WLA - Load balancing unit Distributed by WLA, Page 1 of 4 PT. SINAR ELEKTRINDO PERKASA JL. Panjang no.7, Kedoya Elok Plaza DC-44 Jakarta Barat Phone : + 62-021-5806044 (Hunting); Fax : + 62-021-5806058; Email: sales@sinarelektrindo.com Application: This unit is used for the automatically equalizing the effective of generating sets. A proportional regulation of the nominal value for several generating sets in parallel can be effected. This balancer is often combined with the frequency control unit "FN 1" and the synchronizer unit "SY 1" for a fully automatic synchronization with load balancing. Output impulses for speed governor motors, motorized potentiometers, steam regulating valves are given. Functions: The load balancing unit WLA 2 compares the effective power of two systems and gives output impulses (more or less power) to the speed governor motor. High difference in effective power means a continuous impulse and little difference means increasing the interval time between the impulses, so that an optimums of regulation is given. The sensitivity of this unit is adjustable. Data for ordering : Mains voltage, current transformer ratio and the rated power of the generating sets. The standard unit is developed for 220 VAC (phase-neutral), two current paths each 5 amps, (secondary side of the current transformers) and a power ratio 1:1 of the generating sets. Other voltages, currents and/or power rations for additional prices. Commissioning and adjustments Check first the connection of the current transformers: 1. Alternator 1 with load, alternator 2 switched off. Relay of the measuring circuit N1 > N2 must be energized. 2. Alternator 2 with load, alternator 1 switched off. Relay of the measuring circuit N1 < N2 must be energized. 3. When one set is running with load, start the second set and switch in parallel. Check there after the difference in effective load. The difference should decrease nearly to zero. Increasing of the difference: change the output terminals 3 and 11 with 4 and 12. The required sensitivity can be adjusted with the potentiometer. For example: Sensitivity adjusted at 5 % means output impulses are given when the difference in effective load becomes more than 5 % (referring to the nominal of the current transformer). Distributed by WLA, Page 2 of 4 PT. SINAR ELEKTRINDO PERKASA JL. Panjang no.7, Kedoya Elok Plaza DC-44 Jakarta Barat Phone : + 62-021-5806044 (Hunting); Fax : + 62-021-5806058; Email: sales@sinarelektrindo.com Technical data: Type : WLA 2 Voltage : 220 V +10/ - 15 % Current : 2 x 5 amps. Frequency : 50 / 60 Hz Consumption voltage circuit : 5 VA Consumption current circuit : 1 VA Test voltage : 2 KV Permissible Switch-on time : 100 % Contacts : 2 NO free of potential contact Contact material : Silver coating Rupturing Capacity : Max. 220 V at 220 VAC Terminals : Metric 4, max. Wires 2.5 mm2 Type of protection : Case IP 20, terminals IP 00 Mounting : All positions Service life : Nearly no limit Maintenance : None Weight : 2 Kg Connection Diagram Distributed by WLA, Page 3 of 4 PT. SINAR ELEKTRINDO PERKASA JL. Panjang no.7, Kedoya Elok Plaza DC-44 Jakarta Barat Phone : + 62-021-5806044 (Hunting); Fax : + 62-021-5806058; Email: sales@sinarelektrindo.com Dimension – mm : WLA Order form Active Load Balancing Unit 1 phase / N Voltage Connection Rated Voltage Rated Current 230 Vac 5A WLA 10 230 5 Distributed by WLA, Page 4 of 4 PT. SINAR ELEKTRINDO PERKASA JL. Panjang no.7, Kedoya Elok Plaza DC-44 Jakarta Barat Phone : + 62-021-5806044 (Hunting); Fax : + 62-021-5806058; Email: sales@sinarelektrindo.com