2680 (106) 3040 (120) 2810 (111) 3310 (130)
If air cushion isolators are fitted, add 89 mm (3.5 in) to dimension L.
The figures for overall width are measured at the crosshead. The width at the
base varies as follows:
8804 - 1015 mm (40 in)
8805 - 1175 mm (46 in)
8806 - 1330 mm (52 in)
The height for base mounted tables varies as follows:
8805 - 300 mm (12 in)
8806 - 500 mm (20 in)
3-9
Specification
Dim
Dimensions
M21-28800-70
Table 3-5. Four-Column Frame Overall Height / mm (in)
Frame Configuration
Note:
Frame Type
Actuator In Table
8804
8805
8806
Std Table, B1 Column
3270 (129)
3875 (153)
4516 (178)
Std Table, B2 Column
3670 (145)
4235 (167)
5016 (198)
Ext Table, B1 Column
3505 (138)
4075 (160)
4716 (186)
Ext Table, B2 Column
3905 (154)
4435 (175)
5216 (205)
Actuator In Crosshead
8804
8805
8806
Std Table, B1 Column
4235 (167)
N/A
N/A
Std Table, B2 Column
4635 (183)
N/A
N/A
Ext Table, B1 Column
N/A
4110 (162)
4675 (184)
Ext Table, B2 Column
N/A
4470 (176)
5175 (204)
a. If air cushion isolators are fitted, add 89 mm (3.5 in).
b. The figures shown for the actuator in the crosshead are based upon the
250 mm (10 in) (±125 mm (±5 in)) stroke actuator.
For the 150 mm (6 in) (±75 mm (±3 in)) stroke actuator, subtract 204 mm
(8 in) from the height.
For the 100 mm (4 in) (±50 mm (±2 in)) stroke actuator, subtract 306 mm
(12 in) from the height.
3-10
Specification
Dimensions
Figure 3-4. Load Frame Daylight Dimensions
3-11
Dimensions
M21-28800-70
Table 3-6. Four-Column Frame Daylight Dimensions (see Figure 3-4)
Frame Type
Dim
Description
8805
8806
A
Load Cell
Depth
500 KN (110 kip)
1000 KN (220 kip)
2500 KN (550 kip)
232 (9.1)
N/A
N/A
232 (9.1)
360 (14.2)
N/A
N/A
360 (14.2)
450 (17.7)
B
Piston
Length
Retracted
500KN (110kip)
1000 IKN (220 kip)
2500 KN (550 kip)
118 (4.6)
N/A
N/A
68 (2.7)
303 (11.9)
N/A
N/A
443 (17.4)
421 (16.6)
C
Hydraulic
Grip Depth
500 KN (110 kip)
1000 KN (220 kip)
2500 kn (550 kip)
265 (10.4)
N/A
N/A
265 (10.4)
345 (13.6)
N/A
N/A
345 (13.6)
No Data
D
Pre-Load
Washer
Depth
M72 x 3
M100 x 4
M150 x 4
48 (1.9)
N/A
N/A
48 (1.9)
60 (2.4)
N/A
N/A
60 (2.4)
60 (2.4)
E
Table Height
Base
Std
Ext
N/A
1005 (39.6)
1240 (48.8)
300 (11.8)
1160 (45.7)
1360 (53.5)
500 (19.7)
1656 (65.2)
1856 (73.1)
N/A
930
930
730
730
(36.6)
(36.6)
(28.7)
(28.7)
2375
2375
2505
3005
(93.5)
(93.5)
(98.6)
(118.3)
0
0
Min (base)
Max (base)
Min (std)
F
X-Head To
Table
Distance
N/A
N/A
N/A
207
207
52
52
(8.1)
(8.1)
(2)
(2)
1986
2386
2735
2735
2505
3005
(78.2)
(93.9)
(107.7)
(107.7)
(98.6)
(118.3)
Min (ext)
0
0
0
0
0
0
Max (ext)
1986
2386
2735
2735
2505
3005
(78.2)
(93.9)
(107.7)
(107.7)
(98.6)
(118.3)
B1
B2
B1
B2
B1
B2
Max (std)
Column Length
3-12
8804
Dimensions
Hydraulic Power Supply
The following tables detail the dimensions for the different types of hydraulic
power supply that may be supplied with the 8800 Testing System.
The Type 3410, 3411 and 3420 hydraulic power supplies are packed in crates. The
crate dimensions are given below.
Hydraulic Power Supply
Delivery
litres/min (gal/min)
Height
mm (in)
Width
mm (in)
Depth
mm (in)
30 (8)
1200 (47)
1030 (41)
1630 (64)
45 (12)
1200 (47)
1030 (41)
1630 (64)
80 (21)
1330 (52)
1580 (62)
2440 (96)
230 (60)
1600 (63)
1740 (69)
3340 (131)
Table 3-8. Crated Hydraulic Power Supply Dimensions(Type 3420)
Hydraulic Power Supply
Both capacities use the same
shipping crate
Height
mm (in)
Width
mm (in)
Depth
mm (in)
1260 (49.6)
1020 (40.1)
810 (31.9)
Table 3-9. Type 3410 and 3411 Hydraulic Power Supply Dimensions
Hydraulic Power Supply
Delivery
litres/min (gal/min)
Height
mm (in)
Width
mm (in)
Depth
mm (in)
30 (8)
901 (35.5)
930 (37)
1330 (52)
45 (12)
902 (35.5)
930 (37)
1330 (52)
80 (21)
1010 (10)
1250 (49)
2100 (83)
230 (60)
1200 (47)
1625 (64)
3000 (118)
3-13
Specification
Table 3-7. Crated Hydraulic Power Supply Dimensions (Types 3410
and 3411)
Dimensions
M21-28800-70
Table 3-10. Type 3420 Hydraulic Power Supply Dimensions
Hydraulic Power Supply
Delivery
litres/min (gal/min)
Height
mm (in)
Width
mm (in)
Depth
mm (in)
12.5 (3.3)
870 (34)
877 (35)
663 (26)
25 (6.6)
1000 (39)
877 (35)
663 (26)
Table 3-11. Type 3470 Hydraulic Power Supply Dimensions
Hydraulic Power Supply
Delivery
litres/min (gal/min)
Height
mm (in)
Width
mm (in)
Depth
mm (in)
23 (6)
800 (31.5)
787 (31)
724 (28.5)
38 (10)
1092 (43)
1016 (41)
660 (26)
77 (20)
1118 (44)
1346 (53)
965 (38)
The Type 3470 Hydraulic Power Supply is supplied uncrated, on a wooden pallet.
Note:
A sound enclosure may be used with the 23 l/min hydraulic power supply. The
dimensions for this are: Height 1016 mm (40 in), Width 1118 mm (44 in), Depth
966 mm (38 in).
Electronic Control Equipment
The table below details the dimensions of the tower console and front panel
controller.
Table 3-12. Electronic Control Equipment Dimensions
Note:
3-14
Equipment Type
Height
mm (in)
Width
mm (in)
Depth
mm (in)
Tower
650 (25.6)
280 (11.0)
570 (22.4)
8800 Control
Panel (optional)
280 (11.0)
270 (10.6)
300 (11.8)
Actuator
Interface Box
130 (5.1)
115 (4.5)
60 (2.4)
Handset
200 (7.9)
130 (5.1)
80 (3.1)
An additional 75 mm (3 in) should be provided at the rear of the console for
cooling and cable routing.
Weights
Weights
Load Frame
Table 3-13 and Table 3-14 give the weight and stiffness data for the 8800 Series
Load Frames
Table 3-13. Two-Column Frame Weight and Stiffness
8802
8803
Weight kg (lb)
1330 (2929)
2450 (5396)
Stiffness kN/mm (lb/in)
585 (3.27 × 106)
1066 (5.9 × 106)
Table 3-14. Four-Column Frame Weight and Stiffness
Frame Type
Weight and Stiffness data
Note:
8804
8805
8806
Weight kg (lb)
2952 (6500)
4900 (10790)
10000 (22020)
Stiffness kN/mm (lb/in)
1086 (6.1 × 106)
2102 (1.2 × 107) 4413 (2.5 × 107)
The weights specified in these tables are approximate guides only; where
possible the weight has been assessed with the heaviest actuator, grips and
loadcell for that particular load frame.
The measurements for load frame stiffness are calculated with the crosshead set
1000 mm above the machine table.
3-15
Specification
Frame Type
Weight and Stiffness data
Weights
M21-28800-70
Hydraulic Power Supply
The follwing tables detail the weights appplicable to the various types of
hydraulic power supply that may be supplied with the 8800 Testing System.
Table 3-15. Types 3410 and 3411 Hydraulic Power Supply Weights
Hydraulic Power Supply
Deliveryl/min (gal/min)
Dry Weightkg (lb)
Filled weightkg (lb)
12.5 (3.25)
250 (550)
300 (660)
30 (8)
550 (1210)
660 (1452)
45 (12)
550 (1210)
660 (1452)
80 (21)
860 (1892)
1180 (2596)
230 (60)
1805 (3971)
2605 (5731)
Table 3-16. Type 3420 Hydraulic Power Supply Weights
Hydraulic Power Supply
Deliveryl/min (gal/min)
Dry Weightkg (lb)
Filled weightkg (lb)
12.5 (3.25)
163 (359)
250 (551)
24 (6.6)
213 (469)
300 (661)
Table 3-17. Type 3470 Hydraulic Power Supply Weights
Note:
3-16
Hydraulic Power Supply
Deliveryl/min (gal/min)
Dry Weightkg (lb)
Filled weightkg (lb)
23 (6)
165 (360)
235 (520)
38 (10)
320 (700)
440 (970)
77 (20)
635 (1400)
920 (2020)
A sound enclosure may be used with the 23 l/min hydraulic power supply. The
weight including the hydraulic power supply will be 318 kg (700 lb).
Weights
Electronic Control Equipment
Table 3-18 details the weights applicable to the various components of the
electronic control system.
Table 3-18. Electronic Control System Weights
Weight kg (lb)
8800 Tower
Up to 32 kg (70.5 lb)
(i.e. 32 kg fully populated with all optional boards)
8800 Control Panel (optional)
2.2 kg (48.5 lb)
Actuator Interface Box
1 kg (2.2 lb)
Handset
approx 200g (6oz)
Specification
Equipment
3-17
Power Supplies
M21-28800-70
Power Supplies
Details the reccomended maximum earth fault loop impedance for equipment
supplies.
Table 3-19. Maximum Earth Fault Loop Impedance
(Zs) for circuit supplying electrical equipment
Note:
Fuse Rating (Amps)
Zs (Ohms)
6
14.10
10
7.74
16
4.36
20
3.04
25
2.40
32
1.92
40
1.41
50
1.093
63
0.86
80
0.60
100
0.44
125
0.35
160
0.27
200
0.20
When U0, the nominal voltage to earth (ground) is not 240 V, the tabulated
impedance values must be multiplied by U0/240.
The above figures are based upon the IEE Wiring Regulations, Sixteenth Edition
1991, Table 41D. There are no comparable US standards, but the above values
may be used as guidelines.
3-18
Power Supplies
Input Supply:
30A at 100 to 125V in 5V steps, or 13A at 200 to 250V in 10V
steps, single phase.
Input Frequency: 50-60 Hz ±5 %.
Line voltage
variation:
All ancillary electrical equipment connected to the load frame should be powered
from the same electrical supply.
Specification
Note:
±10 %, free from noise and transients.
3-19
Environmental Conditions
M21-28800-70
Environmental Conditions
Temperature (operating):
5 to 38 °C (41 to 100 °F)
Temperature (storage):
-30 to 50 °C (-22 to 122 °F)
Temperature (rate of change): 2 °C (4 °F) per hour. Changes above this rate may
affect the performance of this equipment.
Relative humidity:
3-20
10 to 90 %, non-condensing.
Air Cushion Isolators (Optional)
Air Cushion Isolators (Optional)
Table 3-20 gives the specification for the different types of air cushion isolators.
Table 3-20. Air Cushion Isolator Specifications
Air Cushion Isolator Type
SLM-6
SLM-12
SLM-14
Height of
Mounting
89 mm (3.5 in)
89 mm (3.5 in)
89 mm (3.5 in)
Diameter of
Mounting
61 mm (2.4 in)
95 mm (3.75 in)
138 mm (5.4 in)
Mounting Thread
0.5” - 13 UNC x
0.54” deep
0.5” - 13 UNC x
0.54” deep
0.625” - 11UNC x
0.75” deep
Maximum static
load per mount
273 kg (600 lb)
545 kg (1200 lb)
1090 kg (2400 lb)
Minimum static
load per mount
68 kg (150 lb)
1236 kg (300 lb)
275 kg (600 lb)
Maximum
inflation pressure
6 bar (90 psi)
6 bar (90 psi)
6 bar (90 psi)
3-21
Specification
Parameter
Air Blast Coolers (Optional)
M21-28800-70
Air Blast Coolers (Optional)
General
If your hydraulic power supply is air-cooled, it may require an air blast cooler.
An air blast cooler circulates hot oil through an external radiator which has a large
fan attached. The fan forces cooling air through the vanes of the radiator, thus
cooling the oil quickly and efficiently.
Dimensions
Refer to Figure 3-5 and Table 3-21.
Figure 3-5. Air Blast Cooler Dimensions
3-22
Air Blast Coolers (Optional)
Table 3-21. Air Blast Cooler Dimensions
Type
BD10
BD20
BD30
BD50
BD75
BD100
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S
X
485
302.5
605
32
272.5
545
291
460
508
384
180
50
553
-
220
190
1"
660
430
860
38
360
760
410
680
742
431
200
50
770
-
220
190
1.25"
850
505
1010
35
465
930
444
750
810
531
300
60
940
70
260
160
1.5"
850
525
1050
51
475
950
505
860
932
541
300
75
960
100
340
200
2"
930
590
1180
51
540
1080
570
960
1062
646
370
100
1090
120
410
250
2"
1160
680
1360
51
630
1260
660
1140
1242
646
370
100
1270
120
410
250
2"
Power Requirements
All Air Blast Coolers require three-phase 380/415V at 50 Hz.
3-23
Specification
Dimension
Air Blast Coolers (Optional)
M21-28800-70
Weight
Table 3-22. Air Blast Cooler Weights
Type
Approximate Dry Weight kg (lbs)
BD10
43 (95)
BD20
86 (190)
BD30
113 (250)
BD50
186 (410)
BD75
311 (685)
BD100
365 (803)
Specification
Table 3-23. Air Blast Cooler Specifications
Type
Airflow m3/S
Motor rpm
Motor kW
Noise dBA*
BD10
0.94
2700
0.37
84
BD20
1.91
1400
0.55
80
BD30
2.48
1400
0.75
83
BD50
3.21
1400
1.1
80
BD75
3.87
1400
1.5
83
BD100
5.29
1400
2.2
85
* averaged at 1 metre.
3-24
Chapter 4
Lifting and Handling
Outline
This chapter gives you information required for moving the load frame to your
desired location and unpacking it.
Unless specifically arranged otherwise, it is the customer’s responsibility to
arrange for off-loading, unpacking and transporting the equipment to the final site
at the customer’s premises. This includes insurance and safety responsibilities.
It is essential to transport the equipment by crane or fork-lift truck from the offloading site to an area for unpacking, as close as possible to the operating site.
While environmental conditions in the vicinity of the testing equipment are not
critical (refer to “Environmental Conditions” on page 3-20), attention should be
given to the siting of the equipment in locations where air-borne dust and dirt can
be held to a minimum. Floor loading is a major consideration, and a reasonably
level floor with a loading capacity in excess of three times the combined weight of
the load frame, control system and the operator is required. Ground floor locations
are preferred, as the loading capacity is usually sufficient and floor vibrations
during testing are minimised.
Warnings
.
Ensure that cranes or fork-lift trucks used to move the equipment have
adequate load capacity (1.5 × gross weight).
Ensure that slings used are serviceable and are of the correct length and
proof loading.
Ensure that the yellow safety collar is clamped under the crosshead
whenever the frame is moved.
Ensure that the crosshead clamp bolts have been tightened for transit to a
torque of 230 Nm (170 lb ft).
4-1
Lifting and
Handling
General
Load Frame
M21-28800-70
Load Frame
Raising the Frame
The 8800 Series Load Frames are packed and mounted horizontally on a pallet,
which should remain in position until the frame is at the operating site, where it
can then be removed with all other straps, hold-downs and loose packing material.
Caution
Do not use the column eye-bolts to raise the frame. They are to be used for
vertical lifting of the frame only.
Two Column Frames
In order to raise the frame to a vertical position, refer to Figure 4-1 and use the
following procedure.
a. Ensure that the crosshead is in the lowest position and that the metal support for the columns is fitted.
b. Fit a fibre sling around the top of the columns, below the metal support as
shown in Figure 4-1. Ensure that adequate packing material is used to
protect the columns.
c. Ensure that the crane or hoist is correctly positioned, and that the pivoting
edges of the frame feet are chocked to prevent movement during lifting.
d. Raise the frame to the vertical position.
4-2
Load Frame
CRANE OR HOIST
MAXIMUM ANGLE OF
SLING 60°
TIE BAR MUST BE IN
POSITION PRIOR TO
LIFTING AND
TRANSPORTATION
METAL SUPPORT MUST
BE IN POSITION PRIOR TO
LIFTING AND
TRANSPORTATION
CROSSHEAD CLAMP
YELLOW SAFETY
COLLAR
USE EYE BOLTS FOR
VERTICAL LIFTING
ONLY. MAXIMUM
ANGLE OF SLING 60°
Lifting and
Handling
PROTECTIVE SOFT
COLUMN PADS
Figure 4-1. Lifting a Two-Column Load Frame
4-3
Load Frame
M21-28800-70
Four-Column Frames
In order to raise the frame, refer to Figure 4-2 and use the following procedure.
a. Ensure that the crosshead is in the lowest position, and that the column
supports are fitted.
b. Fit the shackles to the crosshead lifting brackets and fit a lifting sling to
the shackles as shown in Figure 4-2.
c. Ensure that the crane or hoist is correctly positioned, and that the pivoting
edges of the frame feet are chocked to prevent movement during lifting.
d. Raise the frame to a vertical position.
4-4
Load Frame
CRANE OR HOIST CAPACITY
1.5 x GROSS WEIGHT
Lifting and
Handling
ENSURE THAT METAL
SUPPORTS FOR COLUMNS
ARE IN POSITION AS SHOWN.
TO BE REMOVED UPON
INSTALLATION
Figure 4-2. Lifting a Four-Column Load Frame
4-5
Load Frame
M21-28800-70
Transporting the Frame using a Fork-Lift Truck
There are two methods of transporting the load frame when using a fork-lift truck,
and both are described in this section.
Warning
Hazard - Do not allow the frame to become tilted at an angle greater than 10°
when transporting across sloping or uneven surfaces.
10°
MAXIMUM
TILT ANGLE
Figure 4-3. Maximum tilt angle
4-6
Load Frame
Transporting the Frame on a Pallet
a. Construct or obtain a pallet which is slightly larger than the base of the
frame.
b. With the frame standing in an upright position, use a crane or hoist to lift
the frame onto the pallet.
c. Position the fork-lift truck to that the lifting forks can be inserted from the
front of the frame.
d. Insert the forks fully under the pallet, and for stability pass a sling of soft
fibre around the crosshead and secure it to the fork-lift truck as shown in
Figure 4-4.
e. Raise the frame and transport it to the operating site.
SLING TIED TO FORK-LIFT TRUCK
PALLET
Figure 4-4. Transporting the Frame on a Pallet
4-7
Lifting and
Handling
10° MAXIMUM TILT
ANGLE
Load Frame
M21-28800-70
Transporting the Frame with the Forks under the Crosshead
a. With the frame standing in the upright position, move the fork-lift truck
so that the lifting forks can be inserted from the front of the frame.
b. Place soft padding material onto the forks of the truck to prevent any
damage to the paint finish or to the logo on the crosshead.
c. Carefully insert the forks under the crosshead and, for stability, pass a
sling of soft fibre around the crosshead and secure to the fork-lift truck as
shown in Figure 4-5.
d. Raise the frame and transport it to the operating site.
Figure 4-5. Transporting the Frame with forks under the Crosshead
4-8
Electronic Control Equipment
Electronic Control Equipment
The control system components are normally packed in the same crate as the load
frame. However, this depends on the frame type and the number of accessories
supplied.
Lifting and
Handling
Always ensure that all individually packaged items are removed from the main
packing crate before making any attempt to lift the frame.
4-9
Hydraulic Power Supply
M21-28800-70
Hydraulic Power Supply
Caution
Do not lift the hydraulic power supply with a crane or hoist when there is oil
in the tank.
Do not use the motor lifting ring to lift the hydraulic power supply.
Type 3410
Remove the top and side panels of the packing crate and, using the lifting eyes
located at each corner of the supply, and a four-sided frame lifting sling as shown
in Figure 4-6, raise the hydraulic power supply and transport it to the operating
site. Ensure that the sling does not make contact with any power supply
component.
Type 3411
Remove the top and side panels of the packing crate and the hydraulic power
supply. Using the lifting eyes mounted on the lower frame members and a foursided lifting sling as shown in Figure 4-6, raise the hydraulic power supply and
transport it to the operating site. Ensure that the sling does not make contact with
any power supply component.
Type 3420
Four lifting eyebolts are fitted for handling purposes and when the shipping crate
is dismantled and support packing removed, the pack may be lifted and positioned
by using suitable slings and a hoist which must have a safe working capacity i.e.
1.5 x the gross weight of the hydraulic power supply.
Type 3470
The type 3470 hydraulic power supply is shipped upon an open wooden pallet and
should only be handled using a fork-lift truck.
4-10
Lifting and
Handling
Hydraulic Power Supply
Figure 4-6. Lifting the Type 3410 Hydraulic Power Supply
4-11
Hydraulic Power Supply
Figure 4-7. Lifting the Type 3411 Hydraulic Power Supply
4-12
M21-28800-70
Lifting and
Handling
Hydraulic Power Supply
Figure 4-8. Lifting the Type 3420 Hydraulic Power Supply
4-13
Air Cushion Isolators
M21-28800-70
Air Cushion Isolators
The optional air cushion isolators must not be inflated without the weight of the
load frame upon them. They are therefore supplied fitted to the load frame, but
deflated for shipment.
When the frame is finally positioned at the testing site, they should be sequentially
pressurised to an air pressure which must not exceed 6 bar (90 psi). The overall
mount height between the frame foot and the floor should be 89 ± 6 mm (3.5 ±
0.25 in).
Caution
Deflate the air cushion isolators before moving the load frame.
If the load frame is subsequently moved, the air cushion isolators must first be
deflated. They must be re-inflated after the move is complete.
4-14
Chapter 5
Essential Services
Outline
This chapter details the services required by the 8800 Series Testing System.
These must be available at the operating site.
All references to “gallons” refer to U.S. gallons (3.78litres), not U.K. gallons
(4.54litres).
Essential
Services
Note:
5-1
Electrical Power Supplies
M21-28800-70
Electrical Power Supplies
Load Frame and Control System
Either 230V ± 10%, 50-60Hz single phase via a three pin connector fused at 13
Amps, or 115 V ± 10% 50/60Hz, single phase via a three pin connector, variable
fuse rating.
Hydraulic Power Supply
220 V, 380 - 415 V or 460 V, 50 or 60 Hz dependent upon type, three-phase via an
appropriate three-phase isolator.
Caution
The pump used is either a 50 Hz model or a 60 Hz model. Applying the
wrong frequency voltage can damage the hydraulic power supply.
The following details on starting currents for hydraulic power supplies provide the
user with additional information for ascertaining the correct cabling.
5-2
•
Type 3410 all models, and Type 3420 12.5l/min model. Direct On-line. Surge
currents may reach 6 x full load current for a very short period. Consult the
local electrical regulations for details of wiring requirements. Soft-Start
apparatus may be purchased.
•
Type 3411 all models and Type 3420 24 l/min model. Off-load Star/Delta.
Surge currents may reach 2.2 x full load current for a very short period.
Consult the local electrical regulations for details of wiring requirements.
Soft-Start apparatus may be purchased.
Electrical Power Supplies
Impedance Requirements
Table 5-1 details the recommended maximum earth fault loop impedance for
equipment supplies.
Note:
Fuse Rating (Amps)
Zs (Ohms)
6
14.10
10
7.74
16
4.36
20
3.04
25
2.40
32
1.92
40
1.41
50
1.093
63
0.86
80
0.60
100
0.44
125
0.35
160
0.27
200
0.20
Essential
Services
Table 5-1. Maximum Earth Fault Loop Impedance
(Zs) for circuit supplying electrical equipment
When U0, the nominal voltage to earth (ground) is not 240 V, the tabulated
impedance values must be multiplied by U0/240.
The above figures are based upon the IEE Wiring Regulations, Sixteenth Edition
1991, Table 41D. There are no comparable US standards, but the above values
may be used as guidelines.
Voltage and Frequency Variations
Variations in the electrical power supplies to the testing system can cause
problems such as dropped or lost data, resets, etc. Any variation in line voltage
should be kept within ±10 %, free from noise and transients, while any variation
in line frequency should be kept within ± 0.5Hz.
5-3
Hydraulic Power Supplies
M21-28800-70
Hydraulic Power Supplies
Table 5-2 details the standard hydraulic hose sets that are available from Instron.
Table 5-2. Hydraulic Hose Sets
Low-flow 3 metre hose set (25 l/min) Cat No 3450-035
Pressure Hose
96-1-1166
3/8 in bore
Return Hose
96-1-1103
0.5 in bore
Drain Hose
96-1-1166
3/8 in bore
Low-flow 3 metre hose set (45 l/min) Cat No. 3450-008
Pressure Hose
96-1-1102
0.5 in bore
Return Hose
96-1-1108
0.75 in bore
Drain Hose
96-1-1102
0.5 in bore
Medium-flow 3 metre hose set (230 l/min) Cat No. 3450-009
Pressure Hose
96-1-1060
1 in bore
Return Hose
96-1-1061
1.25 in bore
Drain Hose
96-1-1102
0.5 in bore
High-flow 3 metre hose set (500l/min) Cat No. 3450-010
Pressure Hose
96-1-1106
1.5 in bore
Return Hose
96-1-1104
2 in bore
Drain Hose
96-1-1108
0.75 in bore
Low-flow 6 metre hose set (25 l/min) Cat No. 3450-034
5-4
Pressure Hose
96-1-1167
3/8 in bore
Return Hose
96-1-1102
0.5 in bore
Drain Hose
96-1-1167
3/8 in bore
Hydraulic Power Supplies
Low-flow 6 metre hose set (45 l/min) Cat No. 3450-011
Pressure Hose
96-1-1103
0.5 in bore
Return Hose
96-1-1109
0.75 in bore
Drain Hose
96-1-1103
0.5 in bore
Medium-flow 6 metre hose set (230l/min) Cat No. 3450-012
Pressure Hose
96-1-1065
1 in bore
Return Hose
96-1-1066
1.25 in bore
Drain Hose
96-1-1103
0.5 in bore
High-flow 6 metre hose set (500l/min) Cat No. 3450-013
Pressure Hose
96-1-1107
1.5 in bore
Return Hose
96-1-1105
2 in bore
Drain Hose
96-1-1109
0.75 in bore
Essential
Services
Table 5-3 details the hose thread end type for the hydraulic hose sets listed in
Table 5-2.
Table 5-3. Hose Thread Ends
Hose Bore
Thread
End Type
3/8 in bore
9/16-18 JIC
Female one end,
male one end
0.5 in bore
3/4-16 JIC
Female one end,
male one end
0.75in bore
1 1/16-12 JIC
Female both ends
1 in bore
1 5/16-12 JIC
Female both ends
1.25 in bore
1 5/8-12 JIC
Female both ends
1.5 in bore
1 7/8-12 JIC
Female both ends
2 in bore
2 1/2-12 JIC
Female both ends
5-5
Hydraulic Power Supplies
M21-28800-70
Table 5-4 and Table 5-5 detail the hose fittings at the actuator manifold and at the
hydraulic power supply.
Table 5-4. SAE Hose Fitting to Actuator Manifold
Fitting Assembly Part Number
Actuator
Manifold
Low-Flow Hoses
Medium-Flow Hoses
High-Flow Hoses
3 metre
6 metre
3 metre
6 metre
3 metre
6 metre
3340-030
40 l/min
1477-1072
1477-1072
1477-1073
1477-1073
N/A
N/A
3340-031
80 /min
1477-1072
1477-1072
1477-1073
1477-1073
N/A
N/A
3340-032
230 l/min
N/A
N/A
1477-1092
1477-1092
1477-1093
1477-1093
Table 5-5. SAE Hose Fitting to Hydraulic Power Supply
(Types 3410 and 3411)
Fitting Assembly Part Number
Hydraulic
Power
Supply
Low-Flow Hoses
Medium-Flow Hoses
High-Flow Hoses
3 metre
6 metre
3 metre
6 metre
3 metre
6 metre
30l/min
1477-1076
1477-1076
1477-1077
1477-1077
N/A
N/A
45l/min
1477-1076
1477-1076
1477-1077
1477-1077
N/A
N/A
80l/min
N/A
N/A
1477-1077
1477-1077
N/A
N/A
230l/min
N/A
N/A
1477-1078
1477-1078
1477-1079
1477-1079
If a hydraulic power supply is not ordered from Instron, a hydraulic oil supply of
207 bar (3000 psi) will be necessary. Instron can advise on flow rates required.
The oil temperature must not exceed 50 °C (122 °F), and the recommended
filtration requirements are to ISO Contaminant Code 13/10 (U.S.) regulations,
NAS Class 4, or Thermal Control Class 2 (U.K.).
When the hydraulic power supply is to be situated at a distance greater than 6 m
(20 ft) from the load frame, steel pipe runs should be provided. Table 5-6 details
5-6
Hydraulic Power Supplies
the minimum bore of the steel pipe, and the maximum length of the pipe run
including the connecting hoses at either end. This is to ensure that the drain fluid
back-pressure remains within limits.
Please contact your Instron Sales Office for details of extended run Pressure and
Return line dimensions. These vary depending upon frame and hydraulic power
supply configurations.
Table 5-6. Extended Drain Hydraulic Pipe Run Dimensions
Pipe
O.D. inches x
SWG
Bore inches
Maximum length
metres (Total)
12.5
10.5 x 18
0.404
19
30
0.75 x 14
0.590
48
45
0.75 x 14
0.590
35
80
0.75 x 14
0.590
24
230
1 x 12
0.790
19
This table assumes that the hydraulic pump and the load frame remain at the same
level. Contact Instron for technical advice where another configuration or a
greater length of pipe run is required.
5-7
Essential
Services
Hydraulic Power
Supply Flow Rate
l/min
Water Supplies
M21-28800-70
Water Supplies
Cooling Water Flow Rates
Table 5-7 and Table 5-8 show the various flow rates that are required for the
different types of hydraulic power supplies.
Table 5-7. Cooling Water Flow Rate Requirements for Type 3410 and
3411 Hydraulic Power Supplies
Hydraulic Power Supply
Delivery litres/min (gal/
min)
Cooling Water Flow Rates
litres/min (gal/min)
Water Temperature15 °C
(59°F)
Water Temperature 25 °C
(77°F)
45 (12)
37 (9.8)
43 (11.3)
80 (21)
67 (17.7)
108 (28.5)
230 (60)
110 (29)
170 (45)
Table 5-8. Cooling Water Flow Rate Requirements for Type 3420
Hydraulic Power Supplies
Hydraulic Power Supply
Delivery litres/min (gal/
min)
Cooling Water Flow Rates
litres/min (gal/min)
Water Temperature15 °C
(59°F)
Water Temperature 25 °C
(77°F)
12.5 (3.3)
11 (3)
30 (8)
25 (6.6)
12 (3.2)
25 (6.6)
Table 5-9. Cooling Water Flow Rate Requirements for Type 3470
Hydraulic Power Supplies
Hydraulic Power Supply
Delivery litres/min (gal/
min)
5-8
Cooling Water Flow Rates
litres/min (gal/min)
Water Temperature15 °C
(59°F)
Water Temperature 25 °C
(77°F)
23 (6)
11.4 (3)
13.2 (3.5)
38 (10)
15.1 (4)
25 (4.5)
77 (20)
37.9 (10)
37.9 (10)
Water Supplies
Water Pressure
Caution
Do not use solenoid-operated water shut-off valves on the outlet side of the
heat exchanges. They cause water hammer effects which may cause
internal fractures of the hydraulic power supply, leading to water
contamination of the oil.
The recommended water pressure is 2 bar (29 psi) to 7 bar (100 psi).
Water Quality
Essential
Services
The efficiency of cooling of the hydraulic power supply oil system is highly
dependent upon the quality of the cooling water supply. An analysis of the supply
should be obtained from the local water supply authorities, particularly with
regard to pH levels and the level of suspended solids. As a minimum standard, the
pH level should be within 5.0 to 8.5, and filtration should be provided to screen
suspended particles of 0.8 mm or above.
5-9
Ventilation
M21-28800-70
Ventilation
Table 5-10, Table 5-11 and Table 5-12 are guides to the air circulation required to
cool the hydraulic power supply motor when installed in an enclosed space.
Table 5-10. Types 3410 and 3411 Hydraulic Power Supply Ventillation
Requirements
Hydraulic Power Supply
Delivery
litres/min (gal/min)
Motor Rating kW
Cooling Airflow m3/min
12.5 (3.25)
5.5
5.75
25 (6.5)
11
9.5
45 (12)
22.5
13
80 (21)
46.5
20
230 (60)
110
70
Table 5-11. Type 3420 Hydraulic Power Supply Ventillation
Requirements
Hydraulic Power Supply Delivery
litres/min (gal/min)
Cooling Airflow m3/min
12.5 (3.25)
2.48
25 (6.5)
3.21
Table 5-12. Type 3470 Hydraulic Power Supply Ventillation
Requirements
5-10
Hydraulic Power Supply
Delivery
litres/min (gal/min)
Motor Rating kW
Cooling Airflow m3/min
23 (6)
11.2
8
38 (10)
18.3
11
77 (20)
37.3
17
Noise Levels
Noise Levels
The noise levels of Instron hydraulic power supplies are measured at one metre
from the supply. Table 5-13, Table 5-14 and Table 5-15 are typical noise levels
only.
Table 5-13. Types 3410 and 3411 Hydraulic Power Supply Noise Levels
Hydraulic Power Supply Delivery
litres/min (gal/min)
Noise Level dB(A)
45 (12)
79
80 (21)
83
230 (60)
95
Hydraulic Power Supply Delivery
litres/min (gal/min)
Noise Level dB(A)
12.5 (3.3)
72
25 (6.6)
76
Essential
Services
Table 5-14. Type 3420 Hydraulic Power Supply Noise Levels
Table 5-15. Type 3470 Hydraulic Power Supply Noise Levels
Hydraulic Power Supply Delivery
litres/min (gal/min)
Noise Level dB(A)
23 (6)
75
38 (10)
75
77 (20)
80
It is recommended that the hydraulic power supply is situated remotely from the
actual operating location to minimise the nuisance from noise. If sound proofing
is used, then it is essential that adequate ventilation is provided to keep the motor
and power supply operating temperatures at the correct levels (refer to
“Ventilation” on page 5-10). A minimum distance of 600 mm (24 in) of free floor
space is required all around the hydraulic power supply to allow for installation
and maintenance.
5-11
Environmental Conditions
M21-28800-70
Environmental Conditions
Consideration should be given to the environmental condition in which the testing
system is operated or stored. Table 5-16 details the recommended environmental
specification which should be complied with to ensure the correct operation of the
system.
Table 5-16. Recommended Environmental Specifications
5-12
Parameter
Specification
Operating Temperature
5 to 38 °C (41 to 100 °F)
Storage Temperature
-3 to +50 °C (-22 to +122 °F)
Temperature Rate-of-change
2 °C (4 °F) per hour
Relative Humidity
10 to 90 % non-condensing
Download