Document Date (05/2013) Author: Ed Larsen Document Number: 0600DB1302 www.schneider-electric.us/go/codes Keywords: Circuit Breakers Fire Alarms Emergency Communications Fire Alarm Circuit Breakers Introduction Many have asked if circuit breakers are available with a red handle to feed fire alarm circuits. One circuit breaker manufacturer even offers circuit breakers with a red handle. The quick answer is that a red handled circuit breaker is not necessary to feed a fire alarm circuit. This Electrical Shortz will explain why. NFPA 72® Marking Requirements NFPA 72®, the National Fire Alarm and Signaling Code, “…covers the application, installation, location, performance, inspection, testing, and maintenance of fire alarm systems, supervising station alarm systems, public emergency alarm reporting systems, fire warning equipment and emergency communications systems (ECS), and their components.” How a circuit breaker or other disconnecting means that feeds a fire alarm system needs to be identified is defined in Section 10.6.5.2 Circuit Identification and Accessibility. Here are the requirements in Section 10.6.5.2: 10.6.5.2.1 The location of the branch circuit disconnecting means shall be permanently identified at the control unit. 10.6.5.2.2 System circuit disconnecting means shall be permanently identified as to its purpose in accordance with the following: (1) “FIRE ALARM” for fire alarm systems (2) “EMERGENCY COMMUNICATIONS” for emergency communications systems (3) “FIRE ALARM/ECS” for combination fire alarm and emergency communications systems 10.6.5.2.3 For fire alarm and/or signaling systems, the circuit disconnecting means shall have a red marking. 10.6.5.2.4 The red marking shall not damage the overcurrent protective devices or obscure the manufacturer’s markings. NOTE: A red handle on the disconnecting means is not required! Most installers meet this requirement by affixing a red label adjacent to the circuit breaker. Locking Requirement © 2013 Schneider Electric All Rights Reserved There is another fire alarm system, supervising station alarm system, public emergency alarm reporting system and emergency communication system branch circuit disconnecting means requirement that should be noted. Section 10.6.5.4 requires that, “Where a circuit breaker is the disconnecting means, a listed circuit breaker locking device shall be installed.” ™ ENGLISH Electrical Shortz Fire Alarm Circuit Breakers Electrical Shortz 0600DB1302 Document Date (04/2013) Summary In summary, circuit breakers or other disconnecting means feeding fire alarm or emergency communications branch circuits do not need to have red handles, but circuit breakers or other disconnecting means need to have a red marking adjacent to the device indicating that it is the disconnecting means for a fire alarm and/or emergency communications circuit. The marking may not obscure the circuit breaker markings. Further, if a circuit breaker, a listed handle locking device must be installed. For more information: NFPA 72-2013 National Fire Alarm and Signaling Code For More Information NFPA 72 National Fire Alarm and Signaling Code Visit the Schneider Electric North America Codes and Standards Electrical Shortz website at: http://www.schneider-electric.us/support/codes-and-standards/codes-standards-technical-library1/product-documentation/ Schneider Electric USA, Inc. 1415 S. Roselle Road Palatine, IL 60067 USA 1-888-778-2733 www.schneider-electric.us “Electrical Shortz” are produced by the Schneider Electric North America Codes and Standards Group. These documents provide general guidance on a specific issue. Circumstances regarding particular installation issues may need further consideration. © 2013 Schneider Electric All Rights Reserved Schneider Electric and Square D are trademarks owned by Schneider Electric Industries SAS or its affiliated companies. All other trademarks are the property of their respective owners.