Electrical Inspection Asset Data Priority Condition Inspection

advertisement
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M015
P.S. 15 - MANHATTAN, 333 EAST 4 STREET, MANHATTAN, NY, 10009
School:
InspectionId
Inspection Type
10010 ELECTRICAL
Time In
Last Edited
2014-10-09 08:40AM
2015-05-27 09:25AM
Asset Data
Question
Answer
Have any Systems/Major Building Components been upgraded?
Systems:
Intrusion Alarm System
Years:
Systems:
2001
Emergency Light/Exit Light Panel, Emergency Lights,
Exit Lights
2004
Partial Raceways With Receptacles in Library
Years:
Systems:
Years:
Systems:
2008
Partial Lighting Security, Most Molded Case Circuit
Breaker Panel Boards
2008
LAN-MDF
Years:
Systems:
Years:
Systems:
2011
Intrusion Alarm System Remote Annunciator Panel
(1/3)
Years:
2013
Systems: Fire Alarm System, Public Address System, Local
Sound Systems
Years:
Under Construction
Systems: Interior Lighting, Auditorium Theater Lighting System,
Telephone System
Years:
Under Construction
Below Ground
Type of Service
Does Interactive Whiteboard (IWB) Exist?
Yes
DEDICATED INTERCOMS IN FIRE RESCUE AREAS
Question
Are there any Life Rescue Assistance Areas, Fire Rescue Areas, and/or Holding Rooms
in your building?
Response
No
Priority Condition
Priority Condition
Exist Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s) Notified
No
Emergency
Lighting Not
Operational
Not
Operational
Emergency
Lighting
Gymnasium
Ray Floy
Person(s) Title
Building
Manager
PhotoImage
No Photo Tak
Inspection
Question
Response
Electrical
Does not exist
ATHLETIC FIELD
AUDITORIUM
Inspected
Instance on 1st Floor
House Lighting
Under construction
Instance on 1st Floor
Local Sound System
Under construction
Instance on 1st Floor
Projection System
Does not exist
Instance on 1st Floor
Theater Lighting System
Under construction
Instance on 1st Floor
Inspected
AUXILIARY SIGNAL/BELL SYSTEM
3- Fair
Condition
Deficiency
No deficiencies recorded
CAFETERIA
Mobile Validity Version 2.0 (P)
Page 1 of 5
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M015
Question
Response
CAFETERIA
Instance on 1st Floor
Inspected
Lighting
Under construction
Instance on 1st Floor
Local Sound System
Under construction
Instance on 1st Floor
Projection System
Does not exist
Instance on 1st Floor
Theater Lighting System
Does not exist
Instance on 1st Floor
Inspected
CITY FIRE ALARM SYSTEM
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
CLASSROOM/CORRIDOR/ADMINISTRATIVE SPACE
Under construction
Lighting
COMPUTER LAB
Does not exist
EMERGENCY DC STANDBY BATTERY POWER
Does not exist
EMERGENCY GENERATOR SET
Does not exist
EMERGENCY LIGHT/EXIT LIGHT PANEL
Inspected
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
EMERGENCY LIGHTING
Inspected
Battery Pack
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Non Battery Pack
3- Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
FIXTURE LAMP NOT OPERATIONAL
Gymnasium
6
EACH
MAINTENANCE
PRIORITY 5
LEVEL 6
35093785M
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
EXIT LIGHT
Inspected
Battery Pack
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Non Battery Pack
3- Fair
Condition
Deficiency
No deficiencies recorded
EXIT/EMERGENCY LIGHT
Does not exist
FIRE ALARM SYSTEM
Under construction
GROUNDING SYSTEM
Inspected
3- Fair
Condition
Deficiency
No deficiencies recorded
GYMNASIUM
Instance on 3rd Floor
Inspected
Instance on 3rd Floor
Under construction
Lighting
Local Sound System
Under construction
Instance on 3rd Floor
Projection System
Mobile Validity Version 2.0 (P)
Page 2 of 5
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M015
Question
Response
GYMNASIUM
Projection System
Instance on 3rd Floor
Does not exist
Scoreboard
Does not exist
Instance on 3rd Floor
Theater Lighting System
Does not exist
Instance on 3rd Floor
Does not exist
INTERCOM SYSTEM
KITCHEN/WARMING PANTRY
Instance on 1st Floor
Inspected
Instance on 1st Floor
Under construction
Lighting
Inspected
LAN
Local Distribution Frame (I/LDF)
Does not exist
Main Equipment Rack (MDF)
Inspected
1- Good
Condition
Deficiency
No deficiencies recorded
LIBRARY
Instance on Room 308
Inspected
Has LAN/Modem access
Yes
Instance on Room 308
Under construction
Lighting
Projection System
Does not exist
Instance on Room 308
Raceway With Receptacles
Instance on Room 308
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Does not exist
LIGHTNING PROTECTION
LOCKER ROOM
Instance on 3rd Floor Inside Gymnasium
Inspected
Alternative Use
Yes
Instance on Room 417
Inspected
Alternative Use
Yes
Instance on 3rd Floor Inside Gymnasium
Under construction
Instance on Room 417
Under construction
Lighting
MOTOR CONTROL CENTER
Does not exist
MOTOR STARTER/CONTACTOR
Inspected
3- Fair
Condition
Deficiency
No deficiencies recorded
MULTIPURPOSE ROOM
Does not exist
PANEL BOARD
Inspected
Inspected
Fused Disconnect Switch Type
3- Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PANEL BOARD BEYOND USEFUL LIFE
Boiler Room
1
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Does not exist
Fused Knife Switch Type
Mobile Validity Version 2.0 (P)
Page 3 of 5
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M015
Question
Response
PANEL BOARD
Fused Toggle Switch Type
Does not exist
Molded Case Circuit Breaker Type
Inspected
2- Between Good and Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PANEL BOARD BEYOND USEFUL LIFE
Kitchen and Basement Storage Area
3
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
PUBLIC ADDRESS SYSTEM
Under construction
SCIENCE DEMO ROOM
Does not exist
SCIENCE LAB
Does not exist
SCIENCE PREP ROOM
Does not exist
SECURITY
Inspected
Intrusion Alarm System
Inspected
Central Control Panel
Inspected
Instance
Custodian's Office - Room 108
3- Fair
Instance Condition
Instance Quantity
1
EACH
Instance Quantity Uom
Model
Installation Year
Source of Installation Year
Vista - 50P
2001
Documented
Deficiency
No deficiencies recorded
Inspected
Infrared Sensor
Condition
3- Fair
Deficiency
No deficiencies recorded
Panic Switch
Does not exist
Remote Annunciator
Inspected
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Siren/Strobe
Condition
3- Fair
Deficiency
No deficiencies recorded
Inspected
Ultrasonic Sensor
Condition
3- Fair
Deficiency
No deficiencies recorded
IPDVS/CCTV System
Does not exist
Lighting - Security
Inspected
Condition
2- Between Good and Fair
Replacement Quantity
Replacement Uom
22
EACH
Deficiency
Deficiency Location/Instance
Deficiency Quantity
LIGHTING FIXTURE BEYOND USEFUL LIFE
Main Entrance Soffit, Exit on East 4th Street
8
EACH
REPLACE-UPGRADE
PRIORITY 1
LEVEL 3
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
SERVICE SWITCH
Instance
Mobile Validity Version 2.0 (P)
Electrical Meter Room
Page 4 of 5
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Electrical Inspection
M015
Question
Response
SERVICE SWITCH
Instance Condition
2- Between Good and Fair
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Siemens
N/A
1200
Amps
Nameplate
2008
Documented
Deficiency
Deficiency Quantity
SWITCH ID IS MISSING
1
EACH
MAINTENANCE
PRIORITY 2
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
SWIMMING POOL
Does not exist
SWITCHBOARD
Water Penetration In Electrical Room?
Number of Spares
Inspected
Air Circuit Breaker Type
No
15
Does not exist
Fused Disconnect Switch Type
Inspected
Instance
Basement Cage
2- Between Good and Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Capacity/Size 2 Quantity
Capacity/Size 2 UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Siemens
Switchboard MDS
1200
Amps Total
3
Section(s)
Nameplate
2008
Documented
Deficiency
No deficiencies recorded
Fused Knife Switch Type
Does not exist
Molded Case Circuit Breaker Type
Does not exist
TELEPHONE SYSTEM
Under construction
TOILET ROOM - STAFF
Inspected
Under construction
Lighting
Inspected
TOILET ROOM - STUDENT
Under construction
Lighting
TRANSFORMER
Does not exist
TV SYSTEM
Cable System Exist?
Operational?
Inspected
Yes
Yes
Does not exist
Main Equipment Rack
Mobile Validity Version 2.0 (P)
Page 5 of 5
Print Date: 6/18/2015